    02MiCOM Px20, Px30, Px40Protection Relays

    KEY FEATURES

    TheMiCOMrangeofrelaysfullstherequirementsat

    allvoltagelevelsfromLVtoEHVforIndustrial,

    DistributionandTransmissionSystems.

    COMMON FEATURES

    1A/5AdualratedCTs

    EventandDisturbanceRecording

    Variouscasingandmountingoptions

    RelayshaverearRS485portwithchoiceof

    protocolsandfrontRS232forlocalsetting

    Anumberofauxiliarysupplyanddigitalinput

    voltageoptions

    20SeriesRelays(Px2x)Itwillfullthebasicrequirementsofindustrial,

    transmissionanddistributionsystemsproviding

    simplicityandeaseofapplicationinawiderange

    ofinstallations.

    Scalablesolutionswheretypeandquantityofprotectionfeaturesismodeldependent

    Flexiblelogicequationsavailableonmostmodels

    Compacthardwareoptionsforeasyinstallation

    Commonfunctionsthroughouttherange

    Multi-languageHMI

    AdvancedprotectionfunctionsonPhase2hardware

    30SeriesRelays(Px3x)

    Designedtomeettherigorousrequirementsof

    MV,HVandEHVsystemswithparticularfocuson

    feederandtransformerprotectionandcontrol.

    ProtectionwithBaylevelcontroloptionstofacilitatefeedermanagement

    Input/Outputquantityselectablebasedonrequirements

    AnumberofRearPorthardwareoptionsavailablewithawiderangeofProtocolsselectableviasoftware

    Protectionfunctionsavailableforunearthed/petersencoilearthedsystems

    Surfaceandushmounted(incudingdetachableHMIoption)aswellascompactcasemodelsavailableintherange

    FullProgrammableSchemeLogicandFunctionkeys

    40SeriesRelays(Px4x)

    Itwillfulltheprotectionrequirementsforawide

    marketofMV,HV,EHVandindustrialsystems

    andoffersawiderangeofprotectionfunctions. FullProgrammableSchemelogicavailable

    withGraphicCongurationToolforeasysetting

    ScalableInput/Outputhardwaredependingon

    requirements

    OperatingvoltageselectableviaSoftwarefor

    Optoinputs

    Hardwareaccessoriesavailableforeasy

    mountinginracksorpanels.

    APPLICATIONS

    Px2xSeries

    Theintegratedfunctionsreectthedifferent

    requirementsinsystemprotection.Thepreferred

    applicationsareasfollows:

    P12x:UniversalOvercurrentprotectionfor

    mainorback-upprotectiononMVandHV

    systems

    P22x:MotorProtectionSeriesforLVandMV

    systems

    P52x:LineDifferentialprotectionforMVand

    HVsystemswithmultiplecommunication

    options

    P821:DedicatedBreakerFailureProtection

    suitableforEHV,HVandMVsystems

    P92x:Voltageandfrequencyprotection

    suitableforgenerators,motorsandfeeders

    Px3xSeries

    30Seriesprotectiondevicesprovideawide

    rangeofprotectionandcontrolfunctions

    meetingstringentmarketsegments.Therange

    isespeciallysuitableforpetersencoilearthing

    requirements.Thepreferredapplicationsare:

    P13x:Feedermanagementrelaysandone

    boxsolutionforMVandHVsystems(including

    railwayfeeder)

    P43x:DistanceprotectionforMV,HVandEHV

    systemsandrailcatenaryrequirements

    P53x:LinedifferentialprotectionforMVand

    HVsystems

    P63x:Differentialprotectionfortransformers,

    generatorsandmotors(includingrailway

    transformers).

  • 7/27/2019 Range_1827en.pdf

    3/12

    03MiCOM Px20, Px30, Px40Protection Relays

    Px4xSeries

    40Seriesprotectiondevicesprovideawiderange

    ofprotectionandcontrolfunctionsandmeetsthe

    requirementsofawidemarketsegment.Thepreferredapplicationsare:

    P14x:Feedermanagementrelaysuitablefor

    MVandHVsystems

    P24x:RotatingMachineManagementrelayfor

    applicationonawiderangeofsynchronous

    andinductionmachines

    P34x:Generatorprotectionforsmallto

    sophisticatedgeneratorsystemsand

    interconnectionprotection

    P44x:FullschemeDistanceprotectionrelays

    forMV,HVandEHVsystems.

    P54x:LineDifferentialprotectionrelaysfor

    HV/EHVsystemswithmultiplecommunication

    optionsaswellphasecomparisonprotection

    forusewithPLC.

    P74x:NumericalBusbarprotectionsuitablefor

    applicationonMV,HVandEHVbusbars

    P94x:Frequencyprotectionforloadshedding,

    loadrestorationandgeneratorabnormal

    detection

    CONTROL

    Programmableschemelogic

    Simplelogicequationsaswellasblocklogicis

    availableinanumberof20seriesrelays,

    seegure1.

    Powerfulgraphicallogicavailableinthe30and

    40seriesrelaysallowstheusertocustomizethe

    protectionandcontrolfunctionsoftherelay.Itis

    alsousedtoprogramthefunctionalityoftheopto-

    isolatedinputs,relayoutputs,LEDand

    useralarms.

