Effective from: 03.03.2017 Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations as per RDSO/SPN/218/2016 Ver. 1.0-d0 Version- 1.0 Page 1 of 15 Signature Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal Check By: K.K. Singh ADE/Signal-II Issued By: G. Pavan Kumar Director/Signal-II REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM FOR SIGNALLING INSTALLATIONS SPECIFICATION No. RDSO/SPN/218/2016 Version 1.0 Number of Pages -15 Issued by SIGNAL DIRECTORATE RESEARCH, DESIGNS & STANDARDS ORGANISATION MINISTRY OF RAILWAYS MANAK NAGAR LUCKNOW 226 011

Upload: others

Post on 10-Oct-2019

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 1 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

REASONED DOCUMENT

FOR

AUTOMATIC FIRE SUPPRESSION SYSTEM

FOR

SIGNALLING INSTALLATIONS

SPECIFICATION No. RDSO/SPN/218/2016 Version 1.0

Number of Pages -15

Issued by

SIGNAL DIRECTORATE RESEARCH, DESIGNS & STANDARDS ORGANISATION

MINISTRY OF RAILWAYS MANAK NAGAR

LUCKNOW – 226 011

Page 2: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 2 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

DOCUMENT DATA SHEET

RDSO/SPN/218/2016

Version 1.0

Title of Document REASONED DOCUMENT ON DRAFT SPECIFICATION FOR AUTOMATIC FIRE SUPPRESSION SYSTEM FOR SIGNALLING INSTALLATIONS

Authors

See Document Control Sheet

Approved by RDSO Name: Shri. Sandeep Mathur Designation: Executive Director/Co-Ordination/Signal RDSO, Lucknow- 226 011

Abstract

REASONED DOCUMENT ON DRAFT SPECIFICATION FOR AUTOMATIC FIRE SUPPRESSION SYSTEM FOR SIGNALLING INSTALLATIONS

Page 3: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 3 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Document Control Sheet

Name Organization Function Level

Shri Ranjeet Singh JE (D)/Signal

RDSO Member Prepare

Shri K.K. Singh ADE/Signal-II

RDSO Member Check

Shri G. Pavan Kumar Director/Signal-II

RDSO Member Issue

Page 4: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 4 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

REASONED DOCUMENT ON DRAFT SPECIFICATION FOR AUTOMATIC FIRE SUPPRESSION SYSTEM FOR SIGNALLING INSTALLATIONS Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

0.3 (c) 0.1 Indian Standards ---

M/s MX Systems International Pvt. Ltd.: Please add following Standards:

IS: 2190; Selection, Installation & Maintenance of First Aid Fire Extinguishers. IS: 15908; Selection, Installation & Maintenance of Control Indicating Equipment for Fire detection & Alarm System. IS: 2190 provides basic guidelines for selection and distribution of portable fire extinguishers. IS: 15908 provide specific guidelines for Fire Alarm Control Panels.

Not agreed as already covered in the specification of AFDAS.

4.1.1.1 0.2 Clean Agent Filled Containers as per IS: 7285. ---

M/s Pyrogaurd Engineers Pvt. Ltd.: Clean agent filled container as per IS: 7285 and as per OEM UL Listing. Cylinder sizes should be as per UL listing of OEM as only then can be give you the correct software generated results and proposed UL approved system.

Agreed & the clause 5.2.1.7 modified.

4.1.1.4 0.3 Automatic Fire Suppression System Control Panel(AFSSCP)

--- M/s NASA Fire Technology Ltd.: Automatic Fire Suppression System Control Panel(AFSSCP) (Optional)

Not agreed as AFSSCP is required for central monitoring unit of all the protected rooms.

4.1.2.1 0.4 In-cabinet automatic fire suppression system monitoring panel (ICMP)

--- M/s NASA Fire Technology Ltd.: In-cabinet automatic fire suppression system monitoring panel (ICMP) (Optional)

Not agreed as ICMP is required for monitoring unit of all the protected equipment.

