PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
Click on the hyperlink below to navigate to the appropriate facility guidance page: AMI Kids Big Cypress Wilderness Institute
Knight Island Utilities North Charlotte Water Works
Ave Maria Lake Bonnet Village Plant #1 Orange Blossom Fellowship Community
Bocilla Utilities Lake Bonnet Village Plant #2 Palm and Pines Mobile Home Park
Buttonwood Bay Mobile Home Park
Lake Josephine Heights Plant #3 Palms Estates of Highlands County
Charlotte Correctional Institution Lake Josephine Heights Plant #4 (Sebring Lakes)
Port of the Islands
Country Club of Sebring Lakeport Water Association Riverbend Estates
Country Walk Utilities Lakeside Village Mobile Home Park
River Oaks Subdivision
DeeAnn Lakefront Estates Lee Cypress Water & Sewer Co-Op
Shell Creek Park
DeSoto Correctional Institution Leisure Lakes/Covered Bridge Silver Lake Utility -Buckhorn Housing
DeSoto Village Mobile Home Park
LP Water Works Plant #1 Sun-N-Lakes of Lake Placid
Eagle’s Nest Estates LP Water Works Plant #2 Tomoka Heights (Town of Lake Placid)
Everglades City Mallard Mobile Home Park Town and Country Utility
Everglades Shores Maple Corner Tropical Harbor Estates Plant #1 (North)
Gator Wilderness Camp School Maranatha Village Tropical Harbor Estates Plant #2 (South)
Hidden Acres Estates Marco Shores Tropical Palm Mobile Home Park
Highway Park Meadowlake Subdivision Whisper Creek RV Resort
Kissimmee River Fishing Resort
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Bocilla Utilities, Inc. PWS ID #:6084079
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
ASBESTOS (62-550.511)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
**X
LEAD AND COPPER 40 CFR 141 Subpart I
***X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual sample set consists of a set of two samples collected at the same time and location, with one sample analyzed for TTHMs and one sample analyzed for HAA5s. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** Routine monitoring under the Revised Total Coliform Rule requires this water system to collect microbiological samples at the rate of ONE distribution sample/month. Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
*** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Charlotte Correctional Institution PWS ID #:5084082
CONTAMINANTS
FAC Rule No./Rule Reference Not
Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 2 individual samples. One individual sample for TTHMs shall be collected at the Warden’s House location, and one individual sample for HAA5s shall be collected at the Y Dorm location.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Gator Wilderness Camp School PWS ID #:5084117
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X
INORGANIC CONTAMINANTS (62-550.513)
*X
Sodium only X
Whole Inorganics group TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
**X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
***X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
****X
SECONDARY CONTAMINANTS (62-550.520)
X
LEAD AND COPPER 40 CFR 141 Subpart I
*****X
This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* Continue quarterly monitoring for the Primary Inorganic Contaminant of Sodium during each calendar quarter of 2018.
** During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual sample set consists of a set of two samples collected at the same time and location, with one sample analyzed for TTHMs and one sample analyzed for HAA5s. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
*** Collect one full set of SOCs (all 29 contaminants) during the fourth calendar quarter (October/November/December) of 2018. This will then also count as your Annual sample for the SOC of Di(2-ethylhexyl)phthalte (DEHP) which must be collected during the fourth calendar quarter of 2018.
**** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Knight Island Utilities, Inc. PWS ID #:6084075
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
ASBESTOS (62-550.511)
X
TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
**X
LEAD AND COPPER 40 CFR 141 Subpart I
***X
This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 2 individual samples. One individual sample for TTHMs shall be collected at the Rum Cove location, and one individual sample for HAA5s shall be collected at the Rum Bay Restaurant location.
** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
*** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: North Charlotte Water Works PWS ID #:6084074
This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect Samples for the Radiological contaminants of Gross Alpha, Radium 226, and Radium 228 sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants & DBPs Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Gross Alpha, Radium 226, Radium 228
only SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Shell Creek Park PWS ID #:6080256
CONTAMINANTS FAC Rule No./Rule Reference
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
*X Sodium
only
X Whole Primary
inorganics Group TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
**X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
***X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Radium 226 and Radium 228 only
SECONDARY CONTAMINANTS (62-550.520)
*X Chloride & TDS
only
X Whole Secondaries
group LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* Continue quarterly monitoring for the Primary Inorganic Contaminant of Sodium and the Secondary Contaminants of Chloride, and TDS, during each calendar quarter of 2018. Collect all quarterly Sodium, Chloride, and TDS samples on currently.
** During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
*** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
**** Collect samples for the Radiological contaminants of Radium 226, and Radium 228 only, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Town and Country Utility PWS ID #:5084116 CONTAMINANTS
FAC Rule No./Rule Reference Monthly In 2018
Quarterly In 2018
One Time In 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2
*X **X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
***X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
***X Whole SOCs Group
****X DEHP only
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
X
RADIONUCLIDES Gross Alpha, Uranium, Radium 226, & Radium 228 (62-550.519)
***X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR Part 141
*****X Standard Number of
Monitoring Sites This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* At a minimum, continue increased/quarterly monitoring for the Disinfection Byproducts of TTHMs and HAA5s during the first (January/February/March) and second (April/May/June) calendar quarters of 2018, at the rate of one dual set/quarter. Remain on quarterly monitoring for TTHMs and HAA5s until the Running Annual Average TTHM concentration is less than or equal to 60 ug/L and the Running Annual Average HAA5 concentration is less than or equal to 45 ug/L. ** Please note, if you do qualify to return to Annual monitoring for TTHMs and HAA5s after the monitoring during the first and second calendar quarters of 2018 has been performed, you will still be required to collect one dual set of samples for TTHMs and HAA5s during the third calendar quarter (July/August/September) of 2018.
*** Continue quarterly monitoring for the VOCs Group, SOCs Group (excluding Dioxin), and Radiological contaminants (Gross Alpha, Uranium, Radium 226, and Radium 228) during the first calendar quarter of 2018.
**** Continue quarterly monitoring for the SOC of Di-2(ethylhexyl)phthalate (DEHP) during the first and second calendar quarters of 2018.
***** Collect your second initial set of samples for Lead and Copper (in accordance with your approved sampling plan) sometime between January 1 and June 30, 2018. Please note, the number of sites that are sampled must be in accordance with the number of sites required for Standard monitoring NOT reduced monitoring.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Tropical Palm Mobile Home Park PWS ID #:6080324
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Gross Alpha and
Uranium only SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set at the 279 Balsam location. This dual set of samples must be collected at the above-referenced location (and during the specific month) identified in your DEP approved Stage 2 revised monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha and Uranium (conditional) only, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: AMI Kids Big Cypress Wilderness Institute PWS ID #:5114133
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
*X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
**X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
***X Whole SOCs
Group MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
****X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
*****X Uranium only
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
******X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
IF WATER SYSTEM BECOMES ACTIVE IN 2018
* Since this water system was closed in 2017, with no monitoring for Nitrate, and Nitrite being performed, please collect samples for Nitrate, and Nitrite as soon as possible, but by no later than 30 days after restart-up of the Plant.
** During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
*** Collect one full set of SOCs (all 29 contaminants) during the second calendar quarter (April/May/June) of 2018. This will then also count as your Annual sample for the SOC of Dalapon which must be collected during the second calendar quarter of 2018.
**** Collect Start-up Bactis at two locations in the distribution system for each of two consecutive days and perform a 10 sample well survey prior to placing the Plant or the Well in service.
