r. · 2009. 5. 17. · 1-4244-0189-5/06/$20.00 c2006ieee. 356 authorized licensed use limited to:...

4
Performance of 20 kV Epoxy Resin Outdoor Insulator Under Various Environment Conditions Melda Latif', Suwarno2 IDepartment of Electrical Engineering, Andalas University Ji. Kampus Limau Manis Padang 25163, Indonesia 2Department of Electrical Engineering, Bandung Institute of Technology Ji. Ganesha 10 Bandung 40132, Indonesia *email: i oo.co.uk Abstract: This paper explains the research results of leakage current and flashover measurement on Epoxy Resin 20 kV Outdoor Insulators in a chamber at various artificial polluted conditions. The waveform of the leakage current(LC) was measured using a digital storage oscilloscope. The digital data was transferred to a personal computer using a RS-232 cable. Further analysis of the waveform was done using Fast Fourier Transform. The result showed that LC was affected by various environment conditions like pollution, humidity and temperature. The flashover of insulators occurred at 64 kV for 2600 [[S and 53 kV for 4300 [[S in clean fog and high humidity condition. Keywords: outdoor insulator, epoxy resin, leakage current, flashover voltage INTRODUCTION In some tropical countries, such as Indonesia, insulator flashover frequently happens and greatly affects the electric power system. Insulator flashover mechanism usually relates with leakage current (LC) on insulator surface, and influenced by environment condition, such as pollution, humidity and temperature [1-8]. Several methods for measuring the performance of insulator conditions are reported. Amarh [9] uses LC envelope as parameter of performance, Piah [10] uses dimensional technique for modeling LC, and Yong Zhu [11] reports 3D dynamic model for studying LC waveform. This paper describes the measurement of performance of insulator surface using LC and flashover under various environment conditions. [[/cm 4300 [[/cm. IEC-507 standard was used in this artificial pollution arrangement[12]. r. ................. Fig. 1 20 kV Epoxy Resin Polimer Insulator The LC was measured using a digital oscilloscope Textronik TDS 220 with digitizer of 8 bit, 100 MHz bandwidth, and the maximum sampling rate of 1 GS/s. Digital camcorder was used for flashover monitoring. LC waveform was analyzed using Fast Fourier Transform (FFT) for getting Total Harmonic Distortion (THD) . The THD can be expressed as: 2 lLn THD 2 I1 where In = nth harmonic for n= 2,3,4,... Ii = fundamental harmonic (n= 1). RESULTS AND DISCUSSION Leakage Current as Function of Test Voltage Fig. 2 shows LC as function of test voltage for clean and EXPERIMENTAL polluted insulators under low and high humidity. Tested insulator used in this experiment is Epoxy Resin 20 kV pin type, and 1.8 kg weight. Insulator Filler is ATH (Alumina Tri-Hydrate) with composition 50% of the weight. The Chamber dimensions are 90x90x120 cm3 with 80x80 cm2 transparent acrylic door, chamber humidity varied in low (50-60%) and high humidity (85-95%). Artificial pollutant used in this experiment was kaolin-salt with conductivity varied from 300 From the figure it is seen that LC increased with humidity. LC magnitude flows at polluted insulator surface is more greater than clean insulator. This indicated that at higher humidity, vapor will condensate on the insulator surface resulting in higher conductive layer will occur on insulator surface. This promotes a higher leakage current. 1-4244-0189-5/06/$20.00 ©2006 IEEE. 353 Authorized licensed use limited to: MULTIMEDIA UNIVERSITY. Downloaded on May 15, 2009 at 02:16 from IEEE Xplore. Restrictions apply.

Upload: others

Post on 28-Jan-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Performance of 20 kV Epoxy Resin Outdoor InsulatorUnder Various Environment Conditions

    Melda Latif', Suwarno2IDepartment of Electrical Engineering, Andalas University

    Ji. Kampus Limau Manis Padang 25163, Indonesia2Department of Electrical Engineering, Bandung Institute ofTechnology

    Ji. Ganesha 10 Bandung 40132, Indonesia*email: i oo.co.uk

    Abstract: This paper explains the research results ofleakage current and flashover measurement on EpoxyResin 20 kV Outdoor Insulators in a chamber at variousartificial polluted conditions. The waveform of theleakage current(LC) was measured using a digitalstorage oscilloscope. The digital data was transferred toa personal computer using a RS-232 cable. Furtheranalysis of the waveform was done using Fast FourierTransform. The result showed that LC was affected byvarious environment conditions like pollution, humidityand temperature. The flashover of insulators occurredat 64 kV for 2600 [[S and 53 kV for 4300 [[S in cleanfog and high humidity condition.

