real-time software-in-the-loop performance analysis of synchrophasor-and-active load-based power...
TRANSCRIPT
RT-SIL Performance Analysis of Synchrophasor-and-Active Load-BasedPower System Damping Controllers
G.M. Jónsdóttir*, M.S. Almas*, M. Baudette*, M.P. Palsson¶, L.Vanfretti*†
*Electric Power Systems Division, KTH Royal Institute of Technology, Stockholm, Sweden†R&D Department, Statnett SF, Oslo, Norway, ¶System Planning Department, Landsnet, Reykjavik, Iceland
Introduction
Test System Modelling
Load Controls
Conclusions and Future Work
Discussion and Simulation Results
· Algorithm 1 provides quicker oscillation damping.
· Algorithm 2 best suits to the TSOs where load shedding is undesirable to perform oscillation damping.· Future work:
Deploy load control algorithm on an external controller and test the algorithm in RT-HIL. Analyze flexibility of the algorithm using both local and remote signals from a real PMUs.
· Transmission constraints in the Icelandic power system often lead to inter-area oscillations.
· Conventional stabilization methods have been applied, not enough.
Idea: Control industrial load.
· Introduce two damping controllers with synchrophasor signals and local measurements as inputs.
· Damping is achieved by load modulation generated by a phasor-based oscillation signal.
· RT-SIL testing is performed using Opal-RT’s eMEGAsim Real-Time Simulator.
· First step towards testing in RT-HIL.
G1
G2
Area 1Area 1
Local Loads
900 MVA900 MVA
900 MVA900 MVA
900 MVA20 kV / 230 kV
900 MVA20 kV / 230 kV
25 Km25 Km 10 Km10 Km
900 MVA20 kV / 230 kV
900 MVA20 kV / 230 kV
967 MW100 MVAR (Inductive)
-387 MVAR (Capacitive)
967 MW100 MVAR (Inductive)
-387 MVAR (Capacitive)
220 Km Parallel Transmission Lines
220 Km Parallel Transmission Lines
Power TransferArea 1 to Area 2
Power TransferArea 1 to Area 2
10 Km10 Km 25 Km25 KmG3
900 MVA900 MVA
900 MVA20 kV / 230 kV
900 MVA20 kV / 230 kV
G4
900 MVA20 kV / 230 kV
900 MVA20 kV / 230 kV
900 MVA900 MVA
Local
Loads
1767 MW100 MVAR (Inductive)
-537 MVAR (Capacitive)
1767 MW100 MVAR (Inductive)
-537 MVAR (Capacitive)
Area 2Area 2
Bus1Bus1 Bus2Bus2
Phasor POD
Load Control
Algorithm
Local/RemoteMeasurement
Local/RemoteMeasurement
Oscillatory Content
Oscillatory Content
Load Modulation
Load Modulation
Phasor-POD: is the approach used to generate the command signal for the load control. It separates the oscillatory part from the measured value of the input signal.
Algorithm 1: Increase load at peak of oscillation, shed load at minimum of oscillation.
Algorithm 2: Same as Algorithm 1 except block when load should be shed.
Software-in-the-Loop Validation
MATLAB/SimulinkSimPowerSystems
Model
Model Splitting into Sub-systems for
RT-Simulation
Real-Time Model Simulation in RT
Targets
RT-Lab Software Interface Compiles and Loads the Model into
RT-Targets64 Analog Out
16 Analog In
Simulator Analog and Digital I/Os
OP 5251 (64 DO) Digital Output and Digital Input are looped back
Control Signal from Simulink Load control model is configured to one of the Digital Output of the Simulator
OP 5251 (64 DI)
Control Signal is received at one of the Digital input of the Simulator which is configured in the Simulink Model to change the load.
Workstation with RT-LAB software Interface. Provides console for monitoring real time simulation
Scenario 1: A small disturbance in the form of 5% positive magnitude step in the reference voltage of Generator 1 applied for 4 cycles at t = 60 sec.
Scenario 2: A large disturbance in the form of three phase to ground fault (4 cycles, i.e. 80 ms) at t = 60 sec in the middle of one of the two 220km transmission lines connecting together the two areas.
55 60 65 701.5
2
2.5
3
3.5
4
4.5
5
5.5
6x 10
8
Time [s]
Po
we
r tr
an
sfe
red
fro
m
A
rea
1 t
o A
rea
2 (
Wa
tts
)
Scenario 2: Large Disturbance (Three Phase to Ground Fault for 4 cycles) Power Transfer between Area 1 and Area 2
No Active Load Control
Load Control Algorithm 1
Load Control Algorithm 2
62 64 66 68 70 72 74
1.6
1.62
1.64
1.66
1.68
1.7
1.72
x 109
Time [s]
Ac
tiv
e P
ow
er
Co
ns
um
pti
on
by
Dy
na
mic
Lo
ad
in
A2
(W
att
s)
Scenario 2: Large Disturbance (Three Phase to Ground Fault for 4 cycles) Load Control in Area 2
No Active Load Control
Load Control Algorithm 1
Load Control Algorithm 2
55 60 65 70
3
3.5
4
4.5
5
x 108
Time [s]
Po
we
r tr
an
sfe
red
fro
mA
rea
1 t
o A
rea
2 [
Wa
tts
]
Scenario 1: Small distrubance (5 % Change in Vref
of Generator 1)
Power Transfer Between Area 1 and Area 2
No Active Load Control
Load Control Algorithm 1
Load Control Algorithm 2
55 60 65 70 75
1.63
1.64
1.65
1.66
1.67
1.68
x 109
Time [s]
Scenario 1: Small distrubance (5 % Change in Vref
of Generator 1)
Load Control in Area 2
No Active Load Control
Load Control Algorithm 1
Load Control Algorithm 2
Act
ive
Po
we
r C
on
sum
tio
nB
y D
ynam
ic L
oad
in A
2 (
MW
)
RLS or Low Pass Filtering based
Phasor Extraction Phase
Shift
Δω
Poscillatory
Phase angle computation
Input signal
Unit delay
PIController
Free Running Oscillator
∑
ω
ωt
∑
Paverage
d/dt <0
max
Switch
min
Only for Case 1
Load control algorithm
Damping signal