pts ip paint system
DESCRIPTION
for Petronas Painting SystemTRANSCRIPT
To: Prepared By:
Nicole Leong Sales Administrator Shah Alam Tel: (60)03-7845 5292 Fax: (60)03-7845 5293 [email protected]
Asset / Package Name:
PAINTING SPECIFICATION
Location: Our Ref: 050616-NLEONG-4916F / 76
Prepared On: 18/07/2006
For further information regarding prices, availability and technical information please consult International Protective Coatings. We may at our discretion provide free of charge technical service support to customers
consisting of the provision of a technical service representative who may periodically or on a reasonable request visit the site and liaise with the customer concerning product requirements, application training and
general advice concerning our products. We accept no liability whatsoever in connection with the provision of or a failure to provide such free of charge technical support. We reserve the right to reassess this offer should
the costs to us change significantly during the quotation period. Subject to our Standard Terms and Conditions which are available on request.
http://www.international-pc.com/
Please also refer to our current Product & Material Safety Datasheets prior to
using any products.
PAINTING SPECIFICATION
18/07/2006
Page 2
Summary
Area Description Environment Notes
COATING SYSTEM NO.1A For External Application : INITIAL PAINTING - Carbon Steel Design Temperature < 110°C NON INSULATED in The Atmospheric Zone
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
COATING SYSTEM NO.1B For External Application : MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE - Carbon Steel Design Temperature < 110°C NON INSULATED In the Atmospheric Zone
This specification is intended for Maintenance and Repair.
COATING SYSTEM NO.1C For External Application : MAINTENANCE PAINTING FOR POWER TOOL CLEANED SURFACE - Carbon Steel Design Temperature < 110°C NON INSULATED in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
COATING SYSTEM NO.2A For External Application : INITIAL PAINTING - Carbon Steel Design Temperature < 110°C INSULATED in the Atmospheric Zone
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
COATING SYSTEM NO.2B For External Application : MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE - Carbon Steel Design Temperature < 110°C INSULATED in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
COATING SYSTEM NO.2C For External Application : MAINTENANCE PAINTING FOR POWER TOOL CLEANED SURFACE - Carbon Steel Design Temperature < 110°C INSULATED in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
COATING SYSTEM NO.3A For External Application : INITIAL PAINTING AND MAINTENANCE PAINTING - Offshore Platform Decks (including primary and secondary structures)
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
COATING SYSTEM NO.3B For External Application : INITIAL PAINTING AND MAINTENANCE PAINTING (Alternative) - Offshore Platform Decks (including primary and secondary structures)
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
COATING SYSTEM NO.4A For External Application : INITIAL PAINTING AND MAINTENANCE PAINTING - Splash Zone and Spray Zone
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
COATING SYSTEM NO.4B (ALTERNATIVE) For External Application : INITIAL PAINTING AND MAINTENANCE PAINTING - Splash Zone and Spray Zone
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
PAINTING SPECIFICATION
18/07/2006
Page 3
Summary
Area Description Environment Notes
COATING SYSTEM NO.5A(1) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Carbon Steel Design Facilities with Surface Temperature 110 - 250°C (INSULATED AND NON INSULATED) in the Atmospheric Zone
This specification is designed for areas exposed to elevated temperatures.
COATING SYSTEM NO.5A(2) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Carbon Steel Design Facilities with Surface Temperature 250 - 450 deg C (INSULATED AND NON INSULATED) in the Atmospheric Zone
This specification is designed for areas exposed to elevated temperatures.
COATING SYSTEM NO.5B(1) For External Application : MAINTENANCE PAINTING FOR POWER TOOL CLEANED SURFACE - Carbon Steel Design Facilities with Surface Temperature 110 - 250°C (INSULATED AND NON INSULATED) in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
COATING SYSTEM NO.5B(2) For External Application : MAINTENANCE PAINTING FOR POWER TOOL CLEANED SURFACE - Carbon Steel Design Facilities with Surface Temperature 250 - 450°C (INSULATED AND NON INSULATED) in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
COATING SYSTEM NO.6A For External Application : INITIAL PAINTING - GALVANISED STEEL
A high performance coating specification designed for application over non-ferrous metals
COATING SYSTEM NO.7A(1) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Stainless Steel (NON INSULATED) facilities Operating < 110°C
This specification is designed to be used over Stainless Steel
COATING SYSTEM NO.7A(2) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Stainless Steel (INSULATED) facilities Operating < 110°C
This specification is designed to be used over Stainless Steel
COATING SYSTEM NO.7A(3) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Stainless Steel (INSULATED AND NON INSULATED) facilities Operating 110 - 540°C
This specification is designed to be used over Stainless Steel
COATING SYSTEM NO.8A For External Application : INITIAL PAINTING - Carbon Steel Storage Tank
The specification given is our nearest product match for the system based on information received. Without further details of environment and conditions of service we cannot be certain that the system specified will give the best performance and therefore do not accept any liability for the performance of the product or loss or damage (other than death or personal injury resulting from our negligence) arising out of use of the product.
