r mos gb 0325-1 611867 flm 30 - nibe · installation and maintenance instructions mos gb 0325-1...

20
INSTALLATION AND MAINTENANCE INSTRUCTIONS FLM 30 MOS GB 0325-1 611867 FLM 30 R LEK

Upload: others

Post on 25-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • INSTALLATION AND MAINTENANCE INSTRUCTIONS

    FLM 30MOS GB 0325-1 611867FLM 30

    R

    LEK

  • Contents 1For Home Owners

    FLM 30

    General points for the installationengineer

    Transport and storage .......................................... 6Handling .............................................................. 6Frost protection .................................................... 6Installation ............................................................ 6

    Pipe installationCondensation water hose ...................................... 7Filling and venting the system ................................ 7Pressure expansion vessel .................................... 7Pipe connections (brine) ...................................... 7Effect transfer to brine .......................................... 7

    Ventilation connectionVentilation flow ...................................................... 8Exhaust air duct .................................................... 8Duct installation ...................................................... 8Adjustment ............................................................ 8Fan diagram .......................................................... 8

    Electrical installationElectrical connections ............................................ 9Setting the fan capacity ........................................ 9

    Commissioning and adjustmentPreparations ........................................................ 10Starting ................................................................ 10Setting the ventilation .......................................... 10Commissioning .................................................... 10Readjustment ........................................................ 10

    Electrical circuit diagramElectrical circuit diagram ...................................... 11

    Component locationsComponent locations .......................................... 12

    List of componentsList of components .............................................. 13

    DimensionsDimensions and setting-out coordinates .............. 14

    Technical dataTechnical data ...................................................... 15Accessories .......................................................... 15Enclosed kit .......................................................... 15

    Dealing with malfunctionsLow or a lack of ventilation ................................ 16Helping the circulation pump to start .................. 16

    GeneralConcise product description ................................ 2Installation data .................................................... 2

    System descriptionPrinciple of operation .......................................... 3System diagram .................................................. 3

    Maintenance routinesCleaning the air filter ............................................ 4Cleaning the fan .................................................... 4Cleaning the ventilation devices .......................... 5Checking the condensation water seal ................ 5

    For the Installation engineer

    For Home Owners

  • General2For Home Owners

    FLM 30

    In order to get the ultimate benefit from your FLM 30you should read through the For Home Owners sec-tion in this Installation and Maintenance Instruction.

    FLM 30 is an exhaust air module. This means it canutilise the energy in the ventilation air. The energy isused to raise the temperature of the ingoing brine tothe heat pump.

    FLM 30 is intended to be installed with FIGHTER1110/1210 in houses or the like.

    Installation date

    Installation engineers

    The serial number (95), should always be stated with allcorrespondence with NIBE.

    089_ _ _ _ _ _ _ _ _ _ _

    Trim valve

    Selected fan curve

    Date______________ Signed__________________________________

    Installation dataTo be filled in when the exhaust air module hasbeen installed.

  • System description 3For Home Owners

    FLM 30

    System diagram

    CWhen the room air haspassed through the exhaustair module it is discharged.The temperature has thendropped as FLM 30 hasutilised the energy in theroom air.

    GThe air from the kitchenfan goes directly outinto a separate duct.

    BThe warm roomair is led to FLM30.

    DFLM 30 increases thetemperature of the brine to theheat pump.

    EOutdoor air is drawn into the house.

    AThe warm room air isdrawn into the air ductsystem.

    FAir is transportedfrom rooms withoutdoor air devices torooms with exhaustair devices.

    Brine in

    Brine out

    FIGHTER 1210

    FLM 30

    Exhaust airØ 160

    Extract airØ 160

    Cirk.pump

    Värmepump

    Varmvatten

    Tillsatsvärme

    Larm

    Kontrollera att vatten finns i pan-nan innan den in-kopplas.

