raven seria 4000 5000925d
TRANSCRIPT
-
7/25/2019 Raven seria 4000 5000925D
1/116
SCS 4000/5000 Series Console
Installation & Operation Manual
-
7/25/2019 Raven seria 4000 5000925D
2/116
While every effort has been made to ensure the accuracy of this document,
Raven Industries assumes no responsibility for omissions and errors. Nor is any
liability assumed for damages resulting from the use of information contained
herein.
Raven Industries shall not be held responsible or liable for the effects ofatmospheric conditions and sunspot activity on the performance of our products.
Raven Industries cannot guarantee the accuracy, integrity, continuity, or
availability of the GPS signal from the U.S. Department of Defense/NAVSTAR
GPS satellites, the OmniSTAR correction service, or the WAAS correction
service. Raven Industries accepts no responsibility for the use of the signal for
other than the stated purpose.
Raven Industries shall not be responsible or liable for incidental or consequential
damages or a loss of anticipated benefits or profits, work stoppage or loss, or
impairment of data arising out of the use, or inability to use, this system or any of
its components.
Disclaimer
-
7/25/2019 Raven seria 4000 5000925D
3/116
Table of Contents
Manual No. 016-0159-925 i
Calibration Reference Sheet ..................................................................................................... v
Edit Mode ............................................................................................................................ v
Unit Definitions and Conversions ............................................................................................. vi
Unit of Measure Definitions ................................................................................................ vi
Unit of Measure Conversions ............................................................................................. vi
Chapter 1 Introduct ion ............................................................................. 1
Sprayer & Spreader Control Systems .......................................................................................1
System Components ...........................................................................................................2
SCS 4000/5000 Series Console Feature Overview ............................................................ 3
Care and Use ............................................................................................................................ 5
Contacting Raven Industries ..................................................................................................... 6
Chapter 2 Installation ............................................................................... 7
Installation Overview ................................................................................................................. 7Mounting & Installation ..............................................................................................................8
Mount the SCS Console ...................................................................................................... 8
Mount the Speed Sensor .....................................................................................................9
Installing Components for Liquid Applications .........................................................................13
Mount the Flow Meter ........................................................................................................ 13
Mount the Control Valve ....................................................................................................13
Optional Pressure Transducer Mounting ...........................................................................14
Installing Components for Granular Applications .................................................................... 14
Mount the Encoder ............................................................................................................ 14
Mount the Hydraulic Control Valve ....................................................................................15Optional Fan RPM Sensor Installation ..............................................................................16
Optional Bin Level Sensor Installation ............................................................................... 17
Power Connection ................................................................................................................... 18
Chapter 3 CAN (Control ler Area Network) Setup ................................ 21
Raven CANbus System Installation ........................................................................................21
Best Installation Practices .................................................................................................21
Wiring Power to a CAN System .............................................................................................. 22
Installing the CANbus Cables and Hardware .................................................................... 34
Detecting CAN Nodes ....................................................................................................... 35
Programming CANbus Nodes .................................................................................................36
CAN Troubleshooting .............................................................................................................. 36
CAN Node Off-line Errors ..................................................................................................36
Chapter 4 Initial Startup & Console Programming.............................. 39
Initial Calibration Sequence .................................................................................................... 39
Reprogramming Initial Settings ......................................................................................... 42
-
7/25/2019 Raven seria 4000 5000925D
4/116
Table of Contents
ii SCS 4000/5000 Series Installation & Operation Manual
Console Programming ............................................................................................................. 43
Edit Mode ..........................................................................................................................43
Calibration Keys ................................................................................................................ 43
Function Keys ....................................................................................................................44
Self Test Mode .........................................................................................................................45
Decimal Shift ........................................................................................................................... 46
Unit Definitions and Conversions ............................................................................................47
Unit of Measure Definitions ...............................................................................................47
Unit of Measure Conversions ............................................................................................48
Chapter 5 Data Menu ............................................................................. 49
Serial Submenu .......................................................................................................................49
Additional Serial Options .........................................................................................................50
SCS 4400/4600: ................................................................................................................50
SCS 4000/4070/5000: .......................................................................................................50
Product Submenu ....................................................................................................................51Page 1 ...............................................................................................................................51
Page 2 ...............................................................................................................................52
Console Submenu ...................................................................................................................54
CAN Submenu ........................................................................................................................55
Calibration Summary ............................................................................................................... 56
Data Logger (4400 and 4600 Only) .........................................................................................56
Setup: ................................................................................................................................56
SCS Alarm Definitions .............................................................................................................60
Chapter 6 Console Calibration .............................................................. 63
Speed Cal ................................................................................................................................63
GPS Simulated Radar .......................................................................................................63
Radar Sensor ....................................................................................................................63
Wheel Drive Speed Sensor ...............................................................................................64
Liquid Applications ..................................................................................................................65
Boom Cal ...........................................................................................................................65
Meter Cal ........................................................................................................................... 66
Valve Cal ...........................................................................................................................66
Rate Cal ............................................................................................................................. 67
SCS Multi-Tier Features ..........................................................................................................68
Tier 1 High Volume per Minute ..........................................................................................68
Tier 2 High Volume per Minute ..........................................................................................69
Percent Tier Disable ..........................................................................................................69
Granular Applications .............................................................................................................. 69
Boom Cal ...........................................................................................................................69
Spreader Constant .............................................................................................................69
Verification of Spreader Constant ......................................................................................71
http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?- -
7/25/2019 Raven seria 4000 5000925D
5/116
Table of Contents
Manual No. 016-0159-925 iii
Meter Cal ........................................................................................................................... 71
Rate Cal ............................................................................................................................ 71
Spinner RPM ..................................................................................................................... 72
Additional Calibration Data ...................................................................................................... 72
Entering Tank Volume ....................................................................................................... 72
Zero Out Display Information .......................................................................................... 72
Chapter 7 Job Setup & Field Test ing.................................................... 73
Liquid Applications .................................................................................................................. 73
Initial Job Setup ................................................................................................................. 73
Field Test ........................................................................................................................... 74
Preventive Maintenance ....................................................................................................74
Granular Applications .............................................................................................................. 74
Initial Job Setup ................................................................................................................. 74
Field Test ........................................................................................................................... 75
Preventive Maintenance ....................................................................................................75
Chapter 8 Troubleshoot ing ................................................................... 77
Chapter 9 By-Pass Line Plumbing System .......................................... 81
Installation ............................................................................................................................... 81
Initial System Set-up ............................................................................................................... 82
Field Test ........................................................................................................................... 83
Chapter 10 Testing Extension Cables .................................................... 85
Speed Sensor Cables .............................................................................................................85
Flow Meter Cables .................................................................................................................. 86
Chapter 11 Flow Meter Maintenance & Adjustment Procedure ........... 89
Chapter 12 Ratio Rate Feature ................................................................ 91
Chapter 13 Remote Switch Opt ion ......................................................... 93
Chapter 14 SCS 4000/5000 Series Firmware Update Procedure.......... 95
Chapter 15 Serial Interface & Data Str ing Formats ............................... 97
Remote Computer to SCS Console ........................................................................................97
Rate Change Request: ...................................................................................................... 97
Rate Cal Change Request Example ................................................................................. 98
-
7/25/2019 Raven seria 4000 5000925D
6/116
Table of Contents
iv SCS 4000/5000 Series Installation & Operation Manual
SCS 4000/4070/5000 Console to Remote Computer .............................................................98
SCS 4400/4600 Console to Remote Computer ......................................................................99
Appendix A Connecting an SCS Console to a Raven Field Computer.....101
Firmware Requirements ........................................................................................................101
Operation Guidelines .......................................................................................................101
Field Computer Set Up ..........................................................................................................102
Viper Pro .......................................................................................................................... 102
Envizio Pro ......................................................................................................................102
-
7/25/2019 Raven seria 4000 5000925D
7/116
Manual No. 016-0159-925 v
Calibration Reference Sheet
Calibration Reference Sheet
Record the settings and calibration values used when programming your SCS console and keep this sheet forfuture reference or when contacting a service technician.
Circle the setting selected on your console for the following options:
Write down the calculated calibration values in the spaces provided.
Edit Mode
During normal operation of the SCS console, pressing the Calibration Keys will access a calibration screen. Inorder to program numerical values into the SCS console, you will have to use the Edit mode. To enter Edit
mode:
1. Press the ENTER key. The default or existing value will be cleared and the screen will display an E on thefar right side of the screen.
2. Key in the value you want to replace the existing value. For example, press 2 1 2 3 to enter a value of2123.
3. Press the ENTER key to accept the keyed value and return to normal operation.
Note: During the initial console programming, pressing ENTER accepts the keyed value and advancesto the next calibration screen.