4.2 0.5 The TFAFSS shall be either initiated automatically or manually.

---

M/s Pyrogaurd Engineers Pvt. Ltd.: The TFAFSS must be initiated both automatically & manually because if any of the system fails then you should have other option for releasing/ discharging the system manually.

Agreed and modified.

(Clause Modified as: The TFAFSS shall be initiated by both automatically as well as manually.)

M/s NASA Fire Technology Ltd.: The TFAFSS shall be both initiated automatically and manually.

0.6 M/s MX Systems International Pvt. Ltd.:

Page 5: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 5 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

The TFAFSS shall be actuated automatically on activation of initiating device (Detectors/MCP). The system shall have provision for manual actuation.

0.7 Activation of gas suppression system on auto mode is mandatory requirement as per standards and codes. Manual activation of system can be an additional provision.

4.3 0.8 The ICAFSS shall be suitable to suppress fire/ fire

like situation inside electrical cabinets, transformers, invertors, cable trays and electronic equipment.

---

0.9 M/s MX Systems International Pvt. Ltd.: Please remove; transformers, invertors, cable trays and electronic equipment from the clause.

0.10 The ICAFSS is a pre-engineered system designed to self-detect, actuate & suppress fire/fire like situation within electrical/electronic equipment cabinet before fire could cause damage to any of the above equipment.

0.11 This system is not meant for open surfaces including transformers, invertors, cable trays and electronic equipment as stated in clause 4.3

Not agreed since ICAFSS is meant to protect the equipment. However the equipment shall be closed if protection is planned for.

4.8 0.12 The TFAFSS shall have manual override to initiate TFAFSS or to disable the system.

--- 0.13 M/s Pyrogaurd Engineers Pvt. Ltd.: This

clause is not required (See clarification of clause 4.2 above)

Not agreed.

4.15

0.14 A Lock off valve shall be provided in the discharge pipe between the nozzle and agent supply. This shall be used to prevent discharge of clean agent through distribution pipe work to the protected area during maintenance. The position of Lock off valve shall be monitored by AFSSCP.

---

0.15 M/s Pyrogaurd Engineers Pvt. Ltd.: This clause is not required because Abort switch and other mechanism to prevent discharge of clean agent is already there.

Not agreed.

4.16.3 It shall be friendly to the ozone layer & shall not deplete the oxygen content. ---

M/s NASA Fire Technology Ltd.: It shall be friendly to the ozone layer and shall have minimal ozone depletion potential (not more than 0.1)

Agreed and modified partially.

(Clause Modified as: It shall be friendly to the ozone layer. While discharge, it shall not deplete the oxygen content

Page 6: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 6 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

beyond NOAEL level.)

4.16.5

The containers used for ICAFSS shall be Steel containers manufactured to IS: 7285/IS: 15683 and shall be type approved as per the relevant IS Specification.

---

M/s Supremex Equipments: The container used for ICAFSS shall be Steel containers manufactured to IS: 7285/IS: 15683 and shall be type tested as per the relevant IS Specification.

Not agreed as per the requirement of IS: 7285/IS: 15683 indicates so.

4.16.6

There shall be arrangement of refilling ones the fire extinguisher system is operated. Refilling shall be done at PESO Authorized filling stations. The refilling, transportation of empty and filled container shall be responsibility of manufacturer. Thereafter this activity shall be carried out by manufacturer as per the terms and conditions agreed between purchaser and manufacturer.

---

M/s Pyrogaurd Engineers Pvt. Ltd.:

There shall be arrangement of refilling ones the fire extinguisher system is operated. Refilling shall be done at PESO & UL Authorized filling stations. The refilling, transportation of empty and filled container shall be responsibility of manufacturer. Thereafter this activity shall be carried out by manufacturer as per the terms and conditions agreed between purchaser and manufacturer.