    TheProgrammableSchemeLogiccanbeusedto

    implementadditionalsupervisionfeatures,such

    astripcircuitsupervisionorimplementcomplex

    logicsuchasfrequencyrestorationschemes.

    Schemeshavebeendevelopedcapableof

    supervisingthetripcoilandcircuitwiththecircuit

    breakeropenorclosed.

    ThePx40gatelogicincludesOR,AND,NOTand

    majoritygatefunctions,withtheabilitytoinvert

    theinputsandoutputs,andprovidefeedback.A

    numberofgeneralpurposelogictimersarealso

    availableaswellasthosetimersusedtocondition

    therelaycontacts.Thesystemisoptimized(event

    driven)toensurethattheprotectionoutputs

    arenotdelayedbythePSLoperation.

    TheProgrammableSchemeLogiciscongured

    usingthegraphicalMiCOMS1PCsoftware,as

    showninFigure2

    ThePx30logiccanbecreatedusingBoolean

    Figure3,ProgrammablelogicforPx30

    Figure2,ProgrammablelogicforPx40

    Figure1,FlexiblelogicforPx20

    Equationsoragraphicalinterfaceasshownin

    gure3.

    IndependentProtectionSettingsGroups

    Uptotwosettinggroupsaresupportedinthe20

    Serieswhereasthe30and40seriescanofferup

    tofourindependentsettinggroups.Thesecan

    beactivatedlocally,remotelyorviaadedicated

    inputandareusedtoallowfordifferentsystem

    operatingconditionsandwhereadaptiverelaying

    isapplied.

  • 7/27/2019 Range_1827en.pdf

    4/12

    04MiCOM Px20, Px30, Px40Protection Relays

    Measurement&PostFaultAnalysis

    TheMiCOMRangeofrelaysarecapableof

    measuringandstoringawiderangeofsystem

    quantitiessuchasCurrent,Voltage,Frequency,

    Poweretc.dependingontherelayfunctionality.

    Allevent,faultanddisturbancerecordsaretimetaggedtoaresolutionof1msusingtheinternal

    realtimeclockandarestoredinnon-volatile

    memory.Asupervisedlithiumbatteryensuresthat

    therealtimeclockandrecordsaremaintained

    duringauxiliarysupplyinterruptions.

    WhererelaysarecommunicatingtoaSCADA

    system,theprotocolstelegramscanbeusedfor

    externaltimesynchronizationoralternativelyan

    optionalIRIG-Bportisavailableforaccuratetime

    synchronizationonallPx30andPx40MiCOM

    relays.Somerelayscanalsouseanoptoinputto

    synchronizetherelaysclock.

    PowerSystemMeasurement

    Acomprehensivesetofmeasurementvalues

    includinginstantaneousandderivedvaluesare

    availableontherelays.

    Thesemeasuredvaluescanbedisplayedon

    thefrontLCDdisplayortransferredlocallyor

    remotelyaspertheuserrequirements.

    POST FAULT ANALYSIS

    Eventrecords

    Thesearegeneratedforstatuschangestologicinputsandoutputs,modicationstooneormore

    settingparametersandalarmsignals.Allevents

    aretime-taggedandstoredinchronological

    orderinacyclicmemorywheretheoldestrecord

    isoverwrittenoncetherelaysmaximumevent

    countisexceeded.Thesearereadilyavailable

    forviewingontheLCD,orextractionviathe

    communicationports.

    Figure4,OscillographyanalysisusingMiCOMS1Softwarefor

    Optimumresults

    Figure5,Atypicalsubstationcontrolsystem

    Faultrecords

    Atleast5recordsaresupportedonallrelays

    andforeveryfault,thefollowinginformationis

    capturedintherelayrecords

    Afaultnumber

    Thedateandtime

    Theactivesettinggroup

    Thefunctionthatissuedthetrip

    Themagnitudeofthecurrent/voltagethatgaverisetothetripcommand

    Disturbancerecords

    Theinternaldisturbancerecorderwillrecord

    thesampledvaluesofallanaloginputvariables

    suchasphasecurrentsandvoltagesetc.where

    applicableduringafault.Oscillographicanalysis

    canbeperformedusingMICOMS1whichwill

    providethemeanstoquicklyanalyseanaloganddigitalsignalsonthesametime-scale

    forconvenience.Disturbancerecordscanbe

    extractedfromtherelayviathecommunication

    portsandsavedintheCOMTRADEformat.

    RELAY COMMUNICATIONS

    Asstandard,afrontcommunicationportis

    availableforlocalaccesstotherelay.Anauxiliary

    rearcommunicationportisavailableasanoption

    onrelaysprovidinganengineeringportforeasy

    accesstosettings,recordsandmeasurementsfor

    protectionengineers.AmainrearcommunicationsportisalsoavailableforinterfacetoaSCADA

    system.Anumberofprotocolsareavailableas

    anoptionforthispurpose.

    (Seecorteccodeforeachrelay)

    SCADA

    Interface

    SCADAInterface

    MasterClock(GPS)

    IRIG-Bport

    Modem(remoteaccess)

    EAI232

    (localaccess)

  • 7/27/2019 Range_1827en.pdf

    5/12

  • 7/27/2019 Range_1827en.pdf

    6/12

    06MiCOM Px20, Px30, Px40Protection Relays

    SELF MONITORING

    ComprehensiveSelfmonitoringprocedureswithin

    thedeviceensurethatinternalhardwareand

    softwareerrorsaredetectedthusensuringahigh

    degreeofreliability.Automatictestsareperformed

    duringstart-upandacyclicselfmonitoringtestsareperformedduringoperation.Anydeviations

    arestoredinnon-volatilememoryandtheresult

    ofthefaultdiagnosisdetermineswhethera

    blockingofthedevicewilloccurorwhetheran

    alarmisonlyissued.

