pumps

5
TRANSPORTABLE PUMPS SECTION INDEX Dependapower DPPAT 4025 CAT-R...................................................................... A2 Patterson/Caterpillar 4,000 GPM Dependapower DPGOU 6040 CAT-R .................................................................... A3 Goulds/Caterpillar 6,000 GPM NHancer — Low Pressure / Hi-Volume Pump ............................................. A4-A5 120108 PRODUCTS 409-745-3232 EMERGENCY 409-727-2347 A1 TRANSPORTABLE PUMPS TRANSPORTABLE PUMPS WWW.WILLIAMSFIRE.COM

Upload: jozsef-magyari

Post on 12-Jul-2015

137 views

Category:

Technology


8 download

TRANSCRIPT

Page 1: Pumps

Dependapower DPGOU 6040 CAT-RGoulds/Caterpillar 6,000 GPM

Description: The Dependapower DPGOU 6040 CAT-R is a trailer mounted, diesel driven horizontal split case centrifugal fire water pumping system.

Nominal performance rating is 6,000 gpm @ 150 psi net (10’ lift). Designed to be moved from one location to another without having to realign the pump coupling. Entire assembly is built on a skid base which also serves as a fuel tank. Also includes structural frame with lifting lugs and work lights. Electric start with dual electric primers. Total Package Weight with Fuel = 20,000 lbs.

Trailer:Triple axle 24,000 lb. GAWR steel decked trailer, complete with; electric brakes and coupler, DOT lighting package; leveling jack with rear

stabilizer jacks; 235/85 R16 tires/wheels.

Pump Detail:Manufacturer GouldsSeries 3409Model 10 x 14 x 20 LFittings Cast iron casting, Bronze trimPerformance @ Shutoff 200 psi 6,000 gpm - 150 psi 4,000 gpm - 175 psiPriming Dual 24 VDC Electric

Driver Detail:Manufacturer CaterpillarModel 3412-DITAPower 750 BHP @ 1800 rpmElectrical System 24 VDC Cooling System Radiator with pusher fan

Suction Manifold:14” diameter header, furnished with: six (6) 6” (M) NH inlet connections - capped and one (1) 2.5” valved (F) NST swivel w/plug.

Discharge Manifold:10” diameter header, furnished with: six (6) 5” Storz discharge connections, capped, six (6) worm gear operated butterfly valves - 5”, two

(2) 2.5” (M) auxiliary valved discharge connections - capped.

Control Panel:Includes: start/stop switch, tachometer, oil pressure gauge, coolant temperature gauge, amp meter, vernier throttle, compound suction gauge,

discharge pressure gauge, fuel pressure gauge, primer valves & switches, hour meter.

Options:Jet pump back-up primer6” NH hard suction hoses (20’ each - 6 req’d) or (10’ each - 12 req’d)6” Non-floating basket strainers (6 req’d)

TRANSPORTABLE PUMPS SECTION INDEX

Dependapower DPPAT 4025 CAT-R ......................................................................A2

Patterson/Caterpillar 4,000 GPM

Dependapower DPGOU 6040 CAT-R ....................................................................A3

Goulds/Caterpillar 6,000 GPM

NHancer — Low Pressure / Hi-Volume Pump ............................................. A4-A5

120108

PRODUCTS 409-745-3232 EMERGENCY 409-727-2347A1

TRANSPORTABLE PUMPS TRANSPORTABLE PUMPS

WWW.WILLIAMSFIRE.COM

Page 2: Pumps

Dependapower DPPAT 4025 CAT-RPatterson/Caterpillar 4,000 GPM

Description: The Dependapower DPPAT 4025 CAT-R is a trailer mounted, diesel driven horizontal

split case centrifugal fire water pumping system. Nominal performance rating is 4,000 gpm @ 150 psi (10’ lift). The pump and driver come mounted on a skid containing an integral 325 gallon fuel cell with level indicator. The easily detachable skid is transported on a dual-axle trailer. The 12” suction and 10” discharge headers provide minimal pressure loss for maximum efficiency. The 24VDC electrical system comes standard with two group-D batteries. Paint is basic red polyurethane finish on pump, skid and trailer. (*Not on Driver) Total Package Weight with Fuel = 15,000 lbs.