UNITS US (Acres) SI (Hectares) Turf (1000 Square Feet)
SPEEDSENSOR
SP1 (Wheel Speed) SP2 (Radar)
CONTROLTYPE
Liquid SprayerGran 1
(Single belt bed)
Gran 2
(Split belt bed,single encoder)
Gran 3
(Split belt bed,dual encoders)
Spinner RPMControl
VALVETYPE
Standard Valve Fast Valve Fast Close Valve PWM Valve PWM Close Valve
Speed CalBoom Widths(Boom Cal)
Meter Cal Rate Cal Valve CalVolume inTank/Bin
1. 1. 1. 1. 1. 1.
2. 2. 2. 2. 2.
3. 3. 3. 3. 3.
4. 4. 4. 4. 4.
5. 5. 5. 5. 5.
6.
7.
8.
9.
10.
-
7/25/2019 Raven seria 4000 5000925D
8/116
Unit Definitions and Conversions
vi SCS 4000/5000 Series Installation & Operation Manual
Unit Definitions and Conversions
Unit of Measure Definitions
Unit of Measure Conversions
To convert the METER CAL value into the selected unit of measure, divide the original number printed on theFlow Meter label by the desired conversion value.
Abbreviation Defini tion Abbreviation Definition
GPM Gallons per Minute cm Centimeters
lit/min Liters per Minute dm Decimeters
dl/min Deciliters per Minute m Meter
PSI Pounds per Square Inch MPH Miles per Hour
kPa Kilopascal km Kilometers
GPA Gallons per Acre km/h Kilometers per Hour
lit/ha Liters per Hectare US Volume per Acre
ml/ha Milliliters per Hectare SI Volume per Hectare
GPK Gallons per 1,000 Square Feet TU Volume per 1,000 Square Feet
mm Millimeters [ ] Metric Numbers
Fluid Ounces Conversion Formula Liters Conversion Formula Pounds Conversion Formula
Original METER CAL Number
128
Original METER CAL Number
3.785
Original METER CAL Number
Weight of One Gallon of Product
Liquid Area
1 U.S gallon = 128 fluid ounces 1 square meter = 10.764 square feet
1 U.S. gallon = 3.785 liters 1 hectare = 2.471 acres or 10,000 square meters
1 U.S. gallon = 0.83267 imperial gallons 1 acre = 0.405 hectares or 43,560 square feet
1 U.S. gallon = 8.34 pounds (water) 1 square mile = 640 acres or 258.9 hectares
Length Pressure
1 millimeter (mm) = 0.039 inches 1 psi = 6.89 kPa
1 centimeter (cm) = 0.393 inches 1 kPa = 0.145 psi
1 meter (m) = 3.281 feet
1 kilometer (km) = 0.621 miles
1 inch = 25.4 mm or 2.54 cm
1 mile = 1.609 km
-
7/25/2019 Raven seria 4000 5000925D
9/116
CHAPTER
Manual No. 016-0159-925 1
Chapter1Introduction
Sprayer & Spreader Control Systems
The Raven SCS 4000/5000 Series control systems are designed to simplify sprayer or spreader applications
by providing speed compensated product application regardless of the vehicle speed while adjusting for thewidth and status of programmed boom sections and a target rate set by the operator. SCS control systemsimprove the uniformity of product coverage for up to five liquid (carrier or chemical injection) or granularproducts via product control nodes connected to a CAN, or Controller Area Network.
Once properly installed and calibrated for the machine and application type, the operator sets the targetapplication rate for each product to be controlled by the SCS 4000/5000 Series console. Simply toggle theboom and master switches to the on positions and go. The console and product control nodes adjust thecontrol valves to the target application rate regardless of vehicle speed or gear selection.
During product application, the SCS 4000/5000 Series consoles also function as an area monitor, speedmonitor, and volume totalizer. The actual volume per area, or weight per area, is displayed for each productand a manual override switch allows the operator to manually adjust application of each product for systemcheck-out and spot spraying.
NOTICEPerformance of the system relies on properinstallation of the SCS system and preventivemaintenance of the complete sprayer orspreader. Raven Industries recommends thatthe equipment operator review this manualthoroughly before operating the system. This
manual provides procedures for installing andoperating the SCS console and CAN productcontrol system.
-
7/25/2019 Raven seria 4000 5000925D
10/116
-
7/25/2019 Raven seria 4000 5000925D
11/116
-
7/25/2019 Raven seria 4000 5000925D
12/116
Chapter 1
4 SCS 4000/5000 Series Installation & Operation Manual
SCS 4000/5000 Consoles
The manual flow control switch provides the capability for spot spraying.
Note: The SCS 4000 and 5000 consoles require an external or vehicle switch box to sense boom status.
SCS 4070 Consoles
In addition to the manual flow switch, The SCS 4070 console offers seven boom and a master ON/OFF switchfor boom section control.
Note: The SCS 4070 console features boom sense and speed functionality built in.
-
7/25/2019 Raven seria 4000 5000925D
13/116
Manual No. 016-0159-925 5
Introduction
SCS 4400/4600 Consoles
Like the other SCS consoles, the SCS 4400 and 4600 consoles offer a manual flow control switch for spotspraying. The SCS 4400 features seven boom and one master switch for boom section control while the SCS4600 console requires an external or vehicle switchbox.
The SCS 4400 and 4600 both feature a compact flash card slot for application data transfer.
Note: The SCS 4400/4600 will only recognize compact flash cards up to 512 MB. Do not use cards withlarger storage capacity with SCS consoles.
Care and Use
Refer to the following guidelines for proper care and use of the SCS console.
Mount the console securely and route cables to prevent tripping hazards and to keep the wires frompinching or breaking.
When temperatures are expected to be 10 F (-12 C) or lower, remove the console from the vehicle andstore it in a climate controlled environment.
Do not expose the console to precipitation, condensation, or other liquids. Store the console in a dryenvironment when not in use.
To prevent damaging the console, be sure to disconnect the consoles power connection when jumpstarting or welding on the machine.
CAUTION
Compact FlashCard Slot
-
7/25/2019 Raven seria 4000 5000925D
14/116
Chapter 1
6 SCS 4000/5000 Series Installation & Operation Manual
Contacting Raven Industries
Updates for Raven manuals as well as software updates for Raven consoles are available at the RavenApplied Technology Division web site:
http://www.ravenprecision.com
Sign up for e-mail alerts and we will notify you when updates for your Raven Applied Technology products areavailable on the Raven web site.
For additional support, contact your local Raven dealer or the Raven Customer Support Center by any one ofthe following methods:
Via phone: 1-800-243-5435
Via mail:
Raven IndustriesApplied Technology Division205 E 6th StreetSioux Falls, SD 57104
Via e-mail: http://www.ravenprecision.com/Support/askexpertNew.jsp
http://www.ravenprecision.com/http://www.ravenprecision.com/Support/askexpertNew.jsphttp://www.ravenprecision.com/Support/askexpertNew.jsphttp://www.ravenprecision.com/ -
7/25/2019 Raven seria 4000 5000925D
15/116
CHAPTER
2
Manual No. 016-0159-925 7
Chapter2Installation
Installation Overview
The following is intended as an overview of the installation process. These instructions will cover the basic
system installation and connection. Instructions for building a CAN (Controller Area Network) system can befound in Chapter 3, CAN (Controller Area Network) Setup.
Basic installation of the SCS 4000/5000 Series control system is as follows:
1. Mount the SCS console in the cab of the vehicle for easy operator access
2. Mount the Raven radar or wheel drive speed sensor
Note: If another type of speed sensor will be used, refer to the installation instructions provided with theoptional sensors to ensure proper installation.
3. Mount the product control hardware:
a. For liquid applications:
Mount the motorized control valve and flow meter to the framework supporting the boom. Injection modules (if applicable) mount to the framework of the sprayer with the in-line mixer
mounted just before the boom on/off valves.
b. For granular applications:
Mount the hydraulic control valve to the framework of the vehicle.
Mount the encoder to the conveyor drive shaft.
4. Route and connect cabling
5. Connect any optional components
6. Connect the console cable power leads to the vehicles battery
CAUTIONBe sure to follow instructions for connecting thepower leads to the battery carefully. Reversingthe power leads may cause damage to the SCSconsole. Be sure to connect the battery leadsafter all other components have been properlymounted and connected.
-
7/25/2019 Raven seria 4000 5000925D
16/116
-
7/25/2019 Raven seria 4000 5000925D
17/116
Manual No. 016-0159-925 9
Installation
FIGURE 2. SCS 4400/4600 Series Conso le Connections
Mount the Speed Sensor
The following sections offer installation instructions for the Raven radar or wheel drive speed sensors. Refer to
the section for your specific speed sensor to mount and install the speed sensor on your machine.
Phoenix 10 GPS Speed Sensor
FIGURE 3. Phoenix 10 Speed Sensor Kit (P/N 117-0171-165) Installation
Note: The Phoenix 10 is powered by a 9 - 16 VDC negative ground system.
