Feature Report Part 2 Quick Pipe and Duct How Caiculatious Bruce R. Smith Sidock Group W ould you like to make a quick mental calculation to determine approximate fiowrate, velocity, or pipe and duct sizes for many common situations? This article presents two methods for estimating flow characteristics without the aid of charts, tables, calculators or soft- ware programs. One method applies to liquid flow in pipes, and the other to air flow in ducts. The techniques are intended to be simple enough to yield useful answers within a few seconds. Liquid flow in pipes Sizing pipes for liquid transport nearly always requires an engi- neer to seek a preferred velocity to establish favorable flow character- istics. This calculation technique allows an engineer to estimate ve- locity, flowrate and pipe diameter relationships when reference data is unavailable. The technique first establishes a flowrate (Q, in gpm) corresponding to a velocity of 10 ftIs in a Schedule 40 pipe with diameter D (inches). That information can then be extrapolated for flow prop- erties at other conditions. Equation (1) applies to the flow of liquids through pipes. 1)2 X 25 (1) Consider the following examples, which employ Equation ( 1) to quickly approximate pipe velocity. Example 1. What flowrate will yield a velocity of 8 ft/s in a 2-in. pipe? First, mentally calculate the follow- ing using Equation (1): QJQ = 2^ X 25 = 100 gpm. This means that 100 gpm will flow in the 2-in. pipe at 10 ft/s. We want to determine the flow- Simple calculation methods for estimating flow characteristics in pipes and ducts save engineers' time rate in the same pipe at 8 ft/s. We know that 8 ft/s is 80% of 10 ft/s, so similarly, 80% of 100 gpm is 80 gpm. Literature shows the velocity of 80 gpm in a 2-in. Schedule 40 pipe is 7.65 ft/s. Our estimate is within 5% of the literature value. Example 2. What is the veloc- ity of 2,500 gpm flowing in a 12-in. pipe? Again, we use Equation (1) to mentally calculate the flow at the reference velocity of 10 ft/s: Qio = 122 X 25 = 3,600 gpm flowrate at 10 ft/s. To determine the velocity at 2,500 gpm, we start with the fact that 2,500 is roughly 70% of 3,600. 70% of 10 ft/s is 7 ft/s. Literature shows the velocity of 2,500 gpm in a 12-in. Schedule 40 pipe is 7.17 ft/s. Our estimate is within 3% of the literature value. Each problem is solved in two basic steps. The first is to multiply the square of the pipe diameter by 25. The second step is to determine the ratio of the target flow to the flow yielding 10 ft/s to arrive at the desired conditions. In a man- ner similar to the examples above, pipe diameters can be derived from flow and velocity data. That calcu- lation is performed by assuming a pipe diameter, calculating its flow at 10 ft/s, comparing its flow prop- erties at desired flow or velocity, and iterating to another diameter if necessary. This technique is not exact, but it gives the engineer relatively ac- curate results very quickly. While Equation (1) is intended for Sched- ule 40 pipes, and accuracies for pipes with varjdng wall thicknesses will be slightly different, this calculation method will quickly 5deld a close es- timation. Figure 1 displays how cal- culated values compare to literature values. The error between estimated values and actual values should be accurate enough for initial sizing es- timates. However, accuracy is dimin- ished significantly for pipes with a diameter of less than one inch. Air flow in ducts The technique used for liquids in pipes can be applied to air in ducts at standard (atmospheric) pressure and temperature. Equation (2) ap- plies to air flowing at these condi- tions, using a reference air velocity of 2,000 ft/min. 02x11 (2) Consider the following examples, which employ Equation (2) to evalu- ate flowrate (Q, in ft^/min) in sheet- metal air ducts. Example 3. What flowrate will yield a velocity of 3,000 ft/min in a 10-in. duct? We must first use Equa- tion (2) to mentally calculate the following: Q2000 = 102 X 11 = 1,100 ft3/min, which is the flowrate yield- ing an air velocity of 2,000 ft/min. We want to determine the flowrate that results in a velocity of 3,000 ft/ min. 3,000 ft/min is 150% of 2,000 ft/min. Therefore, 150% of 1,100 ft3/min = 1,650 ft3/min. A check against the literature values shows that the velocity of 1,650 ft^/min in a 10-in. galvanized sheet-metal duct is 3,100 ft/min. Our mental 42 CHEMICAL ENGINEERING WWW.CHE.COM FEBRUARY 2014

