Refrigerant PipingA Trane Air Conditioning Clinic
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
period one
Refrigerant Piping Requirements
Refrigerant Piping
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Vapor-Compression Refrigeration
expansionexpansiondevicedevice
condensercondenser
compressorcompressor
evaporatorevaporatorA B
CD
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Interconnecting Refrigerant Piping
compressorcompressor
condensercondenser
evaporatorevaporator
expansion deviceexpansion device
dischargedischargelineline
suctionsuctionlineline
liquidliquidlineline
A
B
C
D
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Refrigerant Piping Requirements
Return oil to compressor Ensure that only liquid refrigerant enters
the expansion device Minimize system capacity loss Minimize refrigerant charge Insulate lines that are routed through very
warm spaces (Liquid line)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Scroll Compressor
stationarystationaryscrollscroll
drivendrivenscrollscroll
intakeintake
dischargedischarge
intakeintake
dischargedischargeportport
motormotorshaftshaft
sealseal
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Return Oil to Compressors
compressorcompressor
condensercondenser
evaporatorevaporator
expansion expansion devicedevice
dischargedischargelineline
suctionsuctionlineline
liquidliquidlineline
warmwarmliquidliquid
hothotvaporvapor
coolcoolvaporvapor
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Thermostatic Expansion Valve (TXV)
external equalizerexternal equalizer
remote remote bulbbulb
evaporatorevaporator
TXVTXV
refrigerantrefrigerantvaporvapor
distributordistributor
liquid liquid refrigerantrefrigerant
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Subcooling
B
A
pres
sure
pres
sure
enthalpyenthalpy
{
subcoolingsubcooling
C
mixture of liquid mixture of liquid and vaporand vapor
saturatedsaturatedvapor curvevapor curve
saturatedsaturatedliquid curveliquid curve
expansionexpansiondevicedevice
condensercondenser
evaporatorevaporator
compressorcompressor
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Condenser
Evaporator
CompressorExpansion
Device
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Pressure Drop in a Suction Lineim
pact
on
syst
em p
erfo
rman
ce, %
impa
ct o
n sy
stem
per
form
ance
, %
capacitycapacitycapacitycapacity
100100
efficiencyefficiencyefficiencyefficiency
pressure drop, psipressure drop, psi (kPa)(kPa)pressure drop, psipressure drop, psi (kPa)(kPa)
22(13.8)(13.8)
22(13.8)(13.8)
9696
9292
9898
9494
909044
(27.6)(27.6)44
(27.6)(27.6)66
(41.4)(41.4)66
(41.4)(41.4)1010
(69.0)(69.0)1010
(69.0)(69.0)1212
(82.7)(82.7)1212
(82.7)(82.7)88
(55.2)(55.2)88
(55.2)(55.2)
R-22R-22R-22R-22
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Minimize Refrigerant Charge
liquid lineliquid line suction linesuction line
condensercondenser
evaporatorevaporator
filterfilterdrierdrier
compressorcompressordischargedischargelineline
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Involve the Manufacturer
If provided, use refrigerant line sizes recommended by manufacturer
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
General Piping Requirements
Use clean Type L copper tubing Copper-to-copper joints: BCuP-6 without flux Copper-to-steel (or brass) joints: BAg-28, non-acid flux
Properly support piping to account for expansion, vibration, and weight
Avoid installing piping underground Test entire refrigerant circuit for leaks
period two
Suction Line
Refrigerant Piping
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
suction line
Requirements for Sizing and Routing
Ensure adequate velocity to return oil to compressor at all steps of unloading
Avoid excessive noise Minimize system capacity and efficiency loss
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