1. Turn off all equipment on the machine to avoid interference with the speed sensor setup.
2. Apply power to the speed sensor by connecting the white wire to a clean ground and the red wire to a cleanswitched power source.
-
7/25/2019 Raven seria 4000 5000925D
18/116
Chapter 2
10 SCS 4000/5000 Series Installation & Operation Manual
Radar Speed Sensor
Note: Raven Industries suggests using a large, heavy duty mounting bracket (P/N 107-0159-693) whenmounting the radar sensor.
The following guidelines will assure proper installation of the radar speed sensor:
1. Park vehicle on a level surface.2. Select a mounting location for the radar sensor considering:
a. The radar sensor must have a clear line of sight from the lens to the ground and must not beobstructed by parts of the vehicle, tires, or other equipment.
b. The radar sensor must have a minimum of 20 and a maximum of 72 of clearance for properoperation. See Figure 4 on page 11.
c. The radar sensor must be mounted parallel to the ground with respect to the direction of vehicle travel.The sensor may be mounted at an angle between 0 and 15 degrees perpendicular to the direction oftravel to provide more clearance or a clear line of sight to the lens. SeeFigure 4 on page 11.
d. The radar should be mounted so that the length of the radar beam is parallel with direction of travel.
3. Use a carpenters level to verify that the mounting bracket is parallel to the ground.
4. Bolt the mounting bracket securely to the vehicle.5. Bolt the radar sensor to the mounting bracket using the supplied mounting hardware. See Figure 4 on
page 11.
6. Using the radar interface cable (P/N 115-0159-539), connect the radar sensor to the console cable.
a. Connect the red wire from the radar cable to the orange wire on the console cable.b. Connect the white wire from the radar cable to the white wire on the console cable (when available).
Review the Power Connectionsection on page 19for more information.
CAUTIONReversing the polarity of the radar speedsensor could result in damage to the sensor.
-
7/25/2019 Raven seria 4000 5000925D
19/116
Manual No. 016-0159-925 11
Installation
FIGURE 4. Raven Radar Speed Sensor Installation
Wheel Drive Speed Sensor
The wheel drive speed sensor consists of four magnets, a switch assembly and cable, and mountinghardware.
Note: Large tires and very low speed applications may require additional magnets (P/N 063-0159-584)to ensure accurate speed readings. Any even number of magnets may be used as long as theyare of alternating color.
1. Select a non-driven wheel (left front tractor wheel or implement wheel).
2. Check for pre-punched holes (not lug holes) in the rim. On vehicles with pre-drilled rims, proceed to step 3.For wheels which do not have pre-punched mounting holes, proceed as follows:
Rims with Four or Eight Hole Stud Patterns: Use the center of opposite lug holes to draw two perpendicularlines on the rim web and divide the circumference into four equal parts, or quadrants, as shown in Figure 5on page 12. Measure one inch in from the outer edge of the web on each of the lines drawn. Mark this pointas the center and drill 1/2 holes for mounting the magnets at each of these four points.
Rims with Six Hole Stud Patterns: You can use the rim webbing as a guide to locate the center of the holesto be drilled. Cut a small piece of wood to fit exactly over the web similar to the figure below. Measure andmark the center of the piece of wood on the edge that will be against the wheel rim. Using this center mark,mark each of the rim webs. Measure in one inch from the outer edge of the web on each of the lines drawn.
Mark this point as the center and drill 1/2 holes for mounting the magnets at each of these four points.
Radar Mounting Bracket
Radar Sensor Clearance
Optional Mounting Configuration
-
7/25/2019 Raven seria 4000 5000925D
20/116
Chapter 2
12 SCS 4000/5000 Series Installation & Operation Manual
FIGURE 5. Six and Eight Lug Wheel Rim Magnet Installation
Note: Distance (D) between each set of drilled holes must be equal +/- 1/8 [3 mm] to ensure accuracy ofthe system.
3. Securely mount the four magnets on the inside of rim. Magnets must be mounted in alternating red-blackorder. See Figure 6 on page 12.
4. Temporarily mount the switch assembly to a stationary point on the axle or column of the vehicle with thesupplied mounting hardware.
Note: The switch assembly does not need to pivot with the wheel during steering.
FIGURE 6. Wheel Magnet Installation
5. Position the switch assembly so that, as the wheel rotates, each magnet passes across the center of theblack, molded switch assembly.
6. Clearance between the magnets and switch assembly must be between 1/4 inch (6 mm) and 1 inch (25mm) with wheels pointed straight ahead.
a. Rotate the wheel to ensure proper spacing is maintained for each magnet.
b. Make sure the wheels can be steered to full left and right without the magnets colliding with the switchassembly.
Eight Hole Lug Pattern Six Hole Lug Pattern
-
7/25/2019 Raven seria 4000 5000925D
21/116
Manual No. 016-0159-925 13
Installation
7. Tighten the switch assembly bracket.
8. Secure the switch assembly cable to the axle or column with plastic cable ties.
Installing Components for LiquidApplications
FIGURE 7. Liquid System Diagram
Note: When using suspensions, the system should be rinsed thoroughly after each days use.
Mount the Flow Meter1. Mount the flow meter in the area of the boom valves as shown in Figure 7 on page 13. All flow through flow
meter must go to booms with no return line to the tank or pump after the product has gone through the flowmeter.
2. Mount the flow meter so that the flow through the flow meter is parallel with the ground and use the suppliedbracket to secure the flow meter.
3. For best results, allow a minimum of 7-1/2 inches [20 cm] of straight hose on the inlet side of the flow meterand any bend radius on outlet should be gradual.
4. Flow must follow the direction of the arrow on the flow meter.
Mount the Control Valve
1. Mount the motorized control valve in the main hose line between the flow meter and booms and with themotor in the upright position.
Note: For flow less than 3 GPM [11 lit/min], the motorized control valve is mounted in a by-pass line.Refer to Chapter 9, By-Pass Line Plumbing System, for alternate plumbing system installation.
2. Connect the product cable connectors to the boom valves, flow meter, and motorized control valve. Refer tothe system diagrams inChapter 3, CAN (Controller Area Network) Setup, for detailed cable connectiondiagrams.
To Booms 6-10
-
7/25/2019 Raven seria 4000 5000925D
22/116
Chapter 2
14 SCS 4000/5000 Series Installation & Operation Manual
Note: Connect the:
Black wire to boom valve #1
Brown wire to boom valve #2
Blue wire to boom valve #3
Black wire with white stripe to boom valve #4
Brown wire with white stripe to boom valve #5 Blue wire with white stripe to boom valve #6
White wire with black stripe to boom valve #7
White wire with brown stripe to boom valve #8
White wire with blue stripe to boom valve #9
Pink wire to boom valve #10.
Optional Pressure Transducer Mounting
1. Mount optional pressure transducer (P/N 422-0000-090) in desired location. To allow the SCS 4000/5000
Series console to read and display pressure, use the optional cable(P/N 115-0171-151)to connect thepressure transducer to the product cable.
2. With the product pump turned off and 0 PSI [kPa] in the lines, enter 0 for pressure calibration. See theProduct Submenusection on page 51for more information.
-
7/25/2019 Raven seria 4000 5000925D
23/116
-
7/25/2019 Raven seria 4000 5000925D
24/116
Chapter 2
16 SCS 4000/5000 Series Installation & Operation Manual
FIGURE 9. Spinner and Pneumatic Systems
Abo ve: Open Hydraulic System
(Fixed Displacement Pump wi th Spinner)
Abo ve: Closed Hydraulic Sys tem
(Variable Displacement Pump wit h Spinner)
Below: Open Hydraulic System
(Fixed Displacement Pump without Spinner)Below: Closed Hydraulic System
(Variable Displacement Pump wit hout Spinner)
-
7/25/2019 Raven seria 4000 5000925D
25/116
Manual No. 016-0159-925 17
Installation
Optional Fan RPM Sensor Installation
Use the provided hardware to mount the fan RPM sensor (P/N 117-0159-575) to the bracketFigure 10 onpage 17.
FIGURE 10. Fan RPM Sensor Assembly
Attach the fan sensor bracket to the mounting tab. Assemble fan sensor bracket to fan sensor mounting tab onbox with stainless steel bolt, lock washer, and nut.
FIGURE 11. Sensor Gear
Adjust fan sensor air gap between .040 and .080 inch (.080 inch max.)
-
7/25/2019 Raven seria 4000 5000925D
26/116
Chapter 2
18 SCS 4000/5000 Series Installation & Operation Manual
Optional Bin Level Sensor Installation
Install bin level sensor kit (P/N 117-0159-640) in spreader bin at location illustrated. Select mounting location inaccordance to bin construction.
