- 1 - KEW6315

Preface KEW6315KEW6315 Feature

KEW6315 - 2 -

Feature

This is a Clamp-type Power Quality Analyzer that can be used for various wiring systems.

It can be used for simple measurements of instantaneous/ integration/ demand values, and also for

analysis of harmonics and events related to power quality and for the simulation of power factor

correction with capacitor banks. Moreover, it can display waveforms and vectors of voltage and current.

Data can be saved either in the SD card or the internal memory, and can be transferred to PC via USB,

or in real time via Bluetooth communication.

Safety construction

Designed to meet the international safety standard IEC 61010-1 CAT.IV 300V/ CAT.III 600V/ CAT.II 1000V.

Power quality analysis

KEW6315 is designed to meet the international standard IEC61000-4-30 Class S and can measure

frequency and r.m.s. voltage with high accuracy, and also can analyze harmonics. Moreover, it can

measure swell, dip, interruption, transient, inrush current and flicker all at once without a gap.

Power measurement

KEW6315 measures active/reactive/apparent power, electrical energy, power factor, r.m.s. current, phase

angle and neutral current simultaneously.

Wiring configuration

KEW6315 supports: Single-phase 2-wire (4ch), Single-phase 3-wire (2ch), Three-phase 3-wire (2ch) and

Three-phase 4-wire.

Demand measurement

Electricity consumption can be easily monitored so as not to exceed the target maximum demand values.

Waveform/ vector display

Voltage and current can be displayed by waveform or vector.

Saving data

KEW6315 is endowed with a logging function with the preset recording interval. Data can be saved by manual

operation or by specifying date & time. Screen data can be saved by using the Print Screen function.

Dual power supply system

KEW6315 operates either with AC power supply or with batteries. Both dry-cell batteries (alkaline) and

rechargeable batteries (Ni-MH) can be used. To charge the rechargeable battery, use the charger which is

manufactured by the same company as the batteries. In the event of power interruption, while operating with

AC power supply, power to the instrument is automatically restored by the batteries in the instrument.

Large display

TFT color display with large screen.

Light & compact design

Clamp sensor type, compact and light weight design.

Application

Data in the SD card or the internal memory can be saved in PC via USB. Analysis of the downloaded

data and instrument settings are possible by using the special software “KEW Windows for KEW6315”.

Real-time communication is available via Bluetooth.

Input/ Output function

Analog signals from thermometers or light sensors can be measured simultaneously with electrical power

data via 2 analog inputs (DC voltage); when any events related to power quality occur, signals can be

transmitted to alarm devices via one digital output.

111... IIInnnssstttrrruuummmeeennnttt OOOvvveeerrrvvviiieeewww

Preface KEW6315

- 1 - KEW6315

● Preface

This Quick manual is a simplified version of the full instruction manual which can be found in

the supplied CD-ROM. This manual is intended only as a handy reference guide and should

only be used after having read the full instruction manual which contains full details on each

function of this instrument and the items contained in the package.

● Safety Warning!

The instruction manual contains warnings and safety procedures which have to be observed

to ensure safe operation of the instrument and maintain it in a safe condition. Thus, these

operating instructions have to be read prior to using the instrument.

Content

1. Instrument Overview ··············································································· 2

2. Start/ Stop Recording ···································································· 5

3. Instrument Layout ················································································· 13

4. Getting Started ····················································································· 17

5. Inst/ Integration/ Demand

Inst value : W ····················································································· 19

Integration value: Wh/ Demand ······························································ 21

6. Vector ······················································································ 25

7. Waveform ················································································· 26

8. Harmonics Analysis ···································································· 27

9. Power Quality

Event(Swell/ Dip/ Int/ Inrush current/ Transient) ·········································· 30

Flicker ································································································ 33

10. Setting ·················································································· 35

11. SD Card/ Saved Data ··········································································· 38

The latest software can be downloaded from our homepage: http://www.kew-ltd.co.jp.

www.kew-ltd.co.jp

Page 3: Quick Manual - 共立電気計器株式会社

- 2 -KEW6315

KEW6315 FeatureKEW6315 Feature

KEW6315 - 2 -

Feature

This is a Clamp-type Power Quality Analyzer that can be used for various wiring systems.

It can be used for simple measurements of instantaneous/ integration/ demand values, and also for

analysis of harmonics and events related to power quality and for the simulation of power factor

correction with capacitor banks. Moreover, it can display waveforms and vectors of voltage and current.

Data can be saved either in the SD card or the internal memory, and can be transferred to PC via USB,

or in real time via Bluetooth communication.

Safety construction

Designed to meet the international safety standard IEC 61010-1 CAT.IV 300V/ CAT.III 600V/ CAT.II 1000V.

Power quality analysis

KEW6315 is designed to meet the international standard IEC61000-4-30 Class S and can measure

frequency and r.m.s. voltage with high accuracy, and also can analyze harmonics. Moreover, it can

measure swell, dip, interruption, transient, inrush current and flicker all at once without a gap.

Power measurement

KEW6315 measures active/reactive/apparent power, electrical energy, power factor, r.m.s. current, phase

angle and neutral current simultaneously.

Wiring configuration

KEW6315 supports: Single-phase 2-wire (4ch), Single-phase 3-wire (2ch), Three-phase 3-wire (2ch) and

Three-phase 4-wire.

Demand measurement

Electricity consumption can be easily monitored so as not to exceed the target maximum demand values.

Waveform/ vector display

Voltage and current can be displayed by waveform or vector.

Saving data

KEW6315 is endowed with a logging function with the preset recording interval. Data can be saved by manual

operation or by specifying date & time. Screen data can be saved by using the Print Screen function.

Dual power supply system

KEW6315 operates either with AC power supply or with batteries. Both dry-cell batteries (alkaline) and

rechargeable batteries (Ni-MH) can be used. To charge the rechargeable battery, use the charger which is

manufactured by the same company as the batteries. In the event of power interruption, while operating with

AC power supply, power to the instrument is automatically restored by the batteries in the instrument.

Large display

TFT color display with large screen.

Light & compact design

Clamp sensor type, compact and light weight design.

Application

Data in the SD card or the internal memory can be saved in PC via USB. Analysis of the downloaded

data and instrument settings are possible by using the special software “KEW Windows for KEW6315”.

Real-time communication is available via Bluetooth.

Input/ Output function

Analog signals from thermometers or light sensors can be measured simultaneously with electrical power

data via 2 analog inputs (DC voltage); when any events related to power quality occur, signals can be

transmitted to alarm devices via one digital output.

111... IIInnnssstttrrruuummmeeennnttt OOOvvveeerrrvvviiieeewww

Preface KEW6315

- 1 - KEW6315

● Preface

This Quick manual is a simplified version of the full instruction manual which can be found in

the supplied CD-ROM. This manual is intended only as a handy reference guide and should

only be used after having read the full instruction manual which contains full details on each

function of this instrument and the items contained in the package.

● Safety Warning!

The instruction manual contains warnings and safety procedures which have to be observed

to ensure safe operation of the instrument and maintain it in a safe condition. Thus, these

operating instructions have to be read prior to using the instrument.

Content

1. Instrument Overview ··············································································· 2

2. Start/ Stop Recording ···································································· 5

3. Instrument Layout ················································································· 13

4. Getting Started ····················································································· 17

5. Inst/ Integration/ Demand

Inst value : W ····················································································· 19

Integration value: Wh/ Demand ······························································ 21

6. Vector ······················································································ 25

7. Waveform ················································································· 26

8. Harmonics Analysis ···································································· 27

9. Power Quality

Event(Swell/ Dip/ Int/ Inrush current/ Transient) ·········································· 30

Flicker ································································································ 33

10. Setting ·················································································· 35

11. SD Card/ Saved Data ··········································································· 38

The latest software can be downloaded from our homepage: http://www.kew-ltd.co.jp.

Page 4: Quick Manual - 共立電気計器株式会社

- 3 - KEW6315

Functional overview KEW6315Functional overview KEW6315

- 3 - KEW6315

Inst/ Integration/ Demand

Display the avg/ max/ min instantaneous values of

current/ voltage/ active power/ apparent power/

reactive power. Integration values also can be viewed

by switching screens. Moreover, demand values with

the preset target value can also be checked.

See “5. Inst/ Integration/ Demand” for further details.

Vector and Wiring check

Vectors of voltage and current per CH are

displayed on a graph. KEW6315 will perform

wiring check.

See “6. Vector” for further details.

Functional overview

Start/ Stop

Choose either “Quick start guide” or “Start now” to start

recording. Can do simple and fast start-up setting by

selecting “Quick start guide”.

See “2. Start/Stop Recording” for further details.

KEW6315 Functional overview

KEW6315 - 4 -

Waveform

Waveforms of voltage and current per CH are displayed on a

graph.

See “7. Waveform” for further details.

Harmonic Analysis

Harmonic components of voltage and current per CH are

displayed on a graph. See “8. Harmonic Analysis” for further details.

Power Quality (QUALITY) event

Display voltage swell, dip, int, transient, inrush current

and flicker.

See “9. Power Quality” for further details.

Setting (SET UP)

Make settings for KEW6315 and measurements.

See “10. Setting” for further details.

Page 5: Quick Manual - 共立電気計器株式会社

- 4 -KEW6315

KEW6315 Functional overviewFunctional overview KEW6315

- 3 - KEW6315

Inst/ Integration/ Demand

Display the avg/ max/ min instantaneous values of

current/ voltage/ active power/ apparent power/

reactive power. Integration values also can be viewed

by switching screens. Moreover, demand values with

the preset target value can also be checked.

See “5. Inst/ Integration/ Demand” for further details.

Vector and Wiring check

Vectors of voltage and current per CH are

displayed on a graph. KEW6315 will perform

wiring check.

See “6. Vector” for further details.

Functional overview

Start/ Stop

Choose either “Quick start guide” or “Start now” to start

recording. Can do simple and fast start-up setting by

selecting “Quick start guide”.

See “2. Start/Stop Recording” for further details.

KEW6315 Functional overview

KEW6315 - 4 -

Waveform

Waveforms of voltage and current per CH are displayed on a

graph.

See “7. Waveform” for further details.

Harmonic Analysis

Harmonic components of voltage and current per CH are

displayed on a graph. See “8. Harmonic Analysis” for further details.

Power Quality (QUALITY) event

Display voltage swell, dip, int, transient, inrush current

and flicker.