suction line Sizing “Rules”
minimum velocity
1,000 fpm (5 m/s) based on diameter of riserfor vertical risers
500 fpm (2.5 m/s) percentage of minimum for horizontal sections riser velocity
maximum velocity
4,000 fpm (20 m/s) 4,000 fpm (20 m/s)
maximum pressure drop
3 psi (20 kPa) based on specific system requirements
old rules for R-22 new rules for R-22
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
suction line Process for Sizing
1 Determine total length of piping
2 Calculate refrigerant velocity at maximum and minimum capacities
3 Select largest pipe diameter that results in acceptable velocity at both maximum and minimum capacities
4 Calculate total equivalent length of straight pipe and fittings
5 Determine pressure drop due to pipe and fittings
6 Add pressure drop due to accessories
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Unloading Refrigeration Circuits
reciprocating compressorreciprocating compressorwith cylinder unloaderswith cylinder unloaders scroll compressorsscroll compressors
manifolded on amanifolded on asingle circuitsingle circuit
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
velo
city,
fpm
(m/s
)ve
locit
y, fp
m (m
/s)
evaporator capacity, tons (kW)evaporator capacity, tons (kW)
11(3.5)(3.5)
55(17.6)(17.6)
1010(35)(35)
5050(176)(176)
100100(352)(352)
200200(703)(703)
1,0001,000(5.1)(5.1)
500500(2.5)(2.5)
2,0002,000(10.2)(10.2)
5,0005,000(25.4)(25.4)
2020(70)(70)
22(7.0)(7.0)
1/2 (1
2)
1/2 (1
2)
5/8 (1
5)
5/8 (1
5)
7/8 (2
2)
7/8 (2
2)
1 1/8
(28)
1 1/8
(28)
1 3/8
(35)
1 3/8
(35)
1 5/8
(42)
1 5/8
(42)
2 1/8
(54)
2 1/8
(54)
2 5/8
(67)
2 5/8
(67)
3 1/8
(79)
3 1/8
(79)
3 5/8
(105)
3 5/8
(105)
R-22R-22
suction line
Determine Refrigerant Velocitypipe diameter, in. (mm)pipe diameter, in. (mm)
3/8 (1
0)
3/8 (1
0)
4 1/8
(130)
4 1/8
(130)3/4
(18)
3/4 (1
8)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
suction line
Determine Refrigerant Velocity
velocity, fpm (m/s)velocity, fpm (m/s)pipepipediameter,diameter,in. (mm)in. (mm)
20 tons 20 tons (70.3 kW)(70.3 kW)
10 tons 10 tons (35.2 kW)(35.2 kW)
1 1/8 (28)1 1/8 (28) 7,000 (35.6)7,000 (35.6) 3,500 (17.8)3,500 (17.8)1 3/8 (35)1 3/8 (35) 4,600 (23.4)4,600 (23.4) 2,300 (11.7)2,300 (11.7)1 5/8 (42)1 5/8 (42) 3,250 (16.5)3,250 (16.5) 1,625 (8.3)1,625 (8.3)2 1/8 (54)2 1/8 (54) 1,850 (9.4)1,850 (9.4) 925 (4.7) 925 (4.7)2 5/8 (67)2 5/8 (67) 1,200 (6.1)1,200 (6.1) 600 (3.1) 600 (3.1)3 1/8 (79)3 1/8 (79) 850 (4.3)850 (4.3) 425 (2.2) 425 (2.2)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
riserriser horiz/drophoriz/drop3/8 (10)3/8 (10) 370 (1.9)370 (1.9) 275 (1.4)275 (1.4)1/2 (12)1/2 (12) 460 (2.3)460 (2.3) 350 (1.8)350 (1.8)5/8 (15)5/8 (15) 520 (2.6)520 (2.6) 390 (2.0)390 (2.0)3/4 (18)3/4 (18) 560 (2.8)560 (2.8) 420 (2.1)420 (2.1)7/8 (22)7/8 (22) 600 (3.1)600 (3.1) 450 (2.3)450 (2.3)
1 1/8 (28)1 1/8 (28) 700 (3.6)700 (3.6) 525 (2.7)525 (2.7)1 3/8 (35)1 3/8 (35) 780 (4.0)780 (4.0) 585 (3.0)585 (3.0)1 5/8 (42)1 5/8 (42) 840 (4.3)840 (4.3) 630 (3.2)630 (3.2)2 1/8 (54)2 1/8 (54) 980 (5.0)980 (5.0) 735 (3.7)735 (3.7)2 5/8 (67)2 5/8 (67) 1,080 (5.5)1,080 (5.5) 810 (4.1)810 (4.1)3 1/8 (79)3 1/8 (79) 1,180 (6.0)1,180 (6.0) 885 (4.5)885 (4.5)
3 5/8 (105)3 5/8 (105) 1,270 (6.5)1,270 (6.5) 950 (4.8)950 (4.8)4 1/8 (130)4 1/8 (130) 1,360 (6.9)1,360 (6.9) 1,020 (5.2)1,020 (5.2)
suction line
Minimum Allowable Velocitiesminimum velocity, fpm (m/s)minimum velocity, fpm (m/s)pipe diameter,pipe diameter,
in. (mm)in. (mm)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Select Suction Line Size
riserriser horiz/drophoriz/drop
20 (70.3)20 (70.3) 1,850 (9.4)1,850 (9.4)
10 (35.2)10 (35.2) 925 (4.7)925 (4.7)
circuitcircuitcapacity,capacity,tons (kW)tons (kW)
minimum velocity for 2 1/8 in.minimum velocity for 2 1/8 in.(54 mm) pipe, fpm (m/s)(54 mm) pipe, fpm (m/s)
