DESCRIPTION
Plasma torch height control systemTRANSCRIPT
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
1
Plasma torch height control system for profile cutting machines - control PCB.
Features:
- DC 24V output for standard brushed permanent magnet motor - constant torch height control done by means of sampling the arc voltage - initial height sensing prior to cut - adjustable gain and up/down speed - single DC 24V supply - PCB size 100 x 80 x 30 mm
General description:
The R953A control system is an interface between CNC controller or tracing head and Plasma unit. R953A provides all necessary signals for controlling the up/down movement of the cutting torch.
Detailed description:
A switch mode servo driver drives the motor. For simplicity of interfacing the speed feedback (tacho, encoder, etc.) has been omitted and the back EMF voltage from the winding of the motor is integrated and used as a speed feedback for the driver. The driver can deliver close to 2 amperes peak current at nearly 100 % duty cycle. When the up (or down) input is activated, this connects the positive (or negative) supply to input of the driver.
The arc voltage must be externally divided into less than 5 volts. This signal is applied to ARC_VOLTAGE_1 and _2. The difference between arc voltage and reference voltage is amplified and fed to the servo driver. The speed of the movement is proportional to the difference of these voltages. The reference voltage is a preset value of the arc voltage, 0 to +5V, delivered from panel mount potentiometer or analogue output from the CNC.
The auto sequence logics are used for the initial height sensing. When enabled (+AUTO) and +PLASMA signal is toggled on (from manual START switch or CNC controller), the torch is lowered down, the +24V_AIR and +24V_PROXY outputs are activated. The +24V_AIR is used for solenoid controlling a spring returned air cylinder, which lowers the proximity switches to the height of tip of the torch. When the torch is lowered to the cutting height, the proximity switch is activated (the NPN_PROXY input switched to 0V), the down movement and +24V_AIR output are deactivated, what retract the proxy switches to the safe position and plasma on relay is activated, this starts the plasma cut. When +PLASMA is off the up movement is activated.
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
2
+
-
DIFFERENTIAL AMPLIFIER
+
-
ERROR AMPLIFIER
THC ENABLE
DOWNUP
-V
+V0
SPEED
GAIN
+THC
+DN
+UP
ARC_VOLTAGE1
ARC_VOLTAGE2
REF
+
-
ERROR AMPLIFIER
+
-
BACK EMF INTEGRATOR
0
0 INOUT1
OUT2
PWM DRIVER
+PLASMA
+AUTO
NPN_PROXY
+UP
+DN
PLASMA_ON
+24_AIR
+24_PROXY
AUTO SEQUENCE LOGICS
+PLASMA
+AUTO
NPN_PROXY
+UP
+DN
PLASMA_ON
+24_AIR
+24_PROXY
+PLASMA
+AUTO PLASMA_ON
NPN_PROXY
+24_PROXY
+24_AIR
PLASMA_ON1
PLASMA_ON2
MOTOR2
MOTOR1
THC
SERVO DRIVER
Fig. 1.
Interfacing:
Fig 2. and 3. shows the typical connection of R953A (953-000) control system. Both examples use same interface to the plasma unit, CNC controller and cutting torch. The differences are only in the connection of mode selection switches. The whole control system must be supplied from DC 24V power supply; capable delivering enough current for all outputs (motor, solenoid, etc.) plus few hundreds of milli-amperes for R953A PCB. Usually, the 4 amperes power supply is enough.