***** Collect a sample for the Radiological contaminant of Uranium only, sometime during the 2018 calendar year.
****** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Ave Maria PWS ID #:5114154
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 2 individual samples. One individual sample for TTHMs shall be collected at the 4128 Lexington Street location, and one individual sample for HAA5s shall be collected at 5794 Plymouth Street location. These individual samples must be collected at the above-referenced locations (and during the specific month) identified in your DEP approved Stage 2 revised monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Everglades City PWS ID #:5110089
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
Semi Annual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Uranium
only SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X Standard
Number of Monitoring Sites
This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set at the Ted Smallwood’s Store location. This dual set of samples must be collected at the above-referenced location (and during the specific month) identified in your DEP approved Stage 2 revised monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect a sample for the Radiological contaminant of Uranium only, sometime during the 2018 calendar year
***** Collect two sets of samples for Lead and Copper (in accordance with your approved sampling plan) in 2018. Collect the first set of samples by no later than April 1, 2018, following Department approval of your revised Lead and Copper sampling plan. Collect your second set of samples sometime between July 1 and December 31, 2018. Submit the first set of results to DEP by 7/10/18, and the second set by 1/10/19. Please note, the number of sites that are sampled must be in accordance with the number of sites required for Standard monitoring NOT reduced monitoring.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Everglades Shores PWS ID #:5110087
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
Semi Annual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Radium 226 and Radium 228 only
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform routine Annual monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual sample set consists of a set of two samples collected at the same time and location, with one sample analyzed for TTHMs and one sample analyzed for HAA5s. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Radium 226, and Radium 228 only, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 andSeptember 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Lee Cypress Water & Sewer Co-Op, Inc. PWS ID #:5110058
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228 sometime during the 2018 calendar year
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Marco Shores PWS ID #:5110182
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
ASBESTOS (62-550.511)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
**X
LEAD AND COPPER 40 CFR 141 Subpart I
***X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, continue routine Annual monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 2 dual samples sets. Each dual sample set consists of a set of two samples collected at the same time and location, with one sample for analyzed for TTHMs and one sample analyzed for HAA5s. Each set of samples must be collected at the two different locations (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
*** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Port of The Islands PWS ID #:5110230
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set at the 142 Windward Cay location. This dual set of samples must be collected at the above-referenced location (and during the specific month) identified in your DEP approved Stage 2 revised monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228 sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Lakeport Water Association PWS ID #:5220186
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
ASBESTOS (62-550.511)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
**X
LEAD AND COPPER 40 CFR 141 Subpart I
***X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set at the Countryside Cafe location. A dual sample set consists of a set of two samples collected at the same time and location, with one sample analyzed for TTHMs and one sample analyzed for HAA5s. This dual set of samples must be collected at the above-referenced location (and during the specific month) identified in your DEP approved Stage 2 revised monitoring plan.
** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
*** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Maple Corner PWS ID #:5224091
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
One Time in 2018
NITRATE AND NITRITE (62-550.512)
*X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
**X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
***X SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
****X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
*****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
******X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* Collect your Annual samples for Nitrate, and Nitrite during the fourth calendar quarter (October/November/December) of 2018.
** During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
*** Collect one full set of VOCs (all 21 contaminants) during the third calendar quarter (July/August/September) of 2018. This will then also count as your Annual sample for the VOC of Total Xylenes which must be collected during the third calendar quarter of 2018.
**** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
***** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
****** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: River Oaks Subdivision PWS ID #:5220235 CONTAMINANTS
FAC Rule No./Rule Reference Not Required
In 2018 Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
***X Radium 226 and Radium 228 only
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Collect samples for the Radiological contaminants of Radium 226, and Radium 228, only sometime during the 2018 calendar year.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Whisper Creek R.V. Resort PWS ID #:5224074
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the Lot 95 location. Please submit a revised Stage 2 sampling plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Palm and Pines Mobile Home Park PWS ID #:5264050
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X **X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
***X
****X Dalapon Only
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
*****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
******X
This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* At a minimum, continue quarterly monitoring for the Disinfection Byproducts of TTHMs and HAA5s during the first (January/February/March) and second (April/May/June) calendar quarters of 2018, at the rate of one dual set/quarter. Remain on quarterly monitoring for TTHMs and HAA5s until the Running Annual Average TTHM concentration is less than or equal to 60 ug/L and the Running Annual Average HAA5 concentration is less than or equal to 45 ug/L. ** Please note, if you do qualify to return to Annual monitoring for TTHMs and HAA5s after the monitoring during the first and second calendar quarters of 2018 has been performed, you will still be required to collect one dual set of samples for TTHMs and HAA5s during the third calendar quarter (July/August/September) of 2018.