FIGURE 12. Bin Level Sensor Location
Use the mounting plate as a template to mark the location for the holes. Drill and de-burr all holes. Route thesensor cable and secure the mounting plate to the bin wall using u-bolt protectors. Route and connect thesensor cable connector to the flow cable connector. Secure all cables with plastic cable ties.
FIGURE 13. Bin Level Sensor Assembly
-
7/25/2019 Raven seria 4000 5000925D
27/116
Manual No. 016-0159-925 19
Installation
Power Connection
1. Make sure the vehicle accessory power (key) is off before routing the red and white battery wires to a 12-volt battery.
2. Attach the white battery wire to the negative (-) terminal and the red battery wire directly to the positive (+)battery terminal.See Figure 14 on page 19.
Note: Do not connect the red and white leads to the vehicles starter.
3. Secure the battery wires with plastic cable ties but do not tie the battery wires close to the existing batteryleads or any other electrical wiring.
4. Connect the speed sensor cable to the speed sensor port on the console or boom/speed interface cable.
Note: Speed sensor and flow meter extension cables are available from your local Raven dealer.
5. Secure the speed sensor cable and the console cable with plastic cable ties.
FIGURE 14. Battery Connection
ConnectionDetail
One 12 V Battery
White
(Negative)
Red
(Positive)
Console
Battery Wires
Red (Pos.) Console
Battery Wires
White (Neg.)
12 V System Using two 6 V Batteries
Console Battery
Wires
White (Neg.)
12 Volt System using two 6 V Batteries
Red (Pos.)
24 V System usi ng two 12 V Batteries
White (Neg.)
Console
Battery Wires
Red (Pos.)
-
7/25/2019 Raven seria 4000 5000925D
28/116
Chapter 2
20 SCS 4000/5000 Series Installation & Operation Manual
-
7/25/2019 Raven seria 4000 5000925D
29/116
CHAPTER
3
Manual No. 016-0159-925 21
Chapter3CAN (Controller Area
Network) Setup
A Controller Area Network, or CAN, is a high-integrity serial data communications bus that operates at a datarate of 250 kilobits per second for real-time control applications and uses special CAN cables and terminatorsfor operation. The CAN protocol has excellent error detection and confinement capabilities, making it verysuitable and reliable for agricultural applications.
CAN systems allow products to be added to a control system at any time. Up to five product control nodes maybe connected to the SCS control system for any combination of l iquid, granular, chemical injection, or spinnercontrol applications.
The diagrams in this chapter show different hardware configurations for use with the SCS product controlsystem. Some diagrams show optional features which may not apply to each system. These features andcomponents are not required for CAN operation and optional features and cables may be ignored during abasic installation.
-
7/25/2019 Raven seria 4000 5000925D
30/116
Chapter 3
22 SCS 4000/5000 Series Installation & Operation Manual
Raven CANbus System Installation
The following sections contain instructions for proper installation of the Raven CANbus system.
Best Installation Practices
The information below illustrates proper methods for wiring a CANbus system. The diagrams provided later inthis chapter are a good reference for both OEM and aftermarket installations. The main points are summarizedbelow.
Note: Following these recommendations will result in the most robust system possible while greatlyreducing CAN communication problems.
1. Always use sealed connectors with dielectric grease. Avoid unsealed, crimped connections (i.e. buttconnectors).
In addition to using dielectric grease, mount all CAN terminators (P/N 063-0172-369) with the connectorpointing down to avoid collecting water and/or chemical. Liquids collecting within the terminator can corrodepins and may cause CAN issues.
2. Connect the power directly to a controlled clean power source.
3. Connect the ground directly to the vehicles battery.
4. Node logic power should be connected to a clean power bus relay.
5. Use dedicated bus bars to connect the console and all nodes to the same source for both power andground.
6. Provide relays to switch power on and off to avoid draining the battery. Raven recommends connecting theconsole to a clean power source (at relay) and using the console orange wire to power a relay to switch aclean power source to the CAN nodes. This makes the console the master power switch and allows engineshutdown without turning off the console.
Note: If an optional DGPS receiver will be installed with the system, connecting the power (low current)to the low current bus bars will allow engine shutdown without losing GPS reception.
CAN Terminators
Two CAN terminators (P/N 063-0172-369) are required to provide optimal signal integrity through the CANbus.These terminators should be installed at each end of the CANbus. A CAN power adapter tee cable (P/N 115-0171-368) should be placed at the front of the bus with one end terminated. CAN power, obtained from aswitched power source, runs throughout the bus to act as a shield.
NOTICE
Be sure to read all safety instructions and followall installation procedures to ensure properinstallation of the CANbus system.
-
7/25/2019 Raven seria 4000 5000925D
31/116
Manual No. 016-0159-925 23
CAN (Contro ller A rea Network) Setup
Wiring Power to a CAN System
Wiring power to the SCS console and the CAN nodes is especially important for proper operation of thesystem. Many issues with CAN systems can be corrected by diagnosing problems related to improper wiring ofthe power and ground.
The SCS console power must be wired directly to a controlled clean power source.
See the Power Connectionsection on page 19for instructions on connecting the SCS console to a cleanpower source.
All ground wires should be connected directly to the battery ground, not to chassis ground.
The CAN logic power must be wired to a clean power bus that is connected to a clean power bus relay. Use the orange wire from the SCS console cable to switch the clean power bus relay.
The CAN high current power must be wired to a high current power bus connected to a high current powerrelay.
The high current power relay should be controlled by the vehicle ignition switch.
CAUTIONBe sure to follow the instructions for connectingthe power leads to the battery carefully.Reversing the power leads may cause damageto the SCS console.
-
7/25/2019 Raven seria 4000 5000925D
32/116
Chapter 3
24 SCS 4000/5000 Series Installation & Operation Manual
FIGURE 1. CAN Node Wiring Diagram
-
7/25/2019 Raven seria 4000 5000925D
33/116
Manual No. 016-0159-925 25
CAN (Contro ller A rea Network) Setup
FIGURE 2. SCS 4000/5000 Single Product (Liquid) CAN Control System
-
7/25/2019 Raven seria 4000 5000925D
34/116
Chapter 3
26 SCS 4000/5000 Series Installation & Operation Manual
FIGURE 3. SCS 4070 Single Product (Liquid) CAN Control System
-
7/25/2019 Raven seria 4000 5000925D
35/116
Manual No. 016-0159-925 27
CAN (Contro ller A rea Network) Setup
FIGURE 4. Envizio Plus CAN AccuBoom with SCS 4400 Serial Console
-
7/25/2019 Raven seria 4000 5000925D
36/116
Chapter 3
28 SCS 4000/5000 Series Installation & Operation Manual
FIGURE 5. SCS 4000/5000 Multi-Product CAN Control SystemOne Granular Product plus Spinner Control
-
7/25/2019 Raven seria 4000 5000925D
37/116
Manual No. 016-0159-925 29
CAN (Contro ller A rea Network) Setup
FIGURE 6. SCS 4000/5000 Multi -Produc t CAN Control SystemTwo Granular Products
-
7/25/2019 Raven seria 4000 5000925D
38/116
-
7/25/2019 Raven seria 4000 5000925D
39/116
Manual No. 016-0159-925 31
CAN (Contro ller A rea Network) Setup
FIGURE 8. SCS 4400 Granular Control System
-
7/25/2019 Raven seria 4000 5000925D
40/116
Chapter 3
32 SCS 4000/5000 Series Installation & Operation Manual
FIGURE 9. SCS 4600 Granular Control System
-
7/25/2019 Raven seria 4000 5000925D
41/116
Manual No. 016-0159-925 33
CAN (Contro ller A rea Network) Setup
FIGURE 10. CAN Liquid Node Option
FIGURE 11. CAN Granular Node Option
-
7/25/2019 Raven seria 4000 5000925D
42/116
Chapter 3
34 SCS 4000/5000 Series Installation & Operation Manual
FIGURE 12. CAN Chemical Injection Node Option
FIGURE 13. CAN Dual Node (Granular) Option
-
7/25/2019 Raven seria 4000 5000925D
43/116
Manual No. 016-0159-925 35
CAN (Contro ller A rea Network) Setup
Installing the CANbus Cables and Hardware
Up to five products can be connected to the SCS 4000/5000 Series CAN control system plus AccuBoom,and AutoBoom nodes. The SCS control system may require either a boom/speed node or a single productcontrol node for basic CAN product control. Refer to Chapter 1, Introduction, for more information about yourspecific SCS console and required system components.
Installing a New CANbus system
Refer to the following instructions for proper installation of a CANbus system if an existing CAN system doesnot already exist on your machine.
1. Install a CAN power tee cable (P/N 115-0171-368) using the power lead connections described in the BestInstallation Practicessection on page 22.