COATING SYSTEM NO.8B For External Application : INITIAL AND MAINTENANCE PAINTING - Carbon Steel Storage Tank - Underside of Bottom plate (ONLY if painting is required for corrosion protection to supplement cathodic protection)
The specification given is our nearest product match for the system based on information received. Without further details of environment and conditions of service we cannot be certain that the system specified will give the best performance and therefore do not accept any liability for the performance of the product or loss or damage (other than death or personal injury resulting from our negligence) arising out of use of the product.
PAINTING SPECIFICATION
18/07/2006
Page 4
Summary
Area Description Environment Notes
COATING SYSTEM NO.8C For External Application : Carbon Steel Storage Tank - Shell, Roof Plate, Stairways, Stair Treads, Gangways And Others External parts include the piping (NON GALVANISED)
The specification given is our nearest product match for the system based on information received. Without further details of environment and conditions of service we cannot be certain that the system specified will give the best performance and therefore do not accept any liability for the performance of the product or loss or damage (other than death or personal injury resulting from our negligence) arising out of use of the product.
COATING SYSTEM NO.9A For External Application : INITIAL AND MAINTENANCE PAINTING - Timber Decks
A high performance coating specification for application on timbers.
COATING SYSTEM NO.10 For External Application : Timber Decks - Markings
The specification given is our nearest product match for the system based on information received. Without further details of environment and conditions of service we cannot be certain that the system specified will give the best performance and therefore do not accept any liability for the performance of the product or loss or damage (other than death or personal injury resulting from our negligence) arising out of use of the product.
COATING SYSTEM NO.11 For External Application : Timber Decks - Living Quarters, Pressurised Building, Control Room (Interior)
A high performance coating specification for application on timbers.
COATING SYSTEM NO.13A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Fuel Gas (Sweet And Sour) for Service Temperature Up To 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.14A(1) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Roof and Shell Plate Of Service Temperature Up To 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.14A(2) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Bottom Plate and Vessels Up To 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.14A(3) (Alternative) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Bottom Plate Of Service Temperature Up To 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.15A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Naptha, Reformate, Jet A Fuel, Lube Oil, Fuel Oil, Gasoline (Leaded & Unleaded) For Service Temp. Up to 60°
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.16A For Internal Application : INITIAL PAIINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Diesel (Roof and Shell Plate) of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
PAINTING SPECIFICATION
18/07/2006
Page 5
Summary
Area Description Environment Notes
COATING SYSTEM NO.16B For Internal Application : INITIAL PAIINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Diesel (Bottom Plate and Vessels) of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.16C (ALTERNATIVE) For Internal Application : INITIAL PAIINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Diesel (Bottom Plate and Vessels) of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.17A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Sea Water, Produced Water, Brackish, Demineralised Water, Brine of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.18A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Steam (Condensate), Boiler Feed of Service Temperature up to 100°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.19A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Utility Air of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.19B (ALTERNATIVE) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Utility Air of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.19C For Internal Application : INITIAL PAINTING , MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Utility Air of Service Temperature more than 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.21A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Methanol Percroethalyne of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.21B (Alternative) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE (Alternative) - Methanol Percroethalyne of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
COATING SYSTEM NO.22A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Triethylene Glycol / Methylethylene Glycol of Service Temperature Up to 60°
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation ,
C application and cure prior to their use.
PAINTING SPECIFICATION
18/07/2006
Page 6
Summary
Area Description Environment Notes
COATING SYSTEM NO.22B (Alternative) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE (Alternative) - Triethylene Glycol / Methylethylene Glycol of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
PAINTING SPECIFICATION
18/07/2006
Page 7
COATING SYSTEM NO.1A For External Application : INITIAL PAINTING - Carbon Steel Design Temperature < 110°C NON INSULATED in The Atmospheric Zone
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� A mist coat is recommended if cratering results when topcoating the inorganic zinc primer by applying the first coat reduced 1:1 with appropriate thinner and then follow with a second normal coat.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Inorganic Zinc Rich Silicate
Interzinc 22Greenish
GreyAirless Spray, Air Spray
63 75 8 Hr - Ext 8.40International GTA803
Full Coat
EpoxyIntergard 475HS tropical
BeigeAirless Spray, Brush, Roller, Air Spray
80 150 2 Hr - Ext 5.33International GTA007
Full Coat
PolyurethaneInterthane 990
Color Range
Airless Spray, Brush, Conventional Spray, Roller, Air Spray
57 50 3 Hr - Ext 11.40International GTA713
275
NOTE : 1. The alternative thinner for Interthane 990 is GTA733.
