r mos gb 0325-1 611867 flm 30 - nibe · installation and maintenance instructions mos gb 0325-1...
TRANSCRIPT
-
INSTALLATION AND MAINTENANCE INSTRUCTIONS
FLM 30MOS GB 0325-1 611867FLM 30
R
LEK
-
Contents 1For Home Owners
FLM 30
General points for the installationengineer
Transport and storage .......................................... 6Handling .............................................................. 6Frost protection .................................................... 6Installation ............................................................ 6
Pipe installationCondensation water hose ...................................... 7Filling and venting the system ................................ 7Pressure expansion vessel .................................... 7Pipe connections (brine) ...................................... 7Effect transfer to brine .......................................... 7
Ventilation connectionVentilation flow ...................................................... 8Exhaust air duct .................................................... 8Duct installation ...................................................... 8Adjustment ............................................................ 8Fan diagram .......................................................... 8
Electrical installationElectrical connections ............................................ 9Setting the fan capacity ........................................ 9
Commissioning and adjustmentPreparations ........................................................ 10Starting ................................................................ 10Setting the ventilation .......................................... 10Commissioning .................................................... 10Readjustment ........................................................ 10
Electrical circuit diagramElectrical circuit diagram ...................................... 11
Component locationsComponent locations .......................................... 12
List of componentsList of components .............................................. 13
DimensionsDimensions and setting-out coordinates .............. 14
Technical dataTechnical data ...................................................... 15Accessories .......................................................... 15Enclosed kit .......................................................... 15
Dealing with malfunctionsLow or a lack of ventilation ................................ 16Helping the circulation pump to start .................. 16
GeneralConcise product description ................................ 2Installation data .................................................... 2
System descriptionPrinciple of operation .......................................... 3System diagram .................................................. 3
Maintenance routinesCleaning the air filter ............................................ 4Cleaning the fan .................................................... 4Cleaning the ventilation devices .......................... 5Checking the condensation water seal ................ 5
For the Installation engineer
For Home Owners
-
General2For Home Owners
FLM 30
In order to get the ultimate benefit from your FLM 30you should read through the For Home Owners sec-tion in this Installation and Maintenance Instruction.
FLM 30 is an exhaust air module. This means it canutilise the energy in the ventilation air. The energy isused to raise the temperature of the ingoing brine tothe heat pump.
FLM 30 is intended to be installed with FIGHTER1110/1210 in houses or the like.
Installation date
Installation engineers
The serial number (95), should always be stated with allcorrespondence with NIBE.
089_ _ _ _ _ _ _ _ _ _ _
Trim valve
Selected fan curve
Date______________ Signed__________________________________
Installation dataTo be filled in when the exhaust air module hasbeen installed.
-
System description 3For Home Owners
FLM 30
System diagram
CWhen the room air haspassed through the exhaustair module it is discharged.The temperature has thendropped as FLM 30 hasutilised the energy in theroom air.
GThe air from the kitchenfan goes directly outinto a separate duct.
BThe warm roomair is led to FLM30.
DFLM 30 increases thetemperature of the brine to theheat pump.
EOutdoor air is drawn into the house.
AThe warm room air isdrawn into the air ductsystem.
FAir is transportedfrom rooms withoutdoor air devices torooms with exhaustair devices.
Brine in
Brine out
FIGHTER 1210
FLM 30
Exhaust airØ 160
Extract airØ 160
Cirk.pump
Värmepump
Varmvatten
Tillsatsvärme
Larm
Kontrollera att vatten finns i pan-nan innan den in-kopplas.
1
R
0
FLM 30 is an exhaust air module specially designed tocombine recovery of mechanical exhaust air with anenergy collector in the ground or in rock. FLM 30 is designed to connect to the FIGHTER1110/1210 type of ground heat pump.The integrated fan in FLM 30 extracts the air from thewet areas of the house to the recovery unit. Here theenergy is transferred to the heat pump's brine, where-by the temperature increases and raises the heatpump's heating factor. Energy is stored in the groundor rock collector even if the heat pump is not in opera-tion, which fully utilises the exhaust air energy. The heat pump capacity is not bound by the amount ofair, but the output can be optimally adapted to suit thesize of the house.FLM 30 is positioned directly on FIGHTER 1210, butcan also be mounted using brackets (accessory) onthe wall.