velocity insidevelocity inside2 1/8 in. (54 mm) 2 1/8 in. (54 mm) pipe, fpm (m/s)pipe, fpm (m/s)
980 (5.0)980 (5.0) 735 (3.7)735 (3.7)
riserriser horiz/drophoriz/drop
20 (70.3)20 (70.3) 3,250 (16.5)3,250 (16.5)
10 (35.2)10 (35.2) 1,625 (8.3)1,625 (8.3)
circuitcircuitcapacity,capacity,tons (kW)tons (kW)
minimum velocity for 1 5/8 in.minimum velocity for 1 5/8 in.(42 mm) pipe, fpm (m/s)(42 mm) pipe, fpm (m/s)
velocity insidevelocity inside1 5/8 in. (42 mm) 1 5/8 in. (42 mm) pipe, fpm (m/s)pipe, fpm (m/s)
840 (4.3)840 (4.3) 630 (3.2)630 (3.2)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Selected Suction Line Sizes
compressorcompressor
evaporatorevaporator
2 1/8 in.2 1/8 in.(54 mm)(54 mm)
1 5/8 in. 1 5/8 in. (42 mm)(42 mm)riserriser
2 1/8 in.2 1/8 in.(54 mm)(54 mm)
dropdrop
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Double Suction Riser
20 (70.3)20 (70.3) 3,250 (16.5)3,250 (16.5)
5 (17.6)5 (17.6) 810 (4.1)810 (4.1)
circuitcircuitcapacity,capacity,tons (kW)tons (kW)
minimum velocity forminimum velocity for1 5/8 in. (42 mm) riser, 1 5/8 in. (42 mm) riser,
fpm (m/s)fpm (m/s)
velocity insidevelocity inside1 5/8 in. (42 mm) 1 5/8 in. (42 mm) pipe, fpm (m/s)pipe, fpm (m/s)
840 (4.3)840 (4.3)
20 (70.3)20 (70.3) 4,600 (23.4)4,600 (23.4)
5 (17.6)5 (17.6) 1,150 (5.9)1,150 (5.9)
circuitcircuitcapacity,capacity,tons (kW)tons (kW)
minimum velocity forminimum velocity for1 3/8 in. (35 mm) riser, 1 3/8 in. (35 mm) riser,
fpm (m/s)fpm (m/s)
velocity insidevelocity inside1 3/8 in. (35 mm) 1 3/8 in. (35 mm) pipe, fpm (m/s)pipe, fpm (m/s)
780 (4.0)780 (4.0)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Double Suction Riser
largerlargerriserriser
smallersmallerriserriser
traptrap
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Sizing a Double Suction Riser
Sizing the smaller riser
Sizing the larger riser
5 (17.6)5 (17.6) 1,150 (5.8)1,150 (5.8)
circuitcircuitcapacity,capacity,tons (kW)tons (kW)
minimum velocityminimum velocityfor 1 3/8 in. (35 mm) for 1 3/8 in. (35 mm) riser, fpm (m/s)riser, fpm (m/s)
velocity insidevelocity inside1 3/8 in. (35 mm) 1 3/8 in. (35 mm) pipe, fpm (m/s)pipe, fpm (m/s)
780 (4.0)780 (4.0)
15 (52.8)15 (52.8) 2,450 (12.4)2,450 (12.4)
circuitcircuitcapacity,capacity,tons (kW)tons (kW)
minimum velocityminimum velocityfor 1 5/8 in. (42 mm) for 1 5/8 in. (42 mm) riser, fpm (m/s)riser, fpm (m/s)
velocity insidevelocity inside1 5/8 in. (42 mm) 1 5/8 in. (42 mm) pipe, fpm (m/s)pipe, fpm (m/s)
840 (4.3)840 (4.3)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Calculate Total Equivalent Length
LLeqeq is based on r/d is based on r/d
radius of curvature (r)radius of curvature (r)
diameter (d)diameter (d)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Leq for Long-Radius Elbows
equivalent length, ft (m)equivalent length, ft (m)
““old” dataold” data ““new” datanew” data
1 1/8 (28)1 1/8 (28) 1.9 (0.6)1.9 (0.6) 0.8 (0.24)0.8 (0.24)1 3/8 (35)1 3/8 (35) 2.2 (0.7)2.2 (0.7) 0.9 (0.27)0.9 (0.27)1 5/8 (42)1 5/8 (42) 2.6 (0.8)2.6 (0.8) 1.0 (0.30)1.0 (0.30)2 1/8 (54)2 1/8 (54) 3.4 (1.0)3.4 (1.0) 1.4 (0.43)1.4 (0.43)2 5/8 (67)2 5/8 (67) 4.2 (1.3)4.2 (1.3) 1.5 (0.46)1.5 (0.46)3 1/8 (79)3 1/8 (79) 5.1 (1.6)5.1 (1.6) 1.7 (0.52)1.7 (0.52)
elbowelbowdiameter,diameter,in. (mm)in. (mm)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
pres
sure
dro
p, p
si/10
0 ft
(kPa
/10
m)
pres
sure
dro
p, p
si/10
0 ft
(kPa
/10
m)
evaporator capacity, tons (kW)evaporator capacity, tons (kW)
11(3.5)(3.5)
55(17.6)(17.6)
1010(35)(35)
5050(176)(176)
100100(352)(352)
200200(703)(703)
1.01.0(2.3)(2.3)
0.50.5(1.2)(1.2)
2.02.0(4.6)(4.6)
5.05.0(11.5)(11.5)
2020(70)(70)
22(7.0)(7.0)
2 1/
8 (5
4)2
1/8
(54)
2 5/
8 (6
7)2
5/8
(67)
3 1/
8 (7
9)3
1/8
(79)
R-22R-22
pipe diameter, in. (mm)pipe diameter, in. (mm)
1 5/
8 (4
2)1
5/8
(42)10.010.0
(23.0)(23.0)
suction line
