public input no. 5-nfpa 76-2017 [ global input ] statement of …€¦ · organization: ericsson...

130
Public Input No. 5-NFPA 76-2017 [ Global Input ] Replace the word "sensor" with "detector" throughout the document where it is used to refer to a spot-type smoke detector. Statement of Problem and Substantiation for Public Input Using the word "sensor" when referring to spot-type smoke detectors may cause confusion among users of the standard. As multi-criteria detectors (which are comprised of two or more sensors of various types) become more common, the confusion will become worse. Currently, the standard does use the word "detector" in several places, which will only further cause users to wonder if we are referring to two different devices. NFPA 76 is the only standard that I'm aware of that uses the term "sensor" to refer to a smoke detector. Submitter Information Verification Submitter Full Name: Scott Lang Organization: Honeywell International Street Address: City: State: Zip: Submittal Date: Fri Sep 08 10:35:48 EDT 2017 Committee: Committee Statement Resolution: FR-38-NFPA 76-2018 Statement: Using the word "sensor" when referring to spot-type smoke detectors may cause confusion among users of the standard. As multi-criteria detectors (which are comprised of two or more sensors of various types) become more common, the confusion will become worse. Currently, the standard does use the word "detector" in several places, which will only further cause users to wonder if we are referring to two different devices. NFPA 76 is the only standard that I'm aware of that uses the term "sensor" to refer to a smoke detector. Every use of "sensor" in the document was reviewed and confirmed to mean "smoke detector." National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar... 1 of 107 7/30/2018, 10:49 AM

Upload: others

Post on 22-Oct-2020

5 views

Category:

Documents


1 download

TRANSCRIPT

  • Public Input No. 5-NFPA 76-2017 [ Global Input ]

    Replace the word "sensor" with "detector" throughout the document where it is used to refer to aspot-type smoke detector.

    Statement of Problem and Substantiation for Public Input

    Using the word "sensor" when referring to spot-type smoke detectors may cause confusion among users of the standard. As multi-criteria detectors (which are comprised of two or more sensors of various types) become more common, the confusion will become worse. Currently, the standard does use the word "detector" in several places, which will only further cause users to wonder if we are referring to two different devices. NFPA 76 is the only standard that I'm aware of that uses the term "sensor" to refer to a smoke detector.

    Submitter Information Verification

    Submitter Full Name: Scott LangOrganization: Honeywell InternationalStreet Address:City:State:Zip:Submittal Date: Fri Sep 08 10:35:48 EDT 2017Committee:

    Committee Statement

    Resolution: FR-38-NFPA 76-2018Statement: Using the word "sensor" when referring to spot-type smoke detectors may cause confusion among

    users of the standard. As multi-criteria detectors (which are comprised of two or more sensors ofvarious types) become more common, the confusion will become worse. Currently, the standard doesuse the word "detector" in several places, which will only further cause users to wonder if we arereferring to two different devices. NFPA 76 is the only standard that I'm aware of that uses the term"sensor" to refer to a smoke detector. Every use of "sensor" in the document was reviewed andconfirmed to mean "smoke detector."

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    1 of 107 7/30/2018, 10:49 AM

  • Public Input No. 92-NFPA 76-2018 [ Section No. 1.1.1 ]

    1.1.1

    Telecommunications facilities include signal-processing equipment areas, cable entrance facility areas,power areas (including battery areas) , main distribution frame areas, standby engine areas, technicalsupport areas, administrative areas, and building services and support areas occupied by atelecommunications service provider.

    Statement of Problem and Substantiation for Public Input

    Battery fire issues are a major concern for fire services. It would be helpful upfront to clarify that NFPA 76 applies to telecommunications batteries.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 15:14:45 EST 2018Committee:

    Committee Statement

    Resolution: "Power areas" is a defined term which includes "power equipment" which is defined as includingbatteries.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    2 of 107 7/30/2018, 10:49 AM

  • Public Input No. 83-NFPA 76-2018 [ Section No. 1.1.2 ]

    1.1.2 *

    Provisions for small structures that are normally unoccupied and that house telecommunicationsequipment, including on-grade, walk-in cabinets; on-grade huts; cell huts; and controlled environmentalvaults (CEVs), are provided in Chapter 11 .

    Statement of Problem and Substantiation for Public Input

    The content is deleted here and moved to 1.3 Application as it is guidance on application of the standard.

    Related Public Inputs for This Document

    Related Input RelationshipPublic Input No. 85-NFPA 76-2018 [Sections 1.3.1, 1.3.2]

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 14:58:58 EST 2018Committee:

    Committee Statement

    Resolution: FR-1-NFPA 76-2018Statement: The content is deleted here and moved to 1.3 Application as it is guidance on application of the

    standard.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    3 of 107 7/30/2018, 10:49 AM

  • Public Input No. 87-NFPA 76-2018 [ Section No. 1.3 [Excluding any Sub-Sections] ]

    The provisions of this standard shall provide a reasonable level of protection from loss of life, property, andservice continuity from fire.

    This standard applies to free-standing telecommunications facilities, as well as joint use facilities whenseperated by a fire rated partition in accordance with Section 6.1.4.2.

    Statement of Problem and Substantiation for Public Input

    Based on conversations with fire services personnel, it would be helpful to the use of NFPA 76 to upfront state it is applicable to both dedicated and joint use buildings. The detailed information to support this use is included in the body of the standard, but guidance to it up front would be beneficial.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 15:04:38 EST 2018Committee:

    Committee Statement

    Resolution: FR-49-NFPA 76-2018Statement: This revision tries to clearly identify the applicability of NFPA 76 by stating in the application section

    that it is applicable to both dedicated and joint use buildings. The detailed information to support thisuse is included in the body of the standard, but guidance to it up front will be beneficial.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    4 of 107 7/30/2018, 10:49 AM

  • Public Input No. 85-NFPA 76-2018 [ Sections 1.3.1, 1.3.2 ]

    Sections 1.3.1, 1.3.2

    1.3.1

    The requirements of Chapter 4 shall determine the fire protection program for each facility.

    1.3. 1.1 *

    Provisions for small structures that are normally unoccupied and that house telecommunicationsequipment, including on-grade, walk-in cabinets; on-grade huts; cell huts; and controlled environmentalvaults (CEVs), are provided in Chapter 11 .

    1.3. 2*

    For purposes of application of NFPA 101 and NFPA 5000, telecommunications facilities shall be classifiedas special-purpose industrial occupancies.

    Statement of Problem and Substantiation for Public Input

    Wording moved from 1.1.2 as the content speaks of application of the standard.

    Related Public Inputs for This Document

    Related Input RelationshipPublic Input No. 83-NFPA 76-2018 [Section No. 1.1.2] information moved from 1.1.2

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 15:01:41 EST 2018Committee:

    Committee Statement

    Resolution: FR-1-NFPA 76-2018Statement: The content is deleted here and moved to 1.3 Application as it is guidance on application of the

    standard.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    5 of 107 7/30/2018, 10:49 AM

  • Public Input No. 42-NFPA 76-2018 [ New Section after 2.2 ]

    NFPA 855, Standard for the Installation of Stationary Energy Storage Systems, XXXX edition

    Statement of Problem and Substantiation for Public Input

    This proposed standard will have references to NFPA 76 and should be incorporated in NFPA 76.

    Submitter Information Verification

    Submitter Full Name: Jeffrey BetzOrganization: AT&T CorporationStreet Address:City:State:Zip:Submittal Date: Wed Jan 03 13:43:29 EST 2018Committee:

    Committee Statement

    Resolution: NFPA 855 has not been through the entire process of development and is yet to be an officiallyapproved standard. It would be inappropriate to reference it at this time.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    6 of 107 7/30/2018, 10:49 AM

  • Public Input No. 20-NFPA 76-2018 [ Section No. 2.3.4 ]

    2.3.4 UL Publications.

    Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

    ANSI/ UL 44, Thermoset-Insulated Wires and Cables, 2014.

    ANSI/ UL 83, Thermoplastic-Insulated Wire and Cables, 2014 2017 .

    ANSI/ UL 444, Communications Cables, 2008, revised 2010 2017 .

    ANSI/ UL 568, Nonmetallic Cable Tray Systems, 2002, reaffirmed 2009.

    UL 723, Standard for Test For Surface Burning Characteristics of Building Materials, 2008 2013 .

    ANSI/ UL 900, Standard for Air Filter Units, 2004, revised 2009 2015 .

    ANSI/ UL 1277, Electrical Power and Control Tray Cables with Optional Optical-Fiber Members, 2010.

    ANSI/ UL 1651, Optical Fiber Cable, 2008 2015 .

    ANSI/ UL 1666, Standard Test for Flame Propagation Height of Electrical and Optical-Fiber Cables InstalledVertically in Shafts, 2007.

    ANSI/ UL 1685, Standard for Vertical Tray Fire-Propagation and Smoke-Release Test for Electrical andOptical-Fiber Cables, 2007, including revisions through July 7, 2010.

    ANSI/ UL 2024, Cable Routing Assemblies and Communications Raceways, 2014, including revisionsthrough January 9 revised , 2015.

    ANSI/ UL 60950-1, Information Technology Equipment — Safety — Part 1: General Requirements, 2013.

    Statement of Problem and Substantiation for Public Input

    Standard update to newest version of the standards. Many years ago, UL preferred the ANSI/UL reference because there was a transition of traditional UL standards towards an ANSI standards development process.