As per UL requirement if gas is filled in a Non-UL listed filling station then the complete system also become Non-UL as the quality of gas is not assured. The Filling station must be UL approved for maintaining purity and Quality of Clean agent shall be monitored by AFSSCP.

Not agreed since PESO is competent authority in India.

4.17

The TFAFSS shall be installed along with the fire preventive measures described as follows: (This clause is optional for ICAFSS manufacturer)

---

M/s MX Systems International Pvt. Ltd.: To be removed or should be put in scope of customer/others The fire preventive measures described from 4.17.1 to 4.17.8 cannot be in scope of system suppliers and thus should be kept out of scope of supplier/ contractor.

Not agreed since fire protective measures shall form an integral part of AFSS.

Page 7: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 7 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

4.17.2 Air conditioner fire detection and suppression device

---

M/s NASA Fire Technology Ltd.: Air conditioner fire detection and suppression device that also helps in preventing the spread of fire.

Agreed and modified.

4.17.5

0.16 Self-Contained Breathing Apparatus and Protective dress at least two sets for each signalling installation provided with AFSS.

---

M/s Ceasefire Industries Pvt. Ltd.: The technical specifications are required for 4.17.5. If it is in the scope of supply of the vendor who supplies TFAFSS/ICAFSS

Agreed and modified.

It is in the scope of TFAFSS. It is indicated in the clause No. 4.17. (Clause Modified as: Self-Contained Breathing Apparatus as per IS: 10245 Part IV and Protective dress at least two sets for each signalling installation provided with AFSS.) Accordingly Clause 0.3 (c) also modified.

5.1.6 ---

---

M/s NASA Fire Technology Ltd.: Add new point "Clean agent shall be certified non-conductive up to 100KV power supply (AC/DC) as per UL711"

Agreed and added.

(Clause Added as: Clean agent shall be certified non-conductive up to and at least 25KV (AC/DC))

5.2.1.4

The maximum permitted time to extinguish a fire with a halocarbon agent shall not exceed 10 seconds as per clause no. 5.7.1 of NFPA 2001

---

M/s NASA Fire Technology Ltd.: The maximum permitted time to extinguish a fire with a halocarbon agent shall not exceed 20 seconds.

Not agreed.

5.2.1.6

0.17 For safety reasons, the clean agent AFSS container-valve, discharge hose, nozzles must be provided from the same manufacturer to ensure proper performance as a system with UL/FM/Vds/LPCB approvals, thereby giving a confidence that a third party has tested the performance of the whole unit as a system.

---

M/s Pyrogaurd Engineers Pvt. Ltd.: For safety and Quality reasons, the clean agent AFSS container-valve, discharge hose, nozzles, Electric actuators/ Solenoid valve, Check valve, Pressure Release Valve (PRV), Inter-connected Hose, Non-Return Valve (NRV), Manual release station, Supervisory switch for cylinder pressure, Pressure Switch and Pressure gauge must be provided from the same manufacturer to ensure proper performance as a system with UL/FM/Vds/LPCB approvals, thereby giving a confidence that a third party has tested the performance of

Agreed and modified.

(Clause Modified as: For safety and Quality reasons, the clean agent AFSS container-valve, discharge hose, nozzles, Electric actuators/ Solenoid valve, Check valve, Pressure Release Valve (PRV), Inter-connected Hose, Non-Return Valve (NRV), Manual release station, Supervisory switch for cylinder pressure, Pressure Switch and Pressure gauge must be provided from the same manufacturer to ensure proper performance as a system with

Page 8: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 8 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

the whole unit as a system. UL/FM/Vds/LPCB approvals, thereby giving a confidence that a third party has tested the performance of the whole unit as a system..)

5.2.1.7

Container for TFAFSS shall be seamless steel type manufactured and tested in accordance with IS: 7285 standard approved by PESO.

---

M/s Pyrogaurd Engineers Pvt. Ltd.: The seamless Steel container should be UL listed and Approved by PESO and sizes of Cylinder are as per UL listed of OEM.