PAINTING SPECIFICATION
18/07/2006
Page 8
COATING SYSTEM NO.1B For External Application : MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE - Carbon Steel Design Temperature < 110°C NON INSULATED In the Atmospheric Zone
This specification is intended for Maintenance and Repair.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy- Zinc Rich
Interzinc 52 GreyAirless Spray, Brush, Air Spray
59 75 2 Hr - Ext 7.87International GTA220
Full Coat
EpoxyIntergard 475HS tropical
BeigeAirless Spray, Brush, Roller, Air Spray
80 150 2 Hr - Ext 5.33International GTA007
Full Coat
PolyurethaneInterthane 990
Color Range
Airless Spray, Brush, Conventional Spray, Roller, Air Spray
57 50 3 Hr - Ext 11.40International GTA713
275
NOTE : 1. The alternative thinner for Interthane 990 is GTA733.
PAINTING SPECIFICATION
18/07/2006
Page 9
COATING SYSTEM NO.1C For External Application : MAINTENANCE PAINTING FOR POWER TOOL CLEANED SURFACE - Carbon Steel Design Temperature < 110°C NON INSULATED in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
Surface Preparation & Comments
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 125 6 Hr - Ext 6.56International GTA220
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 125 4 Hr - 2 Wk 6.56International GTA220
Full Coat
PolyurethaneInterthane 990
Color Range
Airless Spray, Brush, Conventional Spray, Roller, Air Spray
57 50 3 Hr - Ext 11.40International GTA713
300
NOTE : 1. The alternative thinner for Interthane 990 is GTA733.
PAINTING SPECIFICATION
18/07/2006
Page 10
COATING SYSTEM NO.2A For External Application : INITIAL PAINTING - Carbon Steel Design Temperature < 110°C INSULATED in the Atmospheric Zone
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� A mist coat is recommended if cratering results when topcoating the inorganic zinc primer by applying the first coat reduced 1:1 with appropriate thinner and then follow with a second normal coat.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Inorganic Zinc Rich Silicate
Interzinc 22Greenish
GreyAirless Spray, Air Spray
63 75 8 Hr - Ext 8.40International GTA803
Full Coat
EpoxyIntergard 475HS tropical
BeigeAirless Spray, Brush, Roller, Air Spray
80 150 2 Hr - Ext 5.33International GTA007
225
PAINTING SPECIFICATION
18/07/2006
Page 11
COATING SYSTEM NO.2B For External Application : MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE - Carbon Steel Design Temperature < 110°C INSULATED in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy- Zinc Rich
Interzinc 52 GreyAirless Spray, Brush, Air Spray
59 75 2 Hr - Ext 7.87International GTA220
Full Coat
EpoxyIntergard 475HS tropical
BeigeAirless Spray, Brush, Roller, Air Spray
80 150 2 Hr - Ext 5.33International GTA007
225
PAINTING SPECIFICATION
18/07/2006
Page 12
COATING SYSTEM NO.2C For External Application : MAINTENANCE PAINTING FOR POWER TOOL CLEANED SURFACE - Carbon Steel Design Temperature < 110°C INSULATED in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
Surface Preparation & Comments
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 125 6 Hr - Ext 6.56International GTA220
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 125 4 Hr - 2 Wk 6.56International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
PAINTING SPECIFICATION
18/07/2006
Page 13
COATING SYSTEM NO.3A For External Application : INITIAL PAINTING AND MAINTENANCE PAINTING - Offshore Platform Decks (including primary and secondary structures)
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
Description Product NameColour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
PolyesterInterzone 2000 Malaysia
GreyAirless Spray, Brush
85 400 5 Hr - 3 D 2.13International GTA065
Full Coat
PolyesterInterzone 2000 Malaysia
BlackAirless Spray, Brush
85 400 5 Hr - 3 D 2.13International GTA065
800
PAINTING SPECIFICATION
18/07/2006
Page 14
COATING SYSTEM NO.3B For External Application : INITIAL PAINTING AND MAINTENANCE PAINTING (Alternative) - Offshore Platform Decks (including primary and secondary structures)
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Glass Flake Epoxy
Interzone 505 tropical
GloamingAirless Spray, Brush, Roller, Air Spray
90 400 5 Hr - 2 D 2.25International GTA220
Full Coat
Glass Flake Epoxy
Interzone 505 tropical
BlackAirless Spray, Brush, Roller, Air Spray
90 400 5 Hr - 2 D 2.25International GTA220
800
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
PAINTING SPECIFICATION
18/07/2006
Page 15
COATING SYSTEM NO.4A For External Application : INITIAL PAINTING AND MAINTENANCE PAINTING - Splash Zone and Spray Zone
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
Description Product NameColour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
PolyesterInterzone 2000 Malaysia
GreyAirless Spray, Brush
85 500 5 Hr - 3 D 1.70International GTA065
Full Coat
PolyesterInterzone 2000 Malaysia
BlackAirless Spray, Brush
85 500 5 Hr - 3 D 1.70International GTA065
1000
PAINTING SPECIFICATION
18/07/2006
Page 16
COATING SYSTEM NO.4B (ALTERNATIVE) For External Application : INITIAL PAINTING AND MAINTENANCE PAINTING - Splash Zone and Spray Zone
A low durability (upto 5 years) coating specification designed for environments classified by ISO 12944-2 as C5-I very high corrosivity (Industrial).