Determine Pressure Drop
1 3/
8 (3
5)1
3/8
(35)
1 1/
8 (2
8)1
1/8
(28)
7/8
(22)
7/8
(22)
3/4
(18)
3/4
(18)
5/8
(15)
5/8
(15)
3 5/
8 (1
05)
3 5/
8 (1
05)
4 1/
8 (1
30)
4 1/
8 (1
30)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
suction line
Add Pressure Drop of Accessories
Suction filter = 2 psi (13.8 kPa) Angle valve = 1 psi (6.9 kPa) Ball valve = 1 equivalent ft (0.3 m)
suction line filtersuction line filter
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
TXV Installation
external equalizer lineexternal equalizer line
remote remote bulbbulb
evaporatorevaporator
TXVTXV
refrigerantrefrigerantvaporvapor
distributordistributor
liquid liquid refrigerantrefrigerant
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
single distributor on circuit
Evaporator Coil Connection
TXVTXVbulbbulb
must rise abovemust rise aboveheight of evaporatorheight of evaporator
must drop belowmust drop belowheader outletheader outlet
suction headersuction header
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
single distributor on circuit
Evaporator Coil Connection
TXVTXVbulbbulb
must rise abovemust rise aboveheight of evaporatorheight of evaporator
must drop belowmust drop belowheader outletheader outlet
suction headersuction header
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
multiple distributors on circuit Evaporator Coil Connections
TXVTXVbulbbulb
must drop belowmust drop belowlowest header outletlowest header outlet double-elbowdouble-elbow
configurationconfiguration
must rise abovemust rise aboveheight of evaporatorheight of evaporator
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
suction line
Riser Traps Are Not Required
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
suction line Other Considerations Do not use suction riser traps: they are not
required Pitch horizontal sections to drain toward
evaporator Insulate entire suction line
Prevents condensation Minimizes loss of capacity due to heat gain
Install suction-line filter close to compressor Manual shutoff valves allow isolation for replacement
Install access ports to measure suction pressure and superheat
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Suction-Line Accumulator
Check with equipment manufacturer to determine if required, recommended, or discouraged
photo provided by Henry Technologiesphoto provided by Henry Technologies
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
suction line
Reciprocating Compressors
pipepipeanchoranchor
pitchpitch
period three
Discharge Line
Refrigerant Piping
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
discharge line
Requirements for Sizing and Routing
Ensure adequate velocity to return oil to compressor at all steps of unloading
Avoid excessive noise Minimize efficiency loss
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
discharge line Sizing “Rules”
minimum velocity
1,000 fpm (5 m/s) based on diameter of riserfor risers
500 fpm (2.5 m/s) percentage of minimum for horizontal sections riser velocity
maximum velocity
3,500 fpm (17.5 m/s) 3,500 fpm (17.5 m/s)
maximum pressure drop
6 psi (41 kPa) based on specific system requirements
old rules for R-22 new rules for R-22
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
discharge line Process for Sizing
1 Determine total length of piping
2 Calculate refrigerant velocity at maximum and minimum capacities
3 Select largest pipe diameter that results in acceptable velocity at both maximum and minimum capacity
4 Calculate total equivalent length of straight pipe and fittings
5 Determine pressure drop due to pipe and fittings
6 Add pressure drop due to accessories
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
11(3.5)(3.5)
55(17.6)(17.6)
1010(35)(35)
5050(176)(176)
100100(352)(352)
200200(703)(703)
1,0001,000(5.1)(5.1)
500500(2.5)(2.5)
2,0002,000(10.2)(10.2)