2. Connect a passive CAN terminator (P/N 063-0172-369) to the CAN power tee cable.
3. Attach a tee expansion cable to the other 4-pin connector. Expansion cables are available as listed below.
Note: SCS 4400/4600 consoles do not require an external boom/speed node and feature product controlfor the first product hardwired into the console. To add additional products to a CANbus systemwith these consoles, skip to step 7.
4. Connect the boom interface cable (P/N 115-0171-405) to the installed tee expansion cable. Contact yourRaven distributor for the correct part number for your application.
5. Connect the boom/speed node (P/N 063-0172-272) to the boom interface cable (gray connector to gray
connector and black connector to black connector).6. Add a second tee expansion cable to the other 4-pin connector of the expansion cable installed in step 3.
7. Connect the second passive CAN terminator to one of the 4-pin connectors on the tee expansion cable.
8. Connect the product node cable to the remaining 4-pin connector. Contact your Raven distributor for thecorrect part number for your application.
9. Connect the product node cable to a source of high current power and logic power. Provide power to thenodes as described in the Wiring Power to a CAN Systemsection on page 23.
Note: Connect the ground directly to the battery terminals and the logic to the clean power bus.
10. Connect the product node to the product node cable (gray connector to gray connector and black connectorto black connector).
Part Description Part Number
Tee Expansion Cable - 6 in. 115-0171-364
Tee Expansion Cable - 6 ft. 115-0171-326
Tee Expansion Cable - 12 ft. 115-0171-362
Tee Expansion Cable - 18 ft. 115-0171-690
Tee Expansion Cable - 24 ft. 115-0171-363
-
7/25/2019 Raven seria 4000 5000925D
44/116
Chapter 3
36 SCS 4000/5000 Series Installation & Operation Manual
Interfacing with an Existing CANbus system
The SCS 4000/5000 Series console may also be capable of integrating into almost any existing RavenCANbus system. To connect the SCS control system into the CANbus:
1. Insert a tee expansion cable into the CANbus line by disconnecting an existing CAN expansion cable orCAN passive terminator.
Note: When adding expansion cables or CAN nodes to the system, Raven Industries recommendsalways leaving a CAN terminator connected to the power tee cable (P/N 115-0171-368).
2. Re-connect the existing CANbus cabling to the installed expansion cable.
3. Route the remaining expansion cable connector to the 4-pin Deutsch connector on the main interface cable(P/N 115-0171-746).
Adding CAN Nodes
To add CAN nodes to the SCS control system:
1. Remove the terminator (P/N 063-0172-369) from the tee expansion cable at the end of the CAN cabling.
Note: When adding expansion cables or CAN nodes to the system, Raven Industries recommendsalways leaving a CAN terminator connected to the power tee cable (P/N 115-0171-368).
2. Connect another tee expansion cable to the 4-pin connector from which the terminator was disconnected.
3. Connect the required interface or control cable to one end of the CAN tee expansion cable. Contact yourRaven distributor for the correct part number for the application or feature being added to the CANbussystem.
4. Replace the terminator on the remaining 4-pin Deutsch connector.
Detecting CAN Nodes
The SCS 4000/5000 Series console must be able to communicate with the CANbus system to ensure that theproducts are applied correctly. The SCS console should automatically establish communication with the boom/speed node, the AccuBoom and AutoBoom nodes (if installed), and up to five product control nodes viathe CANbus.
When a node is detected, the node will the program and version of the connected node is displayed in the CANData Menu. To access the CAN Data Menu, press the DATA MENU button until CAN is highlighted at thebottom, left corner of the SCS display. Use the arrow up or down keys to scroll through the list of possiblenodes
Note: If a node is not found, troubleshoot the node to determine why SCS console cannot communicatewith the node. See the Troubleshooting section later in this chapter for more information aboutCAN communication failures.
Node Version Information
The CAN Data Menu displays program number and version of each node detected on the CANbus.
Retry CAN Initialization
If a node, or nodes, currently connected to the CANbus system are not displayed in the CAN Data Menu, pressthe POWER key to cycle power to the console. If nodes still do not display properly when the console is
-
7/25/2019 Raven seria 4000 5000925D
45/116
Manual No. 016-0159-925 37
CAN (Contro ller A rea Network) Setup
rebooted, the CANbus system may need to be readdressed. Proceed to the next section for instructions onreaddressing the product nodes.
Readdressing the Nodes
If the SCS console is unable to detect a CANbus node on startup, troubleshoot the CANbus and the node (seethe CAN Troubleshootingsection on page 38), and then readdress the CANbus:
Note: Only product nodes need to be addressed (single product, dual product, motor control, etc.).
1. From the main screen, press the DATA MENU button until the CAN option is highlighted in the lower, lefthand corner of the SCS display.
2. Use the up or down arrow keys to select the Readdress Control Nodes option on Page 2 of the CAN DataMenu.
3. Press the ENTER button to begin readdressing the product control nodes.
4. When prompted to reboot nodes, disconnect the logic power from the product node to be controlled asProduct 1. After approximately 3 seconds, reconnect the nodes logic power. The SCS console should haverecognized the node as Product 1.
Note: The SCS 4400/4600 consoles feature an integrated product control channel which will alwaysappear as Product 1.
5. If additional product nodes are installed in the CANbus, repeat step 4to readdress additional productnodes.
6. Press the ENTER button to finish readdressing the product nodes and resume normal operation.
Programming CANbus Nodes
The CAN nodes are programmed using the SCS console in Edit mode.
See Chapter 4, Initial Startup & Console Programming, for information on programming CAN product nodes.
Refer to the AutoBoom Calibration & Operation manual for detailed operation of the optional AutoBoomsystem with your SCS 4000/5000 Series console.
-
7/25/2019 Raven seria 4000 5000925D
46/116
Chapter 3
38 SCS 4000/5000 Series Installation & Operation Manual
CAN Troubleshooting
Although the control algorithm is located within the CAN node, all of the same troubleshooting techniques thatare used in a traditional hard-wired system still apply to a CAN system and the behavior of the system remainsthe same. Flow and speed sensors, as well as the control valve and boom valves, are used in the samefashion.
CAN Node Off-line Errors
The most likely causes for losing CAN communication between the console and any one of the nodes are:
1. Corroded and/or open connections in the circuit.
2. Console and/or CAN node logic power and grounds connected to a dirty power source (dirty power isdefined as any circuit with a variable load that exceeds 1 ampere). This is especially true of circuits loadedby electrical coils.
3. Console and/or nodes connected to different power and/or ground sources. This can result in componentsoperating at different voltage planes.
Below are some common causes for communication failures:
Issue Possible Cause Solution
CANbus cannot readthe product node
The node is notconnected to the CANbus
Connect the node and reboot the SCS console to read theproduct node.
Node is not properlypowered
Connect the clean power - 16 gauge red wire and high currentpower - 12 gauge red wire from the product node to a 12V DCpower source that is capable of supplying power to all nodesconnected to the CANbus system
Node is not properlygrounded
Connect the clean ground - 16 gauge white wire and the highcurrent ground - 12 gauge white wire to a good, quality groundsource. Raven recommends grounding the wires to thenegative terminal of the battery.
CANbus ends notterminated
Make sure that both ends of the CANbus system are properlyterminated. See the CAN Terminatorssection on page 22orAdding CAN Nodessection on page 36for more information.
Corroded pins in CANbusconnections
Check CANbus cable connectors for any highly corroded pins.
Ensure dielectric grease has been applied to all cableconnections exposed to weather and field conditions.
Moisture in connection
Check CANbus cable connectors for any corroded pins.
Ensure dielectric grease has been applied to all cableconnections exposed to weather and field conditions.
Connectors not seated
properly
Check that all CANbus cable connectors are inserted fully (untilthe locking tab is engaged).
Be sure to remove any moisture in connections which were notproperly seated. Check for corroded pins and apply dielectricgrease when reconnecting CANbus cables.
-
7/25/2019 Raven seria 4000 5000925D
47/116
CHAPTER
4
Manual No. 016-0159-925 39
Chapter4Initial Startup &
Console Programming
The first time the SCS console is powered on, it will automatically enter a calibration mode. This initialprogramming sequence requires a selection for the units, product control type, speed sensor type, and controlvalve type before the flashing CAL (calibration) alert clears and the console is ready for normal operation.
Reset Console Memory
Occasionally, it may be necessary to reset the internal memory and return to the initial programming screens.
Note: All configuration settings and data will be lost. Before performing a memory reset, be sure to writedown all calibration data to simplify console programming after the memory has been cleared.
To reset the internal memory:
1. Press the POWER button to turn the console OFF.
2. While holding the CE key, press POWER to turn the console ON.
3. Perform the Initial Calibration Sequenceas described in the next section to restore the console to normaloperation. Before beginning product application, verify all other settings on the console are reprogrammed
to ensure proper operation of the control system.