    MECHANICAL DESCRIPTION

    Cases

    TheMiCOMseriesrelaysarehousedina

    speciallydesignedcaseprovidingahighdensity

    offunctionalitywithintheproduct.Communication

    portsandmodel/serialnumberinformationis

    concealedbyupperandlowercovers.

    Physicalprotectionofthefrontpaneluser

    interfaceandpreventionofcasualaccessis

    providedbyanoptionaltransparentfrontcover,

    whichcanbettedoromittedaccordingtochoice,

    sincethefrontpanelhasbeendesignedtoIP52

    protectionagainstdustandwater

    Thecasesaresuitableforeitherrackorpanel

    mountingasshowninFig.9.

    Anoptionforsurfacemountingisalsosupported

    onthe30seriesrangeandacompactcaseoption

    isavailableonafew20and30seriesrelaysfor

    installationswithspacelimitations.

    Takingintoaccountthedifferingcasewidths

    -relayscanbecombinedwithorwithouttheuseofstandardblankingplatestoformacomplete

    19mounting.Thissavesspaceandallowsfora

    neatinstallation.

    Wiring

    Externalconnectionsaremadeviaringtype

    terminalonallMiCOMrelayexceptonthe

    compactcase.Thesetakepintypeterminals

    alongwiththe30seriesrelaysasanoption.

    P439

    C

    G

    G

    TRIP

    ALARM

    HEALTHY

    EDIT MODE

    X6

    OUT OF SERVICE

    F1

    F2

    F3

    F4

    GC

    B

    E

    A

    A

    A

    A(including

    brackets)

    C

    D

    B

    F

    B

    D

    GE

    FRONT

    VIEW

    SIDE

    VIEW

    103240

    (inc. wiring)

    270

    (inc. wiring)157.5

    177

    155139,8223

    166,4249,6

    155.2156

    213.4

    260.2253.6 177.5

    184.5

    434.8

    227.9

    481.6

    260.2

    481.6

    257.1 177.5

    206

    240

    (inc. wiring)

    309.6 270

    (inc. wiring)177

    413.2

    483

    157.5 max

    294.4

    175.6

    253310

    88.5 162.5 294.4

    Note: Maximum sizes for guidance only, for specific product information please check the relevant product

    documentation. (All dimensions in mm)

    In addition 24TE case variant available for P1321)

    1)

    A

    Typical

    case dimensions TableB C D E F G

    20TE

    Px20

    30TE

    40TE

    40TE rack

    84TE

    84TE rack

    40TEsurface

    Px30

    84TEsurface

    40TE

    60TE

    80TEPx40

    80TE rack

    compact

    Px20C/

    Px30C

    Compact

    incl . brack.

    Figure9,Typicalcasedimensions

  • 7/27/2019 Range_1827en.pdf

    7/12

    07MiCOM Px20, Px30, Px40Protection Relays

    TECHNICAL DATA

    Powersupplies

    Awiderangeofpowersupplyoptionsare

    availableattheorderingstage.

    DigitalInputs

    Awiderangeofoptoinputvoltagesaresupported

    throughouttherange

    Nominal Voltage

    Vnom.

    Operate Range (V)

    DC AC

    Px20

    Ph 2

    24-60Vdc 19.2-76Vdc -

    48-250Vdc

    48-240Vac38.4-300Vdc

    38.4-264

    Vac

    Px20

    Ph 1

    24-60DC 19.2-72 -

    48-150DC 38.4-180 -

    130-250DC

    100-250AC

    104-300DC

    -

    -

    80-275

    125-250DC

    100-250AC

    100-300DC

    -

    -

    80-275AC

    Px3024DC

    48-250DC

    19-29

    38-300

    -

    100-230

    Px40

    24-48DC 19-65 -

    48-125DC 37-150 24-110

    110-250 87-300 80-265

    Auxiliary Voltage Digital Operating range (V)

    Px20

    Ph 2

    24-250Vdc 19.2-300Vdc

    24-240Vac 19.2-264Vac

    Px20

    Ph 1

    24-60DC 15.2-60DC

    48-150DC 25.6-180DC

    130-250DC/

    100-250AC38.4-300DC/38.4-275AC

    125-250DC/

    100-250AC84-174DC

    48-150DC

    130-250DC

    25.6-180(ACimmune)

    38.4-300(ACimmune)

    Px30

    Thresholds

    StandardVariant

    >18(Uaux.24-250VDC)

    FurtherOptions

    >73V(67%ofUaux.110VDC)

    >90V(60-70%ofUaux.125/150VDC)

    >146V(67%ofUaux.220VDC)

    >155V(60-70%ofUaux.220/250VDC)

    Px40

    Vmin/Vmaxthresholds

    24/27,30/34,48/54,110/125and220/250

    (softwareselectable)