5,0005,000(25.4)(25.4)
2020(70)(70)
22(7.0)(7.0)
1/2 (1
2)
1/2 (1
2)
5/8 (1
5)
5/8 (1
5)
7/8 (2
2)
7/8 (2
2)
1 1/8
(28)
1 1/8
(28)
1 3/8
(35)
1 3/8
(35)
1 5/8
(42)
1 5/8
(42)
2 1/8
(54)
2 1/8
(54)
2 5/8
(67)
2 5/8
(67)
3 1/8
(79)
3 1/8
(79)
R-22R-22
discharge line
Determine Refrigerant Velocity
velo
city,
fpm
(m/s
)ve
locit
y, fp
m (m
/s)
evaporator capacity, tons (kW)evaporator capacity, tons (kW)
pipe diameter, in. (mm)pipe diameter, in. (mm)
3/8 (1
0)
3/8 (1
0)
3/4 (1
8)
3/4 (1
8)
5/16 (
8)
5/16 (
8)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
discharge line
Determine Refrigerant Velocity
7/8 (22)7/8 (22) 4,050 (20.6)4,050 (20.6) 2,025 (10.3)2,025 (10.3)1 1/8 (28)1 1/8 (28) 2,400 (12.2)2,400 (12.2) 1,200 ( 6.1)1,200 ( 6.1)1 3/8 (35)1 3/8 (35) 1,550 ( 7.9)1,550 ( 7.9) 775 ( 3.9) 775 ( 3.9)1 5/8 (42)1 5/8 (42) 1,100 ( 5.6)1,100 ( 5.6) 550 ( 2.8) 550 ( 2.8)2 1/8 (54)2 1/8 (54) 650 ( 3.3)650 ( 3.3) 325 ( 1.7) 325 ( 1.7)
velocity, fpm (m/s)velocity, fpm (m/s)pipepipediameter,diameter,in. (mm)in. (mm)
20 tons 20 tons (70.3 kW)(70.3 kW)
10 tons 10 tons (35.2 kW)(35.2 kW)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
discharge line
Minimum Allowable Velocities
riserriser horiz/drophoriz/drop5/16 (8)5/16 (8) 220 (1.1)220 (1.1) 165 (0.8)165 (0.8)3/8 (10)3/8 (10) 250 (1.3)250 (1.3) 185 (0.9)185 (0.9)1/2 (12)1/2 (12) 285 (1.4)285 (1.4) 215 (1.1)215 (1.1)5/8 (15)5/8 (15) 315 (1.6)315 (1.6) 235 (1.2)235 (1.2)3/4 (18)3/4 (18) 345 (1.8)345 (1.8) 260 (1.3)260 (1.3)7/8 (22)7/8 (22) 375 (1.9)375 (1.9) 285 (1.4)285 (1.4)
1 1/8 (28)1 1/8 (28) 430 (2.2)430 (2.2) 325 (1.7)325 (1.7)1 3/8 (35)1 3/8 (35) 480 (2.4)480 (2.4) 360 (1.8)360 (1.8)1 5/8 (42)1 5/8 (42) 520 (2.6)520 (2.6) 390 (2.0)390 (2.0)2 1/8 (54)2 1/8 (54) 600 (3.0)600 (3.0) 450 (2.3)450 (2.3)2 5/8 (67)2 5/8 (67) 665 (3.4)665 (3.4) 500 (2.5)500 (2.5)3 1/8 (79)3 1/8 (79) 730 (3.7)730 (3.7) 550 (2.8)550 (2.8)
minimum velocity, fpm (m/s)minimum velocity, fpm (m/s)pipe diameter,pipe diameter,in. (mm)in. (mm)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Select Discharge Line Size
riserriser horiz/drophoriz/drop
20 (70.3)20 (70.3) 1,100 (5.6)1,100 (5.6)
10 (35.2)10 (35.2) 550 (2.8)550 (2.8)
circuitcircuitcapacity,capacity,tons (kW)tons (kW)
minimum velocity for 1 5/8 in.minimum velocity for 1 5/8 in.(42 mm) pipe, fpm (m/s)(42 mm) pipe, fpm (m/s)
velocity insidevelocity inside1 5/8 in. (42 mm) 1 5/8 in. (42 mm) pipe, fpm (m/s)pipe, fpm (m/s)
520 (2.6)520 (2.6) 390 (2.0)390 (2.0)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Selected Discharge Line Size
1 5/8 in.1 5/8 in.(42 mm)(42 mm)
compressorcompressor
condensercondenser 1 5/8 in. 1 5/8 in. (42 mm)(42 mm)riserriser
1 5/8 in. 1 5/8 in. (42 mm)(42 mm)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
pres
sure
dro
p, p
si/10
0 ft
(kPa
/10
m)
pres
sure
dro
p, p
si/10
0 ft
(kPa
/10
m)
evaporator capacity, tons (kW)evaporator capacity, tons (kW)
11(3.5)(3.5)
55(17.6)(17.6)
1010(35)(35)
5050(176)(176)
100100(352)(352)
200200(703)(703)
1.01.0(2.3)(2.3)
0.50.5(1.2)(1.2)
2.02.0(4.6)(4.6)
5.05.0(11.5)(11.5)
2020(70)(70)
22(7.0)(7.0)
7/8
(22)
7/8
(22)
1 1/8
(28)
1 1/8
(28)
1 3/8
(35)
1 3/8
(35)
2 1/8
(54)
2 1/8
(54)
2 5/8
(67)
2 5/8
(67)
3 1/8
(79)
3 1/8
(79)
R-22R-22
pipe diameter, in. (mm)pipe diameter, in. (mm)
1 5/8
(42)
1 5/8
(42)
10.010.0(23.0)(23.0)
discharge line
Determine Pressure Drop
3/4
(18)
3/4
(18)
5/8
(15)
5/8
(15)
1/2
(12)
1/2
(12)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
discharge line
Add Pressure Drop of Accessories
Angle valve = 1 psi (6.9 kPa) Ball valve = 1 equivalent ft (0.3 m)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
discharge line Other Considerations
Do not use discharge riser traps: they are not required
Pitch horizontal sections to drain toward condenser
