Feeder ProtectionRelay
REF 610
-
7/27/2019 REF610_E
2/27
REF 610
Feeder Protection
ABB
AG
-2-
Introduction
The Feeder Protection Relay REF 610
Basedonthesuccessof
thefamousSPAJ140
-
7/27/2019 REF610_E
3/27
REF 610
Feeder Protection
ABB
AG
-3-
Mechanical design
Basic parts
Metal case
Plastic front plate
Metal rear plate
-
7/27/2019 REF610_E
4/27
REF 610
Feeder Protection
ABB
AG
-4-
Mechanical design
Withdrawable relay unit
Case unit
Plug-in unit
-
7/27/2019 REF610_E
5/27
REF 610
Feeder Protection
ABB
AG
-5-
Mechanical design
Front plate
2 x 16 character alphanumeric
display (LCD)
6-button keypad
Local communication port,
wireless or via cable
3 pre-assigned LEDs
8 programmable LEDs
-
7/27/2019 REF610_E
6/27
REF 610
Feeder Protection
ABB
AG
-6-
Mechanical design
Inputs and outputs176mm
Connectors for
Uaux and I/O
Communication
connectors, e.g.
plastic fibre
Compression
type terminals
Ring-lug typeterminals
-
7/27/2019 REF610_E
7/27
REF 610
Feeder Protection
ABB
AG
-7-
Mechanical design
The CT secondaries are automatically short-circuited when the
relay unit is withdrawn from the case
No need for separate short-circuiting arrangements
CT outputs
-
7/27/2019 REF610_E
8/27
REF 610
Feeder Protection
ABB
AG
-8-
Mechanical design
REF 610 product information under the handle
Easy access of type specifications and ratings
Product information
-
7/27/2019 REF610_E
9/27
REF 610
Feeder Protection
ABB
AG
-9-
Battery backup of the real-time clock (RTC) and memory circuits,
disturbance recorder (DR), etc.
Automatically supervised and easy to change
Mechanical design
Battery back-up
-
7/27/2019 REF610_E
10/27
REF 610
Feeder Protection
ABB
AG
-10-
Flush, semi-flush or surface mounting using suitablemounting accessories
50 mm raising frame for semi-flush mounting
Mechanical design
-
7/27/2019 REF610_E
11/27
REF 610
Feeder Protection
ABB
AG
-11-
Tilted frame for high or low mounting
Mechanical design
-
7/27/2019 REF610_E
12/27
REF 610
Feeder Protection
ABB
AG
-12-
Mechanical design
1. Left side + right side+18c rails
2. Left side x 2 + 12c rails
3. Right side x 2 + 24c rails
Mounting alternatives in COMBIFLEX equipment frames
-
7/27/2019 REF610_E
13/27
REF 610
Feeder Protection
ABB
AG
-13-
Mechanical design
Withdrawable mechanical design
Easy to install and handle > short MTTR
Automatic shorting of main CT secondary circuits
Only the communication card remains with the case Mechanical coding for plug-in unit type identification
Possibility to preinstall and prewire empty case in switchgear
Height 4U (~177 mm)
Depth behind the panel only about 150 mm (100 mm possible!)
Easy mounting - no loose mounting accessories
Both compression type connection and ring-lug terminal connectionof CT secondary wires
IP 54 degree of protection by enclosure of the relay case whenflush-mounted.
-
7/27/2019 REF610_E
14/27
REF 610
Feeder Protection
ABB
AG
-14-
LCD, 2 x 16 characters, alphanumeric
7 languages always supported: English, Finnish, Swedish, German,Spanish, French, Italian
Name or code of protected object in display
IEC symbols / ANSI codes selectable
Fault indications
Five fault recordings with time stamp
Measurements
Currents
Historical data since commissioning, number of ARs etc.
Settings in 2 setting groups
Configurations such as protocol settings etc.
Product information, identification etc.
Functionality of REF 610
Front HMI
REF 610
-
7/27/2019 REF610_E
15/27
REF 610
Feeder Protection
ABB
AG
-15-
Four analogue inputs for currents(IL1, IL2, IL3 and I0)
Two binary inputs (+ 3 additional on the optional I/O-card)
Arc-protection light inputs on communication card (option)
Functionality of REF 610
Inputs
Outputs
Three power output contacts capable of direct CB-operation
One contact has an integrated Trip Circuit Supervision
Double-pole operation also possible on main trip contact Two signal output contacts (+ 3 more on optional I/O-card)
IRF output for self-supervision signalling
REF 610
-
7/27/2019 REF610_E
16/27
REF 610
Feeder Protection
ABB
AG
-16-
Functionality of REF 610
Protection functions IECsymbol
IEEEDeviceNo.