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Glass Flake Epoxy
Interzone 505 tropical
GloamingAirless Spray, Brush, Roller, Air Spray
90 500 5 Hr - 2 D 1.80International GTA220
Full Coat
Glass Flake Epoxy
Interzone 505 tropical
BlackAirless Spray, Brush, Roller, Air Spray
90 500 5 Hr - 2 D 1.80International GTA220
1000
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
PAINTING SPECIFICATION
18/07/2006
Page 17
COATING SYSTEM NO.5A(1) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Carbon Steel Design Facilities with Surface Temperature 110 - 250°C (INSULATED AND NON INSULATED) in the Atmospheric Zone
This specification is designed for areas exposed to elevated temperatures.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Inorganic Zinc Rich Silicate
Interzinc 22Greenish
GreyAirless Spray, Air Spray
63 75 8 Hr - Ext 8.40International GTA803
Full Coat
High Temperature Silicone Acrylic
Intertherm 875
WhiteBrush, Roller, Air Spray
39 30 1 Hr - Ext 13.00International GTA007
Full Coat
High Temperature Silicone Acrylic
Intertherm 875
GreyBrush, Roller, Air Spray
39 30 1 Hr - Ext 13.00International GTA007
135
PAINTING SPECIFICATION
18/07/2006
Page 18
COATING SYSTEM NO.5A(2) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Carbon Steel Design Facilities with Surface Temperature 250 - 450 deg C (INSULATED AND NON INSULATED) in the Atmospheric Zone
This specification is designed for areas exposed to elevated temperatures.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Inorganic Zinc Rich Silicate
Interzinc 22Greenish
GreyAirless Spray, Air Spray
63 75 8 Hr - Ext 8.40International GTA803
Full Coat
High Temperature Silicone
Intertherm 50
AluminiumBrush, Roller, Air Spray
45 25 6 Hr - Ext 18.00International GTA007
Full Coat
High Temperature Silicone
Intertherm 50
AluminiumBrush, Roller, Air Spray
45 25 6 Hr - Ext 18.00International GTA007
125
NOTE : 1. The maximum heat resistance for Intertherm 50 is 540 degree C.
PAINTING SPECIFICATION
18/07/2006
Page 19
COATING SYSTEM NO.5B(1) For External Application : MAINTENANCE PAINTING FOR POWER TOOL CLEANED SURFACE - Carbon Steel Design Facilities with Surface Temperature 110 - 250°C (INSULATED AND NON INSULATED) in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
Surface Preparation & Comments
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Zinc Dust GraphiteIntertherm 890
Dark Grey
Brush, Roller, Air Spray
57 40 24 Hr - Ext 14.25International GTA004
Full Coat
High Temperature Silicone Acrylic
Intertherm 875
WhiteBrush, Roller, Air Spray
39 30 1 Hr - Ext 13.00International GTA007
Full Coat
High Temperature Silicone Acrylic
Intertherm 875
GreyBrush, Roller, Air Spray
39 30 1 Hr - Ext 13.00International GTA007
100
Intertherm 890 may require thinning to achieve a DFT of 40 microns.
PAINTING SPECIFICATION
18/07/2006
Page 20
COATING SYSTEM NO.5B(2) For External Application : MAINTENANCE PAINTING FOR POWER TOOL CLEANED SURFACE - Carbon Steel Design Facilities with Surface Temperature 250 - 450°C (INSULATED AND NON INSULATED) in the Atmospheric Zone
This specification is intended for Maintenance and Repair.