    General Series Data Px20 Px20C Px30 Px30C Px40

    Frequency50/60Hz X X X X X

    Dualrated1A/5A X X X X X

    CTthermalratings

    continuous:4Inom

    for10s:30Inom

    for1s:100Inom

    X X X X X

    OptoInputs max8 max7 max.34 max2 max.24

    OutputContacts max9. max8 max46 max8 max.46

    Carry:continuous 5A 5A 5A 5A 10A

    Makeandcarry 30Afor3s 30Afor3s 30Afor0.5s 30Afor0.5s 30Afor3sLEDIndication

    (freelyprogrammable)8(4) 8(4)

    23/18(forproductswith

    textdisplay)17(12) 12(8)

    FunctionKeys/HotKeys No 46(forproductswithtext

    display)4

    10functions/2hotkeys

    (availableonsomemodels)

    SettingsGroups 1/2 2 4 4 4(2)

    FaultRecords 5/25* 5 8 8 5

    EventRecords 75/250* 75 200 100 250-512

    DisturbanceRecords 5(15smax) 8(24smax) 8(16.4smax) 8(16.4smax) 75smax.

    Programmablelogic

    Flexiblelogic

    (availableon

    somemodels)

    SimpleANDlogic Fullyprogrammable Fullyprogrammable Fullyprogrammable

    IRIGB No No Option Option Option

    LCDDisplay Alphanumeric AlphanumericAlphanumeric/Graphical

    (somemodelsonly)Alphanumeric Alphanumeric

    FrontPort(RS232)Yes(most

    models)Yes Yes Yes Yes

    RearPort Yes Yes Yes,2ndrearportoptionYes,2ndrearport

    optionYes,2ndrearportoption

    Courier

    EIA(RS)485

    (availableon

    somemodels)

    No EIA(RS)485orber EIA(RS)485orberK-Bus/EIA(RS)485orber

    (somemodelsonly)

    Modbus EIA(RS)485EIA(RS)485/Glass

    berEIA( RS) 485or ber EIA(RS)485orber

    EIA(RS)485orber(some

    modelsonly)

    IEC60870-5-103 EIA(RS)485EIA(RS)485/Glass

    berEIA( RS) 485or ber EIA(RS)485orber

    EIA(RS)485orber(some

    modelsonly)

    IEC60870-5-101 No No EIA(RS)485orber EIA(RS)485orber No

    DNP3.0

    EIA(RS)485

    (availableon

    somemodelsonly)

    No EIA(RS)485orber EIA(RS)485orberEIA(RS)485orber(some

    modelsonly)