    1

    R

    0

    FLM 30 is an exhaust air module specially designed tocombine recovery of mechanical exhaust air with anenergy collector in the ground or in rock. FLM 30 is designed to connect to the FIGHTER1110/1210 type of ground heat pump.The integrated fan in FLM 30 extracts the air from thewet areas of the house to the recovery unit. Here theenergy is transferred to the heat pump's brine, where-by the temperature increases and raises the heatpump's heating factor. Energy is stored in the groundor rock collector even if the heat pump is not in opera-tion, which fully utilises the exhaust air energy. The heat pump capacity is not bound by the amount ofair, but the output can be optimally adapted to suit thesize of the house.FLM 30 is positioned directly on FIGHTER 1210, butcan also be mounted using brackets (accessory) onthe wall.

    Principle of operation

  • The exhaust air module’s air filter should be cleanedregularly (about 4-5 times a year) by taking it out andshaking off any dirt. If the filter is very dirty, turn it up-side-down and wash it carefully with water.

    ■ Open the front cover by pulling it out by the loweredge, then lifting it up.

    ■ Set the switch (8) to “0”.

    ■ Release the filter holder by turning the two blackknobs a quarter of a turn anticlockwise.

    ■ Pull out the holder, take out the filter (63) andshake off any dirt. Check that the filter is not dam-aged. New original filters can be ordered fromNIBE.

    ■ Assembly takes place in the reverse order.

    The interval between cleaning operations varies and depends on the amount of dust in the exhaust air.

    Maintenance routines4For Home Owners

    FLM 30

    LEK

    63

    LEK

    1 TRYCK1

    TRYCK

    2 DRAG

    2

    1

    34

    93

    FLM 30 and its ventilation ducting require some regu-lar maintenance where the following points should bechecked:

    The numbers in brackets refer to the section “List ofcomponents”.

    Clean the fan once a year by taking it out of the ex-haust air module and carefully brushing the vanesclean.

    ■ Open the front cover by pulling it out by the loweredge, then lifting it up.

    ■ Set the switch (8) to “0”.

    ■ Dismantle the inner cover by loosening the 6 coverscrews.

    ■ The fan is removed by disconnecting the fan cableconnector and the two screws as illustrated.

    ■ Once the inner cover has been removed alsocheck the drip-pan under the heat exchanger. Alsocheck the outlet from the drip-pan (98) to ensure itis not blocked.

    ■ Assembly takes place in the reverse order.

    NOTE! Avoid distorting the fan blades as

    this causes imbalance.

    Do not use water or detergents.

    Switch (8)

    PRESSPRESS

    PULL

    Cleaning the air filter

    Cleaning the fan

  • Maintenance routines 5For Home Owners

    FLM 30

    Check that there is water in the water seal (92) to thedrip-pan (93). If the water seal is empty or has a verylow water level so that it “gurgles” water can be filled,for example, using a watering can through the drip-pan water hose which then forms a water seal or di-rectly in the drip-pan (the inner cover plate must thenbe dismantled). The water seal is maintained duringfilling.After using for a period of time dust and other particlescan clog the water seal, consequently, you shouldcheck this regularly and clean when necessary.

    The ventilation devices in the house should becleaned regularly to maintain the correct ventilation.The device settings must not be changed. NOTE! If you take down more than one ventilation de-vice for cleaning, do not mix them up.

    Cleaning the ventilation devices Checking the condensationwater seal

    LEK

    93

    92

    98

  • General points for the installation engineer6For the Installation engineer

    FLM 30

    FLM 30 is installed on FIGHTER 1210 or using brack-ets when connected to FIGHTER 1110. Noise fromthe circulation pump or fan can be transferred to thebrackets. Consequently, mount on an outside wall ifpossible. If it is not possible to mount FLM 30 on anoutside wall avoid a wall connecting to a bedroom orliving-room.NOTE! Ensure that that there is sufficient space (15mm) above the exhaust air module to open the frontcover, see the section “Dimensions”.Route pipework so it is not fixed to an internal wall thatbacks on to a bedroom or living room.