Surface Preparation & Comments
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Zinc Dust Graphite
Intertherm 890
Dark GreyBrush, Roller, Air Spray
57 40 24 Hr - Ext 14.25International GTA004
Full Coat
High Temperature Silicone
Intertherm 50
AluminiumBrush, Roller, Air Spray
45 25 6 Hr - Ext 18.00International GTA007
Full Coat
High Temperature Silicone
Intertherm 50
AluminiumBrush, Roller, Air Spray
45 25 6 Hr - Ext 18.00International GTA007
90
Intertherm 890 may require thinning to achieve a DFT of 40 microns.
NOTE : 1. The maximum heat resistance for Intertherm 50 is 540 degree C.
PAINTING SPECIFICATION
18/07/2006
Page 21
COATING SYSTEM NO.6A For External Application : INITIAL PAINTING - GALVANISED STEEL
A high performance coating specification designed for application over non-ferrous metals
Surface Preparation & Comments
� Degrease surface according to ISO 8504:2000 using solvent and clean rags or non-ionic detergent. Lightly brush blast surface using ilmenite or by using hand or power tool sanding to remove oxide layer and roughen surfaces. Ensure surfaces are clean and dry prior to coating application
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 125 4 Hr - 2 Wk 6.56International GTA220
Full Coat
PolyurethaneInterthane 990
Color Range
Airless Spray, Brush, Conventional Spray, Roller, Air Spray
57 50 3 Hr - Ext 11.40International GTA713
175
NOTE : 1. The alternative thinner for Interthane 990 is GTA733.
PAINTING SPECIFICATION
18/07/2006
Page 22
COATING SYSTEM NO.7A(1) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Stainless Steel (NON INSULATED) facilities Operating < 110°C
This specification is designed to be used over Stainless Steel
Surface Preparation & Comments
� Light sweep to create profile by aluminium oxide or garnet for stainless steel substrate
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 125 4 Hr - 2 Wk 6.56International GTA220
Full Coat
PolyurethaneInterthane 990
Color Range
Airless Spray, Brush, Conventional Spray, Roller, Air Spray
57 50 3 Hr - Ext 11.40International GTA713
175
NOTE : 1. The alternative thinner for Interthane 990 is GTA733.
PAINTING SPECIFICATION
18/07/2006
Page 23
COATING SYSTEM NO.7A(2) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Stainless Steel (INSULATED) facilities Operating < 110°C
This specification is designed to be used over Stainless Steel
Surface Preparation & Comments
� Light sweep to create profile by aluminium oxide or garnet for stainless steel substrate
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 125 4 Hr - 2 Wk 6.56International GTA220
125
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
PAINTING SPECIFICATION
18/07/2006
Page 24
COATING SYSTEM NO.7A(3) For External Application : INITIAL PAINTING & MAINTENANCE PAINTING - Stainless Steel (INSULATED AND NON INSULATED) facilities Operating 110 - 540°C
This specification is designed to be used over Stainless Steel
Surface Preparation & Comments
� Light sweep to create profile by aluminium oxide or garnet for stainless steel substrate
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
High Temperature Silicone
Intertherm 50
AluminiumBrush, Roller, Air Spray
45 25 6 Hr - Ext 18.00International GTA007
Full Coat
High Temperature Silicone
Intertherm 50
AluminiumBrush, Roller, Air Spray
45 25 6 Hr - Ext 18.00International GTA007
50
NOTE : 1. The maximum heat resistance for Intertherm 50 is 540 degree C.
PAINTING SPECIFICATION
18/07/2006
Page 25
COATING SYSTEM NO.8A For External Application : INITIAL PAINTING - Carbon Steel Storage Tank
The specification given is our nearest product match for the system based on information received. Without further details of environment and conditions of service we cannot be certain that the system specified will give the best performance and therefore do not accept any liability for the performance of the product or loss or damage (other than death or personal injury resulting from our negligence) arising out of use of the product.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
AluminiumAirless Spray, Brush, Roller, Air Spray
82 200 6 Hr - Ext 4.10International GTA220
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 200 4 Hr - 2 Wk 4.10International GTA220
400
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
Please be informed that International Paint will cease manufacture of Tar containing products from the 1st of March 2005. The main reason for concern however is that products containing coal tar, coal tar pitches, tar acids, petroleum tar and petroleum tar pitches are all potential carcinogens (cancer causing). Therefore, we propose an alternative system as above.
