r22 vs r717
TRANSCRIPT
197
J. of Advanced Engineering and Technology
Vol. 1, No. 1 (2008) pp. 197-201
The Comparison of Performance Characteristics in Refrigeration System using R717 and R22
Sung Bae Kim† and Suk Joo Hong*
Graduate School, Dept. of Mechanical Engineering, of Chosun University, Gwangju, 501-759, Korea
*Dept. of Mechanical Engineering, Chosun University, Gwangju, 501-759, Korea
(Received : Jul. 17, 2008, Revised : Aug. 29, 2008, Accepted : Sep. 23, 2008)
Abstract : The production and use of freon substances are recently restrained due to the destruction of ozone
layer and global warming. In this aspect of environmental problems, the best solution is to use natural
refrigerant such as ammonia. This study is to apply R717 and R22, to study performance characteristics from
the superheat control and to compare the energy efficiency of two refrigerants from the high performance.
The condensing pressure of refrigeration system is increased from 1,500 kPa to 1,600 kPa, and the degree
of superheat is increased from 0 to 10 at each condensing pressure. The result of the experiment proved that
R717 is suitable as an alternative refrigerant of R22 compared with each COP.
Keywords : HCFC(hydro chloro fluor carbon), degree of superheat, condensing pressure
1. Introduction
Refrigeration system is being applied widely in industries
such as small refrigerators, cars, ships, skyscrapers and large-
scale chemical plants. It has been used especially in chemical
processing industry for gas separation and liquefaction, solidification
of core material in synthesis to separate, maintenance process
to prevent liquid stored in low temperature from excessive
pressure, and drying and clearing reaction heat, etc[1].
Worldwide pending questions forward are to improve
energy efficiency and to develop alternative refrigerants to Freon.
Consuming those alternatives is very severely controlled. To
study on establishing design technology of mutual assistance
equipment is being progressed actively in the world to cope
with this control. The study on the alternative to R22 is
inevitable of all things[2-4].
Refrigerants like R12, R22 and R717 have not only made
human lives comfortable but also been a motive to generate
all sorts of machinery industries. Ammonia has been used as
a refrigerant in almost all systems except quite small-sized
systems. It had dominated over refrigeration field from 1890
to 1940 due to the good thermodynamic characteristics and
low cost. However, it has not been recognized as a good
refrigerant because of its toxicity and inflammability, even
though its thermodynamic characteristics are excellent as a
refrigerant. After that, R12 and R22 which are called Freon
are recognized as the best refrigerants as mankind has ever
discovered and they have been used broadly. But R22 is a sort
of chemicals like Hydro Chloro Fluor Carbon(HCFC) which
has phased out according to Montreal Protocol, an international
agreement on the materials destructing ozone layer. So it must
be very reasonable that studying on natural refrigerants gets
accomplished very actively.
R717, an organic compound, and propane and propylene,
sorts of hydrocarbon, are natural refrigerants which are easy
to get and purchase cheaply. Especially they are environment-
friendly refrigerants which are not collided with the environment
of the earth. Among them R717 has excellent characteristics
in wide range of temperature and so it is used a lot in chemical
process, and is expected to be preferred as a good refrigerant[5].
R717 generally is considered to be reasonable in efficiency
and price, and is a refrigerant widely used the most in the
process of foods and drinks and in the facilities of refrigerated
warehouses. It is suitable as an alternative refrigerant to R22
for an industrial refrigeration system, although its market share
is small. But its usage in the system for pleasant facilities
goes slowly worrying about its toxicity. Nevertheless R717 is
environment-friendly as a natural refrigerant and known to have
a good efficiency[6]. The existing study on the refrigerant of
R717 has been deficient and restrictive so far. So much more
study on the refrigerant of R717 is required to be carried out.
R717 is a suitable refrigerant for low temperature refrigeration
and R22 for middle temperature air-conditioning. However, a
noticeable result is expected in case of using R717 and R22 in
the same refrigeration system. So we will compare performance
characteristics of each refrigerant through the experiments
whose system shows the degree of superheat changes depending
on condensing pressure. We also try to make clear the superiority
of R717 as an alternative refrigerant to R22.
†Corresponding AuthorTel : 061-689-4951E-mail : [email protected]
공학기술논문지 제1권 제1호 (2008)
198 Sungbae Kim and Sukjoo Hong
2. Experimental Equipments& Procedure
2.1. Experimental Equipments
Figure 1 is the schematic of experimental equipments to
study the performance characteristics in refrigeration system
which shows the degree of superheat changes depending on
condensing pressure.