    The exhaust air module can contain in-flammable anti-freeze in the brine circuit(for example ethanol). Special careshould be exercised during handling, in-stallation, service, cleaning and scrap-ping to avoid the risk of leakage.

    The exhaust air module should be transported andstored in the dry.

    Alt. 1

    Alt. 2

    FLM 30 features integrated frost protection (65) thatautomatically defrosts the heat exchanger (62) if nec-essary. This is achieved by the brine flow through theheat exchanger being slowed sufficiently so that thewarm room air can thaw the ice. Normally the temperature of the incoming brine toFLM 30 is shown on the display on the frost protec-tion. The frost protection is set at the factory andshould not need adjusting. Changes to the parameterscan result in the heat exchanger becoming blocked byfrost. The buttons are locked with a code.In the event of a fault indication the frost protectionstops the FLM 30 (however, not the ventilation flow).Fault indications on the displayEr Memory fault-- Short circuit temperature sensor (66)00 Defective temperature sensor (66)

    VL-Temp 47 (52) °CWW-Temp 48 °C

    LEK

    Installation

    Frost protection

    Handling

    Transport and storage

  • Pipe installation 7

    FLM 30

    For the Installation engineer

    The condensation water hose is routed directly to thefloor drain or other water seal. Ensure that the end ofthe hose runs out above the water level in the floordrain. The pipe installation must be carried out in ac-cordance with current norms.

    Output transfer to brine

    FLM 30 is filled from the heat pump's brine, see theInstallation and Maintenance instructions in question.Vent using the venting screw (5). The switch (38)should be set to “0”. when venting

    SF

    Brine in

    Brine out

    Cirk.pump

    Värmepump

    Varmvatten

    Tillsatsvärme

    Larm

    Kontrollera att vatten finns i pan-nan innan den in-kopplas.

    1

    R

    0

    SÄV

    FLM 30

    Exhaust airØ 160

    Extract airØ 160

    EXP

    BV

    RVP

    EXP Pressure expansion vessel According to therecommendations

    SÄV Safety valveBV Check valve Included in FLM 30SF Particle filterRV Trim valve Included in FLM 30P Pressure gauge

    The brine circuit should be fitted with a pressure ex-pansion vessel. If there is a level vessel this shouldbe replaced. The brine side should be pressurised toat least 0.5 bar.The pressure expansion vessel should be dimen-sioned as set out in the diagram, to prevent operatingdisturbances. The pressure expansion vessel coversthe temperature range from -10 °C to +20 °C at a pre-pressure of 0.5 (bar) and the safety valve’s openingpressure 3 bar.

    0

    0

    l

    100 200 l300

    10

    20

    30

    Pressure expansion vessel

    Brinevolume

    40

    50

    400 500 600 700 800 900 1000

    The lowest permitted incoming brine temperature is -5 °C. When installing on FIGHTER 1210 the space underFLM 30 is limited to 90 mm. This may mean that thepipe connections on FIGHTER 1210 must be short-ened.The brine is connected to FLM 30 as set out on theoutline diagram.

    0

    100

    (m3/h)

    300

    0,5

    1

    1,5

    Överförd effekt (kW)

    Luftflöde

    2

    2,5

    500200 400

    Köldbärare in vid 0 °C

    Köldbärare in vid 5 °C

    The diagram shows the effect transferred from theventilation air to the brine and applies for an air tem-perature of +20 °C and 50% relative air humidity.

    Transferred effect (kW)

    Air flow (m3/h)

    Brine in at 0 °C

    Brine in at 5 °C

    Pipe connections (brine)

    Condensation water hose

    Pressure expansion vessel

    Filling and venting the system

  • Ventilation connection8For the Installation engineer

    FLM 30

    FLM 30 is connected so that all ventilation air, exceptfor the kitchen fan, passes the heat exchanger (62) inthe exhaust air module. Minimum flow should conformto the demands as set out in applicable norms. Theventilation flow should conform to applicable norms. Switching the ventilation capacity is described in thesection “Electrical installation” “Setting the fan capaci-ty”. The numbering of the curves refers to the terminalblock on the fan transformer (22).

