r6010e_mvax (2).pdf
TRANSCRIPT
-
iFeatures
l Low burdenl Trip circuit can be supervised with
breaker open or closedl Mis-tripping of breaker by
accidental short-circuits avoidedl No false alarms given due to
protection operation
Application
The Type MVAX relay supervises thetrip circuit of a circuit breaker,initiating audible alarm and visualindication if the trip circuit fails or themechanism does not operate. Four types are available givingsupervision as follows:Relay type Faults detectedMVAX 12 Failure of trip
Midos2
supply onlyMVAX 21, MVAX 31 andMVAX 91 Failure of trip
supplyOpen circuit trip coil or trip circuit wiringFailure of circuit breaker tripping mechanism
Type MVAX 31 gives supervision withthe circuit breaker in either state, andtype MVAX 21 with circuit breakerclosed only.If required, the alarm units of typesMVAX 21 and MVAX 31 can beoperated via pilot wires.Type MVAX 91, three seperate MVAX 31s in a size 8 case.Type MVAX 12, 21Trip Circuit SupervDescription
The relays are basically attractedarmature units of simple and robustconstruction having a positive actionwithout chatter.Type MVAX12 is a single unit whichis simply connected across the tripcircuit supply as shown in Figure 2(a).The unit is normally energised anddrops off if the trip voltage is lost orfalls below approximately 40% ofnominal. The unit picks up below 80%of rated voltage.
Figure 1: Type MVAX relay withdrawn from ca, 31, 91sion RelaysTo avoid operation due to voltagedips caused by faults in other circuitsa resistance-capacitance time delaycircuit is incorporated to give 100msdelayed drop off.Type MVAX 21 consists of two unitsconnected as shown in Figure 2(b).Under healthy conditions with thecircuit breaker closed, both units areenergised. If the trip circuit becomesopen or the supply fails, unit RL2drops off and opens contact RL21 tode-energise unit RL1. When the circuitbreaker is open, the auxiliary switchshunts contact RL21 to hold in unit RL1.
se
-
C 1 R2
RL12
Viewed from frontCase earth
1 2
3 4
5 6
13 14
21 22
27 28
Module terminalblock viewed from rear
R ext R113
2 134
_
14
(a) CT shorting links make before (b) & (c) disconnect
(b) Short terminals break before (c)
(c) Long terminals
Note 1
Vx+
RL13
+
+
52T
RL2
Alarm supply (Vx (1))
21 28 Rext (1)
27 RL2-1
52-b
CB Auxswitch
CB Auxswitch
Trip supply (Vx (2))Trip coil
Trip relay
Rext (2) 13 14 RL1-1
RL1-2Alarm
contactsNote: Contact arrangement shown is typical only. RL1-35
2
1 3
4
7
52-a
_
_
The units are delayed (by means ofcopper slugs) on drop off for a total of400ms, to prevent a false alarm dueto voltage dips caused by faults inother circuits or during a normaltripping operation, when unit RL2 ismomentarily short circuited by the selfreset trip relay contact. If the trip relayfails to reset due possibly to failure ofthe circuit breaker trippingmechanism, the alarm is initiated.Type MVAX 31 consists of three unitsconnected as shown in Figure 2(c).Under healthy conditions with thecircuit breaker closed, units RL2 andRL1 are energised and the operationis the same as type MVAX 21.When the circuit breaker is open, unitRL3 is also energised via the normallyclosed auxiliary switch and unit RL1 isheld in by contact RL31. Unit RL3 willdetect trip circuit abnormalities withthe circuit breaker open, in a similarmanner to unit RL2 with the circuitbreaker closed.The units are delayed a total of400ms on drop off, as in type
Figure 2(a): MVAX 12 Trip supply supervision
Figure 2(b): MVAX 21 Trip circuit supervision
RL2
Trip relay
Rext (2) 13 14
+
Rext (3) 21 22
52-a52T
+ _
_
RL1-1
RL1-2Alarm
contacts