    Now, years later, a large majority of UL Standards are ANSI approved and follow the ANSI development and maintenance process. However, sometimes readers are confused because they don’t understand the standards are actually UL standards, not developed by ANSI. There are many other references to standards promulgated by other standards development organizations where they are considered ANSI approved but do not include ANSI in the reference.

    Submitter Information Verification

    Submitter Full Name: Kelly NicolelloOrganization: UL LLCAffiliation: UL LLCStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 15:17:08 EST 2018Committee:

    Committee Statement

    Resolution: FR-3-NFPA 76-2018 The ANSI designation is an important identifier as it makes it clear to users of

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    7 of 107 7/30/2018, 10:49 AM

  • the standard that the documents referenced in the standard are those published through an ANSIapproved process. Unless all standards from a standards developer are ANSI accredited it makessense to include it in the referenced publication sections.

    Statement: Standard update to newest version of the standards.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    8 of 107 7/30/2018, 10:49 AM

  • Public Input No. 43-NFPA 76-2018 [ Section No. 2.3.5 ]

    2.3.5 Other Publications.

    California Technical Bulletin 133, Flammability Test Procedure for Seating Furniture for Use in PublicOccupancies.

    Merriam-Webster’s Collegiate Dictionary, 11th 11th edition, Merriam-Webster, Inc., Springfield, MA,2003 2014 .

    Telcordia GR-63-CORE, Network Equipment Building System (NEBS)™ Requirements: PhysicalProtection, 2012 2017 .

    Statement of Problem and Substantiation for Public Input

    Update of editions of resource materials

    Submitter Information Verification

    Submitter Full Name: Jeffrey BetzOrganization: AT&T CorporationStreet Address:City:State:Zip:Submittal Date: Wed Jan 03 13:53:34 EST 2018Committee:

    Committee Statement

    Resolution: FR-4-NFPA 76-2018Statement: Update of editions of resource materials

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    9 of 107 7/30/2018, 10:49 AM

  • Public Input No. 15-NFPA 76-2018 [ Section No. 3.3.3 ]

    3.3.3 Cable Routing Assembly.

    A single channel or connected multiple channels, as well as associated fittings, forming a structural systemthat is used to supportand support and route communications wires and cables, optical fiber cables, datacables associated with information technology and communications equipment, Class 2 and Class 3cables, and power-limited fire alarm cables. [70, 2014]

    Statement of Problem and Substantiation for Public Input

    Typographical error in text.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 13:46:52 EST 2018Committee:

    Committee Statement

    Resolution: FR-5-NFPA 76-2018Statement: A typographical error in the text has been corrected and the definition has been revised to match the

    extraction from the 2017 edition of the NEC.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    10 of 107 7/30/2018, 10:49 AM

  • Public Input No. 11-NFPA 76-2018 [ Section No. 3.3.4 ]

    3.3.4 Cable Telecommunications.

    One- and two-way communications service provided over a network, generally through optical fiber andfiber or coaxial cable.

    Statement of Problem and Substantiation for Public Input

    Cable telecommunications are generally through optical fiber or coaxial cable. They don't need to include both fiber and coaxial to be cable telecommunications as implied by the text.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 13:33:30 EST 2018Committee:

    Committee Statement

    Resolution: FR-6-NFPA 76-2018Statement: Cable telecommunications are generally through optical fiber or coaxial cable. They don't need to

    include both fiber and coaxial to be cable telecommunications as implied by the text.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    11 of 107 7/30/2018, 10:49 AM

  • Public Input No. 12-NFPA 76-2018 [ Section No. 3.3.5 ]

    3.3.5 Central Office (CO).

    A telecommunications facility also known as a telephone exchange or , wire center, or switching center.

    Statement of Problem and Substantiation for Public Input

    In some standards and local regions, COs are also spoken of as wire centers.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 13:37:47 EST 2018Committee:

    Committee Statement

    Resolution: FR-7-NFPA 76-2018Statement: In some standards and local regions, COs are also spoken of as wire centers.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    12 of 107 7/30/2018, 10:49 AM

  • Public Input No. 14-NFPA 76-2018 [ Section No. 3.3.15 ]

    3.3.15 Telecommunications Facility.

    A building or portion of a building that includes telecommunications a telecommunications equipment areaand support areas .

    Statement of Problem and Substantiation for Public Input

    A telecommunications facility need not include a support area as implied by the definition.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 13:43:46 EST 2018Committee:

    Committee Statement

    Resolution: FR-8-NFPA 76-2018Statement: A telecommunications facility need not include a support area as implied by the definition.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    13 of 107 7/30/2018, 10:49 AM

  • Public Input No. 13-NFPA 76-2018 [ Section No. 3.3.18 ]

    3.3.18 Walk-In Cabinet.

    A partially An on grade or partially below grade room, accessible without a ladder, that housestelecommunications equipment and is under controlled temperature and humidity.

    Statement of Problem and Substantiation for Public Input

    Walk-in cabinets are not required to be below grade as the wording implies.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 13:41:42 EST 2018Committee:

    Committee Statement

    Resolution: FR-9-NFPA 76-2018Statement: Walk-in cabinets are not required to be below grade as the wording implies.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    14 of 107 7/30/2018, 10:49 AM

  • Public Input No. 16-NFPA 76-2018 [ Section No. 3.4.2 ]

    3.4.2 Building Services and Support Areas.

    Areas or rooms that typically include utility areas, mechanical equipment areas, ac electrical switch gear,maintenance shops, loading docks, and associated storage areas.

    Statement of Problem and Substantiation for Public Input

    Clarify that building services areas include ac switch gear, as opposed to dc equipment which is considered telecommunications equipment contained in a power area.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 13:48:38 EST 2018Committee:

    Committee Statement

    Resolution: FR-10-NFPA 76-2018Statement: Clarify that building services areas include ac switch gear, as opposed to dc equipment which is

    considered telecommunications equipment contained in a power area.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    15 of 107 7/30/2018, 10:49 AM

  • Public Input No. 74-NFPA 76-2018 [ New Section after 3.5.1 ]

    Combination Fire Detection (CFD) Systems.

    Systems that use Early Warning Fire Detection (EWFD) to sense a fire condition at the ceiling or within araised floor cavity in combination with Very Early Warning Fire Detection (VEWFD) sensors at the return airpoints within air circulation paths. This system supports the existing widely deployed EWFD systems andenhances the detection capabilities with that of VEWFD technologies.

    Statement of Problem and Substantiation for Public Input

    This proposal recognizes the fire detection technologies serving the industry, considering the risk profiles of these facilities, and addresses the industry best practices used by most corporations in their current deployment of fire detection systems. This provides industry options based upon internal risk exposures and the industry's low fire loss history.

    Submitter Information Verification

    Submitter Full Name: Jeffrey BetzOrganization: AT&T CorporationStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 13:52:17 EST 2018Committee:

    Committee Statement

    Resolution: This terminology is not used in the standard. See committee statement on Public Inputs 75 through82.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    16 of 107 7/30/2018, 10:49 AM

  • Public Input No. 69-NFPA 76-2018 [ Section No. 3.6.8 ]

    3.6.8 Telecommunications Equipment.

    Equipment and systems, normally found in a telecommunications facility, that are used for transmitting,receiving, switching, and management of signals, such as electrical, optical, or electromagnetic, by wire,fiber, or through the air. The wire, cable, and electrical/electronic equipment, including signal-processingequipment, cable entrance equipment, batteries and power equipment, main distribution frame equipment,and standby engine equipment are all examples of telecommunications equipment .

    Statement of Problem and Substantiation for Public Input

    The original text includes examples of telecommunications equipment. The added text explicitly includes batteries which are of keen interest to fire services and adds a definition of telecommunications equipment to support the examples listed.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 10:50:37 EST 2018Committee:

    Committee Statement

    Resolution: FR-11-NFPA 76-2018Statement: The original text includes examples of telecommunications equipment. The added text explicitly

    includes batteries which are of keen interest to fire services and adds a definition oftelecommunications equipment to support the examples listed.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    17 of 107 7/30/2018, 10:49 AM

  • Public Input No. 97-NFPA 76-2018 [ Section No. 4.2.2.1 ]

    4.2.2.1

    The following elements shall be documented as part of the risk management analysis:

    (1) Life safety

    (2) Service continuity

    (3) Eco nomic impact to cusomers due to loss of connectivty of voice and data

    (4) Size and value of the facility

    (5) Restoration plans

    (6) Availability of readily deployable replacement telecommunications infrastructure

    (7) Response time to an alarm

    (8) Local fire-fighting capabilities

    (9) Redundant telecommunications infrastructure

    (10) Reputation impact

    Statement of Problem and Substantiation for Public Input

    The economic impact to telecommunication customers due to loss of voice and especially data today is almost immeasurable. I feel this text should be a part of telecommunications risk to protect the public. Additionally, the impact on a companies reputation today is also something that should be considered.

    Related Public Inputs for This Document

    Related Input RelationshipPublic Input No. 96-NFPA 76-2018 [Section No. A.8.2.3.7]

    Submitter Information Verification

    Submitter Full Name: Paul NelsonOrganization: Orr Protection Systems, Inc.Affiliation: FSSAStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 17:11:22 EST 2018Committee:

    Committee Statement

    Resolution: FR-12-NFPA 76-2018Statement: The economic impact to telecommunication customers due to loss of voice and especially data today

    is almost immeasurable. This consideration should be a part of telecommunications risk to protect thepublic that is considered. Additionally, the impact on a companies reputation today is also somethingthat should be considered.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    18 of 107 7/30/2018, 10:49 AM

  • Public Input No. 95-NFPA 76-2018 [ New Section after 6.1.1 ]

    FIGURE 6.1This figure provides a summary of requirements from Chapter 6.