    Keywords: outdoor insulator, epoxy resin, leakagecurrent, flashover voltage

    INTRODUCTION

    In some tropical countries, such as Indonesia, insulatorflashover frequently happens and greatly affects theelectric power system. Insulator flashover mechanismusually relates with leakage current (LC) on insulatorsurface, and influenced by environment condition, suchas pollution, humidity and temperature [1-8].

    Several methods for measuring the performance ofinsulator conditions are reported. Amarh [9] uses LCenvelope as parameter of performance, Piah [10] usesdimensional technique for modeling LC, and Yong Zhu[11] reports 3D dynamic model for studying LCwaveform. This paper describes the measurement ofperformance of insulator surface using LC and flashoverunder various environment conditions.

    [[/cm 4300 [[/cm. IEC-507 standard was used in thisartificial pollution arrangement[12].

    r. .................Fig. 1 20 kV Epoxy Resin Polimer Insulator

    The LC was measured using a digital oscilloscopeTextronik TDS 220 with digitizer of 8 bit, 100 MHzbandwidth, and the maximum sampling rate of 1 GS/s.Digital camcorder was used for flashover monitoring.

    LC waveform was analyzed using Fast FourierTransform (FFT) for getting Total Harmonic Distortion(THD) . The THD can be expressed as:

    2lLn

    THD 2I1

    where In = nth harmonic for n= 2,3,4,...Ii = fundamental harmonic (n= 1).

    RESULTS AND DISCUSSION

    Leakage Current as Function of Test Voltage

    Fig. 2 shows LC as function of test voltage for clean andEXPERIMENTAL polluted insulators under low and high humidity.

    Tested insulator used in this experiment is Epoxy Resin20 kV pin type, and 1.8 kg weight. Insulator Filler isATH (Alumina Tri-Hydrate) with composition 50% ofthe weight. The Chamber dimensions are 90x90x120cm3 with 80x80 cm2 transparent acrylic door, chamberhumidity varied in low (50-60%) and high humidity(85-95%). Artificial pollutant used in this experimentwas kaolin-salt with conductivity varied from 300

    From the figure it is seen that LC increased withhumidity. LC magnitude flows at polluted insulatorsurface is more greater than clean insulator. Thisindicated that at higher humidity, vapor willcondensate on the insulator surface resulting in higherconductive layer will occur on insulator surface. Thispromotes a higher leakage current.

    1-4244-0189-5/06/$20.00 ©2006 IEEE. 353

    Authorized licensed use limited to: MULTIMEDIA UNIVERSITY. Downloaded on May 15, 2009 at 02:16 from IEEE Xplore. Restrictions apply.

  • 120

    100

    80 -

    60 -

    40

    20

    10 12 15 20 25 30 35 40 45 50

    Tegangan (kV)

    - * Clean, lowRH -Clean, high RH - 300uS/cm,low RH- 300uS/cm polluted, high RH - - 600 uS/cm polluted, low RH 600 uS/cm polluted, high RH

    Fig. 2 LC as Function of Test Voltage

    Leakage Current as Function of Temperature

    Table 1 shows the LC waveforms, maximum andfundamental of leakage current for clean and pollutedinsulators at low humidity and at different temperatures.

    temperature increased slightly for clean insulators. Forhighly polluted insulators, LC magnitude increasedrapidly with temperature up to about 420C. Above thistemperature, LC magnitude decreased drastically. Thisis due to dry band formation caused by heating by theflowing LC assisted by high temperature of thesurrounding.

    350

    300

    250

    200

    V 150

    100

    50-

    28 30 32 34 36 38 40 42 44 46 48

    Temperature

    Table 1 LC as function of temperature, RH: 85-95%

    300CTHD = 27%I1ax=46pAI1=25,81 iA

    300CTHD= 15%I, =60tpAI1=56,28 iA

    300CTHD = 23%I 4A=37,05,tA11=42,uA

    70 io 35 msPnd 0rs eid 0

    3100

    44°C 44°C 44°CTHD=18%o THD=12% THD=9%oImax=64pA Ima,=3O4,uA II11X=496,uA

    I3 56,75iA b276,465 I1=467,O4jA

    100

    P-35 d 20 ms

    p~~~id20Nn.d 20 ~~~~~~~~~~~~~~Period 20 n

    440C 446C 442C

    THD=180o THD=12% THD=91I, 8=4tA 1~,,,304~tA THD bo46ot11=567,54~A 11=277,46p 11=34604~A___________________________________ Ii~~~~~~~~4033- 94

    Fig. 3 shows that in general LC magnitude increasedwith temperature for clean and medium pollutedinsulators. For insulators with high pollution and highhumidity, the characteristics of LC as function oftemperature changed drastically at around 420C. This isshown in figure 3. LC magnitude as function of

    -+Clean 300uS/cmPolluted --600 uS/cmPolluted

    Fig. 3 LC as function oftemperature at 12 kV

    Flashover

    Flashover experiment was conducted using test voltagefrom 50 - 85 kV with 2 kV increment at roomtemperature. For clean insulator at various humidity itwas found that flashover did not occur even the testvoltage was increased up to 85 kV.