Insulate only to prevent accidental burns or when system must operate in cold ambient conditions
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
discharge line
Reciprocating Compressors
pipepipeanchoranchor
pitchpitch
period four
Liquid Line
Refrigerant Piping
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Requirements for Sizing and Routing
Ensure that only liquid refrigerant enters expansion device
Minimize refrigerant charge Avoid excessive noise and pipe erosion
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Subcooling
enthalpy, Btu/lb (kJ/kg)enthalpy, Btu/lb (kJ/kg)
241241(1,662)(1,662)
pres
sure
, psia
(kPa
)pr
essu
re, p
sia (k
Pa)
293293(2,020)(2,020) 125°F125°F
(51.7°C)(51.7°C)
subcoolingsubcooling
saturatedsaturatedliquid curveliquid curve
mixture of liquidmixture of liquidand vaporand vapor
110°F110°F(43.3°C)(43.3°C)
{
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Impact of Refrigerant Density Change
AA 7/8 (22)7/8 (22) highhigh 18.0 (10) -18.0 (10) - 5.7 (3.2) =5.7 (3.2) = 12.3 (6.8)12.3 (6.8)BB 1 1/8 (28)1 1/8 (28) highhigh 18.0 (10) -18.0 (10) - 3.8 (2.1) =3.8 (2.1) = 14.2 (7.9)14.2 (7.9)
AA 7/8 (22)7/8 (22) lowlow 12.9 (7.2) -12.9 (7.2) - 7.4 (4.1) =7.4 (4.1) = 5.5 (3.1)5.5 (3.1)BB 1 1/8 (28)1 1/8 (28) lowlow 7.2 (4.0) -7.2 (4.0) - 5.2 (2.9) =5.2 (2.9) = 2.0 (1.1)2.0 (1.1)
available subcooling, °F (°C)available subcooling, °F (°C)liquid lineliquid linediameter, diameter, in. (mm)in. (mm)
leaving leaving subcoolersubcooler
loss due loss due to pipingto piping
outdooroutdoortemperaturetemperature remaining remaining
at TXVat TXV
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line Sizing “Rules”
maximum pressure drop
6 psi (41 kPa) 5°F (2.8°C) subcoolingremaining at inlet to expansion device at all operating conditions
maximum velocity
360 fpm (1.8 m/s) 600 fpm (3 m/s)
old rules for R-22 new rules for R-22
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line Process for Sizing
1 Determine total length of piping
2 Obtain subcooling provided by condenser
3 Determine refrigerant velocity
4 Select smallest pipe diameter that results in acceptable velocity at maximum capacity
5 Calculate total equivalent length of pipe and fittings
6 Determine pressure drop due to pipe and fittings
7 Add pressure drop due to accessories
8 Calculate loss of subcooling due to pressure drop and elevation change
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
System Operating Envelope
saturated suction temperaturesaturated suction temperature
condensing unit,condensing unit,high OA temperaturehigh OA temperature
condensing unit, condensing unit, low OA temperaturelow OA temperature
evaporator,evaporator,high cooling loadhigh cooling load
evaporator,evaporator,low cooling loadlow cooling load
syst
em c
oolin
g ca
pacit
ysy
stem
coo
ling
capa
city
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
System Operating Envelope
high cooling load,high cooling load,high OA temperaturehigh OA temperature
A
B
D
C
high cooling load,high cooling load,low OA temperaturelow OA temperature
low cooling load,low cooling load,high OA temperaturehigh OA temperature
low cooling load,low cooling load,low OA temperaturelow OA temperature
saturated suction temperaturesaturated suction temperature
syst
em c
oolin
g ca
pacit
ysy
stem
coo
ling
capa
city
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
effect of cooling load and outdoor temperature
Subcooling Leaving Condenser
A highhigh highhigh 18 (10.0)18 (10.0) B lowlow highhigh 21 (11.7)21 (11.7)
C lowlow lowlow 13 (7.2) 13 (7.2) D highhigh lowlow 5 (2.8) 5 (2.8)
subcooling leaving subcooling leaving condenser*, °F (°C)condenser*, °F (°C)
cooling cooling loadload
outdooroutdoortemperaturetemperature
* This example system uses a TXV for the expansion device.* This example system uses a TXV for the expansion device.