    Insert current FIGURE A.6.1 to be modified to reflect new edition requirements.

    Additional Proposed Changes

    File Name Description Approved_6.1._NFPA76.docx Figure 6.1

    Statement of Problem and Substantiation for Public Input

    Provides a user friendly format adopted in standard for those using the standard.

    Submitter Information Verification

    Submitter Full Name: Jeffrey BetzOrganization: AT&T CorporationStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 15:38:59 EST 2018Committee:

    Committee Statement

    Resolution: Inserting the Figure into the body of the standard will require a detailed review and wording to requiresome compliance with it. A review as to how the Figure works with prescriptive code requirements willneed to be conducted to avoid conflicts or duplication.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    19 of 107 7/30/2018, 10:49 AM

  • Public Input No. 72-NFPA 76-2018 [ Section No. 6.8.5.1 [Excluding any Sub-Sections] ]

    All signal-processing equipment areas including areas housing informtion technology equipment , whetherowned or co-located, shall be designated as Level A, Level B, or Level C, based on the classification inaccordance with 8.8.3 of the signal-processing equipment within the area.

    Statement of Problem and Substantiation for Public Input

    Recognizes the potential inclusion of information technology equipment in new applications of telecommunications services.

    Submitter Information Verification

    Submitter Full Name: Jeffrey BetzOrganization: AT&T CorporationStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 13:39:59 EST 2018Committee:

    Committee Statement

    Resolution: FR-13-NFPA 76-2018Statement: Making this apply more broadly to all equipment in the area recognizes the potential inclusion of

    information technology equipment in new applications of telecommunications services.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    20 of 107 7/30/2018, 10:49 AM

  • Public Input No. 73-NFPA 76-2018 [ Section No. 6.8.5.1.2 ]

    6.8.5.1.2

    All new signal-processing equipment or information technology equipment , whether owned or co-located,shall be classified as Level A, Level B, or Level C in accordance with 8.8.3.

    Statement of Problem and Substantiation for Public Input

    Addresses new technologies being used within the industry.

    Submitter Information Verification

    Submitter Full Name: Jeffrey BetzOrganization: AT&T CorporationStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 13:44:52 EST 2018Committee:

    Committee Statement

    Resolution: FR-13-NFPA 76-2018Statement: Making this apply more broadly to all equipment in the area recognizes the potential inclusion of

    information technology equipment in new applications of telecommunications services.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    21 of 107 7/30/2018, 10:49 AM

  • Public Input No. 71-NFPA 76-2018 [ New Section after 6.8.5.3 ]

    6.8.5.3 add:

    Mixing of Level A, B and C signaling-processing and information technology equipment

    Signal-procesing and information technology equipment of Level B and C shall be premitted to be locatedwithin all areas (A,B & C) povided that the the equipment housing (in-cabinet) is provided with internal firedetetion and fire suppession.

    Statement of Problem and Substantiation for Public Input

    This provides for the expanded use of the current options of Table 6.8.5.6 applications with in-cabinet fire detection and fire suppression for all Level B and C signal-processing equipment or information technology equipment to be co-located within Level A signal-processing equipment areas.

    Submitter Information Verification

    Submitter Full Name: Jeffrey BetzOrganization: AT&T CorporationStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 13:25:17 EST 2018Committee:

    Committee Statement

    Resolution: The committee recognizes that a solution should be found for protection of these situations. Theproposed text is not complete and an acceptable solution needs to have technical reasoning anddefine the complete impact of such an approach on the other provisions of the standard. A task grouphas been established to further investigate and propose requirements.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    22 of 107 7/30/2018, 10:49 AM

  • Public Input No. 75-NFPA 76-2018 [ Section No. 6.8.6.1 [Excluding any Sub-Sections] ]

    In telecommunications facilities containing greater than 232 m2 (2500 ft2) of signal-processing equipmentareas, the signal-processing equipment areas shall be provided with a very early warning fire detection(VEWFD) system for detection and or combination fire detection (CFD) system for detection and alarmprocessing in accordance with Chapter 8.

    Statement of Problem and Substantiation for Public Input

    Provides for new options based upon individual corporate risk factors and the choice of adequate fire detection for a signal-processing space.

    Submitter Information Verification

    Submitter Full Name: Jeffrey BetzOrganization: AT&T CorporationStreet Address:City:State:Zip:Submittal Date: Thu Jan 04 14:25:37 EST 2018Committee:

    Committee Statement

    Resolution: The proposed approach would lower the protection criteria from what is currently specified in NFPA76 but provides no technical justification for the change. The limited research available (FireProtection Research Foundation; Validation of Modeling Tools for Detection Design in High Air FlowEnvironments) indicates that the approach might not be appropriate as proposed. Other documentswhich specify detection criteria for similar environments, such as NFPA 318, should be reviewed andconsidered.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    23 of 107 7/30/2018, 10:49 AM

  • Public Input No. 17-NFPA 76-2018 [ New Section after 6.10.1.1 ]

    TITLE OF NEW CONTENT6.10.1.3 Automatic fire suppression systems shall not be required in power areas.

    Type your content here ...

    Statement of Problem and Substantiation for Public Input

    Clarifies that automatic suppression is not required in these areas, consistent with current NFPA 76 and other codes which apply to electrical rooms and power rooms.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 14:03:10 EST 2018Committee:

    Committee Statement

    Resolution: Fire suppression is not required by NFPA 76 in these spaces to begin with. There is no reason to addthis specific section under the power areas section.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    24 of 107 7/30/2018, 10:49 AM

  • Public Input No. 18-NFPA 76-2018 [ Section No. 6.10.8 [Excluding any Sub-Sections] ]

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    25 of 107 7/30/2018, 10:49 AM

  • Chapter 6.10.8 Special Hazards

    6.10.8.1 General.6.10.8.1.1

    Telecommunications battery systems shall comply with this chapter.

    6.10.8.2 Lead-Acid and Nickel-Cadmium Batteries.6.10.8.2.1 General.Stationary storage battery systems having an electrolyte capacity of more than 100 gal (378.5 L) insprinklered buildings or 50 gal (189.3 L) in unsprinklered buildings for flooded lead-acid, nickel-cadmium,and valve-regulated lead–acid (VRLA) batteries used for facility standby power, emergency power, oruninterrupted power supplies shall be in accordance with this section and the Table 6.10.8.2.1.

    Table 6.10.8.2.1 Battery Requirements

    Nonrecombinant Batteries Recombinant Batteries

    Requirement

    Flooded

    .Lead-Acid

    Flooded Nickel-Cadmium (Ni-Cd)

    Valve-Regulated Lead–Acid (VRLA)

    Safety caps Ventingcaps Venting capsSelf-resealing flame-arrestingcaps

    Thermal runawaymanagement

    Notrequired Not required Required

    Spill control Required Required Not required

    Neutralization Required Required Required

    Ventilation Required Required Required

    Signage Required Required Required

    Seismic control Required Required Required

    Fire detection Required Required Required

    6.10.8.2.2 Safety Features.6.10.8.2.2.1 Safety Venting.Batteries shall be provided with safety venting caps per 6.10.8.2.2.1.1 and 6.10.8.2.2.1.2.

    6.10.8.2.2.1.1 Nonrecombinant Batteries.Vented lead-acid and nickel-cadmium shall be provided with safety venting caps.

    6.10.8.2.2.1.2 Recombinant Batteries.VRLA shall be equipped with self-resealing flame-arresting safety vents.

    6.10.8.2.2.2 Thermal Runaway.VRLA systems shall be provided with a listed device or other approved method to preclude, detect, andcontrol thermal runaway.

    6.10.8.2.2.3 Location and Occupancy Separation.6.10.8.2.2.3.1

    Battery systems shall be permitted in the same room as the equipment that they support.

    6.10.8.2.2.3.2

    Battery systems shall be housed in a noncombustible, locked cabinet or other enclosure to prevent accessby unauthorized personnel unless located in a separate equipment room accessible only to authorized

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    26 of 107 7/30/2018, 10:49 AM

  • personnel.

    6.10.8.2.2.3.3

    Battery systems shall be located in a room separated from other portions of the building by a minimum of a1-hour fire barrier.

    6.10.8.2.2.3.4

    When telecommunications equipment is located in a structure or building housing multiple tenants oroccupancies which include assembly, educational, detention and correction facilities; health care,ambulatory health care, and day care centers; and, residential board and care and residential occupancies,battery systems shall be located in a room separated from other portions of the building by a minimum of a2-hour fire barrier.

    6.10.8.2.2.4 Spill Control.6.10.8.2.2.4.1

    Rooms, buildings, or areas containing free-flowing liquid electrolyte in individual vessels having a capacityof more than 55 gal (208 L) or multiple vessels having an aggregate capacity exceeding 1000 gal (3785 L)shall be provided with spill control to prevent the flow of liquids to adjoining areas.

    6.10.8.2.2.4.2 * An approved method and materials for the control of a spill of electrolyte shall be provided that will becapable of controlling a spill from the single largest vessel.

    6.10.8.2.2.4.3

    VRLA batteries with immobilized electrolyte shall not require spill control.

    6.10.8.2.2.5 Neutralization.6.10.8.2.2.5.1 * An approved method to neutralize spilled electrolyte shall be provided.

    6.10.8.2.2.5.2

    For VRLA batteries, the method shall be capable of neutralizing a spill from the largest battery to a pHbetween 7.0 and 9.0.