Principle of operation
-
The exhaust air module’s air filter should be cleanedregularly (about 4-5 times a year) by taking it out andshaking off any dirt. If the filter is very dirty, turn it up-side-down and wash it carefully with water.
■ Open the front cover by pulling it out by the loweredge, then lifting it up.
■ Set the switch (8) to “0”.
■ Release the filter holder by turning the two blackknobs a quarter of a turn anticlockwise.
■ Pull out the holder, take out the filter (63) andshake off any dirt. Check that the filter is not dam-aged. New original filters can be ordered fromNIBE.
■ Assembly takes place in the reverse order.
The interval between cleaning operations varies and depends on the amount of dust in the exhaust air.
Maintenance routines4For Home Owners
FLM 30
LEK
63
LEK
1 TRYCK1
TRYCK
2 DRAG
2
1
34
93
FLM 30 and its ventilation ducting require some regu-lar maintenance where the following points should bechecked:
The numbers in brackets refer to the section “List ofcomponents”.
Clean the fan once a year by taking it out of the ex-haust air module and carefully brushing the vanesclean.
■ Open the front cover by pulling it out by the loweredge, then lifting it up.
■ Set the switch (8) to “0”.
■ Dismantle the inner cover by loosening the 6 coverscrews.
■ The fan is removed by disconnecting the fan cableconnector and the two screws as illustrated.
■ Once the inner cover has been removed alsocheck the drip-pan under the heat exchanger. Alsocheck the outlet from the drip-pan (98) to ensure itis not blocked.
■ Assembly takes place in the reverse order.
NOTE! Avoid distorting the fan blades as
this causes imbalance.
Do not use water or detergents.
Switch (8)
PRESSPRESS
PULL
Cleaning the air filter
Cleaning the fan
-
Maintenance routines 5For Home Owners
FLM 30
Check that there is water in the water seal (92) to thedrip-pan (93). If the water seal is empty or has a verylow water level so that it “gurgles” water can be filled,for example, using a watering can through the drip-pan water hose which then forms a water seal or di-rectly in the drip-pan (the inner cover plate must thenbe dismantled). The water seal is maintained duringfilling.After using for a period of time dust and other particlescan clog the water seal, consequently, you shouldcheck this regularly and clean when necessary.
The ventilation devices in the house should becleaned regularly to maintain the correct ventilation.The device settings must not be changed. NOTE! If you take down more than one ventilation de-vice for cleaning, do not mix them up.
Cleaning the ventilation devices Checking the condensationwater seal
LEK
93
92
98
-
General points for the installation engineer6For the Installation engineer
FLM 30
FLM 30 is installed on FIGHTER 1210 or using brack-ets when connected to FIGHTER 1110. Noise fromthe circulation pump or fan can be transferred to thebrackets. Consequently, mount on an outside wall ifpossible. If it is not possible to mount FLM 30 on anoutside wall avoid a wall connecting to a bedroom orliving-room.NOTE! Ensure that that there is sufficient space (15mm) above the exhaust air module to open the frontcover, see the section “Dimensions”.Route pipework so it is not fixed to an internal wall thatbacks on to a bedroom or living room.
The exhaust air module can contain in-flammable anti-freeze in the brine circuit(for example ethanol). Special careshould be exercised during handling, in-stallation, service, cleaning and scrap-ping to avoid the risk of leakage.
The exhaust air module should be transported andstored in the dry.
Alt. 1
Alt. 2
FLM 30 features integrated frost protection (65) thatautomatically defrosts the heat exchanger (62) if nec-essary. This is achieved by the brine flow through theheat exchanger being slowed sufficiently so that thewarm room air can thaw the ice. Normally the temperature of the incoming brine toFLM 30 is shown on the display on the frost protec-tion. The frost protection is set at the factory andshould not need adjusting. Changes to the parameterscan result in the heat exchanger becoming blocked byfrost. The buttons are locked with a code.In the event of a fault indication the frost protectionstops the FLM 30 (however, not the ventilation flow).Fault indications on the displayEr Memory fault-- Short circuit temperature sensor (66)00 Defective temperature sensor (66)
VL-Temp 47 (52) °CWW-Temp 48 °C
LEK
Installation
Frost protection
Handling
Transport and storage
-
Pipe installation 7
FLM 30
For the Installation engineer
The condensation water hose is routed directly to thefloor drain or other water seal. Ensure that the end ofthe hose runs out above the water level in the floordrain. The pipe installation must be carried out in ac-cordance with current norms.