    To prevent fan noise being transferred to the exhaustair devices, it may be a good idea to install a silencerin the duct. This is especially important if there are ex-haust air devices in bedrooms.

    Connections can be made using flexible hoses, whichshould be stretched well and routed to allow easy re-placement. The extract air duct must be provided withdiffusion-tight insulation over its entire length.Provision must be made for inspection of the duct.Make sure that there are no reductions of cross-sec-tional area in the form of creases, tight bends etc,since this will reduce the ventilation capacity. All joinsin the ducting must be sealed and pop-riveted to pre-vent leakage. The duct system must be carried out inaccordance with current norms. A minimum of airtightness class B is recommended.

    To obtain the necessary air exchange in every room ofthe house, the exhaust air devices must be correctlypositioned and adjusted. A defective ventilation instal-lation may lead to reduced exhaust air module effi-ciency and thus poorer operating economy, and mayresult in damage to the house.

    The diagram below shows the available ventilation ca-pacity.

    Ventilation flow

    Fan diagram

    Duct installation

    Adjustment

    NOTE!A duct in a masonry chimney stack

    must not be used for extract air.

    Luftflöde

    Till

    gän

    glig

    t st

    atis

    kt t

    ryck

    Pammvp

    40

    30

    10

    20

    1 23 4 5 6 7 8 9 10

    0 100 200 300 400 m3/h

    400

    300

    200

    100

    0500

    50050

    0 25 50 75 100 l/s

    The kitchen flue must not be connected to FLM 30

    Air flow

    mmwp Pa

    Ava

    ilabl

    e st

    atic

    pre

    ssur

    e

    Exhaust air duct

  • Electrical installation 9For the Installation engineer

    FLM 30

    22

    8

    Selection of the fan capacity is done by connectingthe black cable to a suitable outlet on the terminal block (22). See the section “Ventilation con-nection” - “Fan diagram”.

    Connection1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    Voltage (V)100

    110

    125

    140

    155

    170

    185

    200

    215

    230

    22

    5 6 7 8 9 103 41 2

    Svart

    When FLM 30 is placed directly above the heat pumpthe power supply can be connected to the heatpump’s terminal block. The connection plug musthowever be cut off.If FLM 30 is installed independently (together with aFIGHTER 1110 or if the ceiling level is not highenough to allow placement above 1210) it can be con-nected either to an earthed 1-phase wall socket orthrough permanent installation. When a permanent in-stallation is used, FLM 30 must be preceded by a cir-cuit-breaker.If an insulation test is to be carried out in the building,disconnect the exhaust air module.

    ■ Open the front cover by pulling it out by the loweredge, then lifting it up.

    ■ Switch off the voltage by turning the switch (8) to “0”.

    ■ Remove the securing screw on the electrical boxand pull out the electrical box as illustrated.

    ■ Select a suitable fan capacity, see below.

    ■ Assembly takes place in the reverse order.

    NOTE! Electrical installation and service

    must be carried out under thesupervision of a qualified electrician.

    Electrical installation and wiring mustbe carried out in accordance with the

    stipulations in force. Work behindscrewed covers may only be carried

    out under the supervision of aqualified electrician.