    6.10.8.2.2.6 * Ventilation.For flooded lead-acid, flooded nickel-cadmium, and VRLA batteries, ventilation shall be provided for roomsand cabinets in accordance with the mechanical code and one of the following:

    (1) The ventilation system shall be designed to limit the maximum concentration of hydrogen to1.0 percent of the total volume of the room during the worst-case event of simultaneous “boost”charging of all the batteries, in accordance with nationally recognized standards.

    (2) Continuous ventilation shall be provided at a rate of not less than 1 ft 3 /min/ft 2 (5.1L/sec/m 2 ) of floor area of the room or cabinet.

    6.10.8.2.2.7 Environment.The battery environment shall be controlled or analyzed to maintain temperature in a safe operating rangefor the specific battery technology used.

    6.10.8.2.2.8 Signs.6.10.8.2.2.8.1

    Doors or accesses into the following shall be provided with approved signs:

    (1) Rooms containing stationary storage battery systems

    (2) Other areas containing stationary storage battery systems

    6.10.8.2.2.8.2

    For rooms that contain VRLA batteries, the signs required by 6.10.8.2.2.8.1 shall

    comply with NFPA 1.state the following:

    This room contains:

    (1) Stationary storage battery systems

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    27 of 107 7/30/2018, 10:49 AM

  • (2) Energized electrical circuits

    6.10.8.2.2.8.3

    For rooms that contain lead-acid or flooded Ni-Cd batteries, the signs required by 6.10.8.2.2.8.1 shall statethe following:

    This room contains:

    (1) Stationary storage battery systems

    (2) Energized electrical circuits

    (3) Corrosive battery electrolyte

    6.10.8.2.2.8.4

    Battery cabinets shall be provided with exterior labels that identify the manufacturer and model number ofthe system and electrical rating (i.e., voltage and current) of the contained battery system.

    6.10.8.2.2.8.5

    Signs shall be provided within battery cabinets to indicate the relevant electrical, chemical, and fire hazard.

    6.10.8.2.2.9 Seismic Protection.Battery systems shall be seismically braced in accordance with the building code.

    6.10.8.2.2.10 Smoke Detection.An approved automatic smoke detection system shall be installed in rooms containing stationary batterystorage systems in accordance with NFPA 72 .

    6.10.8.3 * Additional Battery Technologies.6.10.8.3.1 General.Energy storage systems having a capacity greater than the quantities listed in Table 6.10.8.3.1 shall be inaccordance with Section 6.10.8.3.

    Table 6.10.8.3.1 Energy Storage System Threshold Quantities

    Type Capacity a

    Lithium batteries, all types 20 KWh( 18.0 Mega joules)

    Sodium batteries, all types 20 KWh (18.0 Mega joules) c

    Flow batteries b 20 KWh (18.0 Mega joules)

    Other battery technologies 10 KWh (10.8 Mega joules)

    Capacitors 70 KWh (25.2 Mega joules)

    Notes:

    a For batteries and capacitors rated in Amp-Hours, KWh should equal rated voltage times amp-hour ratingdivided by 1000.

    b Includes vanadium, zinc-bromine, polysulfide-bromide, and other flowing electrolyte-type technologies.

    c Or 70 KWh (25.2 Mega joules) for sodium-ion technologies.

    6.10.8.3.2 * Stationary Storage Battery Systems.6.10.8.3.2.1 Location and Occupancy Separation.Stationary storage battery systems shall be located and constructed in accordance with this section.

    6.10.8.3.2.1.1

    Stationary storage battery systems shall be housed in a noncombustible, locked cabinet or other enclosureto prevent access by unauthorized personnel unless located in a separate equipment room accessible onlyto authorized personnel.

    6.10.8.3.2.1.2 Location.6.10.8.3.2.1.2.1

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    28 of 107 7/30/2018, 10:49 AM

  • Stationary storage battery systems shall not be located in areas where the floor is located more than 75 ft(22,860 mm) above the lowest level of fire department vehicle access, or where the floor level is more than30 ft (9144 mm) below the finished floor of the lowest level of exit discharge, unless otherwise permitted by6.10.8.3.2.1.2.

    6.10.8.3.2.1.2.2

    Installations on noncombustible rooftops of buildings exceeding 75 ft (22,860 mm) in height that do notobstruct fire department rooftop operations shall be permitted when approved by the AHJ.

    6.10.8.3.2.1.3 Separation.Rooms containing stationary storage battery systems shall be located in high-hazard occupancies, or shallbe separated from other areas of the building as stated in 6.10.8.3.2.1.3.1 and 6.10.8.3.2.1.3.2. Stationarystorage battery systems shall be allowed to be in the same room with the equipment they support.

    6.10.8.3.2.1.3.1

    Stationary storage battery systems shall be located in a room separated from other portions of the buildingby a minimum of a 1-hour fire barrier.

    6.10.8.3.2.1.3.2

    When telecommunications equipment is located in a structure or building housing multiple tenants oroccupancies which include assembly, educational, detention, and correction facilities; health care,ambulatory health care, and day care centers; and residential board and care and residential occupancies,stationary storage battery systems shall be located in a room separated from other portions of the buildingby a minimum of a 2-hour fire barrier.

    6.10.8.3.2.2 Maximum Allowable Quantities.6.10.8.3.2.2.1

    Fire areas within buildings containing stationary storage battery systems exceeding the maximum allowablequantities in Table 6.10.8.3.2.2.1 shall comply with all applicable ordinary-hazard and high-hazardrequirements as identified in 6.2.2 of NFPA 101 and the building code.

    Table 6.10.8.3.2.2.1

    Type Maximum Allowable Quantities a Hazard Classification

    Lithium batteries, all types 600 KWh High hazard c

    Sodium batteries, all types 600 KWh High hazard c

    Flow batteries b 600 KWh High hazard c

    Other battery technologies 200 KWh High hazard c

    Notes:

    a For batteries rated in amp-hHours, KWh should equal rated voltage times amp-hour rating divided by1000.

    b Includes vanadium, zinc-bromine, polysulfide-bromide, and other flowing electrolyte-type technologies.

    c Can be permitted to be ordinary hazard classification if approved by the AHJ based on (1) a hazardmitigation analysis conducted in accordance with 6.10.8.3.2.4 and (2) large-scale fire and fault conditiontesting conducted or witnessed and reported by an approved testing laboratory that shows that a fireinvolving the stationary storage battery system is contained within the room for a duration equal to the fireresistance rating of the room separation required in 6.10.8.3.2.1.3.1 or 6.10.8.3.2.1.3.2, as applicable.

    6.10.8.3.2.2.2

    Where approved by the AHJ, areas containing stationary storage battery systems that exceed the amountsin Table 6.10.8.3.2.2.1 shall be permitted to be treated as a ordinary-hazard and not a high-hazardclassification based on a hazardous mitigation analysis in accordance with 6.10.8.3.2.4 and large-scale fireand fault condition testing conducted or witnessed and reported by an approved testing laboratory.

    6.10.8.3.2.2.3

    Where areas within buildings contain a combination of energy system technologies, the total aggregate

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    29 of 107 7/30/2018, 10:49 AM

  • quantities shall be determined based on the sum of percentages of each type divided by the maximumallowable quantity of each type. If the sum of the percentages exceeds 100 percent, the area shall betreated as a high-hazard classification in accordance with Table 6.10.8.3.2.2.1.

    6.10.8.3.2.3 * Battery Arrays.6.10.8.3.2.3.1

    Battery arrays shall comply with 6.10.8.3.2.3.2 and 6.10.8.3.2.3.3 unless otherwise permitted by6.10.8.3.2.3.4 or 6.10.8.3.2.3.5.

    6.10.8.3.2.3.2

    Storage batteries, prepackaged stationary storage battery systems, and pre-engineered stationary storagebattery systems shall be segregated into arrays not exceeding 50 KWh (180 Mega joules) each.

    6.10.8.3.2.3.3

    Each array shall be spaced a minimum 3 ft (914 mm) from other arrays and from walls in the storage roomor area. The storage arrangements shall comply with the egress provisions in NFPA 101 .

    6.10.8.3.2.3.4

    Listed pre-engineered stationary storage battery systems and prepackaged stationary storage batterysystems shall not exceed 250 KWh (900 Mega joules) each.

    6.10.8.3.2.3.5

    The AHJ shall be permitted to approve listed pre-engineered and prepackaged battery arrays with largercapacities or smaller battery array spacing if large-scale fire and fault condition testing conducted orwitnessed and reported by an approved testing laboratory is provided showing that a fire involving onearray will not propagate to an adjacent array, and be contained within the room for a duration equal to thefire resistance rating of the room separation required by 6.10.8.3.2.1.3.

    6.10.8.3.2.4 Hazard Mitigation Analysis.A failure mode and effects analysis (FMEA) or other approved hazard mitigation analysis shall be providedto the AHJ when any of the following conditions are present:

    (1) Battery technologies not specifically identified in Table 6.10.8.3.1 are provided.

    (2) More than one stationary storage battery technology is provided in a room or indoor areawhere there is a potential for adverse interaction between technologies.

    (3) When allowed as a basis for increasing maximum allowable quantities as specified in Table6.10.8.3.2.2.1.