PAINTING SPECIFICATION
18/07/2006
Page 26
COATING SYSTEM NO.8B For External Application : INITIAL AND MAINTENANCE PAINTING - Carbon Steel Storage Tank - Underside of Bottom plate (ONLY if painting is required for corrosion protection to supplement cathodic protection)
The specification given is our nearest product match for the system based on information received. Without further details of environment and conditions of service we cannot be certain that the system specified will give the best performance and therefore do not accept any liability for the performance of the product or loss or damage (other than death or personal injury resulting from our negligence) arising out of use of the product.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
AluminiumAirless Spray, Brush, Roller, Air Spray
82 200 6 Hr - Ext 4.10International GTA220
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 200 4 Hr - 2 Wk 4.10International GTA220
400
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
PAINTING SPECIFICATION
18/07/2006
Page 27
COATING SYSTEM NO.8C For External Application : Carbon Steel Storage Tank - Shell, Roof Plate, Stairways, Stair Treads, Gangways And Others External parts include the piping (NON GALVANISED)
The specification given is our nearest product match for the system based on information received. Without further details of environment and conditions of service we cannot be certain that the system specified will give the best performance and therefore do not accept any liability for the performance of the product or loss or damage (other than death or personal injury resulting from our negligence) arising out of use of the product.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy- Zinc Rich
Interzinc 52 GreyAirless Spray, Brush, Air Spray
59 75 2 Hr - Ext 7.87International GTA220
Full Coat
EpoxyIntergard 475HS tropical
BeigeAirless Spray, Brush, Roller, Air Spray
80 150 2 Hr - Ext 5.33International GTA007
Full Coat
PolyurethaneInterthane 990
Color Range
Airless Spray, Brush, Conventional Spray, Roller, Air Spray
57 50 3 Hr - Ext 11.40International GTA713
275
NOTE : 1. The alternative thinner for Interthane 990 is GTA733.
PAINTING SPECIFICATION
18/07/2006
Page 28
COATING SYSTEM NO.9A For External Application : INITIAL AND MAINTENANCE PAINTING - Timber Decks
A high performance coating specification for application on timbers.
Surface Preparation & Comments
� Lightly sand surface and ensure it is free of dust & dirt prior to application of coatings
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
AlkydInterprime 321
Aluminium Wood
Airless Spray, Brush, Conventional Spray, Roller
45 50 14 Hr - 14 D 9.00International GTA004
Full Coat
AlkydInterlac 665
Color Range
Airless Spray, Brush, Roller, Air Spray
48 50 14 Hr - Ext 9.60International GTA004
Full Coat
AlkydInterlac 665
Color Range
Airless Spray, Brush, Roller, Air Spray
48 50 14 Hr - Ext 9.60International GTA004
150
PAINTING SPECIFICATION
18/07/2006
Page 29
COATING SYSTEM NO.10 For External Application : Timber Decks - Markings
The specification given is our nearest product match for the system based on information received. Without further details of environment and conditions of service we cannot be certain that the system specified will give the best performance and therefore do not accept any liability for the performance of the product or loss or damage (other than death or personal injury resulting from our negligence) arising out of use of the product.
Surface Preparation & Comments
� Where necessary remove all weld splatter, smooth weld seams and sharp edges. Fresh water wash to remove all dirt and contamination Degrease according to SSPC-SP1 solvent cleaning.
� Lightly sand surface and ensure it is free of dust & dirt prior to application of coatings
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
PolyurethaneInterthane 990
Color Range
Airless Spray, Brush, Conventional Spray, Roller, Air Spray
57 50 3 Hr - Ext 11.40International GTA713
50
NOTE : 1. The alternative thinner for Interthane 990 is GTA733.
PAINTING SPECIFICATION
18/07/2006
Page 30
COATING SYSTEM NO.11 For External Application : Timber Decks - Living Quarters, Pressurised Building, Control Room (Interior)
A high performance coating specification for application on timbers.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Surface Tolerant Epoxy
Interseal 670HS
GreyAirless Spray, Brush, Roller, Air Spray
82 150 4 Hr - 2 Wk 5.47International GTA220
150
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
PAINTING SPECIFICATION
18/07/2006
Page 31
COATING SYSTEM NO.13A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Fuel Gas (Sweet And Sour) for Service Temperature Up To 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 32
COATING SYSTEM NO.14A(1) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Roof and Shell Plate Of Service Temperature Up To 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 33
COATING SYSTEM NO.14A(2) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Bottom Plate and Vessels Up To 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 100 5 Hr - 21 D 7.60International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 100 5 Hr - 21 D 7.60International GTA220
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 100 5 Hr - 21 D 7.60International GTA220
300
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 34
COATING SYSTEM NO.14A(3) (Alternative) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Bottom Plate Of Service Temperature Up To 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Interline 982 PrimroseAirless Spray, Brush, Roller, Air Spray
30 25 16 Hr - 28 D 12.00International GTA220
Full Coat
Glass Flake Epoxy
Interzone 505 tropical
BlackAirless Spray, Brush, Roller, Air Spray
90 400 5 Hr - 2 D 2.25International GTA220
425
PAINTING SPECIFICATION
18/07/2006
Page 35
COATING SYSTEM NO.15A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Naptha, Reformate, Jet A Fuel, Lube Oil, Fuel Oil, Gasoline (Leaded & Unleaded) For Service Temp. Up to 60°
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting..