Initial Calibration Sequence
Adjust Contrast
When the console is switched on for the first time, the Adjust Contrast screen will display.
1. Press and hold the UP ARROW key to increase the screen contrast or the DOWN ARROW to decrease the
contrast.2. Press ENTER to save this setting and proceed to the Units screen.
Note: The screen contrast can be adjusted through the Data Menu after the initial programming. SeeChapter 5, Data Menu, for more information.
-
7/25/2019 Raven seria 4000 5000925D
48/116
Chapter 4
40 SCS 4000/5000 Series Installation & Operation Manual
Units
The default setting for the Units screen is US Acres.
1. Press the CE key to cycle between SI Metric Hectares, Turf Square Feet, or US Acres.
2. Press ENTER to accept your selection and advance to the Product Control Type screen.
Product Control Type
The default setting for the product control type is Liquid control.
1. Press the CE key to cycle between:
LIQUID - Liquid sprayer
GRANULAR 1 - Single belt bed, single encoder
GRANULAR 2 - Split belt bed, single encoder
GRANULAR 3 - Split belt bed, dual encoders
Note: A spinner control option will be displayed for nodes equipped with firmware supporting this feature.
2. Press ENTER to save this setting and advance to the Valve Type screen.
Valve Type
The default setting for the Valve Type screen is Standard Valve.
1. Press the CE key to cycle between:
STANDARD VALVE
FAST VALVE
FAST CLOSE VALVE
PWM VALVE
PWM CLOSE VALVE
2. Press ENTER to accept your selection and advance to either the Meter Cal or Spreader Constant screen.
If Liquid was selected as the product control type,skip to the Meter Cal (Liquid Applications)section onpage 41. If Spinner RPM Control was selected as the product control type, skip to the Fan Speed Cal(Spinner Applications)section on page 41. If any of the granular control options were selected, a spreaderconstant and a product density or meter cal will have to be entered.
Note: During the initial programming sequence, pressing ENTER in Edit mode will also advance to thenext calibration screen.
Spreader Constant (Granular Applications)
If you have selected any of the granular product control types, the next screen displayed after the valve typewill be the Spreader Constant screen. A value greater than zero must be entered into this screen to advance tothe next screen.
1. Use the Edit mode to input your vehicles spreader constant.
Note: Press the METER CAL button while on this screen to toggle between spreader constant and metercal.
2. The Product Density screen will display.
-
7/25/2019 Raven seria 4000 5000925D
49/116
Manual No. 016-0159-925 41
Initial Startup & Conso le Programming
Product Density (Granular Applications)
After the spreader constant is entered, the SCS console will display the Product Density screen.
1. Use the Edit mode to input a density value for the granular product you will be applying.
Note: You can press and hold the METER CAL button while on this screen to review the value for the
spreader constant entered on the last calibration screen.2. The Valve Cal screen will display.
Meter Cal (Liquid Applications)
If you entered Liquid as the product control type, the Meter Cal screen will display after the Valve Typescreen.
1. Use the Edit mode to input the meter cal value printed on your flow meter tag.
2. The Valve Cal screen will display.
Fan Speed Cal (Spinner Applications)
If you entered Spinner RPM Control as the product control type, the Fan Speed Cal screen will display afterthe Valve Type screen.
1. Use the Edit mode to input the Fan Speed Cal. The Fan Speed Cal value is the number of pulses detectedper ten revolutions of the fan.
2. The Valve Cal screen will display.
Valve Cal
The valve cal value is used to control the response time of control valve motors with respect to changes invehicle speed. The valve cal can be adjusted after the initial programming to refine valve response. Ravenrecommends the following values for the initial control valve calibration number:
Standard valves - 2123
Fast and fast close valves - 743
PWM and PWM close valves - 43
Refer to the Valve Calsection on page 66for details on refining this value for the various valve types.
1. Use the Edit mode to input the valve cal value for the control valves on your equipment.
Note: More recent firmware releases automatically enter the recommended valve cal values based uponthe type of control valve selected.
2. The Rate Cal screen displays
Rate Cal
Enter the target rate cal (GPA) [lit/ha] {GPK}.
1. Use the Edit mode to input the rate cal value.
2. The Speed Sensor Type screen displays.
Speed Sensor Type
The default setting for the Speed Sensor Type is Radar SP2.
-
7/25/2019 Raven seria 4000 5000925D
50/116
Chapter 4
42 SCS 4000/5000 Series Installation & Operation Manual
1. Press the CE key to cycle between:
WHEEL SPEED SP1
RADAR SP2
2. Press ENTER to save your selection and advance to the Speed Cal screen.
Speed Cal
The speed cal is used to configure the SCS console to your vehicle. Initially, Raven recommends values for thespeed cal depending upon the speed sensor type selected on the previous screen. Use one of the followingvalues as the initial speed cal:
Note: The speed cal is vital for proper product application, volume and area totalizers, as well as theconsoles speed and distance displays. This value must be refined to ensure the SCS console isproperly configured to your vehicle. See the Speed Cal section on page 63for details on refiningthis value for your vehicle.
1. Use the Edit mode to input a speed cal value.
2. The Boom Cal screen displays.
Boom Cal
The boom cal value for a boom is the width of that boom section in inches [cm]. Up to ten boom cal values canbe programmed in the SCS console.
1. Use the Edit mode to input the width of your first boom section.2. Once a boom cal value has been entered on the Boom 1 Cal screen, the flashing CAL alert will clear and
the initial programming sequence is complete.
You may want to program the boom cal values for additional boom sections at this time. Press the UP orDOWN Arrow keys to access the Boom Cal screens for booms 2-10 and enter the boom widths for these boomsections.
Note: The Boom Cal screens are also accessible by pressing the BOOM CAL key.
Reprogramming Initial Settings
After the initial console programming sequence is complete, if there is a need to change initial consoleprogramming settings (working units, product control type, valve type, or speed sensor type):
1. Press and hold the SELF TEST key.
2. The display will flash the current settings. After 12 seconds, the display will stop on US ACRES.
3. Press CE to change the working units.
4. Press ENTER to accept the new setting and proceed to the next screen.
5. Repeat step 3and step 4as necessary for the Speed Sensor Type, Product Control Type, and ControlValve Type screens.
Sensor Type English Metric
Raven GPS Receiver 785 199
Internal GPS fromEnvizio Pro/Cruizer
812 206
Raven Radar 598 152
Wheel Magnets 1000 254
-
7/25/2019 Raven seria 4000 5000925D
51/116
Manual No. 016-0159-925 43
Initial Startup & Conso le Programming
Console Programming
Edit Mode
During normal operation of the SCS console, pressing the Calibration Keys will access a calibration screen. Inorder to program numerical values into the SCS console, you will have to use the Edit mode. To enter Editmode:
1. Press the ENTER key. The default or existing value will be cleared and the screen will display an E on thefar right side of the screen.
2. Key in the desired value for the current setting. For example, press 2 1 2 3 to enter a value of 2123.
3. Press the ENTER key to accept the keyed value and return to normal operation.
Note: During the initial console programming, pressing ENTER accepts the keyed value and advancesto the next calibration screen.
Calibration KeysThe calibration keys allow you to program the SCS console and calibrate the system to your specific machine.See the Edit Modesection on page 43for information on programming the SCS console using the Edit mode.
Boom Cal
Pressing the BOOM CAL button displays the boom calibration screen. This screen allows you to view and editboom section widths for up to ten boom sections.
1. Press the BOOM CAL button. The Boom 1 Cal screen is displayed.
2. Press the UP or DOWN arrow keys to view the boom section screens for additional sections.
3. Use the Edit mode to enter or edit boom section widths. If a boom section is not used or not needed, enter0 as the value for that boom sections boom cal.
Speed Cal
Pressing SPEED CAL displays the currently programmed calibration value used to determine vehicle speed.For more information, refer to the Speed Calsection on page 63.
Meter Cal
Pressing the METER CAL button displays the current settings for the selected node. Depending upon theselected product control type entered for the selected node, pressing the METER CAL button displays thefollowing settings for the selected node:
For more information, refer to the Chapter 11, Flow Meter Maintenance & Adjustment Procedure.
For Liquid Products: Pressing METER CAL displays the currently programmed calibration value used tocalculate the volume per minute, rate, and total gallons for each product being applied. The METER CAL valueis printed on the tag on your specific flow meter.
For Granular Products : Press the METER CAL button to display either the product density or spreaderconstant for the selected product node. Continue pressing the METER CAL button to toggle between thespreader constant and product density settings for the selected node.
-
7/25/2019 Raven seria 4000 5000925D
52/116
Chapter 4
44 SCS 4000/5000 Series Installation & Operation Manual
Valve Cal
Pressing VALVE CAL displays the currently programmed calibration value uses to adjust the control valve andkeep product application on the target rate. This value sets control characteristics such as speed and reactionof the various control valves. For more information, refer to the Valve Calsection on page 66.