    IEC61850 No No Availableonsomemodels No Availableonsomemodels

    OneBoxBayControl

    withMimicNo No

    Yes(availableonsome

    models)No No

    Terminals Ring Pin PinorRingType Pin Ring

    *AvailableonMiCOMphase2forP120,P122,P123,P125,P126,andP127

  • 7/27/2019 Range_1827en.pdf

    8/12

    08MiCOM Px20, Px30, Px40Protection Relays

    1 4 4 4 4 4 4 1 4 4 4 4 2 4 5 5 5

    - - - - - - - 1 1 3 3 4/5 1 4/5 3 3 3/4

    5

    42

    5

    3/4

    2 2 3 7 5 - 5 4 7 7 2 40 16 40 8 16 32

    5 5 7 8 9 2 7 7 9 9 8 32 24 32 7 15 30

    - - - - - 1 1 - - - - - - - - -

    - - - - - X X - - - -

    -

    - - - - - -

    16

    15

    -

    -

    32

    32

    -

    -

    - - -

    - - -

    - - -

    - - -

    - - -

    - - -

    X - -

    - X X

    - X X

    - - -

    - - -

    - - -

    - - - - - -

    - - - - - -

    X - - - - -

    - - - - - -

    - - - - - -

    - - - - - -

    - - - - X -

    X X X X - X

    X X X X X X

    - - - - - -

    - - - - X X

    - - - - - - -

    - - 10 1 10

    - - 1/2 1/2 1/2

    - X X - X

    - - X - X

    - - - - X

    - - X - X

    - - - X -

    X X X - X

    X X X X X

    X X X X X

    X X X X X

    - - - -

    - - -

    - - -

    X X X

    - - -

    - - -

    X X X

    - - -

    X X X

    X X X

    X X X

    X X X

    X X X

    -

    -

    -

    X

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    X

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    - - - - - - - - - - X

    - - - - - - X X X X X

    - - -

    -

    - - - - - - -

    -X X X - - X X X -

    - - - - - - - - - -

    - X X X - X - X X

    X

    X X

    - X X X X X - X X X X

    - X X X - - X X X X

    - - - - - - - - X X X

    - - - - - - X X X X X

    - - - - - - - - - X X

    - - - - - - - - XX X

    - - - - - - - - - X X

    - - - - - - - - - X X

    - - - - - - - - - - -

    X X X X X X X X X X X

    - - - - - - - - XX X

    - X X X - X - X X X X

    - - - - - - - - - X X

    - - - - - - - - - X X

    - - - X - X - X X X X

    - - - - - - - - - - X

    - X X X - X - X X - -

    - X X X

    X X

    - X - X X

    X

    X X

    - - - - - - X X

    - - - - - - XX X X

    - X X X - X - X X -

    - X X X - X - X X - X

    - - - - - - - - - XX

    - - - - - - - - - X X

    - - - - - - - - - X X

    - X - - -

    - X X X X

    X XXX X X

    - - X X X

    - - X X X

    - X X X X

    X X X X X

    - X X X X

    X X X X X

    - X X X X

    -

    -

    -

    XX X X

    X X X X X

    - X X X X

    - X - - -

    - X - - -

    X X X X X

    - X - - -

    X X X X X

    - X - - -

    - X - - -

    - X - X X

    - X - - X

    - - X X X

    - X X X X

    - X - - -

    X - X X X X

    - XXX X X

    - X X X X

    X X - - -

    - X - - -

    - X - - -

    -

    -

    X

    -

    -

    X

    -

    X

    X

    X

    X

    X

    -

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    -

    -

    X

    -

    X

    -

    -

    X

    -

    X

    X

    -

    X

    X

    X

    -

    -

    -

    -

    -

    X

    -

    -

    X

    -

    X

    X

    X

    X

    X

    -

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    -

    -

    X

    -

    X

    -

    -

    X

    X

    X

    -- - - - - - - - XX X - X X X X X X

    -- - - - - - - - - X X - X X X X X X

    X

    -

    X

    X

    X

    -

    -

    -

    CT Inputs

    VT inputs

    Opto Inputs ( max)1

    Output Contacts (max)1

    Output for Striker Triggering

    Magnetic Flags

    RTDs (max. option)

    Analogue I/O (max. option)

    Function Keys/Hotkeys

    Bay Control & Monitoring

    - with Mimic

    Interlocking Logic

    1 Phase or Earth overcurrent

    3 Phase overcurrent

    Ground fault

    Phase directional

    Ground Fault directional

    Sensitive directional earthfault

    Transient Ground Fault

    directional

    Wattmetric earthfault

    Neutral admittance

    Restricted earthfault

    Voltage controlled overcurrent

    Negative sequence overcurrent

    Thermal overload

    Undercurrent

    Over/Under voltage

    Residual over voltage

    Negative sequence overvoltage

    Over/Under frequency

    Rate of change of frequency

    Incomplete sequence relay

    Master sequence device

    Lock-out

    Directional Power

    Circuit breaker failure

    Motor

    Startup Monitoring

    Autoreclose

    Check synchronising

    Broken conductor

    Cold load pick-up

    Inrush blocking

    Switch on to fault

    Circuit breaker monitoring

    Trip Circuit Supervision

    Limit value monitoring

    Protective Signalling

    InterMicom

    Protection

    Device P120 P121 P122 P122C P123

    P124

    SelfPower

    P124

    DualPower

    P125 P126 P127 P130C P132P138

    RailP139 P141 P142 P143 P144 P145

    50/51P/N

    50/51P

    50/51N

    67P

    67N

    67N

    67N

    67W

    YN

    64

    51V

    46

    49

    37

    27/59

    59N

    47

    81O/U

    87R

    48

    34

    86

    32

    50BF

    49LR

    66

    79

    25

    46BC

    Voltage transformer supervision VTS

    Current transformer superv ision CTS

    SOTF

    TCS

    85

    MiCOM Series Data

    OVERCURRENT AND FEEDER MANAGEMENT RELAYS

    Pleasenotethatsomerelaysmayhavealimitonmax.I/Owhenusedasacombination.

    3V0measuredinputandallowsveeconnectedVTs.

  • 7/27/2019 Range_1827en.pdf

    9/12

    09MiCOM Px20, Px30, Px40Protection Relays

    Device P220 P225 P226C P241 P242 P243 P341 P342

    CT Inputs

    VT inputs

    Opto Inputs (max)1

    Output Contacts (max)1

    RTDs/thermistors (option)

    Analogue I/O (option)

    Function Keys/Hotkeys

    Interlocking Logic

    Motor Protection

    Short circuit 50/51

    Motor Differential 87M

    Locked Rotor 50S/51LR/51S

    Reverse Power 32R

    Reacceleration 27LV

    Startup Monitoring/Excessive long start 66/48/51

    Negative sequence overvoltage 47

    Out of Step 55

    Loss of load 37

    Undercurrent 37P/37N

    Unbalance/Lock-out 30/46/86

    Speed switch inputs

    Anti Backspin

    14

    100% Stator Earth Fault (Low Freq. Injection) 64S

    Generator Protection

    Generator Differential 87G

    Interturn/split phase 50DT

    Underimpedance 21

    Pole Slipping 78

    Directional Power 32L/O/R

    Loss of Field 40Restricted earthfault 64

    100% Stator earth fault (3rd harmonic) 27TN

    Overfluxing 24

    Unintentional energisation at standstill 50/27

    Voltage dependent O/C

    Rotor Earth Fault

    51V

    64R

    Ancillary Functions

    Phase overcurrent 50/51P

    Phase directional 67P

    Ground fault 50N/51N

    Ground Fault directional 67N

    Negative sequence thermal 46T

    Turbine abnormal frequency 81AB

    Negative sequence overvoltage 47

    Sensitive directional earthfault 67N

    Wattmetric earthfault 64N/32N

    Negative sequence overcurrent 460C

    Thermal overload 38/49

    Under/Over voltage 27/59

    Residual over voltage 59N

    Under frequency 81U

    Over frequency 81O

    Voltage vector shift dVq

    Rate of change of frequency 81R

    Circuit breaker failure 50BF

    Circuit breaker monitoring

    Trip Circuit Supervision TCS

    P343 P344 P345

    Protection

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    -

    X

    X

    X

    X

    X

    X

    X

    X

    -

    -

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    -

    X

    X

    X

    X

    X

    X

    X

    X

    -

    -

    X

    X

    X

    8

    4

    32

    32

    10/0

    4/4

    X

    X

    8

    5

    32

    32

    10/0

    4/4

    X

    X

    4 4 4 4 4 7 4 5

    - 1 1 3 3 3 4 4

    5 6 7 8 16 16 16 24

    6 6 8 7 16 16 15 24

    6/0 or 4/2 10/3 - 10/0 10/0 10/0 - 10/0

    0/1 0/2 - 4/4 4/4 4/4 4/4 4/4

    - - X X XXX X

    - - - X X X X X

    X

    -

    X

    -

    X

    X

    -

    -

    X

    X

    X

    X

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    X

    -

    X

    -

    -

    -

    -

    -

    -

    -

    X

    -

    -

    -

    -

    -

    -

    -

    X

    X X X X X

    - - - - X - -

    X X X X X - -

    - - X X X

    X X X

    - -

    X X - -

    X X X X X - -

    - - X X X - -

    - - X X X - -

    X X X X X - -

    X X X X X - -

    X X X X X - -

    - -

    - -

    - -

    - -

    - -

    - -

    - -

    - -

    - -

    - -

    X X X X X

    X X X X X

    - - - - - - -

    - - - - - - -

    - - - - - - X

    - - - - - - -

    - - - - - X X

    - - - XX XX

    - - - - - X X

    - - - - - - -

    - - - - - - X

    - - - - - - X

    - - - - - - X

    X X X X X X X

    X- - - - - X

    X X X X X X X

    - - - - - X

    - - - - - - X X X

    - - - - - - X X X

    - - - - - XX X X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X XX X

    X

    X

    X

    -

    X

    X

    X

    X

    X

    X

    X

    X

    -

    -

    X

    X

    X

    9

    6

    32

    32

    10/0

    4/4

    X

    X

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    X

    X

    X

    -

    - - X X X - X

    - - X X X X X

    X X X X X - X

    X X X X X X X

    X X X X X X X

    - - X X X X X

    - - X X X X X

    - - - - - X X

    - - - - - X -

    - - - - - X -

    X X X X X X X

    X X X X X X X

    X X X X X X X X

    MOTOR AND GENERATOR MANAGEMENT RELAYS

    Pleasenotethatsomerelaysmayhavealimitonmax.I/Owhenusedasacombination.

  • 7/27/2019 Range_1827en.pdf

    10/12

    MiCOM Px20, Px30, Px40Protection Relays 10

    Broken Conductor 46BC

    Stub Bus Protection 50ST

    Voltage/Current transformer

    supervisionVTS/CTS

    Capacitive voltage transformer

    supervisionCVTS

    P444 P445Device P430C P432 P433 P435 P436

    Rail

    P437 P438

    Rail

    P439 P441 P442 P443

    CT Inputs

    VT inputsOpto Inputs(max)1

    Output Contacts(max)1

    RTDs (option)

    Analogue I/O (option)