See “9. Power Quality” for further details.

Setting (SET UP)

Make settings for KEW6315 and measurements.

See “10. Setting” for further details.

Page 6: Quick Manual - 共立電気計器株式会社

- 5 - KEW6315

Start/ stop recording KEW6315Start/ stop recording KEW6315

- 5 - KEW6315

Steps for measurement

Can start recordings with simple steps by selecting “Quick start guide”.

Ensure your safety and do the appropriate preparations before starting measurements.

Select the

recording item

Select the

wiring system Confirm the

connections

Check the test

environment

(1) Select the item you want to record.

* The number of selected items will have effect on file size and

also on max recording time.

(2) Select the wiring system to be measured.

* Select a proper wiring system for accurate

measurements.

222... SSStttaaarrrttt/// SSStttoooppp RRReeecccooorrrdddiiinnnggg

(3) Connect to the circuit to be tested.

* Read and follow the safety precautions

described in the instruction manual.

(4)(5) Check the Test environment.

* Self-diagnosis, wiring check and detection of connected

sensors will be performed in this test.

* It is recommended to do this test for ensuring the testing

conditions are correct.

See P.17.

See P.8.

See P.7.

See P.40.

KEW6315 Start/ stop recording

KEW6315 - 6 -

Select the

rec. interval

Select the

rec. method

Check the

selected method

Start

recording

(6) Select a recording interval.

* Selecting a short interval gets the file size large. In this

case, a long period recording cannot be performed.

(7)(8)(9) Select a recording method.

(10) Prepared. Recording will start.

The mark “ REC ” will appear on the screen

when the recording starts and the green LED

(status indicator) lights up.

If you want to terminate the recording, press

the “ ” button and follow the instructions

displayed on the screen.

See P.11.

See P.38.

Page 7: Quick Manual - 共立電気計器株式会社

- 6 -KEW6315

KEW6315 Start/ stop recordingStart/ stop recording KEW6315

- 5 - KEW6315

Steps for measurement

Can start recordings with simple steps by selecting “Quick start guide”.

Ensure your safety and do the appropriate preparations before starting measurements.

Select the

recording item

Select the

wiring system Confirm the

connections

Check the test

environment

(1) Select the item you want to record.

* The number of selected items will have effect on file size and

also on max recording time.

(2) Select the wiring system to be measured.

* Select a proper wiring system for accurate

measurements.

222... SSStttaaarrrttt/// SSStttoooppp RRReeecccooorrrdddiiinnnggg

(3) Connect to the circuit to be tested.

* Read and follow the safety precautions

described in the instruction manual.

(4)(5) Check the Test environment.

* Self-diagnosis, wiring check and detection of connected

sensors will be performed in this test.

* It is recommended to do this test for ensuring the testing

conditions are correct.

See P.17.

See P.8.

See P.7.

See P.40.

KEW6315 Start/ stop recording

KEW6315 - 6 -

Select the

rec. interval

Select the

rec. method

Check the

selected method

Start

recording

(6) Select a recording interval.

* Selecting a short interval gets the file size large. In this

case, a long period recording cannot be performed.

(7)(8)(9) Select a recording method.

(10) Prepared. Recording will start.

The mark “ REC ” will appear on the screen

when the recording starts and the green LED

(status indicator) lights up.

If you want to terminate the recording, press

the “ ” button and follow the instructions

displayed on the screen.

See P.11.

See P.38.

Page 8: Quick Manual - 共立電気計器株式会社

- 7 - KEW6315

Wiring system KEW6315Wiring system KEW6315

- 7 - KEW6315

Orientation of Clamp sensor

Power

source

Arrow mark:

Point towards

load side.

Load

Reverse clamping switches the symbols (+/-)

for active power (P).

(2) Wiring system

Any of the followings can be selected.

L1

L1

N

L

Load

(1)

1P2W

Pow

er

supp

ly

1P2W×1

1P2W×2

1P2W×3

1P2W×4

Load

(2)

1P2W

Load

(3)

1P2W

Load

(4)

1P2W

N

L

N

L

N

L

N

L

A4A3

A2 A1

VN V1

NLoad

(1)

1P3W

Pow

er

supp

ly

1P3W×1

1P3W×2

Load

(2)

1P3W

N

L2

L2

N

A4 A3

A2A1

VN

V1

L1

L2

V2

L1(R)

L2(S)

Load

(1)

3P3W

Pow

er

supp

ly

3P3W×1

3P3W×2

Load

(2)

3P3W

L2(S)

L3(T)

A4A3

A2A1

VN

V1

L1(R)

L3(T)

V2

L2(S)

L3(T)

L1(R)

L2(S) Load

3P3W

Pow

er

supp

ly

3P3W3A

L2(S)

L3(T)

A3 A2

A1

V3

V1

L1(R)

L3(T)

V2

L1(R)

L2(S)

Load

3P4W

Pow

er su

pply

3P4W

L2(S)

L3(T)

A3A2

A1

V3

V1

L1(R)

L3(T)

V2

L1(R)

VN

N N

KEW6315 Environment check

KEW6315 - 8 -

(4)/ (5) Test Environment Check

Select and press the “ENTER” on “OK”/

”NG” to see the details.

Test environment check

Select “ Start test ”and press the “ENTER”

button to start the test. The test result will be

displayed on the screen.

Wiring check

Test results of each item will be displayed.

* NG result may be given, even if the wiring is correct,

at the measurement site under bad power factors.

Self-diagnosis

Operating condition of the instrument system will

be checked and the result will be displayed.

Sensor detection

The connected sensors are automatically

detected and their max Ranges will be set.

NOTE:Types of the current sensors used for measurements should be the same.

Page 9: Quick Manual - 共立電気計器株式会社

- 8 -KEW6315

KEW6315 Environment checkWiring system KEW6315

- 7 - KEW6315

Orientation of Clamp sensor

Power

source

Arrow mark:

Point towards

load side.

Load

Reverse clamping switches the symbols (+/-)

for active power (P).

(2) Wiring system

Any of the followings can be selected.

L1

L1

N

L

Load

(1)

1P2W

Pow

er

supp

ly

1P2W×1

1P2W×2

1P2W×3

1P2W×4

Load

(2)

1P2W

Load

(3)

1P2W

Load

(4)

1P2W

N

L

N

L

N

L

N

L

A4A3

A2 A1

VN V1

NLoad

(1)

1P3W

Pow

er

supp

ly

1P3W×1

1P3W×2

Load

(2)

1P3W

N

L2

L2

N

A4 A3

A2A1

VN

V1

L1

L2

V2

L1(R)

L2(S)

Load

(1)

3P3W

Pow

er

supp

ly

3P3W×1

3P3W×2

Load

(2)

3P3W

L2(S)

L3(T)

A4A3

A2A1

VN

V1

L1(R)

L3(T)

V2

L2(S)

L3(T)

L1(R)

L2(S) Load

3P3W

Pow

er

supp

ly

3P3W3A

L2(S)

L3(T)

A3 A2

A1

V3

V1

L1(R)

L3(T)

V2

L1(R)

L2(S)

Load

3P4W

Pow

er su

pply

3P4W

L2(S)

L3(T)

A3A2

A1

V3

V1

L1(R)

L3(T)

V2

L1(R)

VN

N N

KEW6315 Environment check

KEW6315 - 8 -

(4)/ (5) Test Environment Check

Select and press the “ENTER” on “OK”/

”NG” to see the details.

Test environment check

Select “ Start test ”and press the “ENTER”

button to start the test. The test result will be

displayed on the screen.

Wiring check

Test results of each item will be displayed.

* NG result may be given, even if the wiring is correct,

at the measurement site under bad power factors.

Self-diagnosis

Operating condition of the instrument system will

be checked and the result will be displayed.

Sensor detection

The connected sensors are automatically

detected and their max Ranges will be set.

Page 10: Quick Manual - 共立電気計器株式会社

- 9 - KEW6315

Wiring check KEW6315Wiring check KEW6315

- 9 - KEW6315

NG judgment

Wiring check

Close the result display. Then, the blinking vectors and the

values of NG items will be displayed. If all the results are

OK, the ideal vector diagram will be displayed at the lower

left corner.

Criteria of judgment and cause Check Criteria of Judgment Causes

Frequency Frequency of V1 is within 40

- 70Hz.

- Voltage clip is firmly connected to the DUT?

- Measuring too high harmonic components?

AC voltage

input

AC voltage input is 10% or

more of (Nominal voltage x

VT).

- Voltage clip is firmly connected to the DUT?

- Voltage test lead is firmly connected to the

AC voltage input terminal on the instrument?

Voltage

balance

AC voltage input is within

±20% of reference voltage

(V1).

* (not checked in

single-phase wiring)

- Settings are matched with the wiring system under

test?

- Voltage clip is firmly connected to the DUT?

- Voltage test lead is firmly connected to the

AC voltage input terminal on the instrument?

Voltage

phase

Phase of AC voltage input is

within ±10º of reference value

(proper vector).

- Voltage test leads are properly connected?

(Connected to proper channels?)

Current

input

Current input is 5% or more

and 110% or less of (Current

Range x CT).

- Clamp sensors are firmly connected to the Power

input terminals on the instrument?

- Setting for Current Range is appropriate for input levels?

Current

phase

- Power factor (PF, absolute

value) at each CH is 0.5 or

more.

- Active power (P) at each

CH is positive value.

- Arrow mark on the Clamp sensor and the orientation

of flowing current coincide with each other?

(Power supply to Load)

- Clamp sensors are connected properly?

KEW6315 Self-diagnosis

KEW6315 - 10 -

Self-diagnosis

If “NG” judgment is given frequently, there might be something wrong with the instrument. Stop using the

instrument and refer to “Troubleshooting” in the instruction manual.

Sensor detection

If the detection result is NG, each sensor type will be displayed in red.

Criteria of judgment and cause

Causes

Check

Causes

Type of

current sensor

- Types of the connected current sensors are harmonized? Types of the current

sensors used for measurements should be the same.

???

(cause unknown)

- Current sensors are firmly connected to the instrument?

- If any failures are in doubt:

Exchange the connections of the sensors and test again.

Connect the current sensor, for which "NG" is given, to the CH on which

another sensor is properly detected.

If the result "NG" is given for the same CH, a defect of the instrument is

suspected. A defect of sensor is suspected if "NG" is given for the same

sensor connected to another CH.