Three-phase non-directional overcurrent protection,
definite time three stages / IDMT one stage
I>, I>>,
I>>>
50/51
Phase discontinuity protection I> 46
Three-phase thermal overload protection for cables > 49
Non-directional earth-fault protection,definite time two stages / IDMT one stage
I0>, I0>> 50/51N
Arc protection ARC 50/50NLCircuit-breaker failure protection CBFP 62BF
Automatic Reclosing 1-3 shots 01 79
Lockout relay 86
REF 610
-
7/27/2019 REF610_E
17/27
REF 610
Feeder Protection
ABB
AG
-17-
Optional ARC Protection (1) Arc detection via light sensor inputs or remote light signal via digital
input
Remotely detected arc (via digital input) can be used without lightdetection HW
Separate trip value settings for phase currents and earth-fault
current
Arc trip based on current and light/DI
Arc I> 0.5 35 x In (Default 2.50xIn)
Arc Io> 5.0 400 % (Default 20%)
Operate time
-
7/27/2019 REF610_E
18/27
REF 610
Feeder Protection
ABB
AG
-18-
Optional ARC Protection (2) Light signal output L>
Can be set to be activated immediately or to be blocked by ARC trip
Operate time
-
7/27/2019 REF610_E
19/27
REF 610
Feeder Protection
ABB
AG
-19-
Other features Phase / residual current measurement (RMS)
Negative phase sequence component measurement
Display of primary values
Fault indications user selectable in IEC symbols or ANSI codes
8 matrix programmable indication LEDs on front
Disturbance recorder (up to 5 s at 800 Hz)
Event buffer (100 events with time stamp)
Recorded data (5 latest events with time stamp)
Alarm indications
Functionality of REF 610
Real time clock for time-stamping (1ms resolution) of events etc.
REF 610
-
7/27/2019 REF610_E
20/27
REF 610
Feeder Protection
ABB
AG
-20-
Other features continue Galvanically isolated binary inputs with a wide input voltage range
Output contact functions freely matrix-configurable
Normally open HD trip contacts, change-over typesignal contacts
Non-volatile memory for
up to 100 event codes
setting values
disturbance recorder data
recorded data of the five last events with time stamp number of AR shots and starts/trips for protection stages
Functionality of REF 610
operation indication messages and LEDs showing the status at the
moment
REF 610
-
7/27/2019 REF610_E
21/27
REF 610
Feeder Protection
ABB
AG
-21-
Front communication (IrDa), supported protocol SPA
Can be used in wireless mode with laptop PC equipped with IrDA portor via cable RS --> IrDa-adapter (USB->RS->IrDa also possible)
Communication with relay indicated with a LED
Rear communication (via optional communication modules)
Supported protocols: SPA-bus slave
Modbus , RTU mode or ASCII mode
IEC 60870-5-103
DNP 3.0 Physical communication:
RS-485,
Plastic or glass fibre
Line-idle mode is user selectable (light-off/light-on)
Functionality of REF 610
Communication
REF 610
-
7/27/2019 REF610_E
22/27
Feeder Protection
ABB
AG
-22-
Module description Supported protocols
Plastic fibre optic SPA, IEC_103, Modbus
Plastic fibre optic with arc detector inputs SPA, IEC_103, Modbus
RS-485 SPA, IEC_103, Modbus
RS-485 with arc detector inputs SPA, IEC_103, Modbus
Combined plastic and glass fibre optic SPA, IEC_103, ModbusCombined plastic and glass fibre optic with arc
detector inputs
SPA, IEC_103, Modbus
DNP 3.0 communication module (RS-485) DNP 3.0
DNP 3.0 communication module (RS-485) witharc detector inputs
DNP 3.0
Optional communication modules
Functionality of REF 610
REF 610
F i li f REF 610
-
7/27/2019 REF610_E
23/27
Feeder Protection
ABB
AG
-23-
Optional I/O modules includes
Three additional signal outputs (SO3, SO4, SO5)
Three additional digital inputs (DI3, DI4, DI5)
Two options with different DI thresholds
Low: 24/48/60/110/125/220/250 Vdc
High: 110/125/220/250 Vdc
Optional I/O modules
Functionality of REF 610
REF 610
F ti lit f REF 610
-
7/27/2019 REF610_E
24/27
Feeder Protection
ABB
AG
-24-
Semi-flush mounting kit
Inclined (tiltied in 25) semi-flush mounting kit
Wall mounting kit
19 Rack mounting kits
Accessories
Functionality of REF 610
REF 610
REF 610 i t h ll
-
7/27/2019 REF610_E
25/27
Feeder Protection
ABB
AG
-25-
REF 610 in a nutshell
Compact, short box, 4U, draw-out
Easy to install and handle, short MTTR
Large variety of mounting accessories / options
Highly flexible basic feeder protection Multifunction, dual setting banks
Auto-reclose functionality as option
Optional arc-protection
High amount of I/O hardware
All I/O fully matrixed, enables optimal use
Freely programmable LED-indicators on front
Multilingual, ANSI / IEC indications
More communication protocols
More recorded / memorised values
REF 610
O d i
-
7/27/2019 REF610_E
26/27
Feeder Protection
ABB
AG
-26-
Ordering key: