  • RCC SUMP DESIGN

    REFERENCE :1. IS 456-2000.2. IS 3370-2009 Part 1&2.3. SP-16 -1978.

    DATA :Sump Size : 5.0m (L) X 2.0m(B) X 1.25m(H)Concrete Grade : For cover slab M20. For Tank M25.Steel Grade : Fe 415

    Unit weight of water : 10 KN/m3Live Load for Cover slab 2 KN/m2

    DESIGN:DESIGN OF COVER SLAB:Slab size : 2.0m x5.0mL/B =5.0/2.0=2.50> 2.0Hence the slab has to be designed as oneway slab.d required =2000/25 =80mm.However from deflection point of view provide D=120mmd=120-20-10/2=95mm.Loads:Live Load =2.0KN/m2Self weight 0.12x25 =3.0KN/m2Finishing =1.0KN/m2Total Load =6.0KN/m2Effective span =2.0+0.095=2.095mBending Moment =Wl2/8 = 6.0x2.0952/8

    = 3.29 KN.m.Factored B.M. =4.94 KN.m.Mu.lim. =0.138 fck b d2

    =0.138 x 20x 1000 x 952=24.91 KN.m

    Hence under reinforced section.K= Mu/b d2 =4.94 x106/1000 x 952 =0.55From Table 2 of SP 16 pt =0.158Ast= 0.158 x 1000 x 95 =150 mm2 100Using 10mm bars spacing = ast x 1000 Ast =78.5 x 1000 =523 mm 150Max spacing limit to 3d (3x95=285) or 300mm whichever is less.Provide 10mm dia bars at 200mm C/c. (Ast provided=392.5mm2)

  • Distribution Steel :Mini. Ast = 0.12 x 1000x 120 =144mm2 100Using 8mm bars spacing = ast x 1000 Ast =50 x 1000 =347 mm 144Max spacing limit to 5d (3x85=430) or 450mm whichever is less.Provide 8mm dia bars at 200mm C/c.

    Check for Deflection :Actual span ratio = 2095/95 =22.05 d

    For pt= 392.5 x 100 = 0.4132 1000 x 95 Max. Permissible Span ratio from Chart 23 of SP16 =25.20 > 22.05 dHence O.k.

    DESIGN OF WATER TANKDESIGN OF SIDE WALL:

  • This has to be designed by Working Stress Method with the following permissible stresses to avoid leakage problem..Using M25 concrete and Fe415 (HYSD) steel cbc = 8.50N/mm2 st=150 N/mm2

    Design Constants:m=Modular ratio =280/3 cbc = 280 =10.98 =11.00 3x8.5

    n = m cbc = 11 x 8.5 = 0.384 m cbc+ st 11x8.5+150

    j= 1 n = 1- 0.384/3 = 0.872 3

    K = cbc n j =1/2 x 8.50 x 0.384 x 0.872 =1.423The water tank has to be designed for the following two cases.

    1) Tank is full and no earthfill outside.2) Tank is empty and active earth pressure acting from outside.

    Case 1: When Tank is full and no earth pressure outside

  • Long Wall:

    Ph = w xH=10 x 1.25 =12.5 KN/m2

    Cantilever moment M= (1/2x12.5 x 1.25) x1.25/2=4.88 KN.m

    Ast = M/ st x j = 4.88 x 10 6 =327 mm2 150x0.872x120

    Using 10mm dia bars spacing required = = 78.5 x 1000 = 240 mm 327

    Provide 10 mm bars at 150 mm C/c near inner face in vertical direction.

    Horizontal bars in Long wallSince long wall is predominantly acting as a cantilever, distribution steel is provided & checked for axial Tension when tank is full without earth pressure from outside.Mini. % of steel = 0.30 x 1000 x 150 = 450mm2 100 Using 10 mm bars spacing required = 78.5 x 1000 = 174 mm 450

    Provide 10mm bars at 150mm C/c inside the face.

