  • iFeatures

    l Low burdenl Trip circuit can be supervised with

    breaker open or closedl Mis-tripping of breaker by

    accidental short-circuits avoidedl No false alarms given due to

    protection operation

    Application

    The Type MVAX relay supervises thetrip circuit of a circuit breaker,initiating audible alarm and visualindication if the trip circuit fails or themechanism does not operate. Four types are available givingsupervision as follows:Relay type Faults detectedMVAX 12 Failure of trip

    Midos2

    supply onlyMVAX 21, MVAX 31 andMVAX 91 Failure of trip

    supplyOpen circuit trip coil or trip circuit wiringFailure of circuit breaker tripping mechanism

    Type MVAX 31 gives supervision withthe circuit breaker in either state, andtype MVAX 21 with circuit breakerclosed only.If required, the alarm units of typesMVAX 21 and MVAX 31 can beoperated via pilot wires.Type MVAX 91, three seperate MVAX 31s in a size 8 case.Type MVAX 12, 21Trip Circuit SupervDescription

    The relays are basically attractedarmature units of simple and robustconstruction having a positive actionwithout chatter.Type MVAX12 is a single unit whichis simply connected across the tripcircuit supply as shown in Figure 2(a).The unit is normally energised anddrops off if the trip voltage is lost orfalls below approximately 40% ofnominal. The unit picks up below 80%of rated voltage.

    Figure 1: Type MVAX relay withdrawn from ca, 31, 91sion RelaysTo avoid operation due to voltagedips caused by faults in other circuitsa resistance-capacitance time delaycircuit is incorporated to give 100msdelayed drop off.Type MVAX 21 consists of two unitsconnected as shown in Figure 2(b).Under healthy conditions with thecircuit breaker closed, both units areenergised. If the trip circuit becomesopen or the supply fails, unit RL2drops off and opens contact RL21 tode-energise unit RL1. When the circuitbreaker is open, the auxiliary switchshunts contact RL21 to hold in unit RL1.

    se

  • C 1 R2

    RL12

    Viewed from frontCase earth

    1 2

    3 4

    5 6

    13 14

    21 22

    27 28

    Module terminalblock viewed from rear

    R ext R113

    2 134

    _

    14

    (a) CT shorting links make before (b) & (c) disconnect

    (b) Short terminals break before (c)

    (c) Long terminals

    Note 1

    Vx+

    RL13

    +

    +

    52T

    RL2

    Alarm supply (Vx (1))

    21 28 Rext (1)

    27 RL2-1

    52-b

    CB Auxswitch

    CB Auxswitch

    Trip supply (Vx (2))Trip coil

    Trip relay

    Rext (2) 13 14 RL1-1

    RL1-2Alarm

    contactsNote: Contact arrangement shown is typical only. RL1-35

    2

    1 3

    4

    7

    52-a

    _

    _

    The units are delayed (by means ofcopper slugs) on drop off for a total of400ms, to prevent a false alarm dueto voltage dips caused by faults inother circuits or during a normaltripping operation, when unit RL2 ismomentarily short circuited by the selfreset trip relay contact. If the trip relayfails to reset due possibly to failure ofthe circuit breaker trippingmechanism, the alarm is initiated.Type MVAX 31 consists of three unitsconnected as shown in Figure 2(c).Under healthy conditions with thecircuit breaker closed, units RL2 andRL1 are energised and the operationis the same as type MVAX 21.When the circuit breaker is open, unitRL3 is also energised via the normallyclosed auxiliary switch and unit RL1 isheld in by contact RL31. Unit RL3 willdetect trip circuit abnormalities withthe circuit breaker open, in a similarmanner to unit RL2 with the circuitbreaker closed.The units are delayed a total of400ms on drop off, as in type

    Figure 2(a): MVAX 12 Trip supply supervision

    Figure 2(b): MVAX 21 Trip circuit supervision

    RL2

    Trip relay

    Rext (2) 13 14

    +

    Rext (3) 21 22

    52-a52T

    + _

    _

    RL1-1

    RL1-2Alarm

    contacts

    Note: Contact arrangement shown is typical only. RL1-35

    2

    1 3

    4

    7

    Alarm supply (Vx (1))

    27 RL3-1

    RL2-1

    28 Rext (1)RL13

    RL3

    CB Auxswitches

    52-b

    Trip supply (Vx (2))

    Figure 2(c): MVAX 31 Trip circuit supervisionMVAX 21.Type MVAX 91 consists of threeseperate MVAX 31s connected asshown in Figure 2(d).3

  • 4RL2

    Trip relay

    Rext (2) 47 48

    +

    Rext (3) 45 46

    52-a52T

    + _

    _RL1-1

    RL1-2Alarm

    contacts

    Note: Contact arrangements shown are typical only.For 30 110/125V only

    RL1-333

    30

    29 31

    32

    35Alarm supply (Vx (1))