Rate CalPressing RATE CAL displays the currently programmed rate in gallons per acre (liters per hectare). This is thetarget rate for product applications.
Self Test
Pressing SELF TEST will display a test speed for testing the product control system.
Press and hold the SELF TEST button to view the SCS consoles initial programming values and settings. Ifthe SELFT TEST button is held for 12 seconds, the controller will stop scrolling and allow the operator to stepthrough the various settings and enter new values if desired.
Function Keys
The function keys display current application information. This information may also be helpful in calibrating,fine tuning, or testing the controller or product control system. The totalizer buttons can be reset at any time.
Total Area
Pressing TOTAL AREA displays the total area covered.
Total Volume
Pressing TOTAL VOLUME displays the total volume applied during a job.
Field Area
Pressing FIELD AREA displays the field area covered.
Field Volume
Pressing FIELD VOLUME displays the total volume applied to a field.
Distance
To display the SCS consoles odometer, displayed in feet or meters, press DISTANCE.
Note: This reading is also useful when calibrating or fine tuning the speed cal.
Volume/Minute
Pressing the VOLUME/MINUTE key displays the current volume per minute, or flow rate, in the units which theSCS console is programmed to apply.
-
7/25/2019 Raven seria 4000 5000925D
53/116
Manual No. 016-0159-925 45
Initial Startup & Conso le Programming
Area/Hour
Pressing the AREA/HOUR key displays an estimate of the area that could be covered if both the current speedand boom operation were maintained over one hour.
Data Menu
Pressing the DATA MENU key accesses the SCS Data Menu. Refer to Chapter 5, Data Menufor moreinformation on the Data Menu.
Product On/Off
The PRODUCT ON/OFF key toggles product control on or off. When a close type vale is selected, togglingproduct control off will result in the valve closing.
Tank Volume
Press the VOLUME/TANK button to display the current volume remaining in the tank or bin. Use the Edit modeto re-enter a volume of product in a tank or bin when the selected product is refilled.
Product Select
Pressing PRODUCT SELECT toggles your product selection on the controller. The product must be selectedto view application data or change settings.
Self Test Mode
The Self Test mode can be used to simulate speed for testing the system while the vehicle is not moving.Press SELF TEST and use the Edit mode to enter a simulated operating speed. Verify the speed in the lowerleft corner of the display. The Self Test speed will clear when the speed sensor detects motion. If 6 MPH [10km/h] is desired, enter 6.0 [10.0]. A speed cal value of 900 [230] or greater is recommended when operating inthis mode.
Note: To prevent the Self Test speed from disengaging while testing the system, disconnect speedconnector on the console cable or boom sense/speed cable.
-
7/25/2019 Raven seria 4000 5000925D
54/116
Chapter 4
46 SCS 4000/5000 Series Installation & Operation Manual
Decimal Shift
The decimal shift feature is used to increase system accuracy at low application rates. Decimal shift is setduring the setup of meter cal or product density.
Note: The programmed rate cal value is also affected by the decimal shift feature. Be sure to verify theprogrammed rate cal when changing the decimal shift feature.
To enable the decimal shift feature for the selected product:
1. Press the METER CAL button.
2. Press the ENTER key to enable Edit mode.
3. Press the DISTANCE key. The rate display for the selected product will change to reflect the decimal shift.
4. Enter the meter cal or product density for the selected product.
5. Press the ENTER key to accept the value and exit Edit mode.
To disable the decimal shift feature for the selected product:
1. Press the METER CAL button.2. Press the ENTER key to enable Edit mode.
3. Enter the meter cal or product density for the selected product. The rate display for the selected product willchange to reflect the changed decimal.
4. Press the ENTER key to accept the value and exit Edit mode.
The following tables illustrate how shifting the decimal point can increase system accuracy.
TABLE 1. Decimal Place Locations in Liquid Modea
a. When entering a rate cal, remember that 2 GPA [20 lit/ha] is entered as 2.0 [20.0] when unshiftedand 2.00 [20.00] when shifted.
US Metric Turf
Unshifted Shift Unshifted Shift Unshifted Shift
Rate Display 0000.0 000.00 00000 0000.0 000.00 000.00
Rate Cal 0000.0 000.00 00000 0000.0 000.00 000.00
Tank Volume 000000 00000.0 000000 00000.0 00000.0 00000.0
Total Area 000.0 000.0 000.0 000.0 0000 0000
Total Volume 000000 00000.0 000000 00000.0 00000.0 00000.0
Field Area 000.0 000.0 000.0 000.0 0000 0000
Field Volume 000000 00000.0 000000 00000.0 00000.0 00000.0
Vol/Minute 0000 000.0 0000 000.0 000.0 000.0
Area/Hour 000.0 000.0 000.0 000.0 0000 0000
Rate +/- 000.0 00.00 0000 000.0 00.00 00.00
Low Tank Level 0000 000.0 0000 000.0 000.0 000.0
Low Vol/Min 0000 000.0 0000 000.0 000.0 000.0
-
7/25/2019 Raven seria 4000 5000925D
55/116
Manual No. 016-0159-925 47
Initial Startup & Conso le Programming
TABLE 2. Decimal Place Locations in Granular Modea
US Metric Turf
Unshifted Shift Unshifted Shift Unshifted Shift
Rate Display 00000 0000.0 00000 0000.0 0000.0 0000.0
Rate Cal 00000 0000.0 00000 0000.0 0000.0 0000.0
Tank Volume 000000 00000.0 000000 00000.0 00000.0 00000.0
Total Area 000.0 000.0 000.0 000.0 0000 0000
Total Volume 000000 00000.0 000000 00000.0 00000.0 00000.0
Field Area 000.0 000.0 000.0 000.0 0000 0000
Field Volume 000000 00000.0 000000 00000.0 00000.0 00000.0
Vol/Minute 0000 000.0 0000 000.0 000.0 000.0
Area/Hour 000.0 000.0 000.0 000.0 0000 0000
Rate +/- 0000 000.0 0000 000.0 000.0 000.0
Low Tank Level 0000 000.0 0000 000.0 000.0 000.0
Low Vol/Min 0000 000.0 0000 000.0 000.0 000.0
a. When entering rate cal, remember that 200 PPA [kg/ha] is entered as 200 when unshifted and200.0 when shifted.
-
7/25/2019 Raven seria 4000 5000925D
56/116
Chapter 4
48 SCS 4000/5000 Series Installation & Operation Manual
-
7/25/2019 Raven seria 4000 5000925D
57/116
CHAPTER
5
Manual No. 016-0159-925 49
Chapter5Data Menu
Additional features of the SCS console can be modified using the Serial, Product, Console, and CANsubmenus accessed by pressing the DATA MENU key on the SCS keypad. The Data Menu also contains theProduct Summary screens for each product as well as the AutoBoom screen if this feature is installed.
Each time DATA MENU is pressed, the display advances to the next submenu. Pressing the UP and DOWNarrow keys advances to the next option in the current display. Press the CE key to toggle an option setting orthe ENTER key to use the Edit mode to input data.
Note: The Data Menu contains calibrations and settings which are not required for SCS consoleoperation.
The following is a description of the features available under the Data Menu.
Serial SubmenuData Logger
Enables or disables data logging. There must be a Trigger Value and Trigger Unit selected to enable thisfeature. When enabled and saving data to a flash card, the datalog file number will be shown.
Field Reference
Allows user to enter up to a four-digit reference number to represent a job. The Field Reference is included infield begin and field end pages as well as the data logger time/date string.
GPS Baud Rate (SCS 4400/4600 Only)
Set the baud rate that the SCS console should use to communicate to your GPS receiver. Select between1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 baud.
Serial Baud Rate (SCS 4000/4070/5000 Only)
Select 1200 or 9600 baud for serial port communication.
-
7/25/2019 Raven seria 4000 5000925D
58/116
Chapter 5
50 SCS 4000/5000 Series Installation & Operation Manual
Variable Rate Change Alarm
Enable or disable audible and visual alarm upon a variable rate change. When on, an alarm sounds 4 longbeeps when a rate calibration number is changed via the serial port using a valid rate change request datastring.
Trigger ValueThe trigger value determines how often data is sent to the serial port (See Chapter 15, Serial Interface & DataString Formats). The trigger value is the number of trigger units between data strings. Data logger functions willnot work until a non-zero trigger value is set.
Trigger Units
Used in data logging mode. The trigger unit is selectable between feet, meters, or seconds.
Additional Serial Options
SCS 4400/4600:
Data Direction
Select Save Data to Card or Pass Data Through Comm Port (used to communicate to an external device).When Save Data to Card is selected, the datalog software version will be shown for reference.