    6.10.8.3.2.4.1

    The analysis shall evaluate the consequences of the following failure modes, and others deemednecessary by the AHJ. Only single failure modes shall be considered for each mode:

    (1) Thermal runaway condition in a single module or array

    (2) Failure of a battery management system

    (3) Failure of a required ventilation system

    (4) Voltage surges on the primary electric supply

    (5) Short circuits on the load side of the stationary battery storage system

    (6) Failure of the smoke detection, fire suppression, or gas detection system

    6.10.8.3.2.4.2

    The AHJ shall be permitted to approve the hazardous mitigation analysis provided the consequences of theFMEA demonstrate the following:

    (1) Fires or explosions will be contained within unoccupied stationary storage battery systemrooms for the minimum duration of the fire resistance rated specified in 6.10.8.3.2.1.3.1 or6.10.8.3.2.1.3.2, as applicable

    (2) Fires and explosions in stationary storage battery system cabinets in occupied work centersallow occupants to safely evacuate

    (3) Toxic and highly toxic gases released during charging, discharging, and normal operation shallnot exceed the permissible exposure limit (PEL)

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    30 of 107 7/30/2018, 10:49 AM

  • (4) Toxic and highly toxic gases released during fires and other fault conditions shall not reachconcentrations in access of IDLH level in the building or adjacent means of egress routes duringthe time deemed necessary to evacuate from that area

    (5) Flammable gases released from batteries during charging, discharging, and normal operationshall not exceed 25 percent of the lower flammable limit (LFL)

    6.10.8.3.2.4.3

    Construction, equipment, and systems that are required for the stationary storage battery system to complywith the hazardous mitigation analysis shall be installed, maintained, and tested in accordance withnationally recognized standards and specified design parameters.

    6.10.8.3.2.5 Listings.Storage batteries shall be listed in accordance with UL 1973, Standard for Batteries for Use in LightElectric Rail (LER) Applications and Stationary Applications . Prepackaged and pre-engineered stationarystorage battery systems shall be listed in accordance with UL 9540, Outline of Investigation for EnergyStorage Systems and Equipment .

    6.10.8.3.2.5.1 * Prepackaged and Pre-engineered Systems.Prepackaged and pre-engineered stationary storage battery systems shall be installed in accordance withtheir listing and the manufacturer’s instructions.

    6.10.8.3.2.5.2 Environment.The storage battery environment shall be controlled to maintain temperatures and conditions within thebattery manufacturer’s specifications.

    6.10.8.3.2.6 Installation.6.10.8.3.2.6.1 Battery Management System.An approved battery management system shall be provided for battery technologies for monitoring andbalancing cell voltages, currents, and temperatures within the manufacturer’s specifications. The systemshall transmit an alarm signal to an approved location if potentially hazardous temperatures or otherconditions including short circuits, overvoltage (i.e., overcharge) or under voltage (i.e., over discharge) aredetected.

    6.10.8.3.2.6.2 Battery Chargers.Battery chargers shall be compatible with the battery manufacturer’s electrical ratings and chargingspecifications. Battery chargers shall be listed in accordance with the UL 1564, Standard for IndustrialBattery Chargers , or provided as part of a listed pre-engineered or prepackaged stationary storage batterysystem.

    6.10.8.3.2.6.3 Vehicle Impact Protection.Vehicle impact protection shall be provided where stationary storage battery systems are subject to impactby motor vehicles.

    6.10.8.3.2.6.4 Combustible Storage.6.10.8.3.2.6.4.1

    Combustible materials not related to the stationary storage battery system shall not be stored in batteryrooms, cabinets, or enclosures.

    6.10.8.3.2.6.4.2

    Combustible materials in occupied work centers shall comply with NFPA 1, Section 10.18 and shall not bestored within 3 ft (915 mm) of battery cabinets.

    6.10.8.3.2.6.5 Signage.6.10.8.3.2.6.5.1

    Approved signage shall be provided on doors or in approved locations near entrances to stationary batterystorage system rooms.

    6.10.8.3.2.6.5.2

    New signage installations shall require the following items:

    (1) Hazard identification markings in accordance with NFPA 704.

    (2) “This room contains energized battery systems,” or the equivalent.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    31 of 107 7/30/2018, 10:49 AM

  • (3) Identification of the type(s) of batteries present

    (4) AUTHORIZED PERSONNEL ONLY

    (5) Technology-specific markings, if required in 6.10.8.3.2.11

    6.10.8.3.2.6.5.3

    Where the battery storage system disconnecting means is not within sight of the main service disconnect,placards or directories shall be installed at the locations of the main service disconnect to indicate thelocation of all battery storage disconnecting means in accordance with NFPA 70 .

    6.10.8.3.2.6.5.4

    Existing stationary storage battery systems shall be permitted to include the signage required at the time itwas installed.

    6.10.8.3.2.6.5.5

    Battery cabinets shall be provided with exterior labels that identify the manufacturer and model number ofthe system and electrical rating (i.e., voltage and current) of the contained battery system.

    6.10.8.3.2.6.5.6

    Signs shall be provided within battery cabinets to indicate the relevant electrical, chemical, and fire hazard.

    6.10.8.3.2.6.5.7

    Fire command centers in buildings containing stationary storage battery systems shall include signage orreadily available documentation that describes the location of stationary storage battery systems, the typesof batteries present, operating voltages, and location of electrical disconnects.

    6.10.8.3.2.6.6 Seismic Protection.Battery systems shall be seismically braced in accordance with the building code.

    6.10.8.3.2.6.7 Safety Caps.Vented batteries shall be provided with flame-arresting safety caps.

    6.10.8.3.2.6.8 * Mixed Battery Systems.Different types of batteries shall not be installed in the same room or cabinet if there is a potential forunsafe interaction between them, as determined by the AHJ.

    6.10.8.3.2.7 Suppression And Detection.6.10.8.3.2.7.1 Fire suppression.Rooms containing stationary storage battery systems shall be protected by an automatic sprinkler systeminstalled in accordance with NFPA 1, Section 13.3.

    6.10.8.3.2.7.1.1

    Commodity classifications for specific technologies of storage batteries shall be in accordance with Chapter5 of NFPA 13.

    6.10.8.3.2.7.1.2

    If the storage battery types are not specifically addressed in Chapter 5 of NFPA 13, the AHJ shall bepermitted to approve the fire suppression system based on full-scale fire and fault condition testingconducted or witnessed and reported by an approved laboratory.

    6.10.8.3.2.7.2 Smoke Detection.An approved automatic smoke detection system shall be installed in rooms containing stationary batterystorage systems in accordance with NFPA 72 and the required automatic smoke detection system shall besupervised by an approved central, proprietary, or remote station service or a local alarm that will give anaudible signal at a constantly attended location.

    6.10.8.3.2.8 * Ventilation.Where required by 6.10.8.3.2.11, ventilation shall be provided for rooms and cabinets in accordance withthe mechanical code and one of the following:

    (1) The ventilation system shall be designed to limit the maximum concentration of flammable gasto 25 percent of the lower flammable limit (LFL) of the total volume of the room during the worst-case event of simultaneous “boost” charging of all the batteries, in accordance with nationallyrecognized standards.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    32 of 107 7/30/2018, 10:49 AM

  • (2) Mechanical ventilation shall be provided at a rate of not less than 1 ft 3 /min/ft 2 (5.1L/sec/m 2 ) of floor area of the room or cabinet. The ventilation can be either continuous, oractivated by a gas detection system in accordance with 6.10.8.3.2.8.2.

    6.10.8.3.2.8.1

    Required mechanical ventilation systems for rooms and cabinets containing storage batteries shall besupervised by an approved central, proprietary, or remote station service or shall initiate an audible andvisual signal at an approved constantly attended on-site location.

    6.10.8.3.2.8.2

    Where required by 6.10.8.3.2.8(2), rooms containing stationary storage battery systems shall be protectedby an approved continuous gas detection system.

    6.10.8.3.2.8.2.1

    The gas detection system shall be designed to activate when the level of flammable gas exceeds 25percent of the lower flammable limit (LFL)

    6.10.8.3.2.8.2.2

    Activation of the gas detection system shall result in activation of the mechanical ventilation system, whichshall remain on until the flammable gas detected is less than 25 percent of the LFL.

    6.10.8.3.2.8.2.3

    The gas detection system shall include a minimum two hours of standby power.

    6.10.8.3.2.8.2.4

    Failure of the gas detection system shall annunciate a trouble signal at an approved central, proprietary, orremote station service, or when approved at a constantly attended onsite location.

    6.10.8.3.2.9 * Spill Control and Neutralization.Where required by 6.10.8.3.2.11, approved methods and materials shall be provided for the control andneutralization of spills of electrolyte or other hazardous materials in rooms containing stationary storagebatteries as follows:

    (1) For batteries with free-flowing electrolyte, the method and materials shall be capable ofneutralizing a spill of the total capacity from the largest cell or block to a pH between 5.0 and 9.0.

    (2) For batteries with immobilized electrolyte, the method and materials shall be capable ofneutralizing a spill of 3.0 percent of the capacity of the largest cell or block in the room to a pHbetween 5.0 and 9.0.

    6.10.8.3.2.10 Thermal Runaway.Where required by 6.10.8.3.2.11, a listed device or other approved method shall be provided to preclude,detect, and control thermal runaway.

    6.10.8.3.2.11 Battery-Specific ProtectionStationary storage battery systems shall comply with 6.10.8.3.2 through 6.10.8.3.2.10 and this section, asapplicable.

    6.10.8.3.2.11.1 Lithium Batteries.Stationary storage battery systems utilizing lithium batteries shall be provided with thermal runawayprotection in accordance with 6.10.8.3.2.10.

    6.10.8.3.2.11.2 Sodium Batteries.Stationary storage battery systems utilizing sodium batteries shall comply with the following:

    (1) Ventilation shall be provided in accordance with 6.10.8.3.2.8.

    (2) Spill control and neutralization shall be in accordance with 6.10.8.3.2.9.