R22 and R717 were used as operating fluids in this system.
The experimental equipments were composed of a compressor,
a condenser, a receiver, a constant temperature bath, an expansion
valve and other accessory equipments. They were made very
carefully to minimize the loss of pressure in the system. The
part of low pressure in the system was insulated in order not
to be affected from the outside temperature which meets KS
standard. Pressure sensors, temperature sensors, mass flow meters,
a superheat controller, pressure control valves and a power
meter were equipped in the system to measure the phase
change in those operating fluids within the system. And they
were controlled within the range of errors of measuring machines
(± 0.1oC of temperature, ± 0.1bar of pressure, ± 0.1% of mass
flow and ± 0.1% of power consumption). A screw-open type
compressor was used to do the experiment under constant load,
and the side of slide was fixed to maintain the load constantly.
A heat exchanger of shell & tube type was used for a
condenser and an evaporator and water was used as fluid for
phase change(cooling water and chilled water). A heater of
1kW and a 3-way control valve were installed to keep up
constantly the temperature of fluid for phase change. A constant
temperature bath was installed to be controlled automatically
by a thermometer controller.
An inverter circulation pump and a flow control valve were
installed to keep up constantly mass flow of chilled water for
an evaporator.
To control degree of superheat, an electronic expansion valve
was used [7]. It calculates the degree of superheat according
to the suction temperature and the suction pressure of each
sensor attached to a manual expansion valve and an outlet of
an evaporator, and then opens the valve automatically by PID
control to make the set up value. A pressure control valve was
installed to control condensing pressure. It reads a pressure
sensor on the top of a condenser and controls cooling water
flow of a condenser automatically by the set up pressure. A mass
flow meter was installed to measure mass flow of cooling
water of the condenser. Mass flow meters were installed each in
a receiver and an outlet of an evaporator to measure mass
flow of a refrigerant.
2.2. Experimental Procedure
Before operating the experiment of refrigeration system,
the values of each measuring machine attached to equipments
with ones of the transmitted were compared, errors were checked,
and then the operation condition was monitored by monitoring
program. A circulation pump was operated to examine whether
the flow of an evaporator is controlled constantly, then the mass
flow was checked.
In order to keep the same condition of each refrigerant equal,
enough amount of a refrigerant was charged and the load of
R22 was decided about a half of R717 within the system
permitted. If the operation condition became stable, experiments
were conducted by steps of 500kPa of condensing pressure
from 1,500 kPa to 1,600 kPa, and by steps of 1oC of degree of
superheat from 0 to 10oC according to the condition of condensing
pressure. At the beginning of the operation, an electronic expansion
valve was used to make degree of superheat close to the set
up value and then a manual expansion valve was used to keep
up the correct set up value constantly. the experiment was
conducted repeatedly to make accuracy of the experiment data
high. The result data of the experiment were measured by 2
seconds by data acquisition system, and then analyzed by PC.
3. The result & Considerationof The experiment
The result of the experiment was considered, which compared
COP of power consumption of compressor and refrigeration
capacity. It depends on the change of heat capacity of condenser,
heat capacity of evaporator, mass flow of refrigerant, suction
pressure, mass flow of cooling water in a condenser and the
temperature of chilled water in the outlet of an evaporator,
when changing degree of superheat by condensing pressure.
3.1. Refrigerant Mass Flow
Figure 2 shows mass flow of suction vapor in compressor.Figure 1. The schematic of refrigeration system.
J. of Adv. Eng. and Tech., Vol. 1, No. 1 (2008)
The Comparison of Performance Characteristics in Refrigeration System using R717 and R22 199
Mass flow generally decreased as condensing pressure and
degree of superheat increased. The compression rate of a compressor
increased and the volume efficiency decreased as condensing
pressure went high, and then its mass flow decreased.
Being compared refrigerants, the mass flow of R22 increases
the highest under 1,500 kPa of condensing pressure and 0 of
degree of superheat. For R717, however, the highest mass
flow is under 1oC of degree of superheat. Using R717 as a
refrigerant in a heat exchanger of shell & tube type, refrigerant
fluid is vaporized in about 0 of degree of superheat, bubbles
come on the surface of the tube and they rise up getting lost
heat by cold refrigerant fluid around them. At this time the
refrigerant gas becomes liquid again, and this subcooled
boiling [8] is concluded as a cause. Thus, less amount of refrigerant
gas than expected comes into the compressor in around 0
degree. R22, however, didn't show this phenomenon. There may
be delicate differences caused by the type of a heat exchanger
and the value of properties of the refrigerant.