PAINTING SPECIFICATION
18/07/2006
Page 36
COATING SYSTEM NO.16A For Internal Application : INITIAL PAIINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Diesel (Roof and Shell Plate) of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 37
COATING SYSTEM NO.16B For Internal Application : INITIAL PAIINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Diesel (Bottom Plate and Vessels) of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 100 5 Hr - 21 D 7.60International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 100 5 Hr - 21 D 7.60International GTA220
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 100 5 Hr - 21 D 7.60International GTA220
300
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting..
PAINTING SPECIFICATION
18/07/2006
Page 38
COATING SYSTEM NO.16C (ALTERNATIVE) For Internal Application : INITIAL PAIINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Diesel (Bottom Plate and Vessels) of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Interline 982 PrimroseAirless Spray, Brush, Roller, Air Spray
30 40 16 Hr - 28 D 7.50International GTA220
Full Coat
Glass Flake Epoxy
Interzone 505 tropical
BlackAirless Spray, Brush, Roller, Air Spray
90 400 5 Hr - 2 D 2.25International GTA220
440
NOTE : 1. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 39
COATING SYSTEM NO.17A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Sea Water, Produced Water, Brackish, Demineralised Water, Brine of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 40
COATING SYSTEM NO.18A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Steam (Condensate), Boiler Feed of Service Temperature up to 100°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Novolac
Interline 399
WhiteAirless Spray, Brush, Roller, Air Spray
67 100 16 Hr - 2 D 6.70International GTA220
Full Coat
Epoxy Novolac
Interline 399
GreyAirless Spray, Brush, Roller, Air Spray
67 100 16 Hr - 2 D 6.70International GTA220
Full Coat
Epoxy Novolac
Interline 399
WhiteAirless Spray, Brush, Roller, Air Spray
67 100 16 Hr - 2 D 6.70International GTA220
300
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 41
COATING SYSTEM NO.19A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Utility Air of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 42
COATING SYSTEM NO.19B (ALTERNATIVE) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Utility Air of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
Area Size: 1 m2
Coat Type
Description Product NameColour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
PolyesterInterzone 2000 Malaysia
BlackAirless Spray, Brush
85 400 5 Hr - 3 D 2.13International GTA065
400
PAINTING SPECIFICATION
18/07/2006
Page 43
COATING SYSTEM NO.19C For Internal Application : INITIAL PAINTING , MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Utility Air of Service Temperature more than 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Novolac
Interline 399
WhiteAirless Spray, Brush, Roller, Air Spray
67 125 16 Hr - 2 D 5.36International GTA220
Full Coat
Epoxy Novolac
Interline 399
GreyAirless Spray, Brush, Roller, Air Spray
67 125 16 Hr - 2 D 5.36International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 44
COATING SYSTEM NO.21A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Methanol Percroethalyne of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Novolac
Interline 399
WhiteAirless Spray, Brush, Roller, Air Spray
67 125 16 Hr - 2 D 5.36International GTA220
Full Coat
Epoxy Novolac
Interline 399
GreyAirless Spray, Brush, Roller, Air Spray
67 125 16 Hr - 2 D 5.36International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 45
COATING SYSTEM NO.21B (Alternative) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE (Alternative) - Methanol Percroethalyne of Service Temperature up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application Method
VS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Inorganic Zinc Rich Silicate
Interzinc 22
Greenish Grey
Airless Spray, Air Spray
63 75 8 Hr - Ext 8.40International GTA803
75
NOTE : 1. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 46
COATING SYSTEM NO.22A For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE - Triethylene Glycol / Methylethylene Glycol of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Phenolic
Interline 850
WhiteAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
Full Coat
Epoxy Phenolic
Interline 850
GreyAirless Spray, Brush, Roller, Air Spray
76 125 5 Hr - 21 D 6.08International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : 1. Interline 850 only available in White and Grey colours. 2. Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 47
COATING SYSTEM NO.22B (Alternative) For Internal Application : INITIAL PAINTING, MAINTENANCE PAINTING FOR BLAST CLEANED SURFACE AND POWER TOOL CLEANED SURFACE (Alternative) - Triethylene Glycol / Methylethylene Glycol of Service Temperature Up to 60°C
A high performance coating specification for exposure in immersed environments. The specification provided is based on a maximum operating temperature of 50 C. Coatings for immersed conditions require special consideration and you must contact International for detailed advice on preparation , application and cure prior to their use.