    (3) Thermal runaway protection shall be provided for in accordance with 6.10.8.3.2.10.

    (4) A hazard mitigation analysis shall be provided for systems that utilize sodium sulfur batteries,or other sulfur-type battery systems that operate above ambient temperatures.

    (5) The signage required in 6.10.8.3.2.6.5 shall include, where applicable, “Water Reactive Hazard— Apply No Water.”

    6.10.8.3.2.11.3 Flow Batteries.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    33 of 107 7/30/2018, 10:49 AM

  • Stationary storage battery systems utilizing flow batteries shall comply with the following:

    (1) Ventilation shall be provided in accordance with 6.10.8.3.2.8.

    (2) Spill control and neutralization shall be in accordance with 6.10.8.3.2.9.

    6.10.8.3.2.11.4 Other Battery Types.Stationary storage battery systems utilizing battery technologies other than those described in6.10.8.3.2.11.1 through 6.10.8.3.2.11.1 shall comply with the following:

    (1) Ventilation shall be provided in accordance with 6.10.8.3.2.8 where flammable, toxic or highlytoxic gases could be present during charging, discharging, and normal system use.

    (2) Spill control and neutralization shall be in accordance with 6.10.8.3.2.9 where the batteriescontain electrolytes that could be released from the batteries.

    (3) Thermal runaway protection shall be provided in accordance with 6.10.8.3.2.10.

    (4) The signage required in 6.10.8.3.2.6.5 shall also identify any potential hazards associated withthe batteries.

    6.10.8.3.2.12 Testing, Maintenance, and Repairs.6.10.8.3.2.12.1

    Stationary storage batteries and associated equipment and systems shall be tested and maintained inaccordance with the manufacturer’s instructions.

    6.10.8.3.2.12.2

    Any storage batteries or system components used to replace existing units shall be compatible with thebattery charger, battery management systems, other storage batteries, and other safety systems.

    6.10.8.3.3 Capacitor Energy Storage Systems.6.10.8.3.3.1 Capacity.Stationary capacitor energy storage systems having capacities greater than those described in Table6.10.8.3.1 shall comply with 6.10.8.3.3.

    6.10.8.3.3.2 Location and Occupancy Separation.Stationary capacitor energy storage systems shall be located and constructed as required for stationarystorage battery system in accordance with 6.10.8.3.2.1 through 6.10.8.3.2.1.4.3.

    6.10.8.3.3.3 Maximum Allowable Quantities.Fire areas within buildings containing capacitor energy storage systems exceeding 600 KWh (2160 mJ)shall comply with all applicable ordinary-hazard and high-hazard requirements as identified in 6.2.2 ofNFPA 101 and the building code.

    6.10.8.3.3.4 Capacitor Arrays.6.10.8.3.3.4.1

    Capacitors, prepackaged stationary capacitor energy storage systems, and pre-engineered capacitorenergy storage systems shall be segregated into arrays not exceeding 50 KWh (180 Mega joules) each.

    6.10.8.3.3.4.2

    Each array shall be spaced a minimum 3 ft (914 mm) from other arrays and from walls in the storage roomor area. The storage arrangements shall comply with the egress provisions in NFPA 101 .

    6.10.8.3.3.5 Listings.Capacitors shall be listed in accordance with UL 1973, Standard for Batteries for Use in Light Electric Rail(LER) Applications and Stationary Applications . Prepackaged and pre-engineered capacitor energysystems shall be listed in accordance with UL 9540, Outline of Investigation for Energy Storage Systemsand Equipment .

    6.10.8.3.3.5.1 * Prepackaged and Pre-engineered Systems.Prepackaged and pre-engineered capacitor energy storage systems shall be installed in accordance withtheir listing and the manufacturer’s instructions.

    6.10.8.3.3.5.2 Environment.The environment surrounding the capacitors shall be controlled to maintain temperatures and conditionswithin the manufacturer’s specifications.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    34 of 107 7/30/2018, 10:49 AM

  • 6.10.8.3.3.6 Chargers.Capacitor chargers shall be compatible with the capacitor manufacturer’s electrical ratings and chargingspecifications, and shall be listed in accordance with the UL 1564, Standard for Industrial BatteryChargers , or provided as part of a listed pre-engineered or prepackaged capacitor energy storage system.

    6.10.8.3.3.7 Vehicle Impact Protection.Vehicle impact protection shall be provided where capacitor energy storage systems are subject to impactby motor vehicles.

    6.10.8.3.3.8 Combustible Storage.6.10.8.3.3.8.1

    Combustible materials not related to the capacitor energy storage system shall not be stored in capacitorrooms, cabinets, or enclosures.

    6.10.8.3.3.8.2

    Combustible materials in occupied work centers shall comply with NFPA 1, Section 10.18 and shall not bestored within 3 ft (915 mm) of capacitor cabinets.

    6.10.8.3.3.9 Signage.Approved signage shall be provided on doors or in approved locations near entrances to capacitor energystorage systems, and shall include the following:

    (1) Hazard identification markings in accordance with NFPA 704.

    (2) “This room contains energized capacitor systems,” or the equivalent

    (3) Identification of the type(s) of capacitors present

    (4) AUTHORIZED PERSONNEL ONLY

    6.10.8.3.3.9.1

    Where the capacitor energy storage system disconnecting means is not within sight of the main servicedisconnect, placards or directories shall be installed at the locations of the main service disconnect toindicate the location of all capacitor energy storage system disconnecting means in accordance with NFPA70 .

    6.10.8.3.3.9.2

    Capacitor cabinets shall be provided with exterior labels that identify the manufacturer and model numberof the system and electrical rating (i.e., voltage and current) of the contained battery system.

    6.10.8.3.3.9.3

    Signs shall be provided within capacitor cabinets to indicate the relevant electrical, chemical, and firehazard.

    6.10.8.3.3.9.4

    Fire command centers in buildings containing capacitor energy storage systems shall include signage orreadily available documentation that describes the location of the systems, the types of capacitors present,operating voltages, and location of electrical disconnects.

    6.10.8.3.3.10 Seismic Protection.Capacitor energy storage systems shall be seismically braced in accordance with the building code.

    6.10.8.3.3.11 Testing, Maintenance, and Repairs.6.10.8.3.3.11.1

    Capacitor energy storage systems and associated equipment and systems shall be tested and maintainedin accordance with the manufacturer’s instructions.

    6.10.8.3.3.11.2

    Capacitors or system components used to replace existing units shall be compatible with the capacitorcharger, other capacitors, and other safety systems.

    Additional Proposed Changes

    File Name Description Approved

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    35 of 107 7/30/2018, 10:49 AM

  • 1-2015_Chapter_52-updated_for_76.htm

    Modification of NFPA 1, Chapter 52 for inclusion in NFPA 76

    Statement of Problem and Substantiation for Public Input

    Fire services are very concerned with the wide spread proliferation of Lithium-ion and other potentially high risk battery chemistries which are being deployed in private, commercial and utility scale applications. These concerns have driven recent changes to NFPA 1, Chapter 52, IFC section 609, and the development of a new draft NFPA standard on the installation of energy storage systems. IFC committee action testimony confirms that telecommunications battery installations of historically safe lead-acid and nickel-cadmium batteries are not problematic and do not warrant more stringent code treatment. For this reason, in the last update to NFPA 1, the previous code treatment for these technologies was retained, and new more stringent requirements applicable to other battery chemistries were included in a subsequent section.

    Per NFPA 76, Appendix A, NFPA 76 is "intended to avoid requirements that could involve unnecessary complications for or interfere with the normal use, occupancy, and operations of telecommunications facilities and equipment....This standard provides a means by which the industry's accepted fire safety methods are applied to continue the historically good fire safety record of these facilities." Furthermore, specifically with respect to batteries, NFPA 76 states, "The presence of batteries directly supporting power and fuels for standby engines has been considered in the occupancy classification of these facilities. Telecommunications facilities are unique in their fire resistive/limited combustibility construction and the degree of control and high standards for content ignition and combustibility."

    A new draft NFPA standard 855, Standard for the Installation of Stationary Energy Storage Systems, expands further on the requirements of NFPA 1 and is expected to be incorporated into NFPA 1 by reference, completely replacing current chapter 52. It has a broad scope and covers all occupancies but even in the latest draft formation, fails to adequately account for the unique telecommunications environment and exceptional safety record. For this reason, it is recommended that the battery installation content in NFPA 1 applicable to telecommunications environments be directly incorporated into NFPA 76 as this occupancy specific standard best reflects the fire risk characteristics of telecommunications installations.

    Submitter Information Verification

    Submitter Full Name: Richard KlugeOrganization: EricssonAffiliation: ATISStreet Address:City:State:Zip:Submittal Date: Tue Jan 02 14:11:10 EST 2018Committee:

    Committee Statement

    Resolution: FR-40-NFPA 76-2018Statement: Fire services are very concerned with the wide spread proliferation of Lithium-ion and other potentially

    high risk battery chemistries which are being deployed in private, commercial and utility scaleapplications. These concerns have driven recent changes to NFPA 1, Chapter 52, IFC section 609,and the development of a new draft NFPA standard on the installation of energy storage systems. IFCcommittee action testimony confirms that telecommunications battery installations of historically safelead-acid and nickel-cadmium batteries are not problematic and do not warrant more stringent codetreatment. For this reason, in the last update to NFPA 1, the previous code treatment for thesetechnologies was retained, and new more stringent requirements applicable to other batterychemistries were included in a subsequent section.