LM336-5
PLASMA_ON
TCH_ON10K
3K3
AUTO_INIT UP/DOWN
ARC_VOLTAGEMULTITURN POT WITH DIAL
MO
T11
MO
T22
+24V
3
+PR
OX
Y5
+24_
AIR
6
+PLA
SMA
8
PLA
SMA
_ON
19
PLA
SMA
_ON
210
0V4
NPN
_PR
XY
7
THC
_EN
11
AR
C_V
OLT
AG
E112
AR
C_V
OLT
AG
E214
0V13
+UP1 +DN2 +THC3 REF4 +AUTO5 +AUTO6 +PLASMA7 +PLASMA8 THC_EN9 THC_EN10 0V11 0V12 +24V13 +24V14
CONNECTED TO INTERNAL CIRCUIT
RELAY OUTPUT 5A CONTACT
J2
J1
953-000
ARC_VOLTAGE2SCREEN
ARC_VOLTAGE1
PLASMA_ON2PLASMA_ON1
ARC_ON_RLY2ARC_ON_RLY1
THC_EN1THC_EN2
ARC_ON-SENCE2ARC_ON-SENCE1
PLASMA_START2PLASMA_START1
+24
+24
0V
CNC CONTROL
PLASMA UNIT
A
-
+
UP
/DO
WN
DC
MO
TOR
LIM
IT_1
LIM
IT_2
100V
/3A
100V
/3A
+Vin
GN
D
OU
T
PROXY_NPN
+Vin
GN
D
OU
T
PROXY_NPN
AIR
_VA
LVE
CUTTING TORCH ASSEMBLY
+24
0V
24V/~3A
+24
0V
0V
+24
Fig. 2.
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
3
MO
T11
MO
T22
+24V
3
+PR
OX
Y5
+24_
AIR
6
+PLA
SMA
8
PLA
SMA
_ON
19
PLA
SMA
_ON
210
0V4
NPN
_PR
XY
7
THC
_EN
11
AR
C_V
OLT
AG
E112
AR
C_V
OLT
AG
E214
0V13
+UP1 +DN2 +THC3 REF4 +AUTO5 +AUTO6 +PLASMA7 +PLASMA8 THC_EN9 THC_EN10 0V11 0V12 +24V13 +24V14
CONNECTED TO INTERNAL CIRCUIT
RELAY OUTPUT 5A CONTACT
J2
J1
953-000
2K - 10K
UP/DOWN ARC_VOLTAGEMULTITURN POT WITH DIAL
ARC_VOLTAGE2SCREEN
ARC_VOLTAGE1
PLASMA_ON2PLASMA_ON1
ARC_ON_RLY2ARC_ON_RLY1
THC_EN1THC_EN2
ARC_ON-SENCE2ARC_ON-SENCE1
PLASMA_START2PLASMA_START1
+24
+24
0V
CNC CONTROL
PLASMA UNIT
A
-
+
UP
/DO
WN
DC
MO
TOR
LIM
IT_1
LIM
IT_2
100V
/3A
100V
/3A
+Vin
GN
D
OU
T
PROXY_NPN
+Vin
GN
D
OU
T
PROXY_NPN
AIR
_VA
LVE
CUTTING TORCH ASSEMBLY
+24
0V
24V/~3A
+24
0V
0V
+24
+UP 1+DN 2+THC 3REF 4+AUTO 5+AUTO 6+PLASMA 7+PLASMA 8THC_EN 9THC_EN 100V 110V 12+24V 13+24V 14J3
START STOP
THC AUTO
POT_
HI
1PO
T_A
DJ
2PO
T_LO
W3
+DN
1+2
42
+UP
3
J4J5
952-000
IDC
RIB
BO
N C
AB
LE
Fig. 3.
CNC controller:
A dry relay contact should be activated between PLASMA_START1 and PLASMA_START2 to start the plasma unit. A 24 V output from CNC controller connected to PLASMA_START2 can be used instead of relay output. The controller to signalize to the CNC that manual start of the plasma has been activated can also sense this line. A DC 24 V can be sensed between ARC_ON-SENSE1 and ARC_ON-SENSE2. This is usually used to start the motion of machine. If the CNC controller requires a dry contact or different level of signal, insert a coil of additional 24V relay between ARC_ON-SENSE1 and ARC_ON-SENSE2 and with contact of the relay simulate the level, which is required. The CNC controller should provide a normally closed contact, which disables the THC while the machine, does not cut at full cutting speed (e.g.. when is slowing down on the sharp corners or during lead-in or lead-out). This contact should be connected between THC_EN1 and THC_EN2.
