Quality Assurance and Testing of Facades
Sudhanshu Dighe
FITI
![Page 2: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/2.jpg)
f u t u r e s k y l i n e
![Page 3: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/3.jpg)
PERFORMANCE
DESIGN
COST
TIME LINES
QUALITY
T H E C H A L L E N G E S
![Page 4: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/4.jpg)
FAÇADE DESIGN REQUIREMENTS
HIGH WIND PRESSURE PEDESTRAIN COMFORT
WORKMANSHIP DEPENDENCY
FIRE / VENTILATION
SAFETY
![Page 5: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/5.jpg)
Why Façade Testing?
Last chance for correction of design to meet performance.
Key to stability certification to the building.
Must for every building validation and certification.
Must for safety as a whole.
![Page 6: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/6.jpg)
MAIN PERFORMANCE PARAMETERS
Weather
Structural
Seismic
Thermal
Acoustics
Fire
![Page 7: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/7.jpg)
Weather - AIR LEAKAGE
Air Infiltration
-Under positive pressure
-Air infiltration means heat entering inside.
Air Exfiltration
-Under negative pressure
-Air exfiltration means loss of cool air.
Either way is loss of air-conditioning
Also loss in Acoustical performance.
Cannot be verified in drawings alone.
![Page 8: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/8.jpg)
Air Performance Standards
AS-NZ
• 5.76 m3/hr/m2
ASTM –AAMA
• 1.8 m3/hr/m2
CWCT
• 2.06 m3/hr/m2
CAN BE ACHIVED
• 0.50 m3/hr/m2
![Page 9: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/9.jpg)
Air Test Pressure
AS-NZ
• 150 Pa
ASTM –AAMA
• 75 – 300Pa
BS-EN
• 150- 600 Pa
CONSIDERATION
• 10 – 15% OF DWP
![Page 10: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/10.jpg)
Weather - WATER LEAKAGE
Water Leakage-Under positive pressure-Damages interior, False celling and
furnishings.-Ineffective utilization of floor space near
façade perimeter.-Fungal growth
Cannot be verified in drawing alone.Scientific system design to be Followed.
![Page 11: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/11.jpg)
Water Test Pressure
AS-NZ
• 300 Pa
ASTM –AAMA
• 137 – 720 Pa
BS-EN
• 20% of DWP
CONSIDERATION
• 15-20% OF DWP
![Page 12: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/12.jpg)
S I E S M I C & LIVE LOAD M O V E M E N T S
Intermediate Floor Drift
UNITISED WITH SLIDER STACK JOINT
• 0.4 % of Floor Height – L/250
• Flexible Joints at Floor Level
to Release Forces.
• Cast In Chanel With T-Bolt
Allowing Movement.
![Page 13: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/13.jpg)
PERFORMANCE TEST SEQUENCE
50% Structural load –
Vent Open Close 5 times
Air Infiltration test – 300Pa (As per ASTM E 283)
Static Water Test – 450Pa (As per ASTM E 331) –
Dynamic Water Test – 450Pa (As per AAMA 501.1) –
Structural Wind load Test – 1000Pa (As per ASTM E 330)
Repeat Static Water Test – 300Pa (As per ASTM E 331) –
Proof Load Test – 1500Pa (As per ASTM E 330)
![Page 14: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/14.jpg)
Diamond Skin Design
Case Study – Kohinoor Square
![Page 15: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/15.jpg)
ARCHITECTURAL
REQUIREMENT
Articulated Façade
Vision glass inclined
outward & inward.
Spandrel glass inclined
inward & outward.
Profile fin projection
visible in elevation.
![Page 16: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/16.jpg)
2 – 2.75 Kpa
3 – 3.25 Kpa
3.5 – 4 Kpa
4.25 – 5.25 Kpa
90 %
10 %
Wind Pressure Zoning
System Design
4 Kpa
Remaining 10% after
checking the
reserve strength.
W I N D A N A L Y S I S
![Page 17: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/17.jpg)
SYSTEM DESIGN
Articulated Unitized system -1.5 m x 3.9 m units
250mm Deep profile.
Glass articulation in Mullion Fin projection.
Telescopic base profile to receive articulation.
![Page 18: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/18.jpg)
ENGINEERING OF GLASS
High reflective glass.
Vision glass - 32mm IGU glass of 1.5 m x 3.0 m (8 +16AG+8)
Glass fabrication Quality - Flatness of glass within 2 mm.
Annual weather cycle 20% of DWP (800 Pa )
Pressure drop at height
![Page 19: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/19.jpg)
DESIGN VALIDATING
@ 6.0 Kpa Positive Wind Pressure
Design validation by performance test process carried out at Laboratory.
Air leakage test at 300 Pa.
Water leakage test at750 Pa- 1200 Pa – 1500 Pa.
Wind load serviceability test at Step 1 – Passed 4 kpa. Step 2 – Passed 6 kpa. Step 3 – Reserved strength of
7.3 kpa.
Seismic inter story floor drift at 15mm.
![Page 20: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/20.jpg)
Skewed Glazing System
Case Study – Brigade Gateway, World Trade Centre
![Page 21: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/21.jpg)
ARCHITECTURAL REQUIREMENT
Vision glass skewed in Plan.
Spandrel glass straight in plan.
Visible mullion 200mm deep as Fin projection ( South elevation )
Façade curved in plan.
![Page 22: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/22.jpg)
ENGINEERING OF GLASS Vision glass – Floor to Celling – 1.5m x 3.6 m
Wind pressure – 1.6 kpa
Glass fabrication Quality - Flatness of glass within 2 mm.
Annual weather cycle 20% of DWP
Pressure drop at height.
![Page 23: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/23.jpg)
SYSTEM DESIGNUnitized Element Design - 1.5m x 4.2m units
System – Structurally Glazed with mechanical holding
250mm Split mullion with 3 barrier gasket system.
200mm deep mullion projection acting as vertical Fin.
![Page 24: Quality Assurance and Testing of Facades Sudhanshu Dighe Assurance and Testing of Facades.pdf · Case Study –Kohinoor Square. ARCHITECTURAL REQUIREMENT Articulated Façade Vision](https://reader030.vdocument.in/reader030/viewer/2022021711/5b2e7cbf7f8b9a55208bf9d6/html5/thumbnails/24.jpg)
Design validation by performance test process carried out at Laboratory.
Air leakage test at 300 Pa.
Water leakage test at600 pa
Wind load serviceability test at Step 1 – Passed 1.8 kpaStep 2 – Passed 2.7 kpa
Seismic inter story floor drift at 24mm.
DESIGN VALIDATING