Agreed and modified.

(Clause Modified as: Container for TFAFSS shall be seamless steel type manufactured and tested in accordance with IS: 7285 standard approved by PESO. The sizes of container shall be per UL/FM/Vds/LPCB approved.)

5.2.1.8 Container shall be actuated by either a resettable electric actuator or by manual actuator.

---

M/s Pyrogaurd Engineers Pvt. Ltd.: Container should be actuated by both electrically and manually for better safety reasons.

Agreed and modified.

(Clause Modified as: Container shall be actuated by resettable electrical actuator as well as by manual actuator.)

5.2.1.10

0.18 The low-pressure switch shall be wired to the AFSSCP to provide audible and visual "Trouble" alarms in the event the container pressure drops below the value, which is to be specified by Manufacturer of Clean Agent.

---

M/s Ceasefire Industries Pvt. Ltd.: The low-pressure switch shall be wired to the AFSSCP to provide audible and visual "Trouble" alarms in the event the container pressure drops below the value, which is to be specified by Manufacturer of of Clean Agent TFAFSS.

Agreed and modified.

0.19 (Clause Modified as: The low-pressure switch shall be wired to the AFSSCP to provide audible and visual "Trouble" alarms in the event the container pressure drops below the value, which is to be specified by Manufacturer of TFAFSS.)

5.2.1.12

Each pressure gauge shall be calibrated for its „accuracy‟ & „precision in reading‟ from a reputed calibrating agency as per IS: 3624. The calibration of pressure gauges shall be done by the calibrating agency, which shall issue a certificate of calibration & fix a non-erasable and non-peelable by hand sticker bearing validity of calibration at the time of supply.

---

M/s Pyrogaurd Engineers Pvt. Ltd.: Not required if Pressure Gauge is UL Listed / a part of UL listed system.

Agreed for inclusion of certification agency but not for exclusion of calibration.

(Clause Modified as: Each pressure gauge shall be UL/FM/Vds/LPCB approved and calibrated for its „accuracy‟ & „precision in reading‟ from a reputed calibrating agency as per IS: 3624. The calibration of pressure gauges shall be done by the calibrating agency, which shall issue a certificate of calibration & fix a non-erasable and non-peelable sticker

Page 9: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 9 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

bearing validity of calibration at the time of supply.)

5.2.3 STORAGE CONTAINER ARRANGEMENT FOR TFAFSS ---

M/s Pyrogaurd Engineers Pvt. Ltd.: Storage container arrangement for TFAFSS - should be UL/FM/Vds/LPCB approved for safety and Reliability.

Agreed and included in clause 5.2.1.6.

5.2.4 NOZZLES FOR TFAFSS

---

M/s Pyrogaurd Engineers Pvt. Ltd.: Nozzles for TFAFSS - should be UL/FM/Vds/LPCB approved for safety and Reliability.

Agreed and included in clause 5.2.1.6.

5.2.5 VALVE FOR TFAFSS

---

M/s Pyrogaurd Engineers Pvt. Ltd.: VALVE for TFAFSS - should be UL/FM/Vds/LPCB approved for safety and Reliability.

Agreed and included in clause 5.2.1.6.

5.2.6 ELECTRIC ACTUATOR FOR TFAFSS

---

M/s Pyrogaurd Engineers Pvt. Ltd.: ELECTRIC ACTUATOR for TFAFSS- should be UL/FM/Vds/LPCB approved for safety and Reliability.

Agreed and included in clause 5.2.1.6.

5.2.8.1

The discharge time required to achieve 95% of the minimum design concentration with at least 20% safety factor for the fire suppression shall not exceed 10 seconds.

---

M/s NASA Fire Technology Ltd.: The discharge time required to achieve 95% of the minimum design concentration with at least 20% safety factor for the fire suppression shall not exceed 20 seconds.

Not agreed as this clause is framed as per clause 5.7.1.1 of NFPA 2001: 2015.