    49 RL3-1

    RL2-1

    50 Rext (1)RL13

    RL3

    CB Auxswitches

    52-b

    Trip supply (Vx (2))

    Phase A

    RL2

    Trip relay

    Rext (2) 53 54

    +

    Rext (3) 51 52

    52-a52T

    + _

    _RL1-1

    RL1-2Alarm

    contacts

    RL1-341

    38

    37 39

    40

    43Alarm supply (Vx (1))

    55 RL3-1

    RL2-1

    56 Rext (1)RL13

    RL3

    CB Auxswitches

    52-b

    Trip supply (Vx (2))

    Phase B

    RL2

    Trip relay

    Rext (2) 25 26

    +

    Rext (3) 23 24

    52-a52T

    + _

    _RL1-1

    RL1-2Alarm

    contacts

    RL1-35

    2

    1 3

    4

    7Alarm supply (Vx (1))

    27 RL3-1

    RL2-1

    28 Rext (1)RL13

    RL3

    CB Auxswitches

    52-b

    Trip supply (Vx (2))

    Phase C

    Figure 2(d): MVAX 91 Trip circuit supervision

  • 5Case earth

    1 2

    3 4

    5 6

    7 8

    9 10

    11 1213 14

    21 22

    Module terminal block viewed from rear

    (a) CT shorting links make before (b) & (c) disconnect (b) Short terminals break before (c) (c) Long terminals

    Note 1

    27 28

    Rear mounted facing rearviewed from front

    A

    RL3

    V

    Vx +

    ZGO891

    Rear mounted facing rearviewed from front

    A

    RL2

    V

    Vx +

    ZGO891

    Front mounted facing frontviewed from front

    2

    RL1

    V

    Vx +

    ZGO891

    5

    3

    74

    31

    22 14 28

    RL2-A

    RL3-A

    2713 R2R121

    Combinations of Output contacts tooutput contacts module terminals

    1 3 5 7 2 4

    3M M M M

    2M 1B B M M

    1M 2B B M B

    Figure 2(e): MVAX 31 Trip circuit supervision relay with preclosing supervision (ac)

  • 6Case earth1 2

    3 4

    5 6

    7 89 1011 12

    13 14

    21 22

    Module terminal blockposition A viewed from rear

    Module terminal blockposition D viewed from rear

    15 16

    17 18

    19 20

    23 24

    25 26

    Note 1

    Note 2For 30 110V/125V only

    27 28

    Rear mounted facing rearviewed from front

    A

    RL3

    V

    Vx +

    ZGO891

    Rear mounted facing rearviewed from front

    A

    RL2

    V

    Vx +

    ZGO891

    Front mounted facing frontviewed from front

    30

    RL1

    V

    Vx +

    ZGO891

    33

    3

    3532

    3129

    46 48 50

    RL2-A

    RL3-A

    49 47 R2R145

    Case earth29 30

    31 32

    33 34

    35 36

    37 38

    39 4041 42

    49 50

    43 4445 46

    47 48

    51 52

    53 54

    55 56

    Phase A

    Rear mounted facing rearviewed from front

    A

    RL3

    V

    Vx +

    ZGO891

    Rear mounted facing rearviewed from front

    A

    RL2

    V

    Vx +

    ZGO891

    Front mounted facing frontviewed from front

    38

    RL1

    V

    Vx +

    ZGO891

    41

    3

    4340

    3937

    52 54 56

    RL2-A

    RL3-A

    55 53 R2R151

    Phase B

    Rear mounted facing rearviewed from front

    A

    RL3

    V

    Vx +

    ZGO891

    Rear mounted facing rearviewed from front

    A

    RL2

    V

    Vx +

    ZGO891

    Front mounted facing frontviewed from front

    2

    RL1

    V

    Vx +

    ZGO891

    5

    3

    74

    31

    24 26 28

    RL2-A

    RL3-A

    2725 R2R123

    Phase C

    Combination ofoutput contacts

    Phase output contactsto module terminal

    A Phase3M2M1M3B B Phase3M2M1M3BC Phase3M2M1M3B

    29-31MBBB

    37-39MBBB

    1-3MBBB

    33-35MMM

    N/A41-43

    MMM

    N/A5-7MMM

    N/A

    30-32MMBB

    38-40MMBB

    2-4MMBB

    34-36N/AN/AN/A

    B42-44N/AN/AN/A

    B6-8

    N/AN/AN/A

    B

    -1B2B-

    -1B2B-

    -1B2B-

    CT shorting links makebefore (b) & (c) disconnect

    Short terminals break before (c)

    Long terminals

    (a)

    (b)(c)

    Figure 2(f): MVAX 91 Trip circuit supervision relay with preclosing supervision (ac)

  • Technical Data

    Note: For ac supervision relays, the technical information is the same as for dc versions

    Voltage ratings (Vx) Relays are available for use on any combination of the following standard auxiliary supplies for trip and alarm.Rating Operative range(V dc) (V dc)24/27 193030/34 2437.548/54 37.560110/125 87.5137.5220/250 175275All relays will withstand the maximum voltage in the operative range continuously.