Trailer:Gooseneck style dual axle 14,000 lb. GAWR trailer, complete with: electric brakes &

coupler; DOT lighting package; 235/85 R16 LRF tires/wheels. Deck areas covered with safety “Grip” surface.

Pump Detail:Manufacturer PattersonSeries MAAModel 12 x 8 x 20.3Fittings Cast iron casting, Bronze trim, SS packing sleevePerformance @ Shutoff 200 psi 4,000 gpm - 150 psi / 2,500 gpm - 175 psiPriming One 24 VDC Electric vane primer & reservoir

Driver Detail:Manufacturer CaterpillarModel 3406-DITAPower 500 BHP @ 2100 rpmElectrical System 24 VDC Cooling System Radiator with pusher fan*Paint Standard base unit Caterpillar yellow

Suction Manifold:12” diameter flange-fitted header furnished with: four (4) 6” (M) NH inlet connections,

capped & one (1) 2.5” valved (F) NST swivel w/plug.

Discharge Manifold:10” diameter flange-fitted header, furnished with: four (4) 5” storz discharge connections, capped, with gated discharge valves: (1) 2.5” (M)

valved discharge connections.

Control Panel:Includes: start/stop switch, tachometer, oil pressure gauge, coolant temperature gauge, amp meter, vernier throttle, compound suction gauge,

discharge pressure gauge, fuel pressure gauge, primer valves & switches, hour meter.

Options:Manual clutch between pump & driverFour suction hose racks (passenger side only)

for use with 10’ hoses onlySS Suction/Discharge ManifoldsJet pump back-up primerAutomatic battery chargerRetractable awning over pump operator6” NH hard suction hoses

(20’ each - 4 req’d) or (10’ each - 8 req’d)6” NH “Light Weight” hard suction hoses (20’ each - 4 req’d) or (10’ each - 8 req’d)6” Non-floating basket strainers (4 req’d)6” Floating basket strainers (4 req’d)Full skid coverAdd, 2.5” Discharge/Suction4 Work Lights

120108

PRODUCTS 409-745-3232 EMERGENCY 409-727-2347A2

TRANSPORTABLE PUMPS TRANSPORTABLE PUMPS

WWW.WILLIAMSFIRE.COM

Page 3: Pumps

Dependapower DPGOU 6040 CAT-RGoulds/Caterpillar 6,000 GPM

Description: The Dependapower DPGOU 6040 CAT-R is a trailer mounted, diesel driven

horizontal split case centrifugal fire water pumping system. Nominal performance rat-ing is 6,000 gpm @ 150 psi net (10’ lift). Designed to be moved from one location to another without having to realign the pump coupling. Entire assembly is built on a skid base which also serves as a fuel tank. Also includes structural frame with lifting lugs and work lights. Electric start with dual electric primers. Total Package Weight with Fuel = 20,000 lbs.

Trailer:Triple axle 24,000 lb. GAWR steel decked trailer, complete with; electric brakes and coupler, DOT lighting package; leveling jack with rear

stabilizer jacks; 235/85 R16 tires/wheels.

Pump Detail:Manufacturer GouldsSeries 3409Model 10 x 14 x 20 LFittings Cast iron casting, Bronze trimPerformance @ Shutoff 200 psi 6,000 gpm - 150 psi 4,000 gpm - 175 psiPriming Dual 24 VDC Electric

Driver Detail:Manufacturer CaterpillarModel 3412-DITAPower 750 BHP @ 1800 rpmElectrical System 24 VDC Cooling System Radiator with pusher fan

Suction Manifold:14” diameter header, furnished with: six (6) 6” (M) NH inlet connections

- capped and one (1) 2.5” valved (F) NST swivel w/plug.

Discharge Manifold:10” diameter header, furnished with: six (6) 5” Storz discharge connections,

capped, six (6) worm gear operated butterfly valves - 5”, two (2) 2.5” (M) auxil-iary valved discharge connections - capped.