    Per NFPA 76, Appendix A, NFPA 76 is "intended to avoid requirements that could involve

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    36 of 107 7/30/2018, 10:49 AM

  • unnecessary complications for or interfere with the normal use, occupancy, and operations oftelecommunications facilities and equipment....This standard provides a means by which theindustry's accepted fire safety methods are applied to continue the historically good fire safety recordof these facilities." Furthermore, specifically with respect to batteries, NFPA 76 states, "The presenceof batteries directly supporting power and fuels for standby engines has been considered in theoccupancy classification of these facilities. Telecommunications facilities are unique in their fireresistive/limited combustibility construction and the degree of control and high standards for contentignition and combustibility."

    A new draft NFPA standard 855, Standard for the Installation of Stationary Energy Storage Systems,expands further on the requirements of NFPA 1 and is expected to be incorporated into NFPA 1 byreference, completely replacing current chapter 52. It has a broad scope and covers all occupanciesbut in the latest draft formation, appear to not adequately account for the unique telecommunicationsenvironment and exceptional safety record. For this reason, it is recommended that the batteryinstallation content in NFPA 1 applicable to telecommunications environments be directlyincorporated into NFPA 76 as this occupancy specific standard best reflects the fire riskcharacteristics of telecommunications installations.

    National Fire Protection Association Report https://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPar...

    37 of 107 7/30/2018, 10:49 AM

  • SR-65Hide Deleted Chapter 6.10.8 Special Hazards 6.10.8.1 General. 6.10.8.1.1

    Telecommunications battery systems shall comply with this chapter.

    6.10.8.2 Lead-Acid and Nickel-Cadmium Batteries. 6.10.8.2.1 General.

    Stationary storage battery systems having an electrolyte capacity of more than 100 gal (378.5 L) in sprinklered buildings or 50 gal (189.3 L) in unsprinklered buildings for flooded lead-acid, nickel-cadmium, and valve-regulated lead–acid (VRLA) batteries used for facility standby power, emergency power, or uninterrupted power supplies shall be in accordance with this section and the Table 6.10.8.2.1.

    Table 6.10.8.2.1 Battery Requirements

    Nonrecombinant Batteries Recombinant Batteries

    Requirement Flooded . Lead-AcidFlooded Nickel-Cadmium

    (Ni-Cd) Valve-Regulated Lead–Acid

    (VRLA)

    Safety caps Venting caps Venting caps Self-resealing flame-arresting caps

    Thermal runaway management

    Not required Not required Required

    Spill control Required Required Not required

    Neutralization Required Required Required

    Ventilation Required Required Required

    Signage Required Required Required

    Seismic control Required Required Required

    Fire detection Required Required Required

    6.10.8.2.2 Safety Features. 6.10.8.2.2.1 Safety Venting.

    Batteries shall be provided with safety venting caps per 6.10.8.2.2.1.1 and 6.10.8.2.2.1.2. 6.10.8.2.2.1.1 Nonrecombinant Batteries.

    Vented lead-acid and nickel-cadmium shall be provided with safety venting caps.

    6.10.8.2.2.1.2 Recombinant Batteries.

    VRLA shall be equipped with self-resealing flame-arresting safety vents.

    6.10.8.2.2.2 Thermal Runaway.

    VRLA systems shall be provided with a listed device or other approved method to preclude, detect, and control thermal runaway.

    6.10.8.2.2.3 Location and Occupancy Separation. 6.10.8.2.2.3.1

    Battery systems shall be permitted in the same room as the equipment that they support.

    6.10.8.2.2.3.2

    Battery systems shall be housed in a noncombustible, locked cabinet or other enclosure to prevent access by unauthorized personnel unless located in a separate equipment room accessible only to authorized personnel.

    6.10.8.2.2.3.3

    Battery systems shall be located in a room separated from other portions of the building by a minimum of a 1-hour fire barrier.

  • 6.10.8.2.2.3.4

    When telecommunications equipment is located in a structure or building housing multiple tenants or occupancies which include assembly, educational, detention and correction facilities; health care, ambulatory health care, and day care centers; and, residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a 2-hour fire barrier.

    6.10.8.2.2.4 Spill Control. 6.10.8.2.2.4.1

    Rooms, buildings, or areas containing free-flowing liquid electrolyte in individual vessels having a capacity of more than 55 gal (208 L) or multiple vessels having an aggregate capacity exceeding 1000 gal (3785 L) shall be provided with spill control to prevent the flow of liquids to adjoining areas.

    6.10.8.2.2.4.2*

    An approved method and materials for the control of a spill of electrolyte shall be provided that will be capable of controlling a spill from the single largest vessel.

    6.10.8.2.2.4.3

    VRLA batteries with immobilized electrolyte shall not require spill control.

    6.10.8.2.2.5 Neutralization. 6.10.8.2.2.5.1*

    An approved method to neutralize spilled electrolyte shall be provided.

    6.10.8.2.2.5.2

    For VRLA batteries, the method shall be capable of neutralizing a spill from the largest battery to a pH between 7.0 and 9.0.

    6.10.8.2.2.6* Ventilation.

    For flooded lead-acid, flooded nickel-cadmium, and VRLA batteries, ventilation shall be provided for rooms and cabinets in accordance with the mechanical code and one of the following:

    (1) The ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 percent of the total volume of the room during the worst-case event of simultaneous “boost” charging of all the batteries, in accordance with nationally recognized standards.

    (2) Continuous ventilation shall be provided at a rate of not less than 1 ft3/min/ft2 (5.1 L/sec/m2) of floor area of the room or cabinet.

    6.10.8.2.2.7 Environment.

    The battery environment shall be controlled or analyzed to maintain temperature in a safe operating range for the specific battery technology used.

    6.10.8.2.2.8 Signs. 6.10.8.2.2.8.1

    Doors or accesses into the following shall be provided with approved signs:

    (1) Rooms containing stationary storage battery systems

    (2) Other areas containing stationary storage battery systems

    6.10.8.2.2.8.2

    For rooms that contain VRLA batteries, the signs required by 6.10.8.2.2.8.1 shall state the following:

    This room contains:

    (1) Stationary storage battery systems

    (2) Energized electrical circuits

    6.10.8.2.2.8.3

    For rooms that contain lead-acid or flooded Ni-Cd batteries, the signs required by 6.10.8.2.2.8.1 shall state the following:

  • This room contains:

    (1) Stationary storage battery systems

    (2) Energized electrical circuits

    (3) Corrosive battery electrolyte

    6.10.8.2.2.8.4

    Battery cabinets shall be provided with exterior labels that identify the manufacturer and model number of the system and electrical rating (i.e., voltage and current) of the contained battery system.

    6.10.8.2.2.8.5

    Signs shall be provided within battery cabinets to indicate the relevant electrical, chemical, and fire hazard.

    6.10.8.2.2.9 Seismic Protection.

    Battery systems shall be seismically braced in accordance with the building code.

    6.10.8.2.2.10 Smoke Detection.

    An approved automatic smoke detection system shall be installed in rooms containing stationary battery storage systems in accordance with NFPA 72.

    6.10.8.3* Additional Battery Technologies. 6.10.8.3.1 General.

    Energy storage systems having a capacity greater than the quantities listed in Table 6.10.8.3.1 shall be in accordance with Section 6.10.8.3.

    Table 6.10.8.3.1 Energy Storage System Threshold Quantities

    Type Capacitya Lithium batteries, all types 20 KWh( 18.0 Mega joules)

    Sodium batteries, all types 20 KWh (18.0 Mega joules)c

    Flow batteriesb 20 KWh (18.0 Mega joules)

    Other battery technologies 10 KWh (10.8 Mega joules)

    Capacitors 70 KWh (25.2 Mega joules)

    Notes: aFor batteries and capacitors rated in Amp-Hours, KWh should equal rated voltage times amp-hour rating divided by 1000. bIncludes vanadium, zinc-bromine, polysulfide-bromide, and other flowing electrolyte-type technologies. cOr 70 KWh (25.2 Mega joules) for sodium-ion technologies.

    6.10.8.3.2* Stationary Storage Battery Systems. 6.10.8.3.2.1 Location and Occupancy Separation.

    Stationary storage battery systems shall be located and constructed in accordance with this section.

    6.10.8.3.2.1.1

    Stationary storage battery systems shall be housed in a noncombustible, locked cabinet or other enclosure to prevent access by unauthorized personnel unless located in a separate equipment room accessible only to authorized personnel.

    6.10.8.3.2.1.2 Location. 6.10.8.3.2.1.2.1

    Stationary storage battery systems shall not be located in areas where the floor is located more than 75 ft (22,860 mm) above the lowest level of fire department vehicle access, or where the floor level is more than 30 ft (9144 mm) below the finished floor of the lowest level of exit discharge, unless otherwise permitted by 6.10.8.3.2.1.2.

  • 6.10.8.3.2.1.2.2

    Installations on noncombustible rooftops of buildings exceeding 75 ft (22,860 mm) in height that do not obstruct fire department rooftop operations shall be permitted when approved by the AHJ.

    6.10.8.3.2.1.3 Separation.

    Rooms containing stationary storage battery systems shall be located in high-hazard occupancies, or shall be separated from other areas of the building as stated in 6.10.8.3.2.1.3.1 and 6.10.8.3.2.1.3.2. Stationary storage battery systems shall be allowed to be in the same room with the equipment they support.

    6.10.8.3.2.1.3.1

    Stationary storage battery systems shall be located in a room separated from other portions of the building by a minimum of a 1-hour fire barrier.