Taken all together, R717 has a pretty gentle slope compared
with R22, and this shows its stability under the change of
condensing pressure and degree of superheat.
3.2. Compressor Suction Pressure
Figure 3 is the result of the experiment on suction pressure
of compressor. As condensing pressure changed, suction
pressure of compressor resulted differently each other from
refrigerants. Generally the higher degree of superheat, the
lower suction pressure.
Suction pressure of compressor depending on condensing
pressure had seldom changed in case of R717. But in case of
R22 it went up as condensing pressure became high. As
shown in Figure 2, mass flow of suction vapor in compressor
decreased as condensing pressure went higher. All together,
pressure should be decreased, but the increase of condensing
pressure made high pressure go up and had constant degree of
super-cooling. This made low pressure go up, and thus the
rising of low pressure was concluded to work more than the
decrease of mass flow. In case of R717, the decline of mass
flow of practical refrigerant depending on the rising of
compression rate was concluded to work more than the rising
of low pressure because its load was twice of R22.
Suction pressure of a compressor declined as the degree of
superheat went up because mass flow of suction vapor in
compressor decreased as shown in Figure 2. For R717 mass
flow decreased little, on the other hand suction pressure decreased
much. It resulted from the value of heat properties of R717 as
a refrigerant. Its ratio volume depending on the phase change
of the refrigerant increased more being compared with R22,
and it meant suction pressure was more sensitive than the
change of mass flow.
3.3. The Mass Flow and the Temperature of
Condenser Cooling Water
Figure 4 and Figure 5 show the mass flow and the outlet
temperature of condenser cooling water. The outlet temperature
of cooling water declines as the flow of cooling water increases.
On the contrary, the temperature goes high in inverse proportion
to the flow of cooling water decreased.
For R717, the mass flow and the outlet of cooling water in
1,500 kPa and 1,600 kPa of condensing pressure had no
difference even if changed the degree of superheat. The mass
flow of condenser cooling water decreased much as condensing
pressure was high under 1,500 kPa and 1,550 kPa of condensing
pressure and 0~4oC of degree of superheat. But under 4
oC~
10oC, the mass flow of condenser cooling water decreased little
even if condensing pressure went high. The enthalpy of refrigerant
vapor discharged from compressor increased as the degree of
superheat went high under the equal condensing pressure.
The mass flow of cooling water generally should increase
much, but increased less than under 0~4oC. It is concluded that
the large refrigeration area of condenser achieved refrigeration
enough to the increase of enthalpy.
3.4. Condenser Heat Capacity
Figure 6 shows the value of heat capacity measured by the
flow of condenser cooling water and the outlet temperature.
Figure 3. The relations of suction pressure and degree of superheat
at each condensing pressure.
Figure 2. The relations of suction mass flow rate and degree
of superheat at each condensing pressure.
공학기술논문지 제1권 제1호 (2008)
200 Sungbae Kim and Sukjoo Hong
Heat capacity decreased as condensing pressure and degree of
superheat went high. Condenser heat capacity increased in
proportion to mass flow of a refrigerant and suction pressure
high. It shows mass flow of a refrigerant and suction pressure
are the factors which have an effect on the change of condenser
heat capacity.
The aspect of heat capacity of two refrigerants were equal
except the increase of heat capacity resulted from sub-cooled
boiling of R717. The difference of heat capacity due to the
difference of load showed same to other figure.
3.5. Outlet Temperature of Evaporator Chilled
Water and Evaporator Heat Capacity
Figure 7 and Figure 8 show the outlet temperature of
evaporator chilled water and evaporator heat capacity. For both
refrigerants, the chilled water outlet temperature went high and
evaporator heat capacity went low as condensing pressure and
degree of superheat were high. High outlet temperature of
chilled water and low heat capacity of evaporator means that
refrigeration effect gets less that much. High condensing
pressure makes saturation pressure of evaporator refrigerant
high and it makes refrigeration effect decreased. For degree of
superheat, the cause can be the decline of refrigerant mass
flow as shown in Figure 2. Compared condenser heat
capacity with evaporator heat capacity, heat capacity was almost
similar. Generally condenser heat capacity should be as big as the
power consumption of compressor, being compared with
evaporator heat capacity. The reason why the result came out
like this could be explained as the circulation refrigerator oil
was radiated from an oil separator in the system.