PLASMA UNIT:
The plasma unit must be able to be started from external contact. This contact is between PLASMA_ON1 and PLASMA_ON2. As well the plasma unit must have an output, which signalize that the arc is on. This is usually done by a current relay inside the plasma unit, which close the contact between ARC_ON_RLY1 and ARC_ON_RLY2. If this signal is not a dry contact or DC +24V, connect a coil of additional relay to this signal (coil rated same as value of this signal e.g.. AC 110V) and use contact of this relay to close ARC_ON_RLY1 and ARC_ON_RLY2 lines. Many of plasma units have already build in a voltage divider of the arc voltage. This is usually 25:1, 50:1 or 100:1. The voltage from this divider should be applied to ARC_VOLTAGE1 andARC_VOLTAGE2. A twisted pare screened cable should be used and screen should be terminated only on one end. If the plasma unit does not have suitable voltage divider installed, please see section Selection of voltage divider for arc voltage. This divider should be fitted inside, or very close to, the plasma unit to decrease the possibility of radiation of noise from arc current.
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
4
CUTTING TORCH MOVEMENT ASSEMBLY:
The up and down movement of the torch must be motorized and driven by standard permanent magnet DC 24V motor. The limit switches for upper and lower limit should be normally closed and the contact should be bridged with diode that allows driving only to the opposite direction of the position of the limit. If initial height sensing is used, one or more normally open NPN type proximity switches should be used together with solenoid valve for air, which activates the spring, returned air cylinder for lowering the proxy switches to the height of the tip. The proximity switches can be substituted with mechanical switches with extended actuators and air cylinder together with solenoid valve can be substituted with electromechanical solenoid. The electromechanical solenoid should lower the actuators of the switches below the tip of torch, and when the actuator tough the plate solenoid should retract the switches above the tip of torch.
Mode selection switches:
In the second example (Fig.3.), connection to switches is simplified by using the R952 PCB. This PCB is also available from Rutex. See appendix B for description of this PCB. When installing this PCB, four switches (PLASMA START, PLASMA STOP, AUTO and THC) are fitted on the front panel and R952 PCB is directly soldered onto these switches. The up/down switch and the potentiometer for arc voltage are connected via screw-in terminals. The R952 and R953A PCB are connected with 16 ways ribbon cable. The first example (Fig. 2.) is hardwired version of R953A PCB.
Test circuit:
The Fig. 4. shows a bench test circuit of R953A board. This setup should be used before the first installation or when testing a different type of motor etc.
MO
T11
MO
T22
+24V
3
+PR
OX
Y5
+24_
AIR
6
+PLA
SMA
8
PLA
SMA
_ON
19
PLA
SMA
_ON
210
0V4
NPN
_PR
XY
7
THC
_EN
11
AR
C_V
OLT
AG
E112
AR
C_V
OLT
AG
E214
0V13
+UP1 +DN2 +THC3 REF4 +AUTO5 +AUTO6 +PLASMA7 +PLASMA8 THC_EN9 THC_EN10 0V11 0V12 +24V13 +24V14
CONNECTED TO INTERNAL CIRCUIT
RELAY OUTPUT 5A CONTACT
J2
J1
953-000
A
-
+
UP/DOWN DC MOTOR
PROXY_SW
AIR_ON
PROXY_ON
PLASMA
AUTO
THC
UP/DOWN
PLASMA_ON
+24+24
+24
0
10K10K
5V1/0.4W
2K2
0
+24
Fig. 4.
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
5
Selection of voltage divider for plasma arc.
The function of voltage divider is to divide the arc voltage in ratio that the output voltage from the divider does not exceed 5V. When THC operates correctly and certain voltage (REF J2 pin 4) is preset, the height of the torch is adjusted so that reference voltage (J2 pin 4) is equal to divided voltage from arc.
For example a 50:1 divider is used and required arc voltage is 125 volts. The reference voltage must be preset to 125 / 50 = 2.050 volts.
When using R953A PCB, which has 5V reference diode on board, with standard 10-turn multi turn potentiometer with 15 turns dial a voltage can be directly read from dial of this pot. The low side of this pot must be adjusted to 1 volt, high side to 3 volts and dial set from 50 to 150. With 50:1 divider, the preset voltage 2.050 will be read on dial as 125 +/- tolerances.
When selecting values of resistors for voltage divider an input impedance of 20-kilo ohms on ARC VOLTAGE inputs (across pin 12 and 14 of J1) should be taken in account in case of use high value resistors. The output of the divider should be bypassed by the capacitor (in ten or hundreds of nanofarads) to attenuate high frequency from arc and protected by a high-speed low voltage transient suppresser (such General Instrument SA5.0, SGS-Thomson BZW03P5V8, AVX-Kyocera VA100005A150).