Note: Contact arrangement shown is typical only. RL1-35
2
1 3
4
7
Alarm supply (Vx (1))
27 RL3-1
RL2-1
28 Rext (1)RL13
RL3
CB Auxswitches
52-b
Trip supply (Vx (2))
Figure 2(c): MVAX 31 Trip circuit supervisionMVAX 21.Type MVAX 91 consists of threeseperate MVAX 31s connected asshown in Figure 2(d).3
-
4RL2
Trip relay
Rext (2) 47 48
+
Rext (3) 45 46
52-a52T
+ _
_RL1-1
RL1-2Alarm
contacts
Note: Contact arrangements shown are typical only.For 30 110/125V only
RL1-333
30
29 31
32
35Alarm supply (Vx (1))
49 RL3-1
RL2-1
50 Rext (1)RL13
RL3
CB Auxswitches
52-b
Trip supply (Vx (2))
Phase A
RL2
Trip relay
Rext (2) 53 54
+
Rext (3) 51 52
52-a52T
+ _
_RL1-1
RL1-2Alarm
contacts
RL1-341
38
37 39
40
43Alarm supply (Vx (1))
55 RL3-1
RL2-1
56 Rext (1)RL13
RL3
CB Auxswitches
52-b
Trip supply (Vx (2))
Phase B
RL2
Trip relay
Rext (2) 25 26
+
Rext (3) 23 24
52-a52T
+ _
_RL1-1
RL1-2Alarm
contacts
RL1-35
2
1 3
4
7Alarm supply (Vx (1))
27 RL3-1
RL2-1
28 Rext (1)RL13
RL3
CB Auxswitches
52-b
Trip supply (Vx (2))
Phase C
Figure 2(d): MVAX 91 Trip circuit supervision
-
5Case earth
1 2
3 4
5 6
7 8
9 10
11 1213 14
21 22
Module terminal block viewed from rear
(a) CT shorting links make before (b) & (c) disconnect (b) Short terminals break before (c) (c) Long terminals
Note 1
27 28
Rear mounted facing rearviewed from front
A
RL3
V
Vx +
ZGO891
Rear mounted facing rearviewed from front
A
RL2
V
Vx +
ZGO891
Front mounted facing frontviewed from front
2
RL1
V
Vx +
ZGO891
5
3
74
31
22 14 28
RL2-A
RL3-A
2713 R2R121
Combinations of Output contacts tooutput contacts module terminals
1 3 5 7 2 4
3M M M M
2M 1B B M M
1M 2B B M B
Figure 2(e): MVAX 31 Trip circuit supervision relay with preclosing supervision (ac)
-
6Case earth1 2
3 4
5 6
7 89 1011 12
13 14
21 22
Module terminal blockposition A viewed from rear
Module terminal blockposition D viewed from rear
15 16
17 18
19 20
23 24
25 26
Note 1
Note 2For 30 110V/125V only
27 28
Rear mounted facing rearviewed from front
A
RL3
V
Vx +
ZGO891
Rear mounted facing rearviewed from front
A
RL2
V
Vx +
ZGO891
Front mounted facing frontviewed from front
30
RL1
V
Vx +
ZGO891
33
3
3532
3129
46 48 50
RL2-A
RL3-A
49 47 R2R145
Case earth29 30
31 32
33 34
35 36
37 38
39 4041 42
49 50
43 4445 46
47 48
51 52
53 54
55 56
Phase A
Rear mounted facing rearviewed from front
A
RL3
V
Vx +
ZGO891
Rear mounted facing rearviewed from front
A
RL2
V
Vx +
ZGO891
Front mounted facing frontviewed from front
38
RL1
V
Vx +
ZGO891
41
3
4340
3937
52 54 56
RL2-A
RL3-A
55 53 R2R151
Phase B
Rear mounted facing rearviewed from front
A
RL3
V
Vx +
ZGO891
Rear mounted facing rearviewed from front
A
RL2
V
Vx +
ZGO891
Front mounted facing frontviewed from front
2
RL1
V
Vx +
ZGO891
5
3
74
31
24 26 28
RL2-A
RL3-A
2725 R2R123
Phase C
Combination ofoutput contacts
Phase output contactsto module terminal
A Phase3M2M1M3B B Phase3M2M1M3BC Phase3M2M1M3B
29-31MBBB
37-39MBBB
1-3MBBB
33-35MMM
N/A41-43
MMM
N/A5-7MMM
N/A
30-32MMBB
38-40MMBB
2-4MMBB
34-36N/AN/AN/A
B42-44N/AN/AN/A
B6-8
N/AN/AN/A
B
-1B2B-
-1B2B-
-1B2B-
CT shorting links makebefore (b) & (c) disconnect
Short terminals break before (c)
Long terminals
(a)
(b)(c)
Figure 2(f): MVAX 91 Trip circuit supervision relay with preclosing supervision (ac)
-
Technical Data
Note: For ac supervision relays, the technical information is the same as for dc versions
Voltage ratings (Vx) Relays are available for use on any combination of the following standard auxiliary supplies for trip and alarm.Rating Operative range(V dc) (V dc)24/27 193030/34 2437.548/54 37.560110/125 87.5137.5220/250 175275All relays will withstand the maximum voltage in the operative range continuously.