5.2.9 MANUAL ACTUATOR FOR TFAFSS

---

M/s Pyrogaurd Engineers Pvt. Ltd.: MANUAL ACTUATOR for TFAFSS- should be UL/FM/Vds/LPCB approved for safety and Reliability.

Agreed and included in clause 5.2.1.6.

Page 10: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 10 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

5.2.10 ABORT SWITCH FOR TFAFSS

---

M/s Pyrogaurd Engineers Pvt. Ltd.: ABORT SWITCH for TFAFSS- should be UL/FM/Vds/LPCB approved for safety and Reliability.

The Pull type Abort Switch should be prefer over Glass type Abort switch because if accidently or anyhow, glass is broken, the whole gas would be released.

The type of abort switch is left to the manufacturer.

M/s MX Systems International Pvt. Ltd.: We should add more point in abort switch as follows: If the abort switch is initiated before the automatic discharge delay expires, the system will prevent agent release and the automatic delay timer will stop. When the abort switch is restored, the automatic delay timer will resume from the stop point and agent release will occur with the expiration of the timer. This is required for right functioning of system.

Agreed and the proposal is added to clause 5.2.10.5.

5.2.12.1

The AFSSCP shall be of PLC/microcontroller based with monitoring for AC power ON, System ON, system discharge, electrical actuator status, pressure healthy, position of lock off valve, removal of clean agent container and battery low by LED indicator and system operation by LED strobe light and buzzer.

---

M/s NASA Fire Technology Ltd.: Rewrite as "AFSSCP shall be accompanied with LED indicators and system operation by LED strobe light and buzzer."

Not agreed as the AFSSCP is central monitoring unit of the system.

5.2.12.2

Necessary inputs for discharge, pressure switch, trigger from AFDAS and ICMP shall be provided means of potential free contact. Zone wise discharge facility shall be available. All outputs shall have potential free relay contact (NO/NC).

--- M/s NASA Fire Technology Ltd.: Need for this clause? "All the outputs shall have potential free relay contact (NO/NC)".

Not agreed as the PFCs are used for interfacing to other processes.

5.2.12.4 The AFSSCP shall be fitted in an IP-31 enclosure. --- M/s NASA Fire Technology Ltd.: The AFSSCP shall be fitted in an IP-31

Not agreed as the IP is required.

Page 11: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 11 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

enclosure. (optional)

5.2.12.6

The AFSSCP shall be self-checking & diagnostic type. The data regarding health & event shall be logged in the system with date & time stamp, which could be downloaded to a PC/ Laptop at later stage. The system shall have capacity to store data for up to a minimum of 1000 fire events and 1000 other events. The AFSSCP shall be networkable to the Zonal/Divisional Railway headquarters preferably over TCP/IP and shall have clock synchronization facility.

--- M/s NASA Fire Technology Ltd.: Delete this clause

Not agreed as the AFSSCP is central monitoring unit of the system.

5.2.12.7

It shall be possible to download data from Control unit through suitable ports like RS232/ USB into a PC/Laptop operating on Windows platform. The software for downloading and analysing fault data shall be provided & shall be compatible with windows operating system.

--- M/s NASA Fire Technology Ltd.: Delete this clause

Not agreed as the AFSSCP is central monitoring unit of the system.

5.3

0.20 TECHNICAL REQUIREMENTS FOR IN-CABINET AUTOMATIC FIRE SUPPRESSION SYSTEM(ICAFSS):

0.21

---

M/s Ceasefire Industries Pvt. Ltd.: To be added 5.3 as a separate paragraph for specifications of the valve to be provided.

Valve for In Cabinet Automatic Fire Suppression System:

The bidder must submit TPED certificate for valve in conformity to EN ISO 10297: 2006

The valve has an in built pressure gauge to show the pressure inside the cylinder.

The valve has an integrated position control reed switch of the ball valve for “open” and “close position.