    Note: MVAX 91 not available in 220/250V range.

    Burden

    MVAX 12 MVAX 21, 31 and 91 (see note)Rating (V dc) Trip Alarm

    mA W mA W mA W24/27 45 1.23 55 1.5 80 2.530/34 36 1.22 35 1.5 80 348/54 23 1.25 20 1 80 4110/125 15 1.9 20 2.5 63 8220/250 9 2.3 20 4.5 60 15Notes:1. All the burdens are at the maximum rated value2. All burdens are less than the figures quoted3. With the circuit breaker open the trip supply burden of the MVAX 21 is zero4. MVAX 91 = 3 x MVAX 31mA/W, 3 seperate units

    Maximum pilot loop resistance of alarm supply Rating Maximum pilot

    (V dc) loop resistancein ohms

    24/27 10030/34 20048/54 400110/125 400220/250 400The operating range of the alarm supply output relay (RL1) is unimpaired with the above pilot resistances,

    Operating/resetting times

    1.Typical operating times MVAX 12 < 20msMVAX 21, 31, 91 < 70ms

    2.Typical resetting times MVAX 12 >100 msMVAX 21, 31, 91 > 400 msNote: Times measured at the lower rated voltage. 91 (3 x MVAX 31)7

  • 8Operation indicator A hand or self reset mechanical operation indicator can be supplied.

    Contacts

    MVAX 12 2 pairs of electrically separate contacts in any combination of normally open or closedMVAX 21, 31, 91 (3 x MVAX 31) 3 pairs of electrically separate contacts in any combination of normally open or closed

    Contact ratings

    Current Make and Carry Make and Carry BreakContinuously for 3s

    ac 1250VA with 7500VA with 1250VA with maxima of maxima of maxima of 5A and 660V 30A and 660V 5A and 660V

    dc 1250W with 7500VA with 100W (resistive)maxima of maxima of 50W (inductive 5A and 660V 30A and 660V with maxima of

    5A and 660V

    Voltage withstand

    InsulationIEC 2555 2kV rms for 1 minute between all case

    terminals connected together and the case earth terminal2kV rms for 1 minute between independent circuits including contact circuits. 1kV rms for 1 minute across normally open outgoing contact pairs

    High voltage impulseIEC 2555 5kV peak, 1.2/50s, 0.5J between

    all terminals and case earth and between adjacent terminals

    Environmental withstand

    TemperatureIEC 6821/IEC 6822 Storage and transit 25C to +70

    Operating 25C to +55CHumidityIEC 6823 56 days (at 93% RH and +40C)Enclosure protectionIEC 529 IP 50 (dust protected)VibrationIEC 255211 0.5g between 10Hz and 150HzMechanical durability

    Loaded contact 10,000 operations minimumUnloaded contact 100,000 operations minimum

  • 4 holes 4.445

    1324

    Cases

    Type MVAX 12 is available in a size2 case, see Figure 3. Types MVAX 21and MVAX 31 are available in size 3cases see Figure 4. Type MVAX 91 isavailable in a size 8 case, see Figure 5.

    Information Required withOrder

    Relay typeAlarm and trip supply voltagesContact combinationOperation indicator required

    Fi

    FiPush buttonprojection 10 max

    All dimensions in mm

    Panel cut-out:Flush mounting fixing details

    Flush mounting51

    21232 25 min.

    Reset

    157 max.

    48

    159168

    177

    Push buttonprojection 10 max

    All dimensions in mm

    Panel cut-out:Flush mounting fixing details

    4 holes 4.4

    Flush mounting

    71

    77

    21232 25 min.

    Reset

    157 max.

    73

    159168

    2623.5

    177

    gure 3: Case outline size 2

    gure 4: Case outline size 39

  • 10

    Push buttonprojection 10 max

    All dimensions in mm

    Panel cut-out:Flush mounting fixing details

    4 holes 4.4

    Flush mounting

    200

    206

    21232 25 min.

    11

    Reset

    157 max.

    203

    159168

    155.424

    177

    Figure 5: Case outline size 8

    FeaturesApplicationDescriptionTechnical DataVoltage ratings (Vx)BurdenMaximum pilot loop resistance of alarm supplyOperating/resetting timesOperation indicatorContactsContact ratingsVoltage withstandEnvironmental withstandMechanical durability

    CasesInformation Required with Order