Note: MVAX 91 not available in 220/250V range.
Burden
MVAX 12 MVAX 21, 31 and 91 (see note)Rating (V dc) Trip Alarm
mA W mA W mA W24/27 45 1.23 55 1.5 80 2.530/34 36 1.22 35 1.5 80 348/54 23 1.25 20 1 80 4110/125 15 1.9 20 2.5 63 8220/250 9 2.3 20 4.5 60 15Notes:1. All the burdens are at the maximum rated value2. All burdens are less than the figures quoted3. With the circuit breaker open the trip supply burden of the MVAX 21 is zero4. MVAX 91 = 3 x MVAX 31mA/W, 3 seperate units
Maximum pilot loop resistance of alarm supply Rating Maximum pilot
(V dc) loop resistancein ohms
24/27 10030/34 20048/54 400110/125 400220/250 400The operating range of the alarm supply output relay (RL1) is unimpaired with the above pilot resistances,
Operating/resetting times
1.Typical operating times MVAX 12 < 20msMVAX 21, 31, 91 < 70ms
2.Typical resetting times MVAX 12 >100 msMVAX 21, 31, 91 > 400 msNote: Times measured at the lower rated voltage. 91 (3 x MVAX 31)7
-
8Operation indicator A hand or self reset mechanical operation indicator can be supplied.
Contacts
MVAX 12 2 pairs of electrically separate contacts in any combination of normally open or closedMVAX 21, 31, 91 (3 x MVAX 31) 3 pairs of electrically separate contacts in any combination of normally open or closed
Contact ratings
Current Make and Carry Make and Carry BreakContinuously for 3s
ac 1250VA with 7500VA with 1250VA with maxima of maxima of maxima of 5A and 660V 30A and 660V 5A and 660V
dc 1250W with 7500VA with 100W (resistive)maxima of maxima of 50W (inductive 5A and 660V 30A and 660V with maxima of
5A and 660V
Voltage withstand
InsulationIEC 2555 2kV rms for 1 minute between all case
terminals connected together and the case earth terminal2kV rms for 1 minute between independent circuits including contact circuits. 1kV rms for 1 minute across normally open outgoing contact pairs
High voltage impulseIEC 2555 5kV peak, 1.2/50s, 0.5J between
all terminals and case earth and between adjacent terminals
Environmental withstand
TemperatureIEC 6821/IEC 6822 Storage and transit 25C to +70
Operating 25C to +55CHumidityIEC 6823 56 days (at 93% RH and +40C)Enclosure protectionIEC 529 IP 50 (dust protected)VibrationIEC 255211 0.5g between 10Hz and 150HzMechanical durability
Loaded contact 10,000 operations minimumUnloaded contact 100,000 operations minimum
-
4 holes 4.445
1324
Cases
Type MVAX 12 is available in a size2 case, see Figure 3. Types MVAX 21and MVAX 31 are available in size 3cases see Figure 4. Type MVAX 91 isavailable in a size 8 case, see Figure 5.
Information Required withOrder
Relay typeAlarm and trip supply voltagesContact combinationOperation indicator required
Fi
FiPush buttonprojection 10 max
All dimensions in mm
Panel cut-out:Flush mounting fixing details
Flush mounting51
21232 25 min.
Reset
157 max.
48
159168
177
Push buttonprojection 10 max
All dimensions in mm
Panel cut-out:Flush mounting fixing details
4 holes 4.4
Flush mounting
71
77
21232 25 min.
Reset
157 max.
73
159168
2623.5
177
gure 3: Case outline size 2
gure 4: Case outline size 39
-
10
Push buttonprojection 10 max
All dimensions in mm
Panel cut-out:Flush mounting fixing details
4 holes 4.4
Flush mounting
200
206
21232 25 min.
11
Reset
157 max.
203
159168
155.424
177
Figure 5: Case outline size 8
FeaturesApplicationDescriptionTechnical DataVoltage ratings (Vx)BurdenMaximum pilot loop resistance of alarm supplyOperating/resetting timesOperation indicatorContactsContact ratingsVoltage withstandEnvironmental withstandMechanical durability
CasesInformation Required with Order