    Check for Direct Tension :TL= w (H-h) B/2 = 10 x (1.25-1.0) 2.0/2=2.50KN,Ast required = 2.50 x 10 3 = 17 mm2 150Distribution steel takes care of this Tensile forces .

    Case 2: When Tank is empty Ph =k 1 + wH whereK= 1- sin = 1-sin 30 =1/3 1+ sin 1+ sin 30

    1s= s- w =16-10=6 KN/m2

    Ph= (1/3 x 6x 1.25) +(10x1.25) =15.0KN/m2M=(1/2 x 15.0x HxH/3) =(1/2x 15.0 x 1.25x 1.25/3) =3.91 KN.m.Depth of balanced section = sqrt M/k b = Sqrt 3.91 x 10 6 1.423x1000 =52.42mmHowever provide D=150mm, d=150-20-10/2=128mm

  • Ast required = M/ st j = 3.91 x 10 6 150 x0.872x 128 =234mm2

    Using 10mm bars spacing required = 78.5 x 1000 =335mm 234

    Provide 10mm bats at 150mm C/c near inner face of the wall.

    DESIGN OF SHORT WALL :Vertical reinforcement :

    Cantilever action height for lower portionh= H/4 or 1m whichever is more =1m.When water tank is empty and outside soil is saturated ph=(1/3x6x1.25)+(10x1.25)=15KN.m2M= 1/2x15.0x1.0x1.0/3 =2.50KN.m

    Ast = M = 2.50 x 10 6 st x j 150x0.872x128 = 129mm2

    Direct compression due to load on 1m wide long wallP= 15.0 x (1.25-1.0) x1.0 =3.75 KN.Concrete alone can resist if water tank is full and no earth fill.Ph= 10 x 1.25 =12.50KN/m2M= x 12.50 x 1.0x 1.0/3 =2.08 KN.m quite small.Provide mini reinforcement in vertical direction which is 10mm at 150mm C/c

    At Mid span : B.M. is half of 2.08/2 =1.04 KN.m Provide same reinforcement 10mm bars at 150mm C/c near outer face.

  • DESIGN OF BASE SLAB:

    Assume thickness of base slab =200mmd = 200-50-12/2=144mmHeight from base slab =1.25+0.20=1.45mUpward pressure when soil is saturated =10x1.45 =14.50 KN/m2In bottom slab there is no projection.

    Downward Loads:Weight of top slab =0.12x5.30x2.3x25 =36.57KN.Weight of long wall =2x0.15x5.30x1.25x25 =49.69KNWeight of short wall =2x0.15x2.3x1.25x25 =21.56KNWeight of bottom slab =5.30x2.30x0.20x25 =60.95KNTotal Load =168.77KNUplift force on bottom slab= 14.50(5.30+2.30)=110.20KNSince downward force is more than uplift force on bottom slab, projection is not required.Provide 150mmx 150mm haunches at junction. Provide junction reinforcement 10mm bars at 150mm C/c.Self weight of slab directly get transmitted to soil.Net upward soil pressure=(10x1.45)- (0.2x1x1x25) =14.50-5.0=9.50KN/m2

    Bending moment:Considering net upward pressure B.M.=9.50x2.152/8=5.49 KN.mConsidering weight of water alone B.M. =(10x1.25)x 2.152/8=7.22KN.mConsidering higher moment, Ast required = M = 7.22 x 10 6 st x j 150x0.872x144 = 383mm2

  • Minimum Ast = 0.3 x 1000x 200 = 600mm2 100

    Using 12mm bars spacing = 113 x 1000= 188mm 600Provide 12mm bars at 150mm C/c

    Distribution Steel:Mini. Ast = 600mm2Ast on each face =600/2 = 300mm2Using 10mm dia bars spacing = 78.5 x 1000 300Provide 10mm dia bars at 150mm C/c in longitudinal direction near both faces.