    Function Key/Hotkeys

    Bay Control & Monitoring with Mimic

    Interlocking Logic

    Distance Protection

    Distance 21/21N

    3 poleAutoreclose 791/3 pole

    Power Swing Blocking 78

    Out of step tripping 68

    Check synchronising 25

    Directional Power 32

    Switch on-to fault 50/27

    Mutual Compensation

    Rail Catenary Protection HZ

    PMU

    Defrost Protection

    Train startups

    Phasor Measurement

    Phase overcurrent 50/51P

    Phase directional 67P

    Ground fault 50/51N

    Ground Fault directional 67N

    Transient Ground Fault directional 67N

    Neutral admittance YN

    Delta directional comparison

    Wattmetric earthfault 67W

    Negative sequence overcurrent 46

    Directional negative sequence 46/67

    Thermal overload 49

    Under/Over voltage 27/59

    Residual over voltage 59N

    Over/Under frequency 81U

    Rate of change of frequency 81R

    Circuit breaker failure 50BF

    Channel Aided Scheme Logic 85Trip Circuit Supervision TCS

    InterMicom

    Protection

    -

    X

    X

    -

    4

    3

    2

    8

    -

    30

    -

    X X X X

    -

    X

    X

    X

    -

    X

    -

    X

    X

    -

    -

    -

    -

    X

    X

    X

    X

    - -

    -

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    -

    X

    X

    -

    4/5

    4/552

    38

    1

    1/2

    -

    X

    X

    X

    -

    X

    X

    XX

    X

    X

    X

    X

    -

    -

    -

    X

    X

    X

    X

    -

    -

    -

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    -

    X

    X

    X

    -

    4

    20

    1

    1/2

    -

    -

    X

    X-

    X

    X

    X

    X

    -

    -

    -

    -

    X

    X

    X

    X

    X

    -

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    -

    4

    4/54/5

    32

    46

    1

    1/2

    -

    -

    X

    -

    X

    X

    X

    XX

    X

    X

    -

    -

    -

    -

    X

    X

    X

    X

    X

    -

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    - X -

    X X -

    X X X

    - - -

    2 4/5 3

    1 4/5 2

    28 32 28

    46 46 46

    1 1 1

    1/2 1/2 1/2

    - -

    - - -

    - - -

    X X X

    - - -- X -

    - X -

    - X -

    - X -

    - -

    X X X

    - X -

    16 2/3 - 25/50/60

    - - X

    X - X

    X X X

    - X X

    - X -

    - X -

    - - -

    - - -

    - - -

    - - -

    - X -

    - X -

    X X X

    X X X

    - X -

    - X -

    - X -

    X X X

    - X -

    X X X

    XX -

    X X X X

    X X X X

    X X X X

    - X X - -

    X

    X

    X

    X

    4

    4

    24

    46

    -

    -

    X

    -

    X

    -X

    X

    -

    X

    -

    X

    X

    -

    -

    -

    X

    X

    X

    X

    -

    -

    -

    X

    X

    X

    -

    -

    -

    -

    X

    X

    X

    X

    4

    4

    24

    32

    -

    -

    X

    -

    -

    -

    X

    X

    -

    X

    -

    X

    -

    -

    -

    -

    X

    X

    X

    X

    -

    -

    -

    -

    X

    X

    X

    X

    X

    -

    -

    X

    X

    X

    X

    X

    X

    X

    4 4 4 4

    4/5 4 4 4

    40 8 16 24

    26 14 21 32

    1 - - -

    1/2 - - -

    - X X X

    X - - -

    - -- - -X

    X X X X

    X X - -

    - - X X

    X X X

    - - -

    X X X X

    X

    X

    X

    X - - -

    X X X X

    - X X X

    - - - -

    - - - -

    - - - -

    - - - - --- -

    ---

    --

    X X X X

    X X X X

    X X X X

    X X X X

    X - - -

    XX X X

    - - - X

    - -

    - -

    -

    XX X X - -

    X X X X

    X X X X

    X X X X

    X X X X

    X - - X

    X - - -

    X - - -

    X X X X

    X X X X

    X X X X

    X - X X

    di/dt,dv/dt,d/dt

    I/V

    DISTANCE RELAYS AND PHASOR MEASUREMENT UNIT

    Pleasenotethatsomerelaysmayhavealimitonmax.I/Owhenusedasacombination.

  • 7/27/2019 Range_1827en.pdf

    11/12

    MiCOM Px20, Px30, Px40Protection Relays 11

    LINE DIFFERENTIAL, TRANSFORMER AND BUSBAR PROTECTION RELAYS

    Pleasenotethatsomerelaysmayhavealimitonmax.I/Owhenusedasacombination.

    4 4 5 9 5 9 4 6 6 8 12 15 4 4 4

    - - - 4 3 4 3 - - - 1 1 1 - - -

    5 8 16 16 16 24 24

    8 7 14 14 14 32 32

    - - - - - - -

    - - - - - - -

    - X X X X X X

    - X X X X X X

    8 2 4 34 40 34 8

    8 8 14 22 30 22 8

    - - - 1/2 1/2 1/2 -

    - - - 1 1 1 -

    X X - - - - -

    X X - - - - -

    16 24

    8 21

    - -

    - -

    - -

    - -

    87P X

    X

    -

    X

    X

    X

    -

    X

    X

    X

    -

    X

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    X X X X X X X X X X X X X - X X