Stop using the instrument and the sensor, if any defects are in doubt, and refer

to "Troubleshooting" in the instruction manual.

Page 11: Quick Manual - 共立電気計器株式会社

- 10 -KEW6315

KEW6315 Self-diagnosisWiring check KEW6315

- 9 - KEW6315

NG judgment

Wiring check

Close the result display. Then, the blinking vectors and the

values of NG items will be displayed. If all the results are

OK, the ideal vector diagram will be displayed at the lower

left corner.

Criteria of judgment and cause Check Criteria of Judgment Causes

Frequency Frequency of V1 is within 40

- 70Hz.

- Voltage clip is firmly connected to the DUT?

- Measuring too high harmonic components?

AC voltage

input

AC voltage input is 10% or

more of (Nominal voltage x

VT).

- Voltage clip is firmly connected to the DUT?

- Voltage test lead is firmly connected to the

AC voltage input terminal on the instrument?

Voltage

balance

AC voltage input is within

±20% of reference voltage

(V1).

* (not checked in

single-phase wiring)

- Settings are matched with the wiring system under

test?

- Voltage clip is firmly connected to the DUT?

- Voltage test lead is firmly connected to the

AC voltage input terminal on the instrument?

Voltage

phase

Phase of AC voltage input is

within ±10º of reference value

(proper vector).

- Voltage test leads are properly connected?

(Connected to proper channels?)

Current

input

Current input is 5% or more

and 110% or less of (Current

Range x CT).

- Clamp sensors are firmly connected to the Power

input terminals on the instrument?

- Setting for Current Range is appropriate for input levels?

Current

phase

- Power factor (PF, absolute

value) at each CH is 0.5 or

more.

- Active power (P) at each

CH is positive value.

- Arrow mark on the Clamp sensor and the orientation

of flowing current coincide with each other?

(Power supply to Load)

- Clamp sensors are connected properly?

KEW6315 Self-diagnosis

KEW6315 - 10 -

Self-diagnosis

If “NG” judgment is given frequently, there might be something wrong with the instrument. Stop using the

instrument and refer to “Troubleshooting” in the instruction manual.

Sensor detection

If the detection result is NG, each sensor type will be displayed in red.

Criteria of judgment and cause

Causes

Check

Causes

Type of

current sensor

- Types of the connected current sensors are harmonized? Types of the current

sensors used for measurements should be the same.

???

(cause unknown)

- Current sensors are firmly connected to the instrument?

- If any failures are in doubt:

Exchange the connections of the sensors and test again.

Connect the current sensor, for which "NG" is given, to the CH on which

another sensor is properly detected.

If the result "NG" is given for the same CH, a defect of the instrument is

suspected. A defect of sensor is suspected if "NG" is given for the same

sensor connected to another CH.

Stop using the instrument and the sensor, if any defects are in doubt, and refer

to "Troubleshooting" in the instruction manual.

Page 12: Quick Manual - 共立電気計器株式会社

- 11 - KEW6315

Setting for recording method KEW6315Setting for recording method KEW6315

- 11 - KEW6315

(8)/ (9) Setting for recording method

The following explains how to set recording start date and time.

(8) Specify the recording start date and time.

During the selected period, KEW6315 performs recording at the preset intervals.

Example: When the date & time are specified as above, the recording period will be as follows.

From 8:00 on August 2, 2013 to 18:00 on August 7, 2013,

(9) Specify the recording time period.

KEW6315 performs recording during the selected time period at the preset intervals, and repeats

recording processes during the preset time span.

Example: When the time period is specified as above, the recording period is as follows. KEW6315 does not

record data between 18:00 and 8:00.

(i) 8:00 to 18:00 on August 1, 2013,

(ii) 8:00 to 18:00 on August 2, 2013,

(iii) 8:00 to 18:00 on August 3, 2013,

(iv) 8:00 to 18:00 on August 4, 2013,

(v) 8:00 to 18:00 on August 5, 2013,

(vi) 8:00 to 18:00 on August 6, 2013,

(vii) 8:00 to 18:00 on August 7, 2013, and

(viii) 8:00 to 18:00 on August 8, 2013.

KEW6315 Operating procedure

KEW6315 - 12 -

Switching of displayed parameters

Basically, the Cursor Key is used for selecting an item, the ENTER Key is for confirming the

selection, and the ESC Key is for canceling the alternation. Taking the procedures in “Quick Start

Guide” as an example, Key operations are explained as follows.

Press the Cursor Key to move the blue highlight, showing the item

is being selected, over the items in blue letters. In the screen at the

left is the Recording start screen. Press the Cursor Key and move

the blue highlight on the desirable recording method, and press the

ENTER Key to confirm the selection. To quit the start guide, press

the ESC Key.

If the display of the selectable items is similar to the one shown

to the left, then the up, down, right and left Cursor Keys can be

used. Use the Cursor Keys to select the proper wiring system and

press the ENTER Key to confirm the selection. To return to the

previous screen and cancel the changes, press the ESC Key.

To alter the numbers such as Date/ Time, move the blue highlight

over digits with the right and left Cursor Keys and alter the number

with the up and down Cursor Keys.

In the screen to the left, the tenth place of the day is being selected.

The number can be increased or decreased by 1 with the up/ down

Cursor Keys. Press the ENTER Key to confirm the selection, or

press the ESC Key to return to the previous screen and cancel

the changes.

Page 13: Quick Manual - 共立電気計器株式会社

- 12 -KEW6315

KEW6315 Operating procedureSetting for recording method KEW6315

- 11 - KEW6315

(8)/ (9) Setting for recording method

The following explains how to set recording start date and time.

(8) Specify the recording start date and time.

During the selected period, KEW6315 performs recording at the preset intervals.

Example: When the date & time are specified as above, the recording period will be as follows.

From 8:00 on August 2, 2013 to 18:00 on August 7, 2013,

(9) Specify the recording time period.

KEW6315 performs recording during the selected time period at the preset intervals, and repeats

recording processes during the preset time span.

Example: When the time period is specified as above, the recording period is as follows. KEW6315 does not

record data between 18:00 and 8:00.

(i) 8:00 to 18:00 on August 1, 2013,

(ii) 8:00 to 18:00 on August 2, 2013,

(iii) 8:00 to 18:00 on August 3, 2013,

(iv) 8:00 to 18:00 on August 4, 2013,

(v) 8:00 to 18:00 on August 5, 2013,

(vi) 8:00 to 18:00 on August 6, 2013,

(vii) 8:00 to 18:00 on August 7, 2013, and

(viii) 8:00 to 18:00 on August 8, 2013.

KEW6315 Operating procedure

KEW6315 - 12 -

Switching of displayed parameters

Basically, the Cursor Key is used for selecting an item, the ENTER Key is for confirming the

selection, and the ESC Key is for canceling the alternation. Taking the procedures in “Quick Start

Guide” as an example, Key operations are explained as follows.

Press the Cursor Key to move the blue highlight, showing the item

is being selected, over the items in blue letters. In the screen at the

left is the Recording start screen. Press the Cursor Key and move

the blue highlight on the desirable recording method, and press the

ENTER Key to confirm the selection. To quit the start guide, press

the ESC Key.

If the display of the selectable items is similar to the one shown

to the left, then the up, down, right and left Cursor Keys can be

used. Use the Cursor Keys to select the proper wiring system and

press the ENTER Key to confirm the selection. To return to the

previous screen and cancel the changes, press the ESC Key.

To alter the numbers such as Date/ Time, move the blue highlight

over digits with the right and left Cursor Keys and alter the number

with the up and down Cursor Keys.

In the screen to the left, the tenth place of the day is being selected.

The number can be increased or decreased by 1 with the up/ down

Cursor Keys. Press the ENTER Key to confirm the selection, or

press the ESC Key to return to the previous screen and cancel

the changes.

Page 14: Quick Manual - 共立電気計器株式会社

- 13 - KEW6315

Instrument layout KEW6315Instrument layout KEW6315

- 13 - KEW6315

各部の名称

Front View

333... IIInnnssstttrrruuummmeeennnttt LLLaaayyyooouuuttt

Keys

ENTER Key

Confirm the entries.

Display

(LCD)

Function Key

Execute the displayed function.

PRINT SCREEN Key

Save the displayed screen as BMP file.

DATA HOLD Key/ KEY LOCK Key

Hold the readings on the display.

* Measurement continues while the

readings are being held on the display.

KEY

LOCK

Long press (at least 2 sec) disables

all Keys to prevent operational

errors. Another long press (at least

2 sec) is required to restore the

disabled Keys.

LCD Key

Turn on/ off the backlight.

Long press (at least 2 sec) changes

the brightness and contrast.

Cursor Key

Select items or switch displays.

SETUP Key

Change and confirm: Basic, Measurement, Record-

ing and other settings, and also edit the saved data.

Power Key

Power on/ off.

START/ STOP Key

Start/ stop

measurement..

Menu Key

W/Wh

View inst, integration

and demand values.

Harmonic

Analysis

View harmonic voltage, current

and power energy.

Vector View phases.

Power

Quality

View the detailed info about:

swell, dip, int, transient, inrush

current and flicker. Waveform

View voltage/ current

waveforms.

Status LED

Green

Light up: Recording& measuring

Blink: Stand-by

Red Blink: Backlight is off.

ESC Key/ RESET Key

Cancel setting changes and return to

the previous settings.

KEW6315 Connector

KEW6315 - 14 -

Analog Input/ Digital Output Terminal

SD Card Slot

USB port

Connector

Side face Battery case

AC voltage Input Terminal

(VN, V1, V2, V3)

Power Connector

Current Input Terminal

(A1, A2, A3, A4)

Terminal Cover

Battery Cover

Page 15: Quick Manual - 共立電気計器株式会社

- 14 -KEW6315

KEW6315 ConnectorInstrument layout KEW6315

- 13 - KEW6315

各部の名称

Front View

333... IIInnnssstttrrruuummmeeennnttt LLLaaayyyooouuuttt

Keys

ENTER Key

Confirm the entries.

Display

(LCD)

Function Key

Execute the displayed function.

PRINT SCREEN Key

Save the displayed screen as BMP file.

DATA HOLD Key/ KEY LOCK Key

Hold the readings on the display.

* Measurement continues while the

readings are being held on the display.