Surface Preparation & Comments
� Abrasive blast clean to Sa2.5 (ISO 8501-1:1988) or SSPC-SP10. If oxidation has occurred between blasting and application, the surface should be reblasted to the specified visual standard. Surface defects revealed by the blast cleaning process, should be ground, filled, or treated in the appropriate manner
� Hand or Power tool clean all damaged and corroded areas to a minimum standard of St3 of ISO 8501-1:1988 (Swedish Standard SIS 05 5900)/SSPC- SP3.
� Stripe coats should be applied to all welds, lap joints, plate edges, corners, sharp edges, and any other areas where spray application of the overall coating system may prove difficult resulting in low dry film thickness'
� Surface Preparation comments are included at the bottom of this page.
Area Size: 1 m2
Coat Type
DescriptionProduct Name
Colour Group
Application MethodVS %
DFT micron
Overcoating interval at 40 C
Min - Max
TSR m2/l
Thinner
Full Coat
Epoxy Novolac
Interline 399
WhiteAirless Spray, Brush, Roller, Air Spray
67 125 16 Hr - 2 D 5.36International GTA220
Full Coat
Epoxy Novolac
Interline 399
GreyAirless Spray, Brush, Roller, Air Spray
67 125 16 Hr - 2 D 5.36International GTA220
250
This specification complies with our environmental Ecotech Initiative to limit organic solvent emissions and certain potentially harmful substances such as isocyanates. For further information on Ecotech please contact International.
NOTE : Surface Preparation : Blast cleaning to ISO8501-1:1988, Sa2.5, or Power Tool cleaning to ISO8501-1:1988, St3 for minor touch-up painting.
PAINTING SPECIFICATION
18/07/2006
Page 48
Product List
Product Name Colour Group Reference
Intergard 475HS tropical
Beige EVA531/A (20L PACK SIZE) EX-STOCK
Interlac 665 Color Range CL SERIES (5L PACK SIZE) MADE-TO-ORDER STOCK
Interline 399 GreyTLA393/A (20L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Qty Required
Interline 399 WhiteTLA390/A (20L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required
Interline 850 Grey TLA851/A (20L PACK SIZE) EX-STOCK
Interline 850 White TLA850/A (20L PACK SIZE) EX-STOCK
Interline 982 PrimroseTPA018/A (5L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required
International GTA004 A GTA004 (20L PACK SIZE) EX-STOCK
International GTA007 A GTA007 (20L PACK SIZE) EX-STOCK
International GTA220 A GTA220 (20L PACK SIZE) EX-STOCK
International GTA733 A GTA733 (20L PACK SIZE) EX-STOCK
International GTA803 A GTA803 (20L PACK SIZE) EX-STOCK
Interprime 321Aluminium
WoodCWA021 (5L PACK SIZE) MADE-TO-ORDER STOCK
Interseal 670HS Aluminium EGA230/A (5L PACK SIZE) MADE-TO-ORDER STOCK
Interseal 670HS Grey EGA236/A (20L PACK SIZE) EX-STOCK
Interthane 990 Color Range PH SERIES/A (5L PACK SIZE) MADE-TO-ORDER STOCK
Intertherm 50 Aluminium HTA097 (5L PACK SIZE) EX-STOCK
Intertherm 875 GreyHAK766 (5L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required
Intertherm 875 WhiteHAB000 (5L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required
Intertherm 890 Dark GreyHTA290/A (5L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required
Interzinc 22 Greenish Grey QHA028/A (5L PACK SIZE) EX-STOCK
PAINTING SPECIFICATION
18/07/2006
Page 49
Product List
Product NameColour Group
Reference
Interzinc 52 Grey EPA142/A (5L PACK SIZE) EX-STOCK
Interzone 2000 Malaysia
BlackHGA329/A (10L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required
Interzone 2000 Malaysia
GreyHGA637/A (10L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required
Interzone 505 tropical BlackEGA879/A (20L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required
Interzone 505 tropical GloamingEGT000/A (20L PACK SIZE) MADE-TO-ORDER STOCK - Minimum Quantity Required