Offer: EGU000011A13 1- Technical description Feeder Type D1 / NSX100-160 with: DRAWER PART . 1 NSX100-160 - 3P . 1 Micrologic TMD . 1 MX . 1 OF . 1 SD . RAL 1000 . 1 Black mimic diagram FIXED PART . 1 fixed part RAR 6 modules - 3P . 1 Fuse . 1 CT . 1 Ammeter . 1 RH99P . 1 Toroidal Feeder Type D1 / Drawing PV265000- Sheet 011 Starter Type M1 / 0.37kW with: DRAWER PART . 1 NSX100 - 3P . 1 Contactor . 1 Thermal overload . 1 RH99P . 2 Push Buttons . 1 Switch . 1 Fuse . 2 Leds . RAL 1000 . 1 Black mimic diagram FIXED PART . 1 fixed part RAR 6 modules - 3P . 1 Toroidal Feeder Type M1 / Drawing PV265000- Sheet 061 Starter Type M1 / 7.5kW with: DRAWER PART . 1 NSX100 - 3P . 1 Contactor . 1 Thermal overload . 1 RH99P . 2 Push Buttons . 1 Switch . 1 Fuse

Upload: soyona7

Post on 10-Apr-2016

9 views

Category:

Documents


0 download

DESCRIPTION

Technical drawings Switchgear

TRANSCRIPT

Page 1: PV26 Technical Details

Offer: EGU000011A13

1- Technical description

Feeder Type D1 / NSX100-160 with:

DRAWER PART

. 1 NSX100-160 - 3P

. 1 Micrologic TMD

. 1 MX

. 1 OF

. 1 SD

. RAL 1000

. 1 Black mimic diagram FIXED PART . 1 fixed part RAR 6 modules - 3P . 1 Fuse . 1 CT . 1 Ammeter . 1 RH99P . 1 Toroidal

Feeder Type D1 / Drawing PV265000- Sheet 011

Starter Type M1 / 0.37kW with:

DRAWER PART

. 1 NSX100 - 3P

. 1 Contactor

. 1 Thermal overload

. 1 RH99P

. 2 Push Buttons

. 1 Switch

. 1 Fuse

. 2 Leds

. RAL 1000

. 1 Black mimic diagram FIXED PART . 1 fixed part RAR 6 modules - 3P . 1 Toroidal

Feeder Type M1 / Drawing PV265000- Sheet 061

Starter Type M1 / 7.5kW with:

DRAWER PART

. 1 NSX100 - 3P

. 1 Contactor

. 1 Thermal overload

. 1 RH99P

. 2 Push Buttons

. 1 Switch

. 1 Fuse

sadasivam
Typewriter
sadasivam
Typewriter
Toroidal shall be suitable for the cable sizes mentioned in the SLD. ( Typical- Applicable to all the feeders)
sadasivam
Typewriter
Feeder type drawing is not attached.(Typical- Applicable to all feeders)
sadasivam
Arrow
sadasivam
Arrow
sadasivam
Typewriter
Feeder D1: We presume that this feeder is transformer feeder.The following components are to be included as per control circuit for transformer. 1. Over current relay 2. Trip relay 3. Contactor
sadasivam
Typewriter
Qty : 2 nos
sadasivam
Typewriter
Qty : 2 nos
sadasivam
Typewriter
Please include the following feeders as shown in the SLD. 1. 32A 4Pole SFU feeder - 1 no 2. 63A 4 Pole SFU feeders - 3 nos 3. 160A 4 Pole SFU feeder - 1 no These feeders shall be provided with ON/OFF indication lamps.
sadasivam
Typewriter
Fuse characterics and rating shall be suitable for the motor FLC.(Typical- Applicable to all feeders)
sadasivam
Typewriter
OLR range shall be 10-20A
sadasivam
Typewriter
SFU& Fuse rating shall be 63/32A
sadasivam
Typewriter
Component description is required.
sadasivam
Arrow
sadasivam
Arrow
sadasivam
Arrow
sadasivam
Arrow
sadasivam
Arrow
sadasivam
Typewriter
RAL shall be inline with Existing SB. (Typical- Applicable to all feeders)
Page 2: PV26 Technical Details

. 2 Leds

. RAL 1000

. 1 Black mimic diagram FIXED PART . 1 fixed part RAR 6 modules - 3P . 1 Toroidal

Feeder Type M1 / Drawing PV265000- Sheet 061

Starter Type M2 / 22kW with:

DRAWER PART . 1 NSX100 - 3P . 1 Contactor . 1 Thermal overload . 1 RH99P . 2 Push Buttons . 1 Switch . 1 Fuse . 2 Leds . RAL 1000 . 1 Black mimic diagram FIXED PART . 1 fixed part RAR 6 modules - 3P . 1 CT . 2 Ammeters . 1 Toroidal

Feeder Type M2 / Drawing PV265000- Sheet 071

Starter Type M2 / 45kW with:

DRAWER PART

. 1 NSX100 - 3P

. 1 Contactor

. 1 Thermal overload

. 1 RH99P

. 2 Push Buttons

. 1 Switch

. 1 Fuse

. 2 Leds

. RAL 1000

. 1 Black mimic diagram FIXED PART . 1 fixed part RAR 6 modules - 3P . 1 CT . 2 Ammeters . 1 Toroidal

Feeder Type M2 / Drawing PV265000- Sheet 071

sadasivam
Arrow
sadasivam
Typewriter
Please consider 1-no Ammeter. Field ammeter is part of Local control station.
sadasivam
Typewriter
Ammeter shall be suitable for CT with secondary 1A with 0 – 6 x FLC scale
sadasivam
Arrow
sadasivam
Typewriter
Qty : 2 nos
sadasivam
Typewriter
External interface terminals shall be provided as shown in the control circuit.
sadasivam
Arrow
sadasivam
Typewriter
This feeder is not applicable since transformer feeder is covered under feeder type D1.