KEY

LOCK

Long press (at least 2 sec) disables

all Keys to prevent operational

errors. Another long press (at least

2 sec) is required to restore the

disabled Keys.

LCD Key

Turn on/ off the backlight.

Long press (at least 2 sec) changes

the brightness and contrast.

Cursor Key

Select items or switch displays.

SETUP Key

Change and confirm: Basic, Measurement, Record-

ing and other settings, and also edit the saved data.

Power Key

Power on/ off.

START/ STOP Key

Start/ stop

measurement..

Menu Key

W/Wh

View inst, integration

and demand values.

Harmonic

Analysis

View harmonic voltage, current

and power energy.

Vector View phases.

Power

Quality

View the detailed info about:

swell, dip, int, transient, inrush

current and flicker. Waveform

View voltage/ current

waveforms.

Status LED

Green

Light up: Recording& measuring

Blink: Stand-by

Red Blink: Backlight is off.

ESC Key/ RESET Key

Cancel setting changes and return to

the previous settings.

KEW6315 Connector

KEW6315 - 14 -

Analog Input/ Digital Output Terminal

SD Card Slot

USB port

Connector

Side face Battery case

AC voltage Input Terminal

(VN, V1, V2, V3)

Power Connector

Current Input Terminal

(A1, A2, A3, A4)

Terminal Cover

Battery Cover

Page 16: Quick Manual - 共立電気計器株式会社

- 15 - KEW6315

Symbols on the LCD KEW6315Symbols on the LCD KEW6315

- 15 - KEW6315

Icons on the LCD

Icon Status

KEW6315 is operating with battery. This icon varies in 4 steps according to the

battery power condition.

KEW6315 is operating with AC power.

Holding the display update.

Keys are locked.

Buzzer is off.

SD card is set and available.

Recording the data on the SD card.

Available free space in the SD card is not enough.

Failed to access to the SD card.

Internal memory is available.

* This icon is displayed when a measurement starts without SD card.

Recording the data in the internal memory.

Available free space in the internal memory is not enough.

Stand-by mode

Recording the measured data.

Capacity of recording media is full.

USB is available.

Bluetooth is available.

KEW6315 Symbols on the LCD

KEW6315 - 16 -

Symbols on the LCD

*1

W screen: Displays of V and VL can be “customized” when “3P4W” is selected.

*2

W screen: “An” is displayed only when “3P4W” is selected.

*3

W screen: Displays of PA and C can be “customized”.

Backlight and Contrast Adjustment

Hold down the “ ” LCD Key at least 2 sec to show the sliding bar to adjust the backlight brightness and

display contrast. Use the Cursor Key to slide the cursor on the bar for the adjustment. Press the ENTER

Key and exit from the adjustment mode. Press the ESC or LCD Key again to cancel the adjustment and

exit from the adjustment mode.

Symbols displayed on the LCD

V*1

Phase voltage VL*1

Line voltage A Current

P

Active

power

+ consumption

Q

Reactive

power

+ lagging

S

Apparent

power - regenerating - leading

PF

Power

factor

+ lagging

f Frequency

- leading

DC1

Analog input

voltage at 1ch

DC2

Analog input

voltage at 2ch

An*2

Neutral current PA*3

Phase

angle

+ lagging

C*3

Capacitance calculation

- leading

WP+

Active power energy

(consumption)

WS+

Apparent power energy

(consumption)

WQi+

Reactive power energy

(lagging)

WP-

Active power energy

(regenerating)

WS-

Apparent power energy

(regenerating)

WQc+

Reactive power energy

(leading)

THD

Voltage/ Current

total distortion factor

Pst

(1min)

Voltage flicker (1 min) Pst Short term voltage flicker Plt Long term voltage flicker

Brightness adjustment

Backlight brightness can be changed by 11 levels.

Contrast adjustment

Contrast can be changed by 11 levels.

Page 17: Quick Manual - 共立電気計器株式会社

- 16 -KEW6315

KEW6315 Symbols on the LCDSymbols on the LCD KEW6315

- 15 - KEW6315

Icons on the LCD

Icon Status

KEW6315 is operating with battery. This icon varies in 4 steps according to the

battery power condition.

KEW6315 is operating with AC power.

Holding the display update.

Keys are locked.

Buzzer is off.

SD card is set and available.

Recording the data on the SD card.

Available free space in the SD card is not enough.

Failed to access to the SD card.

Internal memory is available.

* This icon is displayed when a measurement starts without SD card.

Recording the data in the internal memory.

Available free space in the internal memory is not enough.

Stand-by mode

Recording the measured data.

Capacity of recording media is full.

USB is available.

Bluetooth is available.

KEW6315 Symbols on the LCD

KEW6315 - 16 -

Symbols on the LCD

*1

W screen: Displays of V and VL can be “customized” when “3P4W” is selected.

*2

W screen: “An” is displayed only when “3P4W” is selected.

*3

W screen: Displays of PA and C can be “customized”.

Backlight and Contrast Adjustment

Hold down the “ ” LCD Key at least 2 sec to show the sliding bar to adjust the backlight brightness and

display contrast. Use the Cursor Key to slide the cursor on the bar for the adjustment. Press the ENTER

Key and exit from the adjustment mode. Press the ESC or LCD Key again to cancel the adjustment and

exit from the adjustment mode.

Symbols displayed on the LCD

V*1

Phase voltage VL*1

Line voltage A Current

P

Active

power

+ consumption

Q

Reactive

power

+ lagging

S

Apparent

power - regenerating - leading

PF

Power

factor

+ lagging

f Frequency

- leading

DC1

Analog input

voltage at 1ch

DC2

Analog input

voltage at 2ch

An*2

Neutral current PA*3

Phase

angle

+ lagging

C*3

Capacitance calculation

- leading

WP+

Active power energy

(consumption)

WS+

Apparent power energy

(consumption)

WQi+

Reactive power energy

(lagging)

WP-

Active power energy

(regenerating)

WS-

Apparent power energy

(regenerating)

WQc+

Reactive power energy

(leading)

THD

Voltage/ Current

total distortion factor

Pst

(1min)

Voltage flicker (1 min) Pst Short term voltage flicker Plt Long term voltage flicker

Brightness adjustment

Backlight brightness can be changed by 11 levels.

Contrast adjustment

Contrast can be changed by 11 levels.

Page 18: Quick Manual - 共立電気計器株式会社

- 17 - KEW6315

Power supply KEW6315Power supply KEW6315

- 17 - KEW6315

測定前の確認 Power supply

KEW6315 operates with either an AC power supply or batteries. Capable of performing measurements in

the event of AC power interruption, power to the instrument is automatically restored by the batteries

installed in the instrument. AA size alkaline battery (LR6) and AA size rechargeable battery (Ni-MH) can

be both used. To charge the rechargeable battery, use the charger which is manufactured by the same

company as the batteries. KEW6315 cannot charge batteries. If an AC supply is interrupted and the batteries have not been inserted, the instrument goes off and

all data may lost.

Battery Mark on the LCD/ Battery level

Power supply icon changes as follows, and the battery icon varies according to the battery condition.

Pow

er su

pply

ic

on

Powered by AC

Powered by

battery

How to install batteries:

Install batteries in correct polarity

as marked inside.

Battery power is consumed even if the instrument is being off. Remove all the batteries if the instrument is

to be stored and will not be in use for a long period.

Battery le

vel

4-level

Possible continuous measurement hours:

- approx 3 hours with size AA alkaline batteries, and

- approx 4.5 hours with size AA Ni-MH (1900mA/h) batteries.

* These are ref. values with LCD turned off.

Instrument works normally.

* Voltage of full-charged Ni-MH battery is lower than the one of the

full-charged alkaline battery, so the level indicator may not be the

same as the one shown above even after fully charged.

Measurement continues, but data save is ceased.

(Further data will not be saved, but the data measured

before the battery level drops to the lowest level are

saved.)

444... GGGeeettttttiiinnnggg SSStttaaarrrttteeeddd

KEW6315 Cord connection

KEW6315 - 18 -

Cord Connection

Start-up Screen

Model name and software version will be displayed upon powering on the instrument. Stop using

the instrument if it does not get started properly, and refer to the “Trouble-shooting” in the

instruction manual.

Match the

arrow marks.

Rated supply voltage : 100 - 240VAC(±10%)

Rated supply frequency : 45 - 65Hz

Max power consumption : 20VAmax

Voltage test leads

Power cord

Clamp sensor

Page 19: Quick Manual - 共立電気計器株式会社

- 18 -KEW6315

KEW6315 Cord connectionPower supply KEW6315

- 17 - KEW6315

測定前の確認 Power supply

KEW6315 operates with either an AC power supply or batteries. Capable of performing measurements in

the event of AC power interruption, power to the instrument is automatically restored by the batteries

installed in the instrument. AA size alkaline battery (LR6) and AA size rechargeable battery (Ni-MH) can

be both used. To charge the rechargeable battery, use the charger which is manufactured by the same

company as the batteries. KEW6315 cannot charge batteries. If an AC supply is interrupted and the batteries have not been inserted, the instrument goes off and

all data may lost.

Battery Mark on the LCD/ Battery level

Power supply icon changes as follows, and the battery icon varies according to the battery condition.

Pow

er su

pply

ic

on

Powered by AC

Powered by

battery

How to install batteries:

Install batteries in correct polarity

as marked inside.

Battery power is consumed even if the instrument is being off. Remove all the batteries if the instrument is

to be stored and will not be in use for a long period.

Battery le

vel

4-level

Possible continuous measurement hours:

- approx 3 hours with size AA alkaline batteries, and

- approx 4.5 hours with size AA Ni-MH (1900mA/h) batteries.

* These are ref. values with LCD turned off.

Instrument works normally.

* Voltage of full-charged Ni-MH battery is lower than the one of the

full-charged alkaline battery, so the level indicator may not be the

same as the one shown above even after fully charged.

Measurement continues, but data save is ceased.

(Further data will not be saved, but the data measured

before the battery level drops to the lowest level are

saved.)

444... GGGeeettttttiiinnnggg SSStttaaarrrttteeeddd

KEW6315 Cord connection

KEW6315 - 18 -

Cord Connection

Start-up Screen

Model name and software version will be displayed upon powering on the instrument. Stop using

the instrument if it does not get started properly, and refer to the “Trouble-shooting” in the

instruction manual.

Match the

arrow marks.