    Black

    Setting the fan capacity

    Electrical connections

  • Commissioning and adjusting10For the Installation engineer

    FLM 30

    Start the heat transfer pump on the heat pump, seethe Installation and Maintenance instructions in ques-tion.The brine flow across the FLM 30 is controlled bymeans of the circulation pump (16) and trim valve (81)so that the temperature difference on the brine in andout through FLM 30 is 3 - 4 degrees. Adjustments aremade when the heat pump is running. The tempera-ture difference applies at a room temperature of 20degrees and 0 degrees on the brine.The brine flow through FLM 30 will be from 0.1 l/s (360l/h) to 0.15 l/s (540 l/h) at the above temperature dif-ferences, depending on the ventilation flow. When the heat pump is at a standstill the internal cir-culation pump in FLM 30 gives from 0.085 l/s (306 l/h)to 0.125 l/s (450 l/h) in the return charging flow to thecollector. This applies to a heat pump with an approxi-mate rated output of 4 kW. For a 15 kW heat pump thecorresponding flow is from 0.09 l/s (324 l/h) to 0.14 l/s(504 l/h).

    Before commissioning check that the brine circuit isfilled and vented. Check the pipe system for leaks.Check that the brine circuit is pressurised to at least0.5 bar.

    Set the switch (38) to 1.Set the switch (8) to 1.Check that the fan and circulation pump are running.

    The ventilation flow and correct outlet on the terminalblock (22) are set out on the ventilation drawing.

    ■ Change the fan capacity by moving the black cableon the terminal block (22) if necessary. Use thelowest possible output to obtain the lowest noiselevels.

    ■ Make sure that all outdoor air devices are fully-open.

    ■ Set correct ventilation flows on the exhaust air de-vices.

    Venting may be necessary after a period of use. Ventusing the venting screw (5). The switch (38) should beset to “0” when venting.

    CommissioningPreparations

    Starting

    Setting the ventilation

    Readjustment

  • Electrical circuit diagram 11For the Installation engineer

    FLM 30

    L3

    41

    2

    12

    NP

    E

    75

    610

    89

    8 791011

    BROWN

    BLACK

    BLUE

    N

    2 1

    34

    12

    78

    56

    910

    BLACK

    54

    36

    8

    9

    4B 1A

    5B 2A

    14

    57

    16

    12

    PEA

    1A

    2L

    22

    N

    66

    59

    20

    6538

    10PE

  • Component locations12For the Installation engineer

    FLM 30

    90 59

    16

    36 74 7320

    62

    5 91

    66

    63

    93

    LEK

    22 5457

    38

    8

    65

    914 10

  • List of components 13For the Installation engineer

    FLM 30

    3 Connection pipe out from FLM 30

    4 Connection pipe in to FLM 30

    5 Air screw

    8 Switch, positions 0 - 1, main switch

    9 Terminal block, incoming supply

    10 Cord with connection plug

    14 Terminal block, internal

    16 Circulation pump

    20 Connector, fan

    22 Terminal block for fan speed

    36 Fan

    38 Switch, positions 0 - 1, circulation pump

    54 Fan transformer

    57 Operating condenser, fan

    59 Solenoid valve

    62 Heat exchanger

    63 Air filter

    65 Frost protection

    66 Temperature sensor, frost protection

    73 Brine out, compression ring Ø 15 mm

    74 Brine in, compression ring Ø 15 mm

    81 Trim valve, DN 15

    82 Check valve, DN 32

    90 Ventilation connection exhaust air, Ø 160 mm

    91 Ventilation connection extract air, Ø 160 mm

    92 Drip-pan water hose

    93 Drip-pan

    95 Type plate

    98 Drip-pan drain

  • Dimensions14For the Installation engineer

    15

    Min avstånd50 mm från vägg

    440

    400

    365

    235

    180

    Köldbärare in Ø 15

    445

    100

    50

    Köldbärare ut Ø 15

    Droppskålsavlopp

    74

    73

    98

    90

    300

    70

    Erforderligt utrymme för demontering av frontlucka

    Vy sedd underifrån

    Fritt installationsutrymmei FLM 30

    445115

    305

    AvluftØ 160

    FrånluftØ 160

    626

    598

    95

    300

    90

    510

    300

    Fritt installationsutrymmei FLM 30

    Clearance in front of FLM 30should be at least 600 mm formaintenance and servicing.