A standard 50 : 1 divider is also available from Rutex (p/n R983).
Installation and adjustment.
During the initial installation the arc voltage should be supplemented with a low current variable DC supply 0-300V (or range of expected arc voltage). Plus of this supply should be connected to ground, negative to input of voltage divider (not directly to R953A board!!!). Correct polarity of connection of voltage divider should be verified by an error LED located on the R953A. If the LED lit up, when the power is on and the arc voltage is applied, swap wires between pin 12 and 14 of J1.
They are only 2 pots for adjustment. The SPEED pot should be set while toggling the UP/DOWN switch and adjusting up & down speed of torch lifter for required speed. For most of the application this can be set to about 20 V DC measured across the motor. The GAIN pot should be adjusted by simulating normal cut by changing the voltage from DC supply connected to the voltage divider. The GAIN pot should be adjusted to maximum available gain just before the point when the correction starts overshooting.
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
6
APPENDIX A
Connector J1 (14 pin KLIPPON connector)
pin #
Name Description Notes
1 MOT1 output for DC motor 24V PWM output 20-30kHz
2 MOT2 output for DC motor 24V PWM output 20-30kHz
3 +24V Supply DC+24V maximum 36V
4 0V Supply return 0V
5 +PROXY +24V output for supplying proxy switches
Output is activated when plasma input (J1 pin 8) or plasma switch (J2 pin 7&8) is activated and AUTO (J2 pin 5&6) is selected
6 +24V_AIR +24V output for supplying mechanisms for lowering switches for initial height sensing
Output is activated after plasma input (J1 pin 8) or plasma switch (J2 pin 7&8) is activated and AUTO is selected, until NPN_PROXY (J1 pin 7) is activated.
7 NPN_PROXY input - active, when switched to 0V
Output from NPN proxy switches or mechanical switches activated when torch is lowered to initial height.
8 +PLASMA Input - +24V active Control from CNC to start the plasma. Same as J2 pin 7&8.
9 PLASMA_ON1 Relay output Connected to Plasma unit; plasma start
10 PLASMA_ON2 Relay output Connected to Plasma unit; plasma start
11 THC_EN Input - +24V active Enables function of height sensing. This input must be interlock with the ARC ON RELAY from plasma unit and CORNER SLOW DOWN output from CNC controller. Directly linked to J2 pin 9&10
12 ARC_VOLTAGE1 Analog input from voltage divider (+V)
Differential input in range -5 to +5 V
13 0V Screen of arc voltage cable
Screen of the cable should be grounded only on this end
14 ARC_VOLTAGE2 Analog input from voltage divider (-V)
Differential input in range -5 to +5 V
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
7
Connector J2 (14 pin IDC connector*)
pin # Name Description Notes
1 +UP input 24V activates movement UP of the motor
2 +DN input 24V activates movement down of the motor
3 +THC input 24V activates function of THC
4 REF analogue input preset of the arc voltage DC 0-5V
5&6 +AUTO input 24V enables automatic initial height sensing
7&8 +PLASMA input 24V when AUTO (J2 pin 5&6) not selected directly activates the plasma relay output (J1 pin 9 and 10); when AUTO (J2 pin 5&6) is selected activates the initial height sensing before activating the plasma relay output(J1 pin 9 and 10).
9&10 THC_EN supply for THC switch Directly linked to J1 pin 11.