    For 2600 [S/cm polluted insulator, in low humidity (drycondition) flashover did not occur with the voltageincreased from 50 kV to 85 kV. On the other hand, inhigh humidity (wet condition) spark occurred first at 54kV and finally flashover occurred at 64 kV. Thiscondition was recorded and shown in Fig. 4. For 4300[[/cm polluted insulator at low humidity spark did notoccur. Flashover occurred at 82 kV.

    a. spark b. FlashoverFig. 4 Spark and flashover in polluted insulator at

    2600 [[/cm, RH:85-95%

    Fig. 5 shows the LC waveform and harmonic spectrumof spark at 75 kV. The peak magnitude of LC was 672[A and THD 40%. In high humidity this heavy pollutedinsulator had LC magnitude approach to 500 pA for 12

    1-4244-0189-5/06/$20.00 C2006 IEEE.

    50

    4 lo1-1 -lo

    -30

    -50

    70-,

    35

    0 -/ `..-35

    -70

    354

    60

    40

    'O j-.,-20U 0-4, j

    Authorized licensed use limited to: MULTIMEDIA UNIVERSITY. Downloaded on May 15, 2009 at 02:16 from IEEE Xplore. Restrictions apply.

  • kV applied voltage. Spark occurred starting at 20 kVand flashover took place at 53 kV.

    magnitude was observed. The THD of the LC reducedsignificantly from those at low humidity.

    High humidity gave vapor contents in chambercontributing the wetting process of the insulatorsurface. Heating effect by LC flow at the surface driedwater droplets that absorbed by polluted surface. Theflashover process is shown in table 2. This phenomenonrelates to dryband forming at insulator surface. Then,this continued until sparkover occurred [13-16].

    Flashover observation showed that the environmentconditions greatly influenced the performance ofinsulator surface. Humidity, especially for highhumidity, gives strong effect to flashover. Asillustration, in high humidity for clean insulator noflashover occurred, for 2600 [[/cm flashover occurredon 64 kV, and for 4300 [[/cm flashover occurred on 53kV.

    700 -

    600 -

    500 -

    400 -

    300 -

    200-

    V 100-

    0-

    -100o

    -200 -

    -300 -

    -400 -

    u

    500 -

    400 -

    300 -

    200 -

    100 -

    0-0:

    -100 -

    -200-

    -300-

    -400-

    -500-

    0. 1 02 0.3 004 0.05second

    (a)

    500

    400

    300

    200

    100

    01 2 3 4 5 6 7 8 9 10 1112 13

    n-th Harmonic

    (b)0 002 0 00.( 10.2 0. 0.04 0.05

    second Fig 6. Typical LC waveform (a) and harmonic content(b) for 4300 [[/cm polluted insulator at high

    humidity, and 12 kV

    5a. LC Waveform

    250 -"6.

    2100 -

    364272

    114 1021277.6 8.6 G 18 49 59666 5.7 S.S 4446 1664846 4.7,nuElm M lnm lll -Mllnnl lM lnlU lM ll Ul

    3 5 7 9 1 1 13 15 17 19 21 23 25

    n-th Harmonic

    5b. Spectrum Harmonics

    Fig. 5 Typical LC waveform (a) and harmonic content(b) of insulator with spark at 4300 [[/cm pollution and

    low humidity, at 75 kV

    Fig. 6 Shows typical LC waveform and harmoniccontent for highly polluted insulator at 12 kV. High LC

    Table 2 Flashover Process for 4300 [[/cm pollutedinsulator, at high humidity

    1 second 13 second 22 second

    31 second 40 second 53 second

    59 second 61 second 70 second

    1-4244-0189-5/06/$20.00 C2006 IEEE.

    T-

    -.1.

    )O

    355

    Authorized licensed use limited to: MULTIMEDIA UNIVERSITY. Downloaded on May 15, 2009 at 02:16 from IEEE Xplore. Restrictions apply.