*** Collect one full set of SOCs (all 29 contaminants) during the third calendar quarter of 2018. This will then also count as your Annual sample for the SOC of Di(2-ethylhexyl)phthalate (DEHP) which must be collected during the third calendar quarter of 2018.
**** Collect your Annual sample for the SOC of Dalapon during the fourth calendar quarter (October/November/December) of 2018.
***** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
****** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Riverbend Estates PWS ID #:5264054
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Buttonwood Bay Mobile Home Park PWS ID #:6284075
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X
TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
**X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
***X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
****X
SECONDARY CONTAMINANTS (62-550.520)
X
LEAD AND COPPER 40 CFR 141 Subpart I
*****X
This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* Continue quarterly monitoring for the Disinfection Byproducts of TTHMs and HAA5s at the rate of two dual sets/quarter. A dual set of samples must be collected at EACH of the two locations (and during the specific month of each calendar quarter) identified in your DEP approved revised Stage 2 sampling plan. Remain on quarterly monitoring for TTHMs and HAA5s until the Running Annual Average TTHM concentration is less than or equal to 60 ug/L and the Running Annual Average HAA5 concentration is less than or equal to 45 ug/L at each location. Please note, you must submit an Operational Evaluation Level report to the Department by no later than the 10th day following the end of any calendar quarter that you violate the OEL for either TTHMs OR HAA5s at ANY sample location. The format is also available at the DEP Drinking Water forms page.
** Please note, if you do qualify to return to Annual monitoring for TTHMs and HAA5s after the monitoring during the first and second calendar quarters of 2018 has been performed, you will still be required to collect two dual sets of samples for TTHMs and HAA5s during the third calendar quarter (July/August/September) of 2018.
*** Collect one full set of SOCs (all 29 contaminants) during the fourth calendar quarter (October/November/December) of 2018. This will then also count as your Annual sample for the SOC of Dalapon which must be collected during the fourth calendar quarter of 2018.
**** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Country Club of Sebring PWS ID #:6284076
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
***X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform routine Annual monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 2 dual sample sets. Each dual sample set consists of a set of two samples collected at the same time and location, with one sample for analyzed for TTHMs and one sample analyzed for HAA5s. Each set of samples must be collected at the two different locations (and during the specific month) identified in your approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Country Walk Utilities, Inc. PWS ID #:6284114
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X **X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
***X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X STANDARD NUMBER
OF MONITORING SITES
This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* Continue quarterly monitoring for the Disinfection Byproducts of TTHMs and HAA5s at the rate of one dual set/quarter. Remain on quarterly monitoring for TTHMs and HAA5s until the Running Annual Average TTHM concentration is less than or equal to 60 ug/L and the Running Annual Average HAA5 concentration is less than or equal to 45 ug/L. Please note, you must submit an Operational Evaluation Level report to the Department by no later than the 10th day following the end of any calendar quarter that you violate the OEL for either TTHMs OR HAA5s at ANY sample location. The format is also available at the DEP Drinking Water forms page.
** Please note, if you do qualify to return to Annual monitoring for TTHMs and HAA5s after the monitoring during the first and second calendar quarters of 2018 has been performed, you will still be required to collect one dual set of samples for TTHMs and HAA5s during the third calendar quarter (July/August/September) of 2018.
*** Collect one full set of SOCs (all 29 contaminants) during the third calendar quarter (July/August/September) of 2018. This will then also count as your Annual sample for the SOC of Dalapon which must be collected during the third calendar quarter of 2018.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect two sets of samples for Lead and Copper (in accordance with your approved sampling plan) in 2018. Collect the first set of samples sometime between January 1 and June 30, 2018. Collect your second set of samples sometime between July 1 and December 31, 2018. Submit the first set of results to DEP by 7/10/18, and the second set by 1/10/19. Please note, the number of sites that are sampled must be in accordance with the number of sites required for Standard monitoring NOT reduced monitoring.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: DeeAnn Lakefront Estates PWS ID #:6284097
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Eagle's Nest Estates PWS ID #:5284114
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
**X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
***X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
****X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
*****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
******X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** Collect one full set of VOCs (all 21 contaminants) during the third calendar quarter (July/August/September) of 2018. This will then also count as your Annual sample for the VOC of Total Xylenes which must be collected during the third calendar quarter of 2018.
*** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
**** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
***** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
****** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Hidden Acres Estates PWS ID #:5280129
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** Collect one full set of SOCs (all 29 contaminants) during the second calendar quarter (April/May/June) of 2018. This will then also count as your Annual sample for the SOC of Dalapon which must be collected during the second calendar quarter of 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Highway Park PWS ID #:5284133
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
**X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
***X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
****X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
*****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
******X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the 1357 Hwy 27 location. Please submit a revised Stage 2 sampling plan.
** Collect one full set of VOCs (all 21 contaminants) during the third calendar quarter (July/August/September) of 2018. This will then also count as your Annual sample for the VOC of Total Xylenes which must be collected during the third calendar quarter of 2018.
*** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
**** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
***** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
****** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Kissimmee River Fishing Resort PWS ID #:5280155
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform routine Annual monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** Collect one full set of SOCs (all 29 contaminants) during the fourth calendar quarter (October/November/December) of 2018. This will then also count as your Annual sample for the SOC of Dalapon which must be collected during the fourth calendar quarter of 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Lake Bonnet Village-Plant #1 PWS ID #:6280158
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the Lot C-22 Campground location.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Lake Bonnet Village-Plant #2 PWS ID #:6280158
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the Lot C-22 Campground location.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Lake Josephine Heights Plant #3 PWS ID #:6280162
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Gross Alpha and Uranium
only SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the 10809 Hwy 27 Lake Josephine RV Campground location.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, and Uranium (conditional), sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Lake Josephine Heights Plant #4 (Sebring Lakes) PWS ID #:6280162
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the 10809 Hwy 27 Lake Josephine RV Campground location.
** Collect one full set of SOCs (all 29 contaminants) during the fourth calendar quarter (October/November/December) of 2018. This will then also count as your Annual sample for the SOC of Dalapon which must be collected during the fourth calendar quarter of 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Lakeside Village Mobile Home Park PWS ID #:6280167 CONTAMINANTS
FAC Rule No./Rule Reference Not Required
In 2018 Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Leisure Lakes/Covered Bridge PWS ID #:6280064
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Gross Alpha and
Uranium only SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform routine Annual monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 2 dual sample sets. Each dual sample set consists of a set of two samples collected at the same time and location, with one sample for analyzed for TTHMs and one sample analyzed for HAA5s. Each set of samples must be collected at the two different locations (and during the specific month) identified in your approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, and Uranium (conditional) sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: LP Water Works Plant #1 PWS ID #:6280304
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X
LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the Mens Restroom at the Pool location.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: LP Water Works Plant #2 PWS ID #:6280304
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the Mens Restroom at the Pool location.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCsin 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Mallard Mobile Home Park PWS ID #:5280180
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Maranatha Village PWS ID #:6280181
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Radium 226 and Radium 228 only
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Meadowlake Subdivision PWS ID #:6284089
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Orange Blossom Fellowship Community PWS ID #:6284077
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: The Palms Estates of Highlands County PWS ID #:5280211
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (62-550.516)
**X MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Radium 226 and Radium 228 only
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Silver Lake Utility-Buckhorn Housing PWS ID #:5284101
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** Collect one full set of SOCs (all 29 contaminants) during the second calendar quarter (April/May/June) of 2018. This will then also count as your Annual sample for the SOC of Dalapon which must be collected during the second calendar quarter of 2018.