Not agreed since complete functionality of the system is to be ensured.

Page 12: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 12 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

5.3.2

0.22 STORAGE CONTAINER FOR ICAFSS:

0.23 ---

M/s Ceasefire Industries Pvt. Ltd.: To be added 5.3.2 “Storage Container for ICAFSS”:

Each vessel needs to be checked for tensile strength up to 35 kgf/cm

2 and

manufacturer has to submit hydrostatic pressure testing certificate for the same.

The extinguishers should be pressurized using high grade dry nitrogen as per IS: 1747 standard. OEM declaration should be submitted.

Can construction: Deep drawn & CO2

Mig welded.

Internal coating of Can: Epoxy Powder coating.

External coating of Can: Epoxy Polyester Powder coating.

Not agree as containers are PESO approved. PESO approval will take of these parameters if they are approved.

M/s Supremex Equipments: Complete cylinder shall be helium leak tested in order to ensure no pressure drop for 5 years. Individual certificates shall be provided for each cylinder.

Clauses for leak detection test is included in the specification.

5.3.2.5

0.24 The low-pressure switch shall be wired to the ICMP to provide audible and visual "Trouble" alarms in the event the container pressure drops below the value, which is to be specified by Manufacturer of Clean Agent.

---

M/s Ceasefire Industries Pvt. Ltd.: The low-pressure switch shall be wired to the ICMP to provide audible and visual "Trouble" alarms in the event the container pressure drops below the value, which is to be specified by Manufacturer of Clean Agent ICAFSS.

Agreed and modified.

0.25 (Clause Modified as: The low-pressure switch shall be wired to the ICMP to provide audible and visual “Trouble" alarms in the event the container pressure drops below the value, which is to be specified by Manufacturer of ICAFSS.)

M/s NASA Fire Technology Ltd.: Delete this clause

Not agreed.

Page 13: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 13 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

5.3.2.7

Each pressure gauge shall be calibrated for its „accuracy‟ & „precision in reading‟ from a reputed calibrating agency as per IS 3624. The calibration of pressure gauges shall be done by the calibrating agency, which shall issue a certificate of calibration & fix a non-erasable and non-peelable by hand sticker bearing validity of calibration at the time of supply.

---

M/s NASA Fire Technology Ltd.: Each pressure gauge shall be calibrated for its „accuracy‟ & „precision in reading‟ from a reputed calibrating agency as per IS 3624/UL standards. The calibration of pressure gauges shall be done by the calibrating agency, which shall issue a certificate of calibration & fix a non-erasable and non-peelable by hand sticker bearing validity of calibration at the time of supply.

Agreed and modified.

(Clause Modified as: Each pressure gauge shall be UL/FM/Vds/LPCB approved and calibrated for its „accuracy‟ & „precision in reading‟ from a reputed calibrating agency as per IS: 3624. The calibration of pressure gauges shall be done by the calibrating agency, which shall issue a certificate of calibration & fix a non-erasable and non-peelable sticker bearing validity of calibration at the time of supply.)

5.3.3

0.26 DETECTION ARRANGEMENT FOR ICAFSS:

0.27 ---

M/s Ceasefire Industries Pvt. Ltd.: In clause 5.3.3 “Detection Arrangement for ICAFSS” the following points need to be added for better clarity on the system required and its specifications. Heat sensing tube:

The tube must be made of special modified polyamide (PA) in black colour.

Sensor tube UV resistance with pressurization of tube using Nitrogen gas.

Burst temperature at 15 Bar: 150ºC to 180ºC.

Tube‟s other technical specifications should be certified by the OEM of the tube to its own specifications.

Not agreed.

5.3.4.1 The ICMP shall have the facility to trigger the TFAFSS (if provided).

---

M/s MX Systems International Pvt. Ltd.: This clause to be removed. ICAFSS and TFAFSS are different systems and we request not to mix and thus delete this specific requirement of triggering the TFAFSS from ICMP which is meant for ICAFSS.