Output transfer to brine
FLM 30 is filled from the heat pump's brine, see theInstallation and Maintenance instructions in question.Vent using the venting screw (5). The switch (38)should be set to “0”. when venting
SF
Brine in
Brine out
Cirk.pump
Värmepump
Varmvatten
Tillsatsvärme
Larm
Kontrollera att vatten finns i pan-nan innan den in-kopplas.
1
R
0
SÄV
FLM 30
Exhaust airØ 160
Extract airØ 160
EXP
BV
RVP
EXP Pressure expansion vessel According to therecommendations
SÄV Safety valveBV Check valve Included in FLM 30SF Particle filterRV Trim valve Included in FLM 30P Pressure gauge
The brine circuit should be fitted with a pressure ex-pansion vessel. If there is a level vessel this shouldbe replaced. The brine side should be pressurised toat least 0.5 bar.The pressure expansion vessel should be dimen-sioned as set out in the diagram, to prevent operatingdisturbances. The pressure expansion vessel coversthe temperature range from -10 °C to +20 °C at a pre-pressure of 0.5 (bar) and the safety valve’s openingpressure 3 bar.
0
0
l
100 200 l300
10
20
30
Pressure expansion vessel
Brinevolume
40
50
400 500 600 700 800 900 1000
The lowest permitted incoming brine temperature is -5 °C. When installing on FIGHTER 1210 the space underFLM 30 is limited to 90 mm. This may mean that thepipe connections on FIGHTER 1210 must be short-ened.The brine is connected to FLM 30 as set out on theoutline diagram.
0
100
(m3/h)
300
0,5
1
1,5
Överförd effekt (kW)
Luftflöde
2
2,5
500200 400
Köldbärare in vid 0 °C
Köldbärare in vid 5 °C
The diagram shows the effect transferred from theventilation air to the brine and applies for an air tem-perature of +20 °C and 50% relative air humidity.
Transferred effect (kW)
Air flow (m3/h)
Brine in at 0 °C
Brine in at 5 °C
Pipe connections (brine)
Condensation water hose
Pressure expansion vessel
Filling and venting the system
-
Ventilation connection8For the Installation engineer
FLM 30
FLM 30 is connected so that all ventilation air, exceptfor the kitchen fan, passes the heat exchanger (62) inthe exhaust air module. Minimum flow should conformto the demands as set out in applicable norms. Theventilation flow should conform to applicable norms. Switching the ventilation capacity is described in thesection “Electrical installation” “Setting the fan capaci-ty”. The numbering of the curves refers to the terminalblock on the fan transformer (22).
To prevent fan noise being transferred to the exhaustair devices, it may be a good idea to install a silencerin the duct. This is especially important if there are ex-haust air devices in bedrooms.
Connections can be made using flexible hoses, whichshould be stretched well and routed to allow easy re-placement. The extract air duct must be provided withdiffusion-tight insulation over its entire length.Provision must be made for inspection of the duct.Make sure that there are no reductions of cross-sec-tional area in the form of creases, tight bends etc,since this will reduce the ventilation capacity. All joinsin the ducting must be sealed and pop-riveted to pre-vent leakage. The duct system must be carried out inaccordance with current norms. A minimum of airtightness class B is recommended.
To obtain the necessary air exchange in every room ofthe house, the exhaust air devices must be correctlypositioned and adjusted. A defective ventilation instal-lation may lead to reduced exhaust air module effi-ciency and thus poorer operating economy, and mayresult in damage to the house.
The diagram below shows the available ventilation ca-pacity.
Ventilation flow
Fan diagram
Duct installation
Adjustment
NOTE!A duct in a masonry chimney stack
must not be used for extract air.
Luftflöde
Till
gän
glig
t st
atis
kt t
ryck
Pammvp
40
30
10
20
1 23 4 5 6 7 8 9 10
0 100 200 300 400 m3/h
400
300
200
100
0500
50050
0 25 50 75 100 l/s
The kitchen flue must not be connected to FLM 30
Air flow
mmwp Pa
Ava
ilabl
e st
atic
pre
ssur
e
Exhaust air duct
-
Electrical installation 9For the Installation engineer
FLM 30
22
8
Selection of the fan capacity is done by connectingthe black cable to a suitable outlet on the terminal block (22). See the section “Ventilation con-nection” - “Fan diagram”.
