r407f applications_en.pdf
DESCRIPTION
RefrigerationTRANSCRIPT
![Page 1: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/1.jpg)
Application with Reciprocating and Screw Compressors operated on R407F
![Page 2: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/2.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Contents
![Page 3: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/3.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Contents
/ Physical properties
/ General information about the application with reciprocating compressors
operated on R407F
/ Application limits for reciprocating compressors (current series):
/ C1, C2 and C3 with VARICOOL “SL(A)”
/ C1, C2 and C3 with VARICOOL “SL(B)”
/ C4, B5 and B6 with CIC® system
/ General information about the application with screw compressors
operated on R407F
/ Application limits for screw compressors (HS./OS. series):
/ Standard operating mode
/ ECO operating mode
![Page 4: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/4.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Physical Properties
![Page 5: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/5.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Physical Properties
R22 R404A R407F R407A
Bubble Point Temperature at 1 bar(a) [°C] -41,0 -46,8 -46,5 -45,5
Dew Point Temperature at 1 bar(a) [°C] -41,0 -46,0 -40,0 -39,0
Temperature glide [K] at 1 bar(a) 0,0 0,8 6,5 6,5
Critical Temperature [°C] 96,2 72,1 82,5 82,0
Critical Pressure [bar(a)] 49,9 37,3 47,5 44,9
Condensing temperature at 26 bar(a) [°C] 63,2 55,5 56,8 58,7
Discharge gas temperature at MT (-10°C/45°C/20°C) (isentropic) [°C] 101,4 77,8 93,8 88,0
Discharge gas temperature at LT (-35°C/40°C/20°C) (isentropic) [°C] 143,2 102,2 129,3 120,1
ODP [R11 = 1] 0,055 0 0 0
GWP (100 a) - IPCC III (2001) [CO2 = 1,0] 1700 3780 1705 1990
![Page 6: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/6.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Physical Properties
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
-50 -40 -30 -20 -10 0 10 20 30 40 50 60
Pressure[bar(a)]
Temperature [°C]
R404A
R407F
R407A
R22
Reference: Dew Point
![Page 7: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/7.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
General Information about the Application
with Reciprocating Compressors operated
on R407F
![Page 8: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/8.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
General Information about the Application with
Reciprocating Compressors operated on R407F
/ BSE32 (POE) is recommended for every application with R407F
Lubricant oil:
/ KT-651-2
Special guidelines for handling zeotropic refrigerant blends:
/ KT-651-2
Pressure/refrigerant temperature table:
/ KT-651-2
General application range:
![Page 9: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/9.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Reciprocating
Compressors (Current Series)
![Page 10: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/10.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Reciprocating Compressors
(Current Series)
C1, C2 and C3 Series with VARICOOL “SL(A)”Suction gas cooling “SL(A)”
2KC-05.2Y .. 4CC-9.2Y
![Page 11: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/11.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Reciprocating Compressors
(Current Series)
C1, C2 and C3 Series with VARICOOL “SL(A)”Suction gas cooling “SL(A)”
/ Motor version 1 might be necessary for some operating points at high
evaporating temperatures with VARICOOL “SL(A)”
/ Further information about VARICOOL System: KB-100-6
/ Compressor selection and performance data for applications with R407F
and VARICOOL “SL(A)” on request in the Department of Application
Engineering
![Page 12: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/12.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Reciprocating Compressors
(Current Series)
C1, C2 and C3 Series with VARICOOL “SL(B)”Air cooling – direct suction “SL(B)”
![Page 13: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/13.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Reciprocating Compressors
(Current Series)
C1, C2 and C3 Series with VARICOOL “SL(B)”Air cooling – direct suction “SL(B)”
/ Motor version 2 must be selected for the operation with
VARICOOL “SL(B)”
/ Further information about VARICOOL System: KB-100-6
/ Compressor selection and performance data for applications with R407F
and VARICOOL “SL(B)” on request in the Department of Application
Engineering
![Page 14: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/14.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Reciprocating Compressors
(Current Series)
C4, B5 and B6 with CIC® System
![Page 15: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/15.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Reciprocating Compressors
(Current Series)
C4, B5 and B6 with CIC® System
/ Motor version 2 must be selected for the operation with CIC® System
/ Motor version 1 might be necessary for some operating points at high
evaporating temperatures where CIC® System is not required
/ Further information about CIC® System: KT-130-1
/ Compressor selection and performance data for applications with
R407F and CIC® System on request in the Department of Application
Engineering
![Page 16: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/16.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
General Information about the Application with
Screw Compressors operated on R407F
![Page 17: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/17.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
General Information about the Application with
Screw Compressors operated on R407F
/ BSE170 (POE) is recommended for every application with R407F
Lubricant oil:
/ KT-651-2
Special guidelines for handling zeotropic refrigerant blends:
/ KT-651-2
Pressure/refrigerant temperature table:
![Page 18: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/18.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Screw Compressors
(HS./OS. Series)
![Page 19: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/19.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Screw Compressors (HS./OS. Series)
HS./OS. Series (Standard)
HS.53.. / OS.53..
HS.64..
HS.74.. / OS.74..
HS.85.. / OS.85..
![Page 20: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/20.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Screw Compressors (HS./OS. Series)
HS./OS. Series (ECO):
HS.53.. / OS.53..
HS.64..
HS.74.. / OS.74..
HS.85.. / OS.85..
![Page 21: R407F Applications_EN.PDF](https://reader035.vdocument.in/reader035/viewer/2022062418/552cb0f6550346e8198b4850/html5/thumbnails/21.jpg)
BITZER // Application with Reciprocating and Screw Compressors operated on R407F
Application Limits for Screw Compressors (HS./OS. Series)
HS./OS. Series (Standard and ECO):
/ Oil cooling is necessary for high compression ratios
/ Compressor selection and performance data for applications with R407F
on request in the Department of Application Engineering