Not agreed.

Page 14: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 14 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

5.4 0.28 ALARM UNIT (AU):

---

M/s Ceasefire Industries Pvt. Ltd.: Clause 5.4 Alarm unit needs to be removed as it is not required for people to vacate in case of activation of ICAFSS. This provision is required mandatorily for TFAFSS only.

0.29 Clause 5.4.1.1 Modified as: The AU shall be provided for warning of hazardous condition.

5.4.1.1 The AU shall be provided for warning of hazardous condition. It shall provide audio & visual warning alarm for personnel evacuation prior to discharge.

M/s Supremex Equipments: In case of ICAFSS the pressure switch is activated after the system is discharged. In that case prior audio visual alarm is not possible. However alarm is received during discharge. Also since the gas is being released within cabinet, and also due to the fact that localized suppression cylinders are small, the quantity of gas involved is very less hence personnel evacuation is not required. However for the sake of their awareness we can certainly give an alarm during discharge.

0.30 Noted and modified.

6.1.3

The manufacturer seeking approval for TFAFSS shall be a firm whose system shall be UL/FM/Vds/LPCB listed/approved and shall manufacture Container, Valve, Nozzle, Hose, Electric Actuator, Manual Actuator, Alarm Unit and AFSSCP.

---

M/s Ceasefire Industries Pvt. Ltd.: The manufacturer seeking approval for TFAFSS shall be a firm whose system shall be UL/FM/Vds/LPCB listed/approved and shall manufacture Container, Valve, Nozzle, Hose, Electric Actuator, Manual Actuator, Alarm Unit and AFSSCP.

0.31 Not agreed.

6.1.4

The manufacturer seeking approval for ICAFSS shall be a firm which manufactures Container, Valve, Nozzle, and ICMP.

---

M/s Ceasefire Industries Pvt. Ltd.: The manufacturer seeking approval for ICAFSS shall be a firm which manufactures Container, Valve, Nozzle, and ICMP.

0.32 Not agreed.

M/s NASA Fire Technology Ltd.: The manufacturer seeking approval for ICAFSS shall be a firm which manufactures container, valve, nozzle, and ICMP.

Not agreed.

Page 15: REASONED DOCUMENT FOR AUTOMATIC FIRE SUPPRESSION SYSTEM ...rdso.indianrailways.gov.in/works/uploads/File/Resoned Document AFSS... · Effective from: 03.03.2017 Reasoned Document on

Effective from: 03.03.2017

Reasoned Document on Draft Specification For Automatic Fire Suppression System for Signalling Installations

as per RDSO/SPN/218/2016 Ver. 1.0-d0

Version- 1.0 Page 15 of 15

Signature

Name & Designation Prepared By: Ranjeet Singh JE (D)/Signal

Check By: K.K. Singh ADE/Signal-II

Issued By: G. Pavan Kumar

Director/Signal-II

Clause No.

Description Comments by Railways

Comments by the Firm’s

RDSO’s Remarks

8.10.1.3

The standalone electrical actuators (solenoid or equivalent) along with low pressure switch shall be subjected to 10,000 cycle of operation by extending the supply of 24VDC through make & break of contacts at specified time interval. At the end of this test the electrical actuators (solenoid or equivalent) shall be completely functional.

---

M/s Supremex Equipments: As standalone electrical actuator can be subjected to operation not more than 10 times in its life, we can test the endurance of the actuator only up to 10 times of its operational cycle.

0.33 Not agreed.

--- --- ---

M/s MX Systems International Pvt. Ltd.: As Halo carbon based gas suppression systems are available with various pressure arrangements, we recommend to include following two design parameters in specifications: (a) Design Pressure - 50 Bars (b) Design Concentration of 4.2% by volume for Class A hazards and a minimum of 5.85% by volume for Class B.

0.34 Not agreed as it has been left to the choice of manufacturer. Manufacturer has specify these items while applying for vendor registration.