Connection1
2
3
4
5
6
7
8
9
10
Voltage (V)100
110
125
140
155
170
185
200
215
230
22
5 6 7 8 9 103 41 2
Svart
When FLM 30 is placed directly above the heat pumpthe power supply can be connected to the heatpump’s terminal block. The connection plug musthowever be cut off.If FLM 30 is installed independently (together with aFIGHTER 1110 or if the ceiling level is not highenough to allow placement above 1210) it can be con-nected either to an earthed 1-phase wall socket orthrough permanent installation. When a permanent in-stallation is used, FLM 30 must be preceded by a cir-cuit-breaker.If an insulation test is to be carried out in the building,disconnect the exhaust air module.
■ Open the front cover by pulling it out by the loweredge, then lifting it up.
■ Switch off the voltage by turning the switch (8) to “0”.
■ Remove the securing screw on the electrical boxand pull out the electrical box as illustrated.
■ Select a suitable fan capacity, see below.
■ Assembly takes place in the reverse order.
NOTE! Electrical installation and service
must be carried out under thesupervision of a qualified electrician.
Electrical installation and wiring mustbe carried out in accordance with the
stipulations in force. Work behindscrewed covers may only be carried
out under the supervision of aqualified electrician.
Black
Setting the fan capacity
Electrical connections
-
Commissioning and adjusting10For the Installation engineer
FLM 30
Start the heat transfer pump on the heat pump, seethe Installation and Maintenance instructions in ques-tion.The brine flow across the FLM 30 is controlled bymeans of the circulation pump (16) and trim valve (81)so that the temperature difference on the brine in andout through FLM 30 is 3 - 4 degrees. Adjustments aremade when the heat pump is running. The tempera-ture difference applies at a room temperature of 20degrees and 0 degrees on the brine.The brine flow through FLM 30 will be from 0.1 l/s (360l/h) to 0.15 l/s (540 l/h) at the above temperature dif-ferences, depending on the ventilation flow. When the heat pump is at a standstill the internal cir-culation pump in FLM 30 gives from 0.085 l/s (306 l/h)to 0.125 l/s (450 l/h) in the return charging flow to thecollector. This applies to a heat pump with an approxi-mate rated output of 4 kW. For a 15 kW heat pump thecorresponding flow is from 0.09 l/s (324 l/h) to 0.14 l/s(504 l/h).
Before commissioning check that the brine circuit isfilled and vented. Check the pipe system for leaks.Check that the brine circuit is pressurised to at least0.5 bar.
Set the switch (38) to 1.Set the switch (8) to 1.Check that the fan and circulation pump are running.
The ventilation flow and correct outlet on the terminalblock (22) are set out on the ventilation drawing.
■ Change the fan capacity by moving the black cableon the terminal block (22) if necessary. Use thelowest possible output to obtain the lowest noiselevels.
■ Make sure that all outdoor air devices are fully-open.
■ Set correct ventilation flows on the exhaust air de-vices.
Venting may be necessary after a period of use. Ventusing the venting screw (5). The switch (38) should beset to “0” when venting.
CommissioningPreparations
Starting
Setting the ventilation
Readjustment
-
Electrical circuit diagram 11For the Installation engineer
FLM 30
L3
41
2
12
NP
E
75
610
89
8 791011
BROWN
BLACK
BLUE
N
2 1
34
12
78
56
910
BLACK
54
36
8
9
4B 1A
5B 2A
14
57
16
12
PEA
1A
2L
22
N
66
59
20
6538
10PE
-
Component locations12For the Installation engineer
FLM 30
90 59
16
36 74 7320
62
5 91
66
63
93
LEK
22 5457
38
8
65
914 10
-
List of components 13For the Installation engineer
FLM 30
3 Connection pipe out from FLM 30
4 Connection pipe in to FLM 30
5 Air screw
8 Switch, positions 0 - 1, main switch
9 Terminal block, incoming supply
10 Cord with connection plug
14 Terminal block, internal
16 Circulation pump
20 Connector, fan
22 Terminal block for fan speed
36 Fan
38 Switch, positions 0 - 1, circulation pump
54 Fan transformer
57 Operating condenser, fan
59 Solenoid valve
62 Heat exchanger
63 Air filter
65 Frost protection
66 Temperature sensor, frost protection
73 Brine out, compression ring Ø 15 mm
74 Brine in, compression ring Ø 15 mm
81 Trim valve, DN 15
82 Check valve, DN 32
90 Ventilation connection exhaust air, Ø 160 mm
91 Ventilation connection extract air, Ø 160 mm
92 Drip-pan water hose
93 Drip-pan
95 Type plate
98 Drip-pan drain
-
Dimensions14For the Installation engineer
15
Min avstånd50 mm från vägg
440
400
365
235
180
Köldbärare in Ø 15
445
100
50
Köldbärare ut Ø 15
Droppskålsavlopp
74
73
98
90
300
70
Erforderligt utrymme för demontering av frontlucka
Vy sedd underifrån
Fritt installationsutrymmei FLM 30
445115
305
AvluftØ 160
FrånluftØ 160
626
598
95
300
90
510
300
Fritt installationsutrymmei FLM 30
Clearance in front of FLM 30should be at least 600 mm formaintenance and servicing.