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Involve the Manufacturer
If provided, use refrigerant line sizes recommended by manufacturer
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002 evaporator capacity, tons (kW)evaporator capacity, tons (kW)
11(3.5)(3.5)
55(17.6)(17.6)
1010(35)(35)
5050(176)(176)
100100(352)(352)
200200(703)(703)
100100(0.5)(0.5)
5050(0.25)(0.25)
200200(1.0)(1.0)
500500(2.5)(2.5)
2020(70)(70)
22(7.0)(7.0)
5/16 (
8)
5/16 (
8)3/8
(10)
3/8 (1
0)
1/2 (1
2)
1/2 (1
2)
5/8 (1
5)
5/8 (1
5)
2 1/8
(54)
2 1/8
(54)
1 5/8
(42)
1 5/8
(42)
R-22R-22
pipe diameter, in. (mm)pipe diameter, in. (mm)
1 1/8
(28)
1 1/8
(28)1,0001,000
(5.1)(5.1)
liquid line
Determine Refrigerant Velocityve
locit
y, fp
m (m
/s)
velo
city,
fpm
(m/s
)
7/8 (2
2)
7/8 (2
2)
1 3/8
(35)
1 3/8
(35)
1/4 (6
)1/4
(6)
3/4 (1
8)
3/4 (1
8)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Determine Refrigerant Velocity
1/2 (12)1/2 (12) 850 (4.3)850 (4.3)5/8 (15)5/8 (15) 525 (2.7)525 (2.7)3/4 (18)3/4 (18) 350 (1.8)350 (1.8)7/8 (22)7/8 (22) 250 (1.3)250 (1.3)
1 1/8 (28)1 1/8 (28) 150 (0.8)150 (0.8)1 3/8 (35)1 3/8 (35) 100 (0.5)100 (0.5)
velocity, fpm (m/s)velocity, fpm (m/s)pipepipediameter,diameter,in. (mm)in. (mm)
20 tons 20 tons (70.3 kW)(70.3 kW)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Calculate Total Equivalent Length
evaporatorevaporator
condensercondenser
5/8 in.5/8 in.(15 mm)(15 mm)riserriser
5/8 in.5/8 in.(15 mm)(15 mm)
5/8 in.5/8 in.(15 mm)(15 mm)dropdrop
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002 evaporator capacity, tons (kW)evaporator capacity, tons (kW)
11(3.5)(3.5)
55(17.6)(17.6)
1010(35)(35)
5050(176)(176)
100100(352)(352)
200200(703)(703)
2020(70)(70)
22(7.0)(7.0)
R-22R-22
pipe diameter, in. (mm)pipe diameter, in. (mm)
liquid line
Determine Pressure Droppr
essu
re d
rop,
psi/
100
ft (k
Pa/1
0 m
)pr
essu
re d
rop,
psi/
100
ft (k
Pa/1
0 m
)
1.01.0(2.3)(2.3)
2.02.0(4.6)(4.6)
5.05.0(11.5)(11.5)
10.010.0(23)(23)
20.020.0(46)(46)
50.050.0(115)(115)
5/8
(15)
5/8
(15)
7/8
(22)
7/8
(22)
1 1/
8 (2
8)1
1/8
(28)
1 3/
8 (3
5)1
3/8
(35)
1 5/
8 (4
2)1
5/8
(42)
1/2
(12)
1/2
(12)
3/4
(18)
3/4
(18)
2 1/
8 (5
4)2
1/8
(54)
3/8
(10)
3/8
(10)
5/16
(8)
5/16
(8)
1/4
(6)
1/4
(6)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Add Pressure Drop of Accessories
Filter-drier = 6 psi (41.4 kPa) Solenoid valve = 4 psi (27.6 kPa) Sight glass = 1 equivalent ft (0.3 m) Angle valve = 1 psi (6.9 kPa) Ball valve = 1 equivalent ft (0.3 m)
solenoidsolenoidvalvevalve
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Pressure Drop Due to Elevation
evaporatorevaporator
condensercondenser 15 ft 15 ft (4.6 m)(4.6 m)vertical rise vertical rise creates creates pressure droppressure drop
11 ft 11 ft (3.4 m)(3.4 m)vertical drop vertical drop creates creates pressure gainpressure gain
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Pressure Drop Due to Elevation
liquid temperature, °F (°C)liquid temperature, °F (°C)
pres
sure
dro
p/ne
t liq
uid
rise,
psi/
ft (k
Pa/m
)pr
essu
re d
rop/
net l
iqui
d ris
e, p
si/ft
(kPa
/m)
4040(4.4)(4.4)
6060(15.6)(15.6)
8080(26.7)(26.7)
100100(37.8)(37.8)
120120(48.9)(48.9)
140140(60.0)(60.0)
160160(71.1)(71.1)
0.4250.425(9.6)(9.6)
0.4500.450(10.2)(10.2)
0.4750.475(10.7)(10.7)
0.5000.500(11.3)(11.3)
0.5250.525(11.9)(11.9)
0.5500.550(12.4)(12.4)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Calculate Loss of Subcooling
liquid temperature, °F (°C)liquid temperature, °F (°C)
loss
of s
ubco
olin
g, p
si/°F
(kPa
/°C)
loss
of s
ubco
olin
g, p
si/°F
(kPa
/°C)
4040(4.4)(4.4)
6060(15.6)(15.6)
8080(26.7)(26.7)
100100(37.8)(37.8)
120120(48.9)(48.9)
140140(60.0)(60.0)
160160(71.1)(71.1)
00(0)(0)
1.01.0(12.4)(12.4)
2.02.0(24.9)(24.9)
3.03.0(37.3)(37.3)
4.04.0(49.7)(49.7)
5.05.0(62.2)(62.2)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Subcooling Remaining at Expansion Device
15 (8.3)15 (8.3) -- 9.9 (5.5)9.9 (5.5) == 5.1 (2.8)5.1 (2.8)
leavingleavingcondensercondenser
subcooling, °F (°C)subcooling, °F (°C)
loss due toloss due toliquid lineliquid line
remaining at remaining at expansion expansion devicedevice
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Evaporator Coil Connections
TXVTXV
distributordistributor
evaporatorevaporator
solenoidsolenoidvalvevalve
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line
Refrigerant Accessories
sightsightglassglass
TXVTXV
liquid lineliquid line
solenoid solenoid valvevalve
filter-drierfilter-drier
evaporatorevaporator
condensercondenser
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Liquid Line Routing