Rated supply voltage : 100 - 240VAC(±10%)

Rated supply frequency : 45 - 65Hz

Max power consumption : 20VAmax

Voltage test leads

Power cord

Clamp sensor

Protective fingerguard / BarrierIt is a part providing protection against electrical shock and ensuring the minimum required air and creepage distances.* When the instrument and the test lead are combined and used together, whichever lower category either of them belongs to will be applied.

Page 20: Quick Manual - 共立電気計器株式会社

- 19 - KEW6315

Instantaneous value: W KEW6315Instantaneous value: W KEW6315

- 19 - KEW6315

瞬時値/積算値/デマンド

Switching screens

Press the button to toggle the screens.

瞬時値「W」

Switching the items to be displayed

Use the right and left Cursor Keys to switch the displayed systems and the up and down Cursor

Keys to switch the avg, max and min inst values.

W (Inst value) Wh (Integration value) Demand

Measured values

per CH

Sum of measured

values (all CHs)

555... IIInnnsssttt/// IIInnnttteeegggrrraaatttiiiooonnn/// DDDeeemmmaaannnddd vvvaaallluuueeesss

IIInnnsssttt vvvaaallluuueee::: “““WWW”””

KEW6315 Instantaneous value: W

KEW6315 - 20 -

Zoom Zoom and display the selected items.

4-split 8-split

Customize Select and change the items to be displayed.

Trend

Changes of measured values are displayed on a graph.

Page 21: Quick Manual - 共立電気計器株式会社

- 20 -KEW6315

KEW6315 Instantaneous value: WInstantaneous value: W KEW6315

- 19 - KEW6315

瞬時値/積算値/デマンド

Switching screens

Press the button to toggle the screens.

瞬時値「W」

Switching the items to be displayed

Use the right and left Cursor Keys to switch the displayed systems and the up and down Cursor

Keys to switch the avg, max and min inst values.

W (Inst value) Wh (Integration value) Demand

Measured values

per CH

Sum of measured

values (all CHs)

555... IIInnnsssttt/// IIInnnttteeegggrrraaatttiiiooonnn/// DDDeeemmmaaannnddd vvvaaallluuueeesss

IIInnnsssttt vvvaaallluuueee::: “““WWW”””

KEW6315 Instantaneous value: W

KEW6315 - 20 -

Zoom Zoom and display the selected items.

4-split 8-split

Customize Select and change the items to be displayed.

Trend

Changes of measured values are displayed on a graph.

Page 22: Quick Manual - 共立電気計器株式会社

- 21 - KEW6315

Integration value: Wh KEW6315Integration value: Wh KEW6315

- 21 - KEW6315

積算値「Wh」 Switching the measurement items

Select the proper system with the right and left Cursor Keys and the CH with the up and down

Cursor Keys.

デマンド

Switching the measurement items

Switch and select the items with the up and down Cursor Keys.

Σ: sum of the all measured values

Σ: sum of measured values per CH

IIInnnttteeegggrrraaatttiiiooonnn vvvaaallluuueee::: “““WWWhhh”””

DDDeeemmmaaannnddd

KEW6315 Demand

KEW6315 - 22 -

Parameters displayed when selecting “Meas.” on the right row.

DEM Max with recorded date

Max demand recorded in a measuring period is displayed.

Displayed value will be refreshed if any higher demands

are detected.

DEM Present

Demand value (average power) within a demand

interval. (Integration values of “WP+”

from the start of measurement) x 1 hour

Demand interval

DEM Guess

Estimate and display the demand value that would

be when this demand interval ends.

Present value x demand interval

Elapsed time from the start of the measurement

DEM Target

Set the value by: [SETUP]→ [Measurement]

→[Demand]→[Target].

Time left

Count down the time set by: [SETUP] →

[Measurement] → [Demand] → [Measurement].

Page 23: Quick Manual - 共立電気計器株式会社

- 22 -KEW6315

KEW6315 DemandIntegration value: Wh KEW6315

- 21 - KEW6315

積算値「Wh」 Switching the measurement items

Select the proper system with the right and left Cursor Keys and the CH with the up and down

Cursor Keys.

デマンド

Switching the measurement items

Switch and select the items with the up and down Cursor Keys.

Σ: sum of the all measured values

Σ: sum of measured values per CH

IIInnnttteeegggrrraaatttiiiooonnn vvvaaallluuueee::: “““WWWhhh”””

DDDeeemmmaaannnddd

KEW6315 Demand

KEW6315 - 22 -

Parameters displayed when selecting “Meas.” on the right row.

DEM Max with recorded date

Max demand recorded in a measuring period is displayed.

Displayed value will be refreshed if any higher demands

are detected.

DEM Present

Demand value (average power) within a demand

interval. (Integration values of “WP+”

from the start of measurement) x 1 hour

Demand interval

DEM Guess

Estimate and display the demand value that would

be when this demand interval ends.

Present value x demand interval

Elapsed time from the start of the measurement

DEM Target

Set the value by: [SETUP]→ [Measurement]

→[Demand]→[Target].

Time left

Count down the time set by: [SETUP] →

[Measurement] → [Demand] → [Measurement].

Page 24: Quick Manual - 共立電気計器株式会社

- 23 - KEW6315

Demand KEW6315Demand KEW6315

- 23 - KEW6315

Parameters displayed when selecting “ ” (Change in specific period) on the right

row.

DEM P

Load factor: percentage of the present value

against the target value. Present value Target value DEM G

Percentage of the predicted value against the

target value. Predicted value

Target value

Time left

Count down the time set by: [SETUP] →

[Measurement] → [Demand] → [Measurement].

Save point

Audible warning warns

when the predicted value

exceeds the target value.

(Elapsed time)

Prediction

Demand value

(present value)

Target

Inspection

cycle

Inspection

cycle

Inspection

cycle

Demand

interval

KEW6315 Demand

KEW6315 - 24 -

Parameters displayed when selecting “ ” (Demand change) on the right row.

Cursor

Use the right and left Cursor

Keys to move the cursor.

Max measured demand

(Displayed on measurement

screen.)

Start of demand

Rec. start date& time

Demand value

(Elapsed time)

Bar graph

White bar: Percentage of hidden pages

Orange bar: Percentage of the present displayed

pages

Measured demand with recorded date

Demand value is displayed with recorded

date & time info where the cursor is located.

Target value

End of demand

Most recent rec. date& time

Page 25: Quick Manual - 共立電気計器株式会社

- 24 -KEW6315

KEW6315 DemandDemand KEW6315

- 23 - KEW6315

Parameters displayed when selecting “ ” (Change in specific period) on the right

row.

DEM P

Load factor: percentage of the present value

against the target value. Present value Target value DEM G

Percentage of the predicted value against the

target value. Predicted value

Target value

Time left

Count down the time set by: [SETUP] →

[Measurement] → [Demand] → [Measurement].

Save point

Audible warning warns

when the predicted value

exceeds the target value.

(Elapsed time)

Prediction

Demand value

(present value)

Target

Inspection

cycle

Inspection

cycle

Inspection

cycle

Demand

interval

KEW6315 Demand

KEW6315 - 24 -

Parameters displayed when selecting “ ” (Demand change) on the right row.

Cursor

Use the right and left Cursor

Keys to move the cursor.

Max measured demand

(Displayed on measurement

screen.)

Start of demand

Rec. start date& time

Demand value

(Elapsed time)

Bar graph

White bar: Percentage of hidden pages

Orange bar: Percentage of the present displayed

pages

Measured demand with recorded date

Demand value is displayed with recorded

date & time info where the cursor is located.

Target value

End of demand

Most recent rec. date& time

Page 26: Quick Manual - 共立電気計器株式会社

- 25 - KEW6315

Vector KEW6315Vector KEW6315

- 25 - KEW6315

ベクトル

Switching screens

Wiring check Checked results will be displayed.

: toggle the line lengths of voltage vector.

1 2 5 10

: toggle the line lengths of current vector.

1 2 5 10

666... VVVeeeccctttooorrr

Wiring diagram Diagram of the selected wiring is

displayed.

* time(s)

* time(s)

KEW6315 Waveform

KEW6315 - 26 -

波形

Switching displayed items Select the items with up and down Cursor Keys and check for the waveforms.

Measured values

per CH

Restore all the changed magnification settings and automatically

select the appropriate magnification.

: toggle the magnifications of voltage waveform (vertical).

0.1 0.5 1 2 5 10

: toggle the magnifications of current waveform (vertical).

0.1 0.5 1 2 5 10

: toggle the magnifications of time axis (horizontal).

1 2 5 10

777... WWWaaavvveeefffooorrrmmm

* time(s)

* time(s)

* time(s)

Page 27: Quick Manual - 共立電気計器株式会社

- 26 -KEW6315

KEW6315 WaveformVector KEW6315

- 25 - KEW6315

ベクトル

Switching screens

Wiring check Checked results will be displayed.

: toggle the line lengths of voltage vector.

1 2 5 10

: toggle the line lengths of current vector.

1 2 5 10

666... VVVeeeccctttooorrr

Wiring diagram Diagram of the selected wiring is

displayed.

* time(s)

* time(s)

KEW6315 Waveform

KEW6315 - 26 -

波形

Switching displayed items Select the items with up and down Cursor Keys and check for the waveforms.

Measured values

per CH

Restore all the changed magnification settings and automatically

select the appropriate magnification.

: toggle the magnifications of voltage waveform (vertical).

0.1 0.5 1 2 5 10

: toggle the magnifications of current waveform (vertical).

0.1 0.5 1 2 5 10

: toggle the magnifications of time axis (horizontal).

1 2 5 10

777... WWWaaavvveeefffooorrrmmm

* time(s)

* time(s)

* time(s)

Page 28: Quick Manual - 共立電気計器株式会社

- 27 - KEW6315

Harmonic analysis KEW6315Harmonic analysis KEW6315

- 27 - KEW6315

高調波解析

Switching displayed items Graph Use the up and down Cursor Keys to toggle the CHs for checking each harmonic.

List

Use the up and down Cursor Keys to scroll the displayed degree of harmonics.