The distance to the wall mustbe at least 50 mm with the in-stallation of FLM 30 on FIGHT-ER 1210.
Dimensions and setting-out coordinates
FLM 30
Space required for removalof front access panel
Brine in Ø15
View from belowBrine out Ø15
Drip-pan drain
Extract airØ 160
Exhaust airØ 160
Minimum distancefrom wall 10 mm
Clear installationspacein FLM 30
Clear installationspacein FLM 30
-
Technical specifications 15For the Installation engineer
FLM 30
Width 600 mm
Net weight 60 kg
Rated output fan 225 W
Max air flow approx. 400 m3/h
Enclosure class IP 21
Sound level in the boiler house*** 34-44 dB(A)
Height 400 mm
Depth 625 mm
Supply voltage 230 V 50 Hz
Rated output, circulation pump 95 W
Max cooling effect 2,3 kW
Sound power level** 38-48 dB(A)
Technical data
IP 21
Brackets and cover plateWall mounting of FLM 30Part no 089304
Accessories
Enclosed kit
** A-weighted sound power level (LwA). The value varies with the selected fan curve.
*** A-weighted sound pressure level (LpA). The value varies with the room’s damping capacity.
These values apply with a damping of 4 dB.
LEK
Trim valve
Drip-pan water hose Connecting pipeCheck valve
LEK
LEK
LEK
3492
81
82
LEK
LEK
-
Dealing with malfunctions16For the Installation engineer
FLM 30
If the operating disturbance cannot be rectified by means of the above an installationengineer should be called.
Cause: Filter (63) clogged.Action: Clean or replace the filter, see the section
“Maintenance procedures” - “Cleaning theair filter”.
Cause: Closed or too hard throttled exhaust air de-vice.
Action: Check and measure the air flow.
Cause: Circuit or main MCB tripped.Action: Reset or replace the MCB.
Cause: Fan clogged.Action: Check the fan, clean if necessary. See the
section “Maintenance routines” - “Cleaningthe fan”.
Cause: The battery blocked by frost.Action: Switch off the circulation pump using
switch (38). Let it remain switched off for 24hours.
Low or a lack of ventilation
In the event of malfunction or operating disturbances first check the points below:
NOTE! The
product’s serial numbershould always be stated with all
correspondence with NIBE.089_ _ _ _ _ _ _ _ _ _
■ Open the front cover by pulling it out by the loweredge, then lifting it up.
■ Set the switch (8) to “0”.
■ Dismantle the inner cover by loosening the 6 cov-er screws.
■ Loosen the venting screw with a screwdriver. Holda cloth around the screwdriver blade as a certainamount of fluid may run out.
■ Insert a screwdriver and turn the pump rotor.■ Screw in the venting screw.■ Start FLM 30 and check whether the circulation
pump runs.It is usually easier to start the circulation pump withFLM 30 running, switch (8) set to “1”. If helping the cir-culation pump to start is performed with FLM 30 run-ning, be prepared for the screwdriver to jerk when thepump starts.
Helping the circulation pump to start
Luftningsskruv
16
LE
K
GR
UN
DFO
SType
UP
S25 -
60
130
P/N
:59526447
230V
-
HE
JS
AN
PC
;0017N
IBD
K50H
z
IP 44
TF
110
Cla
ss H
Max. 1
0bar
2.5
uF
45
0.2
065
0.3
090
0.4
0
1m(A
)P,
(W)
Venting screw
-
R
NIBE ABSWEDEN
Box 14Järnvägsgatan 40SE-285 21 MARKARYD
Tel: +46 - (0)433 - 73 000Fax: +46 - (0)433 - 73 190www.nibe.com