    - - X X X X - - - - - - - - -

    X X X X X X X

    - - X X X X -

    - - X X X X

    X X X X

    -

    - - X X X X -

    - - X X X X -

    - X X X X -

    - X - X

    X X X

    X X X

    - - -

    X X X X X - - - - - - - -

    - - - - - - - - - - - - - -

    X X X X X - - - - - - - - -

    X X X X X - - - - - - - -

    - - - - - - - - - - - - -

    - - - - - - - - - - - -

    - X XX X - - - - - - - - -

    X X - - - - - - - - - - -

    X X - - - - - - - - - - -

    X

    X

    X

    X

    X- - - - - - - - - - -

    X - X - - - - - - - - -

    - - - - -

    X -

    -

    X

    X -

    - -

    - - -

    -

    X X

    - - -

    X X X X X X - - - -

    - - - - - - X - - - - - - - -

    X - - - - - - - -

    - X X X X X - - -

    - 2 2 2 3 4 - - -

    - - 2 3 3 - - -

    - X X X X X - - -

    - - - X X X - - -

    - X X X X X - - -

    - - - X X X

    -

    -

    - - - - - -

    - - - - - -

    - - - - - -

    - - - - - -

    - - - - - -

    - - - - - -

    - - - - - -

    - - - - - - - -

    - - - - - - - - - - - - X - -

    - - - - - - - - - - - - - X X

    - - - - - - - - - - - X - -

    - - - - - - - - - - - - X - -

    - - - - - - - - - - - - X - -

    - - - - - - - - - - - - X X X

    - - - - - - - - - - - - - X X

    - - - - - - - - - - - X X X

    -

    -

    X X X X X X -

    - - - - - - - - -

    -

    X X X X X X X

    - - - - - - - -

    - - - - - - - -

    - - - - - -

    - - - - - -

    - - - - - - - - - -

    X - - X X X X X X -

    X X X X

    X

    X X X X X X -

    X - - - - - - - - - - - - -

    - - - - X X X -

    - -

    X X

    -

    - - -

    - - - -

    - -

    - -

    - -

    - -

    - -

    X

    - - - - -

    X X X X X X X X - -

    - - 3 pole3 pole 1/3

    pole

    1/3

    pole

    - - - - -

    - - - - - - X

    X X

    4

    3

    2

    8

    -

    -

    X

    X

    -

    X

    X

    X

    -

    X

    -

    X

    -

    X

    X

    X

    -

    X

    X

    -

    -

    -

    X

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    X

    X

    -

    -

    X

    X

    - X X X X X

    X X X X

    X X X X

    -

    - - - X X X

    - - - - - -

    X X - - -

    X X X X X

    CT Inputs

    VT inputs

    Opto Inputs(max) 1

    Output Contacts(max) 1

    Analogue I/O (opti

    RTDs (option)

    Function Keys/Hotkeys

    Interlocking Logic

    Protection

    Line Differential

    2 terminal

    2/3 terminal

    FO signalling

    Metallic signalling

    Transient Bias (CT saturation)

    SDH/Sonet ne

    In Zone transformer

    2 harmonic restraint

    Vector Compensation

    2 breaker configuration

    Direct/Permissive Intertripping

    Phase Comparison

    PLC signalling

    Transformer Differential

    windings

    Restricted earth fault

    overfluxing/5 harmonic

    overexcitation

    2 harmonic restraint

    Busbar Protection

    Central unit up to 28

    feeders

    Peripheral units 8 zones

    regated differential

    8 zones

    Sensitive earth fault differential

    6 zones

    Check Zone 8 zones

    CT supervision

    CT Saturation Detection

    Fibre optic signalling

    Ancillary Functions

    Phase overcurrent

    se directional

    Ground fault

    Ground Fault directional

    Sensitive directional earthfault

    Wattmetric earth

    Distance Protection

    Power Swing Blocking

    Check Sync

    Negative sequence overcurrent

    Thermal overload

    Loss of load/Undercurrent

    Under/Over frequency

    Circuit breaker failure

    Autoreclose

    Over/Under voltage

    Trip Circuit Supervision

    CT supervision

    Device P521 P541P530C P542 P543 P544 P545 P546 P547 P630C P631 P632 P633 P634 P741 P742 P743

    4

    on)

    tworks

    -

    nd

    th

    nd

    -

    -

    Phase seg

    Pha

    fault

    81U/O

    50BF

    79

    27/59

    TCS

    87PC

    87P

    87G/

    64

    24

    87BB

    87P

    87N

    87CZ

    CTS

    50/51P

    67P

    50/51N

    67N

    CTS

    67N

    64W

    21

    78

    25

    46

    49

    37

  • 7/27/2019 Range_1827en.pdf

    12/12

    2010SchneiderElectric-Allrightsreserved

    Asstandards,specicationsanddesignschangefromtimetotime,pleaseaskforconrmation

    oftheinformationgiveninthispublication.

    Publishing:SchneiderElectricDesign:SchneiderElectricPrinting:

    This document has been printedon ecological paper

    Schneider Electric

    35,rueJosephMonier

    CS3032392506Rueil-MalmaisonCedex,FranceTel:+33(0)141297000

    RCSNanterre954503439Capitalsocial896313776www.schneider-electric.com

    MiCOM Px20, Px30, Px40Protection Relays 12

    4 - 6 - - - - -

    - 4 3 4 4 4 3 3

    5 48 16 2 5 5 16 32

    9 32 24 4 8 8 15 30

    X - - - - - - -

    X - - - - - - -

    X - - - - - - -

    X - - - - - - -

    - X - - - - - -

    - X - - - - - -

    - X - - - - - -

    - X - - - - - -

    - - X - - - - -

    - - X - - - - -

    - - X - - - - -

    - - X - - - - -

    - - - X X X X X

    - - - X X X X X

    - - - X X X - -

    - - - - X X - -

    - - - - X X X X

    - - - - - X X X

    - - - - - X X

    - - - - - - X X

    - - - - - - X X

    - - - - - - X X

    X X X - X X X X

    yes

    by

    logic

    Device P821 P842 P846 P921 P922 P923 P941 P943

    CT Inputs

    VT inputs

    Opto Inputs(max)

    Output Contacts(max)

    Protection

    Breaker Failure Protection 50BF

    2 Stage

    Pole Discrepancy

    Dead Zone Function

    Autoreclose 79

    Mesh Corner/Single Switch

    Check Sync 25

    Ferroresonance Suppression

    Open Line Detector DLO

    High Speed Breaker Fail 50BF

    Fast Hybrid Output contacts

    3 pole tripping

    Voltage and Frequency Protection

    Undervoltage 27

    Overvoltage 59

    Residual Overvoltage 59N

    Phase Sequence Voltage 47/27D

    Under/Over frequency 81U/O

    Rate of change of

    Frequency (df/dt+t)

    81R

    Frequency supervised Rate of change of Frequency

    (f+df/dt)

    81RF

    Frequency supervised average

    Rate of change of Frequency

    (f+f/t)

    81RAV

    Generator Abnormal Frequency 81AB

    Load Restoration logic

    Trip Circuit Supervision TCS

    VOLTAGE, FREQUENCY AND ANCILLARY PROTECTION RELAYS