COM 1 Stop Bits
Select between one or two stop bits for communicating with a GPS receiver.
Datalog Mode
Select between logging GPS and Console Data or GPS Data only. The master switch will pause the datalog if GPS and console data are being recorded. GPS data only creates a continuous log.
VRC
Enable or disable variable rate control through the serial and CAN ports. When VRC is disabled, the SCSconsole will ignore variable rate information.
SCS 4000/4070/5000:
Print Field
Sends data to an optional printer connected to the consoles serial port to print field beginning and field endingpages. This option is not available when the data logger is set to on.
-
7/25/2019 Raven seria 4000 5000925D
59/116
-
7/25/2019 Raven seria 4000 5000925D
60/116
Chapter 5
52 SCS 4000/5000 Series Installation & Operation Manual
PWM Frequency
Used to set the coil frequency of PWM valve (default is 122 Hz). Refer to the PWM control valve manufacturerspecifications for recommended PWM frequency.
Preset PWM Offset (PWM Valves Only)
When valve selection is programmed in PWM-Close mode, this can be set to provide an initial pulse width tothe valve upon turning on booms or product. When programmed to zero, pulse width will return to previousstate. When non-zero, initial pulse width can be selected between 1 (slow) and 255 (full scale). Whenprogrammed in PWM Valve mode, PWM output will not exceed this value if non-zero when booms are off.
Rate Bump Delta
Sets the increment at which rate cal is increased or decreased using INC/DEC switch while in AUTO operation.
Low Flow Limit
If actual volume/minute falls below the assigned limit, the control valve will be controlled to Low Flow Limit and
Low Limit Alarm is activated. This value is automatically proportioned to the percentage of booms that are on(i.e. if the entered low limit is 4 and half the total boom length is shut off, the console automatically reduces thelow limit to 2). Low Limit Value is entered in GPM [lit/ha] or PPM [ka/ha].
Low Tank
When level in tank falls below the volume/tank value, the low level alarm is activated. The alarm will deactivatewhen the booms are turned OFF or a value equal to or greater than the low tank value is entered as theVOLUME/TANK. Entering 0 in Low Tank disables the alarm.
Valve Delay
This value is the delay between when the SCS console will control flow rate after the booms have been turnedon. This setting can be set between 0-9 seconds.
This delay is active if the time between turning OFF and turning ON the booms is less than 30 seconds.
Spreader Constant
The spreader constant should be set at zero when applying liquid products.
See theSpreader Constantsection on page 69for details on calculating the spreader constant. The spreaderconstant may be entered during initial console programming or through the Data Menu.
-
7/25/2019 Raven seria 4000 5000925D
61/116
Manual No. 016-0159-925 53
Data Menu
Page 2
Valve Cal 2
This value can fine tune control valve response and help control application rate oscillations when the consoleis programmed in PWM mode.
When a fast close valve is selected, valve cal 2 is utilized to enable a high resolution rate control for lowerapplication rates. Enter a non-zero value for the time, in milliseconds, which the valve will be fully openedbefore switching into high resolution control. For example, a value of 200 will give the valve a 200 millisecondburst at a full 12V to open the fast valve from the closed position before resuming product rate control. A zerovalue will disable this feature.
Pump Cal/Fan Cal
Set the number of pulses per revolution of the pump or fan for Pump/Fan RPM readout.
Dual Sensor Alarm %
For liquid chemical injection applications, sets tolerance between flow switch monitor and flow readings beforeFLOW SW alarm is enacted. For Gran 3 applications, sets tolerance between dual encoder readings beforeDUAL FLOW alarm is enacted (Boom Select feature must be set up for only booms being used). Out oftolerance condition must be met for 5 seconds before alarm occurs.
Vacuum or Bin Level Alarm
When controlling chemical injection, the vacuum alarm can be enabled or disabled. For granular applications,a bin level sensor can be enabled or disabled. Disable this feature if a bin level sensor is not present or whenthe SCS console is not controlling injection.
Flow Switch Alarm (Chemical Injection Unit)
When controlling chemical injection, the flow switch alarm can be enabled or disabled. Disable when notcontrolling injection.
Note: The flow switch alarm setting is only displayed for products controlled by a motor control node.
Valve Advance (Standard or Fast Valve)
This feature allows the operator to set the amount of time (in seconds) in which the valve will be opened uponall boom sections being turned off and control in automatic (AUTO). A value of 1-9 means an advance of 1-9seconds respectively. A value of 0 means no advance. This setting may be used in conjunction with the valvedelay for low rate applications to build up pressure when the master switch is toggled on. For best results,
approach the headlands at consistant speeds while turning all boom sections off.
Pressure
When equipped with pressure transducer(s), this area will display the current PSI [KPA/BAR]. Press CE totoggle between PSI, KPA, and BAR. If no pressure transducer is installed, NOT INST will be displayed.
-
7/25/2019 Raven seria 4000 5000925D
62/116
Chapter 5
54 SCS 4000/5000 Series Installation & Operation Manual
Pressure 1 Cal
Used to calibrate pressure transducer #1. With pump turned off and 0 PSI [KPA] on the line, enter a Pressure 1of 0.
Pressure 2 Cal
Used to calibrate pressure transducer #2. With pump turned off and 0 PSI [KPA] on the line, enter a Pressure 2of 0.
Agitator
If equipped with an injection system featuring an agitator enabled output, this option enables or disables achemical agitator.
PWM Output
Indicated position (output status) of PWM valve. Value will range from 0 (valve fully closed) to 255 (valve fullyopen). This can be used to fine tune the PWM low and high offsets.
VLV STATUS (when not programmed in PWM mode)
Displays the current status of the control valve (i.e. increasing, decreasing or idle) and gives further detail onthe control status (Full on, in second breakpoint, or in first breakpoint).
Console Submenu
ContrastPress ENTER to adjust the screen contrast. Press and hold the UP ARROW key to lighten or the DOWN
ARROW to darken. Press ENTER when complete.
Audible Alarm
Press the CE key to toggle audible alarm ON or OFF.
Display Smoothing
Press the CE key to toggle display smoothing ON or OFF. Display Smoothing ON means the displayed RATEwill be the target rate if the actual rate is within 10% of the target rate. The actual rate is displayed if theconsole does not reach deadband within 10 seconds. Display Smoothing OFF means the displayed RATE willbe the actual rate at all times.
Time, Month, Day, and Year
These selections are used to set the current date and time. Enter the last two digits of the current year.
-
7/25/2019 Raven seria 4000 5000925D
63/116
Manual No. 016-0159-925 55
Data Menu
Days Wait
Set the number of days after the console is powered off before the console goes into very low powerconsumption mode and time settings are lost.
Data Lock
Prohibits the entry of calibration values without first entering the DATA-LOCK code. Enter a 4-digit securitycode or 0 to disable.
PGM REV Update
Displays the SCS console software program number and revision level.
The SCS console can be updated by pressing ENTER to initialize console update procedure via serial port.
Requires programming software, PC with null modem cable, and replacement firmware (See Chapter 14, SCS4000/5000 Series Firmware Update Procedure).
Ratio Rate
Enable or disable ratio rate application mode. When enabled, products 2 and above will apply in ratio toproduct 1 flow (See Chapter 12, Ratio Rate Feature).
Zero Speed Shutoff
Enable or disable low speed shutoff feature. If enabled, product control will be shut off if speed drops below 0.7MPH [km/H] in automatic mode. The master switch must be cycled OFF and then ON to restart the system. If aconstant speed greater than 0.7 MPH [km/H] is not attained within 10 seconds, the low speed shutoff will beenacted again.
CAN Submenu
Boom Sense and Speed Node
Indicates status of boom sense/speed node. Installation required for use with SCS 4000 or SCS 5000 system.Installed on-board with SCS 4400 or SCS 4600.
-OR-
Speed Signal Source (SCS 4070 Only)Press CE to toggle speed signal source between Console and Speed/AccuBoom node (if equipped).
AutoBoom Control Node
Indicates status of AutoBoom control node. This screen will only display if an AutoBoom node is installed.Refer to the AutoBoom Calibration & Operation Manual for detailed setup instructions.
-
7/25/2019 Raven seria 4000 5000925D
64/116
Chapter 5
56 SCS 4000/5000 Series Installation & Operation Manual
Product Control Node 1
Installation required for use with SCS 4000, SCS 4070, or SCS 5000. Installed on-board with SCS 4400 orSCS 4600. The program and revision number of the product control node will be displayed if installed.
Product Control Node 2
Indicates status of CAN product control node #2. Program and revision of node will appear if installed.
Product Control Node 3
Indicates status of CAN product control node #3. Program and revision of node will appear if installed.
Product Control Node 4
Indicates status of CAN product control node #4. Program and revision of node will appear if installed.
Product Control Node 5
Indicat