    6.10.8.3.2.1.3.2

    When telecommunications equipment is located in a structure or building housing multiple tenants or occupancies which include assembly, educational, detention, and correction facilities; health care, ambulatory health care, and day care centers; and residential board and care and residential occupancies, stationary storage battery systems shall be located in a room separated from other portions of the building by a minimum of a 2-hour fire barrier.

    6.10.8.3.2.2 Maximum Allowable Quantities. 6.10.8.3.2.2.1

    Fire areas within buildings containing stationary storage battery systems exceeding the maximum allowable quantities in Table 6.10.8.3.2.2.1 shall comply with all applicable ordinary-hazard and high-hazard requirements as identified in 6.2.2 of NFPA 101 and the building code.

    Table 6.10.8.3.2.2.1

    Type Maximum Allowable Quantitiesa Hazard Classification Lithium batteries, all types 600 KWh High hazardc

    Sodium batteries, all types 600 KWh High hazardc

    Flow batteriesb 600 KWh High hazardc

    Other battery technologies 200 KWh High hazardc

    Notes: aFor batteries rated in amp-hHours, KWh should equal rated voltage times amp-hour rating divided by 1000. bIncludes vanadium, zinc-bromine, polysulfide-bromide, and other flowing electrolyte-type technologies. cCan be permitted to be ordinary hazard classification if approved by the AHJ based on (1) a hazard mitigation analysis conducted in accordance with 6.10.8.3.2.4 and (2) large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory that shows that a fire involving the stationary storage battery system is contained within the room for a duration equal to the fire resistance rating of the room separation required in 6.10.8.3.2.1.3.1 or 6.10.8.3.2.1.3.2, as applicable.

    6.10.8.3.2.2.2

    Where approved by the AHJ, areas containing stationary storage battery systems that exceed the amounts in Table 6.10.8.3.2.2.1 shall be permitted to be treated as a ordinary-hazard and not a high-hazard classification based on a hazardous mitigation analysis in accordance with 6.10.8.3.2.4 and large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory.

    6.10.8.3.2.2.3

    Where areas within buildings contain a combination of energy system technologies, the total aggregate quantities shall be determined based on the sum of percentages of each type divided by the maximum allowable quantity of each type. If the sum of the percentages exceeds 100 percent, the area shall be treated as a high-hazard classification in accordance with Table 6.10.8.3.2.2.1.

  • 6.10.8.3.2.3* Battery Arrays. 6.10.8.3.2.3.1

    Battery arrays shall comply with 6.10.8.3.2.3.2 and 6.10.8.3.2.3.3 unless otherwise permitted by 6.10.8.3.2.3.4 or 6.10.8.3.2.3.5.

    6.10.8.3.2.3.2

    Storage batteries, prepackaged stationary storage battery systems, and pre-engineered stationary storage battery systems shall be segregated into arrays not exceeding 50 KWh (180 Mega joules) each.

    6.10.8.3.2.3.3

    Each array shall be spaced a minimum 3 ft (914 mm) from other arrays and from walls in the storage room or area. The storage arrangements shall comply with the egress provisions in NFPA 101.

    6.10.8.3.2.3.4

    Listed pre-engineered stationary storage battery systems and prepackaged stationary storage battery systems shall not exceed 250 KWh (900 Mega joules) each.

    6.10.8.3.2.3.5

    The AHJ shall be permitted to approve listed pre-engineered and prepackaged battery arrays with larger capacities or smaller battery array spacing if large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory is provided showing that a fire involving one array will not propagate to an adjacent array, and be contained within the room for a duration equal to the fire resistance rating of the room separation required by 6.10.8.3.2.1.3.

    6.10.8.3.2.4 Hazard Mitigation Analysis.

    A failure mode and effects analysis (FMEA) or other approved hazard mitigation analysis shall be provided to the AHJ when any of the following conditions are present:

    (1) Battery technologies not specifically identified in Table 6.10.8.3.1 are provided.

    (2) More than one stationary storage battery technology is provided in a room or indoor area where there is a potential for adverse interaction between technologies.

    (3) When allowed as a basis for increasing maximum allowable quantities as specified in Table 6.10.8.3.2.2.1.

    6.10.8.3.2.4.1

    The analysis shall evaluate the consequences of the following failure modes, and others deemed necessary by the AHJ. Only single failure modes shall be considered for each mode:

    (1) Thermal runaway condition in a single module or array

    (2) Failure of a battery management system

    (3) Failure of a required ventilation system

    (4) Voltage surges on the primary electric supply

    (5) Short circuits on the load side of the stationary battery storage system

    (6) Failure of the smoke detection, fire suppression, or gas detection system

    6.10.8.3.2.4.2

    The AHJ shall be permitted to approve the hazardous mitigation analysis provided the consequences of the FMEA demonstrate the following:

    (1) Fires or explosions will be contained within unoccupied stationary storage battery system rooms for the minimum duration of the fire resistance rated specified in 6.10.8.3.2.1.3.1 or 6.10.8.3.2.1.3.2, as applicable

    (2) Fires and explosions in stationary storage battery system cabinets in occupied work centers allow occupants to safely evacuate

    (3) Toxic and highly toxic gases released during charging, discharging, and normal operation shall not exceed the permissible exposure limit (PEL)

  • (4) Toxic and highly toxic gases released during fires and other fault conditions shall not reach concentrations in access of IDLH level in the building or adjacent means of egress routes during the time deemed necessary to evacuate from that area

    (5) Flammable gases released from batteries during charging, discharging, and normal operation shall not exceed 25 percent of the lower flammable limit (LFL)

    6.10.8.3.2.4.3

    Construction, equipment, and systems that are required for the stationary storage battery system to comply with the hazardous mitigation analysis shall be installed, maintained, and tested in accordance with nationally recognized standards and specified design parameters.

    6.10.8.3.2.5 Listings.

    Storage batteries shall be listed in accordance with UL 1973, Standard for Batteries for Use in Light Electric Rail (LER) Applications and Stationary Applications. Prepackaged and pre-engineered stationary storage battery systems shall be listed in accordance with UL 9540, Outline of Investigation for Energy Storage Systems and Equipment.

    6.10.8.3.2.5.1* Prepackaged and Pre-engineered Systems.

    Prepackaged and pre-engineered stationary storage battery systems shall be installed in accordance with their listing and the manufacturer’s instructions.

    6.10.8.3.2.5.2 Environment.

    The storage battery environment shall be controlled to maintain temperatures and conditions within the battery manufacturer’s specifications.

    6.10.8.3.2.6 Installation. 6.10.8.3.2.6.1 Battery Management System.

    An approved battery management system shall be provided for battery technologies for monitoring and balancing cell voltages, currents, and temperatures within the manufacturer’s specifications. The system shall transmit an alarm signal to an approved location if potentially hazardous temperatures or other conditions including short circuits, overvoltage (i.e., overcharge) or under voltage (i.e., over discharge) are detected.

    6.10.8.3.2.6.2 Battery Chargers.

    Battery chargers shall be compatible with the battery manufacturer’s electrical ratings and charging specifications. Battery chargers shall be listed in accordance with the UL 1564, Standard for Industrial Battery Chargers, or provided as part of a listed pre-engineered or prepackaged stationary storage battery system.

    6.10.8.3.2.6.3 Vehicle Impact Protection.

    Vehicle impact protection shall be provided where stationary storage battery systems are subject to impact by motor vehicles.

    6.10.8.3.2.6.4 Combustible Storage. 6.10.8.3.2.6.4.1

    Combustible materials not related to the stationary storage battery system shall not be stored in battery rooms, cabinets, or enclosures.

    6.10.8.3.2.6.4.2

    Combustible materials in occupied work centers shall comply with NFPA 1, Section 10.18 and shall not be stored within 3 ft (915 mm) of battery cabinets.

    6.10.8.3.2.6.5 Signage. 6.10.8.3.2.6.5.1

    Approved signage shall be provided on doors or in approved locations near entrances to stationary battery storage system rooms.

    6.10.8.3.2.6.5.2

    New signage installations shall require the following items:

    (1) Hazard identification markings in accordance with NFPA 704.

    (2) “This room contains energized battery systems,” or the equivalent.

  • (3) Identification of the type(s) of batteries present

    (4) AUTHORIZED PERSONNEL ONLY

    (5) Technology-specific markings, if required in 6.10.8.3.2.11

    6.10.8.3.2.6.5.3

    Where the battery storage system disconnecting means is not within sight of the main service disconnect, placards or directories shall be installed at the locations of the main service disconnect to indicate the location of all battery storage disconnecting means in accordance with NFPA 70.

    6.10.8.3.2.6.5.4

    Existing stationary storage battery systems shall be permitted to include the signage required at the time it was installed.

    6.10.8.3.2.6.5.5

    Battery cabinets shall be provided with exterior labels that identify the manufacturer and model number of the system and electrical rating (i.e., voltage and current) of the contained battery system.

    6.10.8.3.2.6.5.6

    Signs shall be provided within battery cabinets to indicate the relevant electrical, chemical, and fire hazard.

    6.10.8.3.2.6.5.7

    Fire command centers in buildings containing stationary storage battery systems shall include signage or readily available documentation that describes the location of stationary storage battery systems, the types of batteries present, operating voltages, and location of electrical disconnects.

    6.10.8.3.2.6.6 Seismic Protection.

    Battery systems shall be seismically braced in accordance with the building code.

    6.10.8.3.2.6.7 Safety Caps.

    Vented batteries shall be provided with flame-arresting safety caps.

    6.10.8.3.2.6.8* Mixed Battery Systems.

    Different types of batteries shall not be installed in the s