Upload: lesuts

Post on 18-Jul-2016

31 views

Category:

Documents


5 download

DESCRIPTION

Quick Pipe and Duct Flow Calculations

TRANSCRIPT

Page 1: Quick Pipe and Duct Flow Calculations

Feature Report Part 2

Quick Pipe and DuctHow CaiculatiousBruce R. SmithSidock Group

Would you like to make aquick mental calculationto determine approximatefiowrate, velocity, or pipe

and duct sizes for many commonsituations? This article presentstwo methods for estimating flowcharacteristics without the aid ofcharts, tables, calculators or soft-ware programs. One method appliesto liquid flow in pipes, and the otherto air flow in ducts. The techniquesare intended to be simple enoughto yield useful answers withina few seconds.

Liquid flow in pipesSizing pipes for liquid transportnearly always requires an engi-neer to seek a preferred velocity toestablish favorable flow character-istics. This calculation techniqueallows an engineer to estimate ve-locity, flowrate and pipe diameterrelationships when reference datais unavailable. The technique firstestablishes a flowrate (Q, in gpm)corresponding to a velocity of 10 ftIsin a Schedule 40 pipe with diameterD (inches). That information canthen be extrapolated for flow prop-erties at other conditions. Equation(1) applies to the flow of liquidsthrough pipes.

1)2 X 25 (1)

Consider the following examples,which employ Equation ( 1) to quicklyapproximate pipe velocity.Example 1. What flowrate will yielda velocity of 8 ft/s in a 2-in. pipe?First, mentally calculate the follow-ing using Equation (1): QJQ = 2^ X25 = 100 gpm. This means that 100gpm will flow in the 2-in. pipe at 10ft/s. We want to determine the flow-

Simple calculation methods for estimatingflow characteristics in pipes and ducts

save engineers' time

rate in the same pipe at 8 ft/s. Weknow that 8 ft/s is 80% of 10 ft/s, sosimilarly, 80% of 100 gpm is 80 gpm.Literature shows the velocity of 80gpm in a 2-in. Schedule 40 pipe is7.65 ft/s. Our estimate is within 5%of the literature value.Example 2. What is the veloc-ity of 2,500 gpm flowing in a 12-in.pipe? Again, we use Equation (1) tomentally calculate the flow at thereference velocity of 10 ft/s: Qio =122 X 25 = 3,600 gpm flowrate at10 ft/s. To determine the velocity at2,500 gpm, we start with the factthat 2,500 is roughly 70% of 3,600.70% of 10 ft/s is 7 ft/s. Literatureshows the velocity of 2,500 gpm ina 12-in. Schedule 40 pipe is 7.17 ft/s.Our estimate is within 3% of theliterature value.

Each problem is solved in twobasic steps. The first is to multiplythe square of the pipe diameter by25. The second step is to determinethe ratio of the target flow to theflow yielding 10 ft/s to arrive atthe desired conditions. In a man-ner similar to the examples above,pipe diameters can be derived fromflow and velocity data. That calcu-lation is performed by assuming apipe diameter, calculating its flowat 10 ft/s, comparing its flow prop-erties at desired flow or velocity,and iterating to another diameterif necessary.

This technique is not exact, butit gives the engineer relatively ac-curate results very quickly. WhileEquation (1) is intended for Sched-ule 40 pipes, and accuracies for pipes

with varjdng wall thicknesses willbe slightly different, this calculationmethod will quickly 5deld a close es-timation. Figure 1 displays how cal-culated values compare to literaturevalues. The error between estimatedvalues and actual values should beaccurate enough for initial sizing es-timates. However, accuracy is dimin-ished significantly for pipes with adiameter of less than one inch.

Air flow in ductsThe technique used for liquids inpipes can be applied to air in ductsat standard (atmospheric) pressureand temperature. Equation (2) ap-plies to air flowing at these condi-tions, using a reference air velocityof 2,000 ft/min.