888... HHHaaarrrmmmooonnniiicccsss AAAnnnaaalllyyysssiiisss

Measured values

per CH

Measured values

per CH

KEW6315 Harmonic analysis

KEW6315 - 28 -

Zoom

Logarithm List, Rate of content

Phase angle

Voltage, Linear, Overall display

Current Power

RMS value

Current Power

Page 29: Quick Manual - 共立電気計器株式会社

- 28 -KEW6315

KEW6315 Harmonic analysisHarmonic analysis KEW6315

- 27 - KEW6315

高調波解析

Switching displayed items Graph Use the up and down Cursor Keys to toggle the CHs for checking each harmonic.

List

Use the up and down Cursor Keys to scroll the displayed degree of harmonics.

888... HHHaaarrrmmmooonnniiicccsss AAAnnnaaalllyyysssiiisss

Measured values

per CH

Measured values

per CH

KEW6315 Harmonic analysis

KEW6315 - 28 -

Zoom

Logarithm List, Rate of content

Phase angle

Voltage, Linear, Overall display

Current Power

RMS value

Current Power

Page 30: Quick Manual - 共立電気計器株式会社

- 29 - KEW6315

Harmonic analysis KEW6315Harmonic analysis KEW6315

- 29 - KEW6315

Parameters displayed on graph

Overall display

Zoom

Logarithm

Max value

Max values of each order will be marked and

displayed. To turn on/off this function: [SETUP]→

[Measurement]→[Harmonics]→[MAX hold].

Harmonic analysis: 15/ 50th Scroll bar

White: Overall range up to 50th.

Dark orange: Current displayed area.

Use the left and right Cursor Keys to scroll and zoom the desirable area.

Harmonic analysis: max. 50th

Rate of content

Harmonic content against the 1st basic wave.

When selecting “Logarithm”, 10% will be the

max percentage of the vertical axis, and the

higher content rates will not be displayed.

Graph color

If multiple CHs are used, colors harmonized with

each CH will be used and displayed.

Exceeding axis value

Exceeding threshold

Allowable range

Complied with IEC61000-2-4, Class3.

To change the range: [SETUP]→ [Measurement]

→[Harmonics]→[Edit allowable range].

KEW6315 Power quality

KEW6315 - 30 -

電源品質

Switching displayed items

イベント Switching measurement items Use the up and down Cursor Keys and toggle the occurred events to be displayed on the screen.

Event

Displayed events are toggled in the following sequence.

All events Swell Dip Int Transient Inrush current

Flicker

999... PPPooowwweeerrr QQQuuuaaallliiitttyyy

EEEvvveeennnttt

Page 31: Quick Manual - 共立電気計器株式会社

- 30 -KEW6315

KEW6315 Power qualityHarmonic analysis KEW6315

- 29 - KEW6315

Parameters displayed on graph

Overall display

Zoom

Logarithm

Max value

Max values of each order will be marked and

displayed. To turn on/off this function: [SETUP]→

[Measurement]→[Harmonics]→[MAX hold].

Harmonic analysis: 15/ 50th Scroll bar

White: Overall range up to 50th.

Dark orange: Current displayed area.

Use the left and right Cursor Keys to scroll and zoom the desirable area.

Harmonic analysis: max. 50th

Rate of content

Harmonic content against the 1st basic wave.

When selecting “Logarithm”, 10% will be the

max percentage of the vertical axis, and the

higher content rates will not be displayed.

Graph color

If multiple CHs are used, colors harmonized with

each CH will be used and displayed.

Exceeding axis value

Exceeding threshold

Allowable range

Complied with IEC61000-2-4, Class3.

To change the range: [SETUP]→ [Measurement]

→[Harmonics]→[Edit allowable range].

KEW6315 Power quality

KEW6315 - 30 -

電源品質

Switching displayed items

イベント Switching measurement items Use the up and down Cursor Keys and toggle the occurred events to be displayed on the screen.

Event

Displayed events are toggled in the following sequence.

All events Swell Dip Int Transient Inrush current

Flicker

999... PPPooowwweeerrr QQQuuuaaallliiitttyyy

EEEvvveeennnttt

Page 32: Quick Manual - 共立電気計器株式会社

- 31 - KEW6315

Swell/ Dip/ Int/ Inrush current KEW6315Swell/ Dip/ Int/ Inrush current KEW6315

- 31 - KEW6315

Measurement method

Swell/ Dip/ Int/ Inrush current

Each event will be detected with the r.m.s. values in one gapless waveform and with a half-wave over-

lapping. The beginning of the waveform where the first event is detected is regarded as the start of the

event. If further events are not detected in the following waveform, the beginning of the waveform is

regarded as the end of the event. The detected event is assumed to be continued between the start to

the end of event detection.

Example: Dip event detection

*

Int events are detected in the same method.

Example: Swell event detection

*

Inrush current events are detected in the same method.

rms value(1)

rms value(2)

rms value(3) rms value (5) rms value (7) rms value(9)

rms value(4) rms value(6) rms value(8)

Measured

waveform

rms value(1)

rms value(2)

rms value(3) rms value(5) rms value(7) rms value(9)

rms value(4) rms value(6) rms value(8)

Measured

waveform

RMS waveform

Start of dip End of dip

duration

Hysteresis

Threshold

(4)

(5)

(6)

(7) (8) (9) (1) (2) (3)

RMS waveform

Start of swell

duration

End of swell

(4)

(5)

(6)

(7) (8) (9) (1) (2) (3)

Threshold

KEW6315 Transient

KEW6315 - 32 -

Transient

Voltage waveforms will be monitored at approx 40ksps, gapless, to calculate and check for transient event

every 200ms. The beginning of the 200ms period where the first transient is detected is regarded as the

start of the event. If further events are not detected in the following 200ms period, the beginning of the

period is regarded as the end of the event. The detected transient is assumed to be continued between the

start to the end of event detection.

Example: Transient event detection

Saved data

When an event occurs and is detected, KEW6315 records the type of the event, start/ end time and the

values. The following data will also be recorded. The event waveform is recorded for 200ms during the

1 sec of the data refresh period. Event waveform

Waveforms and also event data on all the chs are recorded for approx. 200ms (50Hz: 10-cycle, 60Hz:

12-cycle) at 8192 points in total. When different events occur within 1 sec, only the waveforms which

contain the highest-priority events will be recorded. However, if the same type of events occur at the

same time, the one containing the highest (deepest) values will be recorded. If the highest (deepest)

values are also the same, the one with a longer duration will be recorded. As for the channels, there is

no priority order.

Priority order: Voltage transient-> Int-> Dip-> Swell-> Inrush current

RMS variations

Voltage/ current rms value (resolution: half-cycle) variations and event data on all chs are recorded for

1 sec at data refresh.

Example: Dip detection in 800ms period:

for approx 200ms

Waveform at event start (approx. 200ms) Waveform at event end (approx. 200ms)

r.m.s variations at the detection of

event start (approx. 1sec)

r.m.s variations at the detection of

event end (approx. 1sec)

Measured

waveform

RMS

waveform

End of transient

Threshold value

Measured

waveform

Start of transient

Duration

Page 33: Quick Manual - 共立電気計器株式会社

- 32 -KEW6315

KEW6315 TransientSwell/ Dip/ Int/ Inrush current KEW6315

- 31 - KEW6315

Measurement method

Swell/ Dip/ Int/ Inrush current

Each event will be detected with the r.m.s. values in one gapless waveform and with a half-wave over-

lapping. The beginning of the waveform where the first event is detected is regarded as the start of the

event. If further events are not detected in the following waveform, the beginning of the waveform is

regarded as the end of the event. The detected event is assumed to be continued between the start to

the end of event detection.

Example: Dip event detection

*

Int events are detected in the same method.

Example: Swell event detection

*

Inrush current events are detected in the same method.

rms value(1)

rms value(2)

rms value(3) rms value (5) rms value (7) rms value(9)

rms value(4) rms value(6) rms value(8)

Measured

waveform

rms value(1)

rms value(2)

rms value(3) rms value(5) rms value(7) rms value(9)

rms value(4) rms value(6) rms value(8)

Measured

waveform

RMS waveform

Start of dip End of dip

duration

Hysteresis

Threshold

(4)

(5)

(6)

(7) (8) (9) (1) (2) (3)

RMS waveform

Start of swell

duration

End of swell

(4)

(5)

(6)

(7) (8) (9) (1) (2) (3)

Threshold

KEW6315 Transient

KEW6315 - 32 -

Transient

Voltage waveforms will be monitored at approx 40ksps, gapless, to calculate and check for transient event

every 200ms. The beginning of the 200ms period where the first transient is detected is regarded as the

start of the event. If further events are not detected in the following 200ms period, the beginning of the

period is regarded as the end of the event. The detected transient is assumed to be continued between the

start to the end of event detection.

Example: Transient event detection

Saved data

When an event occurs and is detected, KEW6315 records the type of the event, start/ end time and the

values. The following data will also be recorded. The event waveform is recorded for 200ms during the

1 sec of the data refresh period. Event waveform

Waveforms and also event data on all the chs are recorded for approx. 200ms (50Hz: 10-cycle, 60Hz:

12-cycle) at 8192 points in total. When different events occur within 1 sec, only the waveforms which

contain the highest-priority events will be recorded. However, if the same type of events occur at the

same time, the one containing the highest (deepest) values will be recorded. If the highest (deepest)

values are also the same, the one with a longer duration will be recorded. As for the channels, there is

no priority order.

Priority order: Voltage transient-> Int-> Dip-> Swell-> Inrush current

RMS variations

Voltage/ current rms value (resolution: half-cycle) variations and event data on all chs are recorded for

1 sec at data refresh.

Example: Dip detection in 800ms period:

for approx 200ms

Waveform at event start (approx. 200ms) Waveform at event end (approx. 200ms)

r.m.s variations at the detection of

event start (approx. 1sec)

r.m.s variations at the detection of

event end (approx. 1sec)

Measured

waveform

RMS

waveform

End of transient

Threshold value

Measured

waveform

Start of transient

Duration

Page 34: Quick Manual - 共立電気計器株式会社

- 33 - KEW6315

Flicker KEW6315Flicker KEW6315

- 33 - KEW6315

フリッカ Switching displayed items

Use the up and down Cursor Keys and toggle the items.

Parameters displayed when selecting “ V ” on the right row.

Pst Calc...

Time length required for Pst calculation.

V

Average voltage

Pst(1min)

Pst value is displayed and refreshed every

minute.

Pst

Short-term flicker (Pst) is displayed and refreshed

every 10 min.

MAX: the max values detected through the start to

the end of measurement, and will be refreshed

every time when the max value is exceeded.

Plt

Long-term flicker (Plt) is displayed and refreshed

every 2 hours.

MAX: the max values detected through the start to

the end of measurement, and will be refreshed

every time when the max value is exceeded.

Frequency

The value will be refreshed every second.

FFFllliiiccckkkeeerrr

KEW6315 Flicker

KEW6315 - 34 -

Parameters displayed when selecting “ Pst(1min) ” on the right row.

Parameters displayed when selecting “ Plt ” on the right row.

Max.

Max values detected through the start to the end of

measurement, and will be refreshed every time

when the max value is exceeded.

Pst Calc... Time length required for Pst calculation.

Pst(1min)

Latest measured value.

Max.

Max values detected through the start to the end

of measurement, and will be refreshed every time

when the max value is exceeded. Trend graph

Change of the latest 120 data Pst(1min.).

Cursor

Press the right and left Cursor Keys to move.

(Elapsed time)

Bar graph

White bar:percentage of whole pages.

Orange bar:percentage of the present

displayed pages.

Plt

Plt value and the recorded date & time info where

the cursor is located.

Latest rec. time Rec. start time

Page 35: Quick Manual - 共立電気計器株式会社

- 34 -KEW6315

KEW6315 FlickerFlicker KEW6315

- 33 - KEW6315

フリッカ Switching displayed items

Use the up and down Cursor Keys and toggle the items.

Parameters displayed when selecting “ V ” on the right row.

Pst Calc...

Time length required for Pst calculation.

V

Average voltage

Pst(1min)

Pst value is displayed and refreshed every

minute.

Pst

Short-term flicker (Pst) is displayed and refreshed

every 10 min.

MAX: the max values detected through the start to

the end of measurement, and will be refreshed

every time when the max value is exceeded.

Plt

Long-term flicker (Plt) is displayed and refreshed

every 2 hours.

MAX: the max values detected through the start to

the end of measurement, and will be refreshed

every time when the max value is exceeded.

Frequency

The value will be refreshed every second.

FFFllliiiccckkkeeerrr

KEW6315 Flicker

KEW6315 - 34 -

Parameters displayed when selecting “ Pst(1min) ” on the right row.

Parameters displayed when selecting “ Plt ” on the right row.

Max.

Max values detected through the start to the end of

measurement, and will be refreshed every time

when the max value is exceeded.

Pst Calc... Time length required for Pst calculation.

Pst(1min)

Latest measured value.

Max.

Max values detected through the start to the end

of measurement, and will be refreshed every time

when the max value is exceeded. Trend graph

Change of the latest 120 data Pst(1min.).

Cursor

Press the right and left Cursor Keys to move.

(Elapsed time)

Bar graph

White bar:percentage of whole pages.

Orange bar:percentage of the present

displayed pages.

Plt

Plt value and the recorded date & time info where

the cursor is located.

Latest rec. time Rec. start time

Page 36: Quick Manual - 共立電気計器株式会社

- 35 - KEW6315

Setting (SETUP) KEW6315Setting (SETUP) KEW6315

- 35 - KEW6315

設定

Press the Key to access to any of the following five settings.

Press the Cursor Keys to move to each setting.

Basic setting Make settings for the items common to each measurment.

Meas. setting Make settings for each measurement mode.

Rec. setting Make settings for recoding.

Saved data Edit the recorded data or alter the instrument setting.

Others Configure the environmental setting.

Each setting

Basic

(Wiring)

(Voltage)

(Current)

(External input DC)

(Frequency)

Saved data

(REC data)

(KEW6315 setting)

Others

(Environment)

(KEW6315 setting)

111000... SSSeeettttttiiinnnggg

Recording

(REC item)

(REC method)

(Manual/

Constant rec./

Time period rec.)

Measurement

(Demand)

(Harmonics)

(Power quality)

(Flicker)

(Capacitance

Calc.)

Page 37: Quick Manual - 共立電気計器株式会社

- 36 -KEW6315

KEW6315 Setting (SETUP)Setting (SETUP) KEW6315

- 35 - KEW6315

設定

Press the Key to access to any of the following five settings.

Press the Cursor Keys to move to each setting.

Basic setting Make settings for the items common to each measurment.

Meas. setting Make settings for each measurement mode.

Rec. setting Make settings for recoding.

Saved data Edit the recorded data or alter the instrument setting.

Others Configure the environmental setting.

Each setting

Basic

(Wiring)

(Voltage)

(Current)

(External input DC)

(Frequency)

Saved data

(REC data)

(KEW6315 setting)

Others

(Environment)

(KEW6315 setting)

111000... SSSeeettttttiiinnnggg

Recording

(REC item)

(REC method)

(Manual/

Constant rec./

Time period rec.)

Measurement

(Demand)

(Harmonics)

(Power quality)

(Flicker)

(Capacitance

Calc.)

Page 38: Quick Manual - 共立電気計器株式会社

- 37 - KEW6315

Setting (SETUP) KEW6315Setting (SETUP) KEW6315

- 37 - KEW6315

Measurement setting

Setting item Details of setting

Demand

Interval Not be used/ 10min/15min/30min

Inspection

cycle

Interval: 10min/ 15min 1min/2min/5min

Interval: 30min 1min/2min/5min/10min/15min

Target 0.001mW-999.9TW(100.0kW)

Harmonics

THD(total harmonic distortion) calc. THD-F(based on the fundamental waveform)/

THD-R(based on all rms values)

Allowable range Default/ customize(V/A)

MAX HOLD ON/OFF

Power quality

Hysteresis against nominal V: 1 to 10%(5%)

Transient against nominal V: ±50 to ±2200Vpeak(300%)

Swell against nominal V: 100 to 200%(110%)

Dip against nominal V: 0 to 100%(90%)

Int against nominal V: 0 to 100%(10%)

InrushCurrent against “A” range: 0 to 110%(100%)

Flicker Filter (Ramp) 230V/220V/120V/100V

Capacitance

calculation

Target PF 0.5-1(1.000)

Recording setting

Setting item Details of setting

Recording

item

Harmonics Record/ Do not record

Power quality (event) Record/ Do not record

Recording

method

Interval

1sec/2sec/5sec/10sec/15sec/20sec/30sec/

1min/2min/5min/10min/15min/20min/30min/

1hour/2hours/150,180 cycles (approx 3sec)

Start Manual/Constant rec./Time period rec.

Constant

measurement

REC Start Day/ Month/ Year Hour: Minute (00/00/0000 00:00)

REC End Day/ Month/ Year Hour: Minute (00/00/0000 00:00)

Timer

Rec. period Start-End Day/ Month/ Year (DD/MM/YYYY)- Day/ Month/ Year (DD/MM/YYYY)

Time period Start-End Hour: Minute (hh:mm)- Hour: Minute (hh:mm)

* Default values are highlighted in gray.

Save setting

Setting item Details of setting

REC data

Delete data.

Transfer data.

Format

KEW6315 setting

Save setting.

Read settings.

KEW6315 Saved data

KEW6315 38

Other settings

Setting item Details of setting

Environment

Language* Japanese/ English

Date format* YYYY/MM/DD / MM/DD/YYYY / DD/MM/YYYY

CH color* white/ yellow/ orange/ red/ gray/ blue/ green

The selected colro for VN is refected on the wiring diagram only.

KEW6315

setting

Time* dd/mm/yyyy hh:mm:ss

ID Number 00-001 to 99-999(00-001)

Buzzer ON/OFF

Bluetooth ON/OFF

Power AC power Power off in 5 min./Disable auto-off

Battery Power off in 5 min.

Backlight AC power Power off in 5 min./Disable auto-off

Battery Power off in 2 min.

System reset Reset the system. Confirmation message appears before resetting the system.

*Items listed with “*” mark will not be restored to default even after the system is reset.

* Default values are highlighted in gray.

SD カード/保存データについて Possible recording time When the 2GB of SD is used:

Interval REC item

Interval REC item

Power +Harmonics Power +Harmonics 1sec 13days 3days 1min 1-year or more 3months 2sec 15days 3days 2min 2-year or more 6months 5sec 38days 7days 5min 6-year or more 1-year or more

10sec 2.5months 15days 10min

10-year or more

2-year or more 15sec 3.5months 23days 15min 3-year or more 20sec 5months 1month 20min 5-year or more 30sec 7.5months 1.5months 30min 7-year or more

1hour 10-year or more

2hours 150/180-cycle 23days 4days

* Data of power quality events are not considered to estimate the possible recording time. The max possible time will be shortened by recording such events.

* Please ensure to use the SD cards provided with this instrument or as optional parts.

111111... SSSDDD CCCaaarrrddd/// SSSaaavvveeeddd DDDaaatttaaa

Page 39: Quick Manual - 共立電気計器株式会社

- 38 -KEW6315

KEW6315 Saved dataSetting (SETUP) KEW6315

- 37 - KEW6315

Measurement setting

Setting item Details of setting

Demand

Interval Not be used/ 10min/15min/30min

Inspection

cycle

Interval: 10min/ 15min 1min/2min/5min

Interval: 30min 1min/2min/5min/10min/15min

Target 0.001mW-999.9TW(100.0kW)

Harmonics

THD(total harmonic distortion) calc. THD-F(based on the fundamental waveform)/

THD-R(based on all rms values)

Allowable range Default/ customize(V/A)

MAX HOLD ON/OFF

Power quality

Hysteresis against nominal V: 1 to 10%(5%)

Transient against nominal V: ±50 to ±2200Vpeak(300%)

Swell against nominal V: 100 to 200%(110%)

Dip against nominal V: 0 to 100%(90%)

Int against nominal V: 0 to 100%(10%)

InrushCurrent against “A” range: 0 to 110%(100%)

Flicker Filter (Ramp) 230V/220V/120V/100V

Capacitance

calculation

Target PF 0.5-1(1.000)

Recording setting

Setting item Details of setting

Recording

item

Harmonics Record/ Do not record

Power quality (event) Record/ Do not record

Recording

method

Interval

1sec/2sec/5sec/10sec/15sec/20sec/30sec/

1min/2min/5min/10min/15min/20min/30min/

1hour/2hours/150,180 cycles (approx 3sec)

Start Manual/Constant rec./Time period rec.