  • Table 3 shows the correlation between arch length andapplied voltage. The table clearly indicates that the archlength is strongly affected by the applied voltage. Thisis more clearly seen from Fig. 7.

    Table 4 Correlation between arch length and appliedvoltage

    21

    25

    30

    35

    37

    48

    50

    51

    53

    26.38

    28.59

    60.34

    77.52

    80.54

    86.44

    96.91

    103.3

    400

    400 400

    350 -

    , 300-

    250-. 200- /o 150 -

    50-

    21 25 30 35 37 48 50 51

    Arching voltage (kV)

    53

    Fig. 7 Arching distance as function of applied voltage

    CONCLUSION

    The performance of 20 kV Epoxy Resin OutdoorInsulator under various environment conditions hasbeen analyzed in this paper. The result showed thatpollution, humidity and temperature give influence tothe performance. LC magnitude, THD, and flashover asindicators showed that they strongly correlated toinsulator performance.

    REFERENCES

    [1] Gorur, R.S, et al, "Electrical Performance ofCycloaliphatic Epoxy Materials and Insulators forOutdoor Use", IEEE Trans. On Power Delivery,Vol.15, No. 4, pp.1274-1278, Oct.2000

    [2] Fernando M.A.R.M., et al, "Leakage Current onNon-ceramic Insulators and Materials", IEEETrans. Dielect. Elect. Insul., vol. 6 No.5, pp. 660-664, Oct. 1999.

    [3] Schwardt W.H., et al, "A Comparison BetweenMeasured Leakage Current And SurfaceConductivity During Salt Fog Tests, preprint

    [4] Gustavsson Tomas G., Silicone Rubber Insulators-Impacts of material formulation in coastalenvironment, Thesis For The Degree Of Doctor OfPhilosophy, Goteborg, Sweden, April 2002

    [5] Gorur, R.S, E.A. Cherney, et al, "The ElectricalPerformance Of Polymeric Insulating MaterialsUnder Accelerated Aging In A fog Chamber",IEEE Trans. On Power Delivery, Vol. 3, No. 3,pp.1157-1164, July 1988

    [6] Besztercey G. G., et al, "An ArtificialContamination Method for Composite Insulators",IEEE Trans. On Power Delivery, Vol.15, No. 2,pp.732-736, April 2000

    [7] Sillars. R.W, et al, Electrical Insulating Materialsand Their Application, Peter Peregrinus Ltd., 1973

    [8] Gorur, R.S, E.A. Cherney, et al, "The AC And DCPerformance Of Polymeric Insulating MaterialsUnder Accelerating Aging In A Fog Chamber",IEEE Trans. On Power Delivery, Vol. 3, No. 4,pp.1892-1902, Oct.1988

    [9] Amarh Felix, et al, " Level Crossing Analysis ofLeakage Current Envelope of Polluted Insulators",IEEE Power Engineering Review, August 2001

    [10]Piah, M. A. M, "Modelling Leakage Curent andElectric Field Bahavior of Wet ContaminatedInsulators", IEEE Trans. On Power Delivery,Vol.19, No. 1, pp.432-434, January 2004

    [11]Yong Zhu, et al, "Mechanism for Change inLeakage Current Waveform on a Wet SiliconeRubber Surface-A Study using a Dynamic 3-DModel", IEEE Trans. On Dielectrics and ElectricalInsulation, Vol.12, No.3, pp.556-565, June 2005

    [12] IEC 507, "Artificial pollution test on high-voltageinsulators to be used on ac systems", 2nd edition,Geneve, Suisse, 1991

    [13] Gorur, R.S., et al, Outdoor Insulator, Ravi S.Gorur, Inc., Phoenix, USA, 1999

    [14]T. Sorqvist and S. M. Gubanski, "Leakage currentand flashover of field-aged polymeric insulators,"IEEE Trans. Dielect. Elect. Insul., vol. 6, pp. 744-753, Oct. 1999.

    [15]A. de la and Gorur, R.S., "Flashover ofContaminated Nonceramic Outdoor Insulators in aWet Atmosphere", IEEE Trans. On Dielectrics andElectrical Insulation, Vol.5, No.61, pp.814 -823,December 1998

    [16] George G. Karady, "Flashover Mechanism of Non-ceramic Insulators", IEEE Trans. Dielect. Elect.Insul., vol. 6 no.5, pp. 718-723, Oct. 1999.

    1-4244-0189-5/06/$20.00 C2006 IEEE. 356

    Authorized licensed use limited to: MULTIMEDIA UNIVERSITY. Downloaded on May 15, 2009 at 02:16 from IEEE Xplore. Restrictions apply.