02x11 (2)

Consider the following examples,which employ Equation (2) to evalu-ate flowrate (Q, in ft^/min) in sheet-metal air ducts.Example 3. What flowrate willyield a velocity of 3,000 ft/min in a10-in. duct? We must first use Equa-tion (2) to mentally calculate thefollowing: Q2000 = 102 X 11 = 1,100ft3/min, which is the flowrate yield-ing an air velocity of 2,000 ft/min.We want to determine the flowratethat results in a velocity of 3,000 ft/min. 3,000 ft/min is 150% of 2,000ft/min. Therefore, 150% of 1,100ft3/min = 1,650 ft3/min. A checkagainst the literature values showsthat the velocity of 1,650 ft^/minin a 10-in. galvanized sheet-metalduct is 3,100 ft/min. Our mental

4 2 CHEMICAL ENGINEERING WWW.CHE.COM FEBRUARY 2014

Page 2: Quick Pipe and Duct Flow Calculations

25,000

^ 20,000

ISi.« 15,000£o

10,000

% 5,000

Pipe diameter, Inches(standard waii thickness, Sch. 40 pipe)

FIGURE 1 . A comparison of literature values with calculatedvalues shows that these quici<, simplified pipe-fiow caicula-tions are accurate enough for initiai sizing estimates

g 9,000

í' 8 000

i : 7 nnn

cte

>A U

li

e 5 000

N" 4,000

£ 3 000

1 2 000

" l 1,000O

0

Calculated valuesyr

y

/

/

y f Literature values

D 5 10 15 20 25 30Duct diameter, inches (sheet-metal)

FIGURE 2. The rough estimates resulting from the duct-flowcaiouiation method are extremely close to iiterature vaiues forairflow in sheet-metal ducts

calculation is within 3.2% of theliterature value.Example 4. What is the velocitythat corresponds to a flowrate of6,000 fb3/min in a 20-in. duct? First,of course, we must mentally calcu-late the flowrate corresponding tothe reference velocity of 2,000 ft/min: Q2000 = 202 x 11 = 4,400 ft̂ /min. Now, we can solve for the ve-locity which corresponds to 6,000ft^/min flow in the pipe — 6,000 isslightly less than 150% of 4,400,and 150% of 2,000 ft/min is 3,000 ft/min. Literature shows the velocity of6,000 ft̂ /min in a 20-in. sheet-metalduct is 2,800 ft/min. Our estimateis 7% greater than the literaturevalue, but a value somewhat greaterthan the actual was expected whenwe rounded to 150%.

This technique is accurate towithin 1% if exact numbers arecalculated for the flowrate percent-ages. As seen in Examples 3 and 4,accuracy diminishes if estimates arenot exact. While this technique is

AuthorBruce Smith is a projectmanager at Sidock Group,Inc. (379 W. Western Ave.,Muskegon, Mich. 49441;Phone: 231-722-4900; Email:[email protected]).Previously, he was employedas a senior research engineerat The Dow Chemical Co.after working as an engineerin the automotive and miningindustries. He has experience

with a wide variety of technologies and is a reg-istered professional engineer in multiple states.Smith is credited with several patents and tech-nical articles. He holds a B.S.Ch.E. from Michi-gan Technological University.

intended for use with sheet-metalducts, accuracies for ducts withvarying wall thicknesses will not besigniflcantly different. Figure 2 com-pares these calculations to literaturevalues. The two lines are practicallyidentical when calculations are pre-

cise, rather than rough estimates.In conclusion, when rough initial

estimates are needed, engineers canconfidently apply these simple, time-saving methods to characterize flowin pipes and ducts. •

Edited by Mary Page Bailey

In today's operating environment, it's moreimportant than ever that the piping withinyour iVIechanicai Integrity Program complieswith standards such as API-570 and API-574.

Quest Integrity offers a comprehensive solutionfor piping circuits using our proprietary,ultrasonic-based intelligent pigging technologycombined with LifeQuest™ Fitness-for-Servicesoftware.

Ensure your piping integrity by identifyingdegradation before loss of containment occurs.

www.Questlntegrity.com/CE+1 253 893 7070

100% inspection ofinternal and externalpipe surfaces

Inspection resultstailored to comply withAPI-570 and API-574

LifeQuest Fitness-for-Service resultstailored to comply withAPI-579

QUESTINTEGRITY GROUP

Process . Pipeline . Power

A TEAM Industrial Services Company

Circle 22 on p. 60 or go to adlinks.che.com/50973-22

CHEMICAL ENGINEERING WWW.CHE.COM FEBRUARY 2014 4 3

Page 3: Quick Pipe and Duct Flow Calculations

Copyright of Chemical Engineering is the property of Access Intelligence LLC d/b/a PBIMedia, LLC and its content may not be copied or emailed to multiple sites or posted to alistserv without the copyright holder's express written permission. However, users may print,download, or email articles for individual use.