route the horizontal leg below the riserroute the horizontal leg below the riser
evaporatorevaporatorcondensercondenser
condensercondenser
evaporatorevaporator
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
liquid line Other Considerations
Pitch horizontal sections to run alongside suction or discharge line
Insulate lines that are routed through very warm spaces
period five
Hot-Gas Bypass Line
Refrigerant Piping
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
hot-gas bypass line
Requirements for Sizing and Routing
Ensure that oil and refrigerant are not trapped in piping
Avoid excessive noise Proper routing is more critical than pipe
diameter
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Hot-Gas Bypass to Evaporator Inlet
evaporatorevaporator
condensercondenser
compressorcompressor
hot-gas hot-gas bypass valvebypass valve
TXVTXV
distributordistributor
suction linesuction line
liquid lineliquid line
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Hot-Gas Bypass Valve Installation
condensercondenser
compressorcompressor
hot-gas hot-gas bypass valvebypass valve
pitch back toward pitch back toward discharge linedischarge line
pilotpilotlineline
suctionsuctionlineline
dischargedischargelineline
pitch awaypitch awayfrom hot-gasfrom hot-gasbypass valvebypass valve
hot-gas hot-gas bypass linebypass line
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Hot-Gas Bypass Risers
hot-gashot-gasbypass riserbypass riser
suctionsuctionlinelinecompressorcompressor
drain legdrain leg
oil-returnoil-returnlineline
condensercondenser
hot-gas hot-gas bypass valvebypass valve
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
hot-gas bypass line
Connection to Evaporator
evaporatorevaporator
distributordistributor
liquidliquidlineline
hot-gas hot-gas bypass linebypass line
solenoidsolenoidvalvevalve
TXVTXV
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
hot-gas bypass line
Connection to Evaporator
evaporatorevaporator
distributordistributor
hot-gas hot-gas bypass linebypass line
solenoidsolenoidvalvevalve
checkcheckvalvesvalves
TXVTXV
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Hot-Gas Bypass to Suction Line
evaporatorevaporator
condensercondenser
compressorcompressor
hot-gas hot-gas bypass valvebypass valve
suction linesuction line
liquid lineliquid line
liquid-injection liquid-injection valvevalve
TXVTXV
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
hot-gas bypass line
Connection to Suction Line
condensercondenser
compressorcompressor suction linesuction line
liquidliquidlineline
hot-gas hot-gas bypass valvebypass valve
liquid-injection liquid-injection valvevalve
solenoidsolenoidvalvevalve
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Hot-Gas Bypass Line Sizing
1/2 (12)1/2 (12) 6,700 (34.0)6,700 (34.0)5/8 (15)5/8 (15) 4,200 (21.3)4,200 (21.3)3/4 (18)3/4 (18) 2,825 (14.4)2,825 (14.4)7/8 (22)7/8 (22) 2,025 (10.3)2,025 (10.3)
1 1/8 (28)1 1/8 (28) 1,200 ( 6.1)1,200 ( 6.1)1 3/8 (35)1 3/8 (35) 775 ( 3.9)775 ( 3.9)
velocity, fpm (m/s)velocity, fpm (m/s)pipepipediameter,diameter,in. (mm)in. (mm)
10 tons 10 tons (35.2 kW)(35.2 kW)
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
hot-gas bypass line Other Considerations
Insulate entire line to prevent refrigerant vapor from condensing
Minimize overall length of the line Install solenoid valve if system includes a
pump-down cycle
period six
Review
Refrigerant Piping
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Review—Period One
Refrigerant Piping Requirements Return oil to compressor Ensure that only liquid refrigerant (no vapor) enters
the expansion device Minimize system capacity loss Minimize refrigerant charge
If provided, use line sizes recommended by the manufacturer
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Review—Period Two
Suction line Ensure adequate velocity to return oil to the
compressor at all steps of unloading Avoid excessive noise Minimize system capacity and efficiency loss
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Review—Period Three
Discharge line Ensure adequate velocity to return oil to the
compressor at all steps of unloading Avoid excessive noise Minimize efficiency loss
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Review—Period Four
Liquid line Ensure that only liquid refrigerant enters the
expansion device Minimize refrigerant charge Avoid excessive noise and pipe erosion
Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002
Review—Period Five
Hot-gas bypass line Ensure that oil and refrigerant are not trapped in the
piping Avoid excessive noise Proper routing is more critical than pipe diameter