*** Each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Sun-N-Lakes of Lake Placid PWS ID #:6280273
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Radium 226 and Radium 228 only
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Tomoka Heights (Town of Lake Placid) PWS ID #:6284074
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X Gross Alpha and Uranium
only SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform routine Annual monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 2 dual sample sets. Each dual sample set consists of a set of two samples collected at the same time and location, with one sample for analyzed for TTHMs and one sample analyzed for HAA5s. Each set of samples must be collected at the two different locations (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, and Uranium (conditional), sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Tropical Harbor Estates-Plant #1 (North) PWS ID #:6280296
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
SECONDARY CONTAMINANTS (62-550.520)
X LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the 517 Beachcraft Lot 171 location.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Gross Alpha, Uranium (conditional), Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: Tropical Harbor Estates-Plant #2 (South) PWS ID #:6280296
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X
TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
****X
Uranium, Radium 226, and Radium 228 only
SECONDARY CONTAMINANTS (62-550.520)
X
LEAD AND COPPER 40 CFR 141 Subpart I
*****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual set of samples at the 517 Beachcraft Lot 171 location.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for the Radiological contaminants of Uranium, Radium 226, and Radium 228, sometime during the 2018 calendar year.
***** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: DeSoto Correctional Institution PWS ID #:6140451
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time In 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X
TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X
LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Annual reduced monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set at the East Trailer Park location. This dual set of samples must be collected at the above-referenced location (and during the specific month) identified in your DEP approved Stage 2 revised monitoring plan. ** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.
PUBLIC WATER SYSTEM CONTAMINANT MONITORING GUIDANCE FOR CALENDAR YEAR 2018
SYSTEM NAME: DeSoto Village MHP PWS ID #:6144834
CONTAMINANTS FAC Rule No./Rule Reference
Not Required In 2018
Monthly In 2018
Quarterly In 2018
SemiAnnual (2 in 2018)
One Time in 2018
NITRATE AND NITRITE (62-550.512)
X INORGANIC CONTAMINANTS (62-550.513)
X
TOTAL TRIHALOMETHANES & HALOACETIC ACIDS 40 CFR 141 Subpart V, Stage 2 Disinfectants and Disinfection Byproducts Rule
*X
VOLATILE ORGANIC CONTAMINANTS (62-550.515)
X
SYNTHETIC ORGANIC CONTAMINANTS (PEST & PCBS) (62-550.516)
**X
MICROBIOLOGICAL Revised Total Coliform Rule 40 CFR 141 Subpart Y
***X
RADIONUCLIDES Gross Alpha, Uranium, Radium-226, Radium-228 (62-550.519)
X
SECONDARY CONTAMINANTS (62-550.520)
X
LEAD AND COPPER 40 CFR 141 Subpart I
****X This chart is the DEP's good faith assessment for the contaminant monitoring requirements for the above referenced public water system for the calendar year 2018 (only). If you disagree, then please contact the DEP as soon as possible. Please be aware that monitoring schedules are subject to change at any time based upon analyses results or other factors. This chart shall not relieve any person from any requirement of Florida law.
* During the third calendar quarter (July/August/September) of 2018, perform Reduced/Triennial monitoring for TTHMs and HAA5s under Stage 2 of the Disinfectants and Disinfection Byproducts Rule by collecting 1 dual sample set. A dual set of samples must be collected at the location (and during the specific month) identified in your DEP approved Stage 2 monitoring plan.
** You are required to collect one full set of samples for all of the SOCs (except Dioxin) during the 2018 calendar year. However, if you submit a Reduced Monitoring Application Questionnaire for Synthetic Organic Contaminants to the Department, available at: http://www.dep.state.fl.us/water/drinkingwater/forms.htm, you may receive Department approval to either fully or partially waive monitoring for SOCs in 2018. If you do not receive approval to waive any of the required monitoring for SOCs for 2018, or do not submit the Questionnaire, you will have to perform one full set of monitoring for SOCs in 2018.
*** Please note that each water system is required to develop and adhere to a written RTCR sample siting plan that is subject to State review and revision.
**** Collect samples for Lead and Copper (in accordance with your approved sampling plan) sometime between June 1 and September 30, 2018. Submit the analyses results to the DEP by no later than October 10, 2018.