11&
12
0V return of supply same as J1 pin 4 & 13
13&
14
+24V supply 24V same as J1 pin 3
* - for a upward compatibly a 16-pin header is used with pin # 15 & 16 removed
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
8
APPENDIX B
952-000 PCB
V11LM336-5
0V
K1
G5V0V
24
V15
1N4004
0V24
0V
S1
SW-MOM
S2
SW-MOM
S3
SW-LATCH
S4
SW-LATCH
0V 123
J43PIN
STOPSTART
AUTOTHC
ARC POT 3V
ARC POT 1VARC POT ADJ
123456789
1011121314
J3
IDC14
240V
123
J53PIN
R375KR38
5K
R39
3K3
24
24
R40470R
R41
470R
R42
470R
UP SWITCH
DN SWITCHCOMMON
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
9
LM336-5TCH_ON
1K
3K3
UP/DOWN
ARC_VOLTAGE2- 4 V ( eq. to 100 - 200 V arc)
MO
T11
MO
T22
+24V
3
+PR
OX
Y5
+24_
AIR
6
+PLA
SMA
8
PLA
SMA
_ON
19
PLA
SMA
_ON
210
0V4
NPN
_PR
XY
7
THC
_EN
11
AR
C_V
OLT
AG
E112
AR
C_V
OLT
AG
E214
0V13
+UP1 +DN2 +THC3 REF4 +AUTO5 +AUTO6 +PLASMA7 +PLASMA8 THC_EN9 THC_EN10 0V11 0V12 +24V13 +24V14
CONNECTED TO INTERNAL CIRCUIT
RELAY OUTPUT 5A CONTACT
J2
J1
953-000
ARC_VOLTAGE2SCREEN
ARC_VOLTAGE1
PLASMA_ON2PLASMA_ON1
ARC_ON_RLY2ARC_ON_RLY1
THC_EN1THC_EN2
ARC_ON-SENCE2ARC_ON-SENCE1
PLASMA_START2PLASMA_START1
+27
+27
0V
MAX 100
BURNY 2.5 RS
A
-
+
UP/DOWN DC MOTOR
LIMIT_1
LIMIT_2100V/3A
100V/3A
OXY CUL VALVE
CUTTING TORCH ASSEMBLY
0V
+27
1K
1K
1K
HL82 OXY ONLY ( NO PLASMA PROVISION)
CONNCETED TO SUPPLY CAPACITOR
MANUAL CUT SW
?
?
?
?
AC110V
DC24V
+27+27
DIODE
0
R953A (953-000) interfaced to the MAX100 plasma, Burny 2.5 controller and old type HL82 tracing head.
R953A [R953A.doc rev: 0807]
© 2001-2008 RUTEX, 8 Jean Ave, Berkeley Vale 2261, Australia, ph +61-2-43884798 (http://rutex.com)
10
MO
T11
MO
T22
+24V
3
+PR
OX
Y5
+24_
AIR
6
+PLA
SMA
8
PLA
SMA
_ON
19
PLA
SMA
_ON
210
0V4
NPN
_PR
XY
7
THC
_EN
11
AR
C_V
OLT
AG
E112
AR
C_V
OLT
AG
E214
0V13
+UP1 +DN2 +THC3 REF4 +AUTO5 +AUTO6 +PLASMA7 +PLASMA8 THC_EN9 THC_EN10 0V11 0V12 +24V13 +24V14
CONNECTED TO INTERNAL CIRCUIT
RELAY OUTPUT 5A CONTACT
J2
J1
ARC_VOLTAGE2SCREEN
ARC_VOLTAGE1
PLASMA_ON2PLASMA_ON1
ARC_ON_RLY2ARC_ON_RLY1
THC_EN1THC_EN2
ARC_ON-SENCE2ARC_ON-SENCE1
PLASMA_START2PLASMA_START1
+24
0V
CNC CONTROL
PLASMA UNIT 1
0V
MO
T11
MO
T22
+24V
3
+PR
OX
Y5
+24_
AIR
6
+PLA
SMA
8
PLA
SMA
_ON
19
PLA
SMA
_ON
210
0V4
NPN
_PR
XY
7
THC
_EN
11
AR
C_V
OLT
AG
E112
AR
C_V
OLT
AG
E214
0V13
+UP1 +DN2 +THC3 REF4 +AUTO5 +AUTO6 +PLASMA7 +PLASMA8 THC_EN9 THC_EN10 0V11 0V12 +24V13 +24V14
CONNECTED TO INTERNAL CIRCUIT
RELAY OUTPUT 5A CONTACT
J2
J1
ARC_VOLTAGE2SCREEN
ARC_VOLTAGE1
PLASMA_ON2PLASMA_ON1
ARC_ON_RLY2ARC_ON_RLY1
+24 PLASMA UNIT 2
0V
+24
PLASMA 1 PLASMA 2
Two R953A (953-000) interfaced to one CNC and two plasma units