Control Panel:Includes: start/stop switch, tachometer, oil pressure gauge, coolant temperature gauge, amp

meter, vernier throttle, compound suction gauge, discharge pressure gauge, fuel pressure gauge, primer valves & switches, hour meter.

Options:Jet pump back-up primer6” NH hard suction hoses (20’ each - 6 req’d) or (10’ each - 12 req’d)6” Non-floating basket strainers (6 req’d)

120108

PRODUCTS 409-745-3232 EMERGENCY 409-727-2347A3

TRANSPORTABLE PUMPS TRANSPORTABLE PUMPS

WWW.WILLIAMSFIRE.COM

Page 4: Pumps

Submersible Pump

Pump easily backs into any available water source of at least 2-foot depth.

Visually accessible grease fittings at the operator panel

Lo-Pressure / Hi-Volume Submersible Pump N-Hancer Submersible Pump

Description:Trailer mounted diesel driven submersible pump. Originally designed

for agricultural service, now redesigned for utilization for the fire service – industrial and municipal.

• Industrial uses – (1) de-inventory water flooded areas in process areas, tank farms, etc. from flooded waterways or tropical events, (2) re-inventory water to supply fire water from restricted inventory levels, (3) gain access to water supplies otherwise not available, and (4) enhance pumping operations to make existing centrifugal pumps more effective by reducing the strain by pumping from draft.

• Municipal uses – (1) in optimal areas, supply large volumes of water to municipal pumpers (either profes-sional or volunteer departments) during large fire operations requiring significant support, (2) improve water shuttling opera-tions to maintain supply needs for insurance ratings for depart-ments, and (3) support for areas affected by flooding.

Features:Trailers are fitted with a 2” ball coupler, and can be pulled

over the road by a ¾-ton truck. Trailers can be spotted in place (in a waterway) with same vehicle. Suggested logistical deploy-ment would be via flatbed truck for long distances. The trailers are road legal, but would need appropriate tags and serial num-bers. Trailers are outfitted with lifting lugs in the event condi-tions would not permit placement via vehicle (pump and motor weight is less than 6000 lbs). Visually accessible grease fittings.

In field testing the large N-Hancer pump provided 9000 gpm to the pump suction of a Williams 6000 pump (Patterson package) and was demonstrated with a Ranger 3 nozzle and an Ambassador monitor – results indicated a flow rate of 8,326 gpm at the monitors at 125 psi.

Adaptations:Pumps are outfitted with a dual 12” Storz discharge

manifold, and include 2 sections of 50’, 12” hose with Storz connections, and 2 distribution manifolds each with 12” Storz inlet and 4, 6” Storz outlets —manifolds are constructed of stainless steel.

Pump Data: Small Pump Pump Data: Large PumpAt 1000 RPM

Flow 2000 gpm 3000 gpm 4000 gpm

Head (ft) 86 80 67

Effy % 56 69 67

HP (~) 78 88 100

At 1000 RPM

Flow 4000 gpm 6000 gpm 9000 gpm

Head (ft) 71.5 61.5 32.5

Effy % 60 64 40

HP (~) 120 145 176

120108

PRODUCTS 409-745-3232 EMERGENCY 409-727-2347A4

TRANSPORTABLE PUMPS TRANSPORTABLE PUMPS

WWW.WILLIAMSFIRE.COM

Page 5: Pumps

Models Available (presently through WF&HC):

Small Pump Discharge Suction Flow Head (ft) Power

10” pipe ...Fitted with a single 12” Storz discharge to reduce friction & pressure loss

8” double suction 4000 gpm 70 • 160 hp Deutz diesel direct drive• 50 gallon fuel tank • 6 hours of runtime

Large PumpDischarge Suction Flow Head (ft) Power

16” pipe ...Fitted with two (2) 12” Storz connections at the discharge manifold

10” double suction 9000 gpm 50 • 176 hp Deutz diesel direct drive• 50 gallon fuel tank • 6 hours of runtime

120108

PRODUCTS 409-745-3232 EMERGENCY 409-727-2347A5

TRANSPORTABLE PUMPS TRANSPORTABLE PUMPS

WWW.WILLIAMSFIRE.COM