    The distance to the wall mustbe at least 50 mm with the in-stallation of FLM 30 on FIGHT-ER 1210.

    Dimensions and setting-out coordinates

    FLM 30

    Space required for removalof front access panel

    Brine in Ø15

    View from belowBrine out Ø15

    Drip-pan drain

    Extract airØ 160

    Exhaust airØ 160

    Minimum distancefrom wall 10 mm

    Clear installationspacein FLM 30

    Clear installationspacein FLM 30

  • Technical specifications 15For the Installation engineer

    FLM 30

    Width 600 mm

    Net weight 60 kg

    Rated output fan 225 W

    Max air flow approx. 400 m3/h

    Enclosure class IP 21

    Sound level in the boiler house*** 34-44 dB(A)

    Height 400 mm

    Depth 625 mm

    Supply voltage 230 V 50 Hz

    Rated output, circulation pump 95 W

    Max cooling effect 2,3 kW

    Sound power level** 38-48 dB(A)

    Technical data

    IP 21

    Brackets and cover plateWall mounting of FLM 30Part no 089304

    Accessories

    Enclosed kit

    ** A-weighted sound power level (LwA). The value varies with the selected fan curve.

    *** A-weighted sound pressure level (LpA). The value varies with the room’s damping capacity.

    These values apply with a damping of 4 dB.

    LEK

    Trim valve

    Drip-pan water hose Connecting pipeCheck valve

    LEK

    LEK

    LEK

    3492

    81

    82

    LEK

    LEK

  • Dealing with malfunctions16For the Installation engineer

    FLM 30

    If the operating disturbance cannot be rectified by means of the above an installationengineer should be called.

    Cause: Filter (63) clogged.Action: Clean or replace the filter, see the section

    “Maintenance procedures” - “Cleaning theair filter”.

    Cause: Closed or too hard throttled exhaust air de-vice.

    Action: Check and measure the air flow.

    Cause: Circuit or main MCB tripped.Action: Reset or replace the MCB.

    Cause: Fan clogged.Action: Check the fan, clean if necessary. See the

    section “Maintenance routines” - “Cleaningthe fan”.

    Cause: The battery blocked by frost.Action: Switch off the circulation pump using

    switch (38). Let it remain switched off for 24hours.

    Low or a lack of ventilation

    In the event of malfunction or operating disturbances first check the points below:

    NOTE! The

    product’s serial numbershould always be stated with all

    correspondence with NIBE.089_ _ _ _ _ _ _ _ _ _

    ■ Open the front cover by pulling it out by the loweredge, then lifting it up.

    ■ Set the switch (8) to “0”.

    ■ Dismantle the inner cover by loosening the 6 cov-er screws.

    ■ Loosen the venting screw with a screwdriver. Holda cloth around the screwdriver blade as a certainamount of fluid may run out.

    ■ Insert a screwdriver and turn the pump rotor.■ Screw in the venting screw.■ Start FLM 30 and check whether the circulation

    pump runs.It is usually easier to start the circulation pump withFLM 30 running, switch (8) set to “1”. If helping the cir-culation pump to start is performed with FLM 30 run-ning, be prepared for the screwdriver to jerk when thepump starts.

    Helping the circulation pump to start

    Luftningsskruv

    16

    LE

    K

    GR

    UN

    DFO

    SType

    UP

    S25 -

    60

    130

    P/N

    :59526447

    230V

    -

    HE

    JS

    AN

    PC

    ;0017N

    IBD

    K50H

    z

    IP 44

    TF

    110

    Cla

    ss H

    Max. 1

    0bar

    2.5

    uF

    45

    0.2

    065

    0.3

    090

    0.4

    0

    1m(A

    )P,

    (W)

    Venting screw

  • R

    NIBE ABSWEDEN

    Box 14Järnvägsgatan 40SE-285 21 MARKARYD

    Tel: +46 - (0)433 - 73 000Fax: +46 - (0)433 - 73 190www.nibe.com