Constant

measurement

REC Start Day/ Month/ Year Hour: Minute (00/00/0000 00:00)

REC End Day/ Month/ Year Hour: Minute (00/00/0000 00:00)

Timer

Rec. period Start-End Day/ Month/ Year (DD/MM/YYYY)- Day/ Month/ Year (DD/MM/YYYY)

Time period Start-End Hour: Minute (hh:mm)- Hour: Minute (hh:mm)

* Default values are highlighted in gray.

Save setting

Setting item Details of setting

REC data

Delete data.

Transfer data.

Format

KEW6315 setting

Save setting.

Read settings.

KEW6315 Saved data

KEW6315 38

Other settings

Setting item Details of setting

Environment

Language* Japanese/ English

Date format* YYYY/MM/DD / MM/DD/YYYY / DD/MM/YYYY

CH color* white/ yellow/ orange/ red/ gray/ blue/ green

The selected colro for VN is refected on the wiring diagram only.

KEW6315

setting

Time* dd/mm/yyyy hh:mm:ss

ID Number 00-001 to 99-999(00-001)

Buzzer ON/OFF

Bluetooth ON/OFF

Power AC power Power off in 5 min./Disable auto-off

Battery Power off in 5 min.

Backlight AC power Power off in 5 min./Disable auto-off

Battery Power off in 2 min.

System reset Reset the system. Confirmation message appears before resetting the system.

*Items listed with “*” mark will not be restored to default even after the system is reset.

* Default values are highlighted in gray.

SD カード/保存データについて Possible recording time When the 2GB of SD is used:

Interval REC item

Interval REC item

Power +Harmonics Power +Harmonics 1sec 13days 3days 1min 1-year or more 3months 2sec 15days 3days 2min 2-year or more 6months 5sec 38days 7days 5min 6-year or more 1-year or more

10sec 2.5months 15days 10min

10-year or more

2-year or more 15sec 3.5months 23days 15min 3-year or more 20sec 5months 1month 20min 5-year or more 30sec 7.5months 1.5months 30min 7-year or more

1hour 10-year or more

2hours 150/180-cycle 23days 4days

* Data of power quality events are not considered to estimate the possible recording time. The max possible time will be shortened by recording such events.

* Please ensure to use the SD cards provided with this instrument or as optional parts.

111111... SSSDDD CCCaaarrrddd/// SSSaaavvveeeddd DDDaaatttaaa

Page 40: Quick Manual - 共立電気計器株式会社

- 39 - KEW6315

Saved data KEW6315Saved data KEW6315

39 KEW6315

Saved data

The file name will be assigned automatically. File no. is kept and saved, even after powering off the

instrument, untill the system is reset. The file number will increase until it exceeds “999”.

Print screen: Press the to save the screen images as BMP files in the root directory on the SD card. File name: PS- SD 000 .BMP

| | |

Dest. code

SD:SD card

ME:Internal memory

File No.

(000-999)

Extension

(BMP file)

* Dest. = Destination

KEW6315 Setting: Press the key and move to “Saved data” tab, and then select “Save Settings”.

File name: SUP S 0000 .PRE

| |

Dest. code

S:SD card

M:Internal memory

File No.

(0000-9999)

Data folder: New folder will be created per measurement to save the interval and power quality data.

Folder name: / KEW/ S 0000

| |

Dest. code

S:SD card

M:Internal memory

Data No.

(0000-9999)

Interval data

KEW6315 setting File name SUP S 0000 .KEW

Measurement setting INI S 0000 .KEW

Power measurement INP S 0000 .KEW

Harmonics measurement INH S 0000 .KEW

| |

Dest. code

SD:SD card

M:Internal memory

Data No.

(0000-9999)

Power quality data

Event type File name EVT S 0000 .KEW

Waveform WAV S 0000 .KEW

V/ A change VAL S 0000 .KEW

| |

Dest. code

S:SD card

M:Internal memory

Data No.

(0000-9999)

KEW6315 Saved items

KEW6315 40

Saved items

The following data measured on each CH will be saved according to the selected recording method.

Saved items are depending on the selected recording method and wiring system.

REC file REC item

Meas./ Rec. setting

Power +Harmonics +Event

Power

measurement

RMS voltage (line/ phase)

● ● ●

RMS current

Active power

Reactive power

Apparent power

Power factor

Frequency

Neutral current(3P4W)

V/ A phase angle (1st order)

Analog input voltage, 1CH, 2CH

V/A unbalance ratio

1-min Voltage flicker

Short-term V Flicker (Pst)

Long-term V Flicker (Plt)

Capacitance calculation

Active power energy (consumption/ regenerating)

Reactive power energy (consumption) lagging/ leading

Apparent power energy (consumption/ regenerating)

Reactive power energy (regenerating) lagging/ leading

Demand (W/VA)

Target demand (W/VA)

Total harmonic distortion of V(F/R)

Total harmonic distortion of A(F/R)

Harmonics

measurement

Harmonic V/ A(1-50th order)

V/ A phase angle (1-50th order)

V/ A phase difference (1-50th order)

Harmonic power(1-50th order)

V/ A Change RMS voltage per half-cycle

● RMS current per half-cycle

Event type

Event detected date&time

● Event type

Measured values at event detection

Waveform V/A waveform ●

Page 41: Quick Manual - 共立電気計器株式会社

- 40 -KEW6315

KEW6315 Saved itemsSaved data KEW6315

39 KEW6315

Saved data

The file name will be assigned automatically. File no. is kept and saved, even after powering off the

instrument, untill the system is reset. The file number will increase until it exceeds “999”.

Print screen: Press the to save the screen images as BMP files in the root directory on the SD card. File name: PS- SD 000 .BMP

| | |

Dest. code

SD:SD card

ME:Internal memory

File No.

(000-999)

Extension

(BMP file)

* Dest. = Destination

KEW6315 Setting: Press the key and move to “Saved data” tab, and then select “Save Settings”.

File name: SUP S 0000 .PRE

| |

Dest. code

S:SD card

M:Internal memory

File No.

(0000-9999)

Data folder: New folder will be created per measurement to save the interval and power quality data.

Folder name: / KEW/ S 0000

| |

Dest. code

S:SD card

M:Internal memory

Data No.

(0000-9999)

Interval data

KEW6315 setting File name SUP S 0000 .KEW

Measurement setting INI S 0000 .KEW

Power measurement INP S 0000 .KEW

Harmonics measurement INH S 0000 .KEW

| |

Dest. code

SD:SD card

M:Internal memory

Data No.

(0000-9999)

Power quality data

Event type File name EVT S 0000 .KEW

Waveform WAV S 0000 .KEW

V/ A change VAL S 0000 .KEW

| |

Dest. code

S:SD card

M:Internal memory

Data No.

(0000-9999)

KEW6315 Saved items

KEW6315 40

Saved items

The following data measured on each CH will be saved according to the selected recording method.

Saved items are depending on the selected recording method and wiring system.

REC file REC item

Meas./ Rec. setting

Power +Harmonics +Event

Power

measurement

RMS voltage (line/ phase)

● ● ●

RMS current

Active power

Reactive power

Apparent power

Power factor

Frequency

Neutral current(3P4W)

V/ A phase angle (1st order)

Analog input voltage, 1CH, 2CH

V/A unbalance ratio

1-min Voltage flicker

Short-term V Flicker (Pst)

Long-term V Flicker (Plt)

Capacitance calculation

Active power energy (consumption/ regenerating)

Reactive power energy (consumption) lagging/ leading

Apparent power energy (consumption/ regenerating)

Reactive power energy (regenerating) lagging/ leading

Demand (W/VA)

Target demand (W/VA)

Total harmonic distortion of V(F/R)

Total harmonic distortion of A(F/R)

Harmonics

measurement

Harmonic V/ A(1-50th order)

V/ A phase angle (1-50th order)

V/ A phase difference (1-50th order)

Harmonic power(1-50th order)

V/ A Change RMS voltage per half-cycle

● RMS current per half-cycle

Event type

Event detected date&time

● Event type

Measured values at event detection

Waveform V/A waveform ●

Page 42: Quick Manual - 共立電気計器株式会社

- 41 - KEW6315

Data transfer KEW6315Data transfer KEW6315

41 KEW6315

Data transfer

1. SD card and USB

Data in the SD card or the internal memory can be transferred to PC using USB connection or

SD card slot/ reader.

Method of transfer

USB Card reader

SD card data (file) △*1

O

Internal memory data (file) O ---------

*1

: It is reccomended to transfer the large data by use of SD card since transfering large data files by

USB requires more time than using the SD card reader. (transfer time : approx 320MB/ hour)

As to the manipulation of SD cards, please refer to the instruction manual attached to the card.

In order to save data without any problem, make sure to delete the files other than the data measured

with this instrument from the SD card beforehand.

2. Bluetooth

Measuring data can be checked on android devices in real-time via Bluetooth communication.

It is necessary to enable Bluetooth function prior to using Bluetooth communication.

(Setting No. 26: Bluetooth) Before starting to use this function, download the special application “KEW Smart” from the Internet site.

The application “KEW Smart” is available on the download site for free. (Internet access is required and

charges may be incurred.)

USB

Bluetooth

Android device

SD card

SD card slot or

card reader

Internal memory/

SD card data

KEW6315

KEW6315 - 42 -

MEMO

Page 43: Quick Manual - 共立電気計器株式会社

- 42 -KEW6315

KEW6315 Data transfer KEW6315

41 KEW6315

Data transfer

1. SD card and USB

Data in the SD card or the internal memory can be transferred to PC using USB connection or

SD card slot/ reader.

Method of transfer

USB Card reader

SD card data (file) △*1

O

Internal memory data (file) O ---------

*1

: It is reccomended to transfer the large data by use of SD card since transfering large data files by

USB requires more time than using the SD card reader. (transfer time : approx 320MB/ hour)

As to the manipulation of SD cards, please refer to the instruction manual attached to the card.

In order to save data without any problem, make sure to delete the files other than the data measured

with this instrument from the SD card beforehand.

2. Bluetooth

Measuring data can be checked on android devices in real-time via Bluetooth communication.

It is necessary to enable Bluetooth function prior to using Bluetooth communication.

(Setting No. 26: Bluetooth) Before starting to use this function, download the special application “KEW Smart” from the Internet site.

The application “KEW Smart” is available on the download site for free. (Internet access is required and

charges may be incurred.)

USB

Bluetooth

Android device

SD card

SD card slot or

card reader

Internal memory/

SD card data

KEW6315

KEW6315 - 42 -

MEMO