3.6. Power Consumption and COP
Figure 9 and Figure 10 show power consumption and COP.
Figure 4. The relations of cooling water mass flow rate and
degree of superheat at each condensing pressure.
Figure 5. The relations of cooling water outlet temperature and
degree of superheat at each condensing pressure.
Figure 6. The relations of condenser heat capacity and superheat
temperature at each condensing pressure.
Figure 7. The relations of chilled water outlet temperature
and degree of superheat at each condensing pressure.
Figure 8. The relations of evaporator heat capacity and degree
of superheat at each condensing pressure.
J. of Adv. Eng. and Tech., Vol. 1, No. 1 (2008)
The Comparison of Performance Characteristics in Refrigeration System using R717 and R22 201
For both refrigerants, power consumption increased as
condensing pressure and degree of superheat went high. Keeping
up condensing pressure constantly and making the degree of
superheat high decreases the refrigerant mass flow vaporized
from evaporator and evaporation pressure. It makes compression
ratio go up and power consumption increase.
Figure 10 is the result of the experiment on COP. COP is
the relation of evaporator heat capacity and power consumption.
As condensing pressure and degree of superheat went high,
evaporator heat capacity decreased and power consumption
increased. R22 showed higher because of subcooled boiling
at 0~2oC of degree of superheat. But R717 showed higher at
more than 2oC of degree of superheat.
Being compared the leading slope of each refrigerant, R717
showed more stable COP than R22 did depending on the
degree of superheat. R717 also showed almost equal COP to
R22 even though it had twice of load. It means that R717 will
show higher COP in case it is measured under the equal load.
4. Conclusion
This study compared the performance characteristics in
refrigeration system using R22 and R717, and concluded as
follows;
1. For circulation amount of refrigerant, R717 was more
stable than R22 at the change of condensing pressure
and degree of superheat. Its circulation amount of refrigerant
was about 1/4 of R22 and the suction pressure was much
lower even if operated with double load of R22. This
confirmed that R717 is superior to R22 in miniaturizing
refrigeration system.
2. As degree of superheat went up, refrigerant mass flow come
into evaporator decreased, compression ratio became big,
the power increased and then the loss of energy got bigger.
3. COP showed R717 became higher than R22 at more
than 2oC of degree of superheat. If operated with the
equal load, R717 must show the higher than R22 on the
whole. R717 was proved to have the most suitable condition
to save operating cost with energy-saving at 1oC of
degree of superheat.
4. R717 is a natural refrigerant. Considering not only its
efficiency depending on developing attached systems
hereafter and its stability being complemented but also
economical and environmental aspects, it seems to be
suitable as an alternative refrigerant to R22 which is
currently one of restricted items.
Nomenclature
r : Mass flow of refrigerant, [/h]
cw : Mass flow of condenser cooling water, [/h]
Tch : Outlet temperature of evaporator chilled water, [oC]
Tcw : Outlet temperature of condenser cooling water, [oC]
Ps : Suction pressure of compressor, [kPa]
Qe : Evaporator heat capacity, [kW]
Qc : Condenser heat capacity, [kW]
References
(1) Stoecker, W. F., Refrigeration and Air conditioning, 2nd ed.,
McGraw-Hill, New York, 1-12, 296-307 (1982).
(2) Nonaka, M., et al., The Int. Symp. on HCFC Alternative
Refrigerants., 111-116 (1998).
(3) Nakayama, M., et al., Room A/C, Ref., 72(835) 60-64(1997).
(4) Akutsu, M., et al., Sanyo Technical Review., 30(1) 20-26
(1998).
(5) Effect of Ammonia, Refrig., Res. Found. Inform. Bull.,
Washington, D.C., 4 (1979).
(6) James, M., and Piotr, A. Domanski, Magazine of the SAREK.,
34, (1), 60-69 (2005).
(7) Higuchi, K., Refrigeration., 61, 45-52 (1986).
(8) Cengel, Y. A., Heat Transfer., McGraw-Hill, New York, 461-505
(2002).
m·
m·
Figure 9. The relations of power and degree of superheat at each
condensing pressure.
Figure 10. The relations of COP and degree of superheat at each
condensing pressure.