Regard 3900 Modbus Gateway
Instructions For Use
2
Purpose The Regard 3900 Modbus Gateway is needed for the communication between the control unit Regard 3900/3910 and the visualisation panel RVP 3900. The visualisation panel receives data from up to 8 control units and displays them in a graphical form. Every system needs its own Regard 3900 Gateway. The gateway transforms the CAN bus data from the Regard 3900/3910 in to the Modbus protocol. This Modbus data is needed for the visualisation of the Regard 3900 System. Before using the Regard 3900 Modbus Gateway it has to be addressed. The addressing is carried out via a null modem cable, software and a configuration file. Example:
Regard 3900/3910 System
Gateway Address Modbus Address
RVP3900 Max. 8 Controller
1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 9 9 Not possible! 10 10 Not possible!
For this procedure there is a CD containing the program and the configuration file. A null modem cable is also included in the package. By using more than one unit the termination resistors (Jumper 1 and 2) have to be set on the last used Regard 3900 Modbus Gateway in the bus system. NOTE: It is NOT possible to run the program directly from CD. First you have to copy it onto a local hard drive. Installation and configuration Copy program to a local hard drive Before using the program it is required to to copy it from the CD to a non write protected local hard drive. You'll find the software on the CD in following path: D*\Software\RMG3900conf\ D* is standing for the local CD drive. Copy the folder 'RMG3900conf' to a destination of your choice. The program does not need a installation routine and can be started directly.
3
Addressing the Regard 3900 Gateway Set jumper 3 from to the Boot Mode (from position 2 to 3). Connect the null modem cable to the PC/Notebook and gateway. Connect the 24 VDC power supply. Start software "FlashWrite.exe" (on CD in folder "Software"). Select a free COM port on the PC/Notebook (default COM port is COM 1). pic.1 start software / select COM port
4
Click "File Open" in the program window and chose the required configuration file. The configuration files are deposited in to the folder "Regard 3900_idX" ("X" is standing for the number of the address) (pic.2). Controller No. 1 = File "Regard 3900_id1" Controller No. 2 = File "Regard 3900_id2" Controller No. 3 = File "Regard 3900_id3"… When the folder is opened choose the file "New_SX67012.sx" (pic.3). pic.2 ""File Open"
5
pic.3 choose configuration file and open
After choosing the configuration file the path will be showed in the program window. Now press the "Download" button. The communication will be set up and display the message "STEP DEVICE: connected" (pic.4). pic.4
6
Whist the file is downloading the following messages are shown (pic.5; pic.6) pic.5 file download
pic.6 download completed
When the download is finished the message "OK Done" is shown (pic.6), in the bottom right hand side of the program window. The gateway is now addressed. The program can now be closed. De‐connect the null modem cable and the power supply from the gateway. Remove the jumper 3 from Boot Mode (from 3 to 2).
7
Electricial Installation of the Regard 3900 Modbus Gateway The Regard 3900 Modbus Gateway is designed for DIN Rail mounting. Shematic drawing
Connection Dräger RVP 3900 to Dräger Regard 3900 Modbus Gateway RS 485 Communication settings Baud rate: 38400 Data bits: 8 Parity: none Stop bits: 1
8
Connection Dräger Regard 3900 to Dräger Regard 3900 Modbus Gateway
9
Connection Dräger Regard 3910 to Regard 3900 Modbus Gateway (without display board)
Connection Regard 3900/3910 ribbon cable to Regard 3910 Modbus Gateway cable
Regard 3910 Modbus Gateway cable (SC00085)
Regard 3900/3910 ribbon cable
Connection Regard 3900/3910 ribbon cable toRegard 3910 Input or Relay cards
Regard 3910 Modbus Gateway (SC00083)
Connection:Cable GatewayPIN 2 → LowPIN 3 → High
Connector for Regard 3900/3910 configuration cable (4208785)
Connection Dräger Regard 3910 (without display board) to Dräger Regard 3900 Modbus Gateway
10
Bit Status
0 A1
1 A2
2 A3
3 F1
4 F2
5 Maitenance
6 Underrange
7 Overrange
Modbus function 04 ‐ registers (words): Example for Channel 01 Channel Register addresses 01 30002‐30006 02 30017‐30021 03 30032‐30036 04 30047‐30051 05 30062‐30066 06 30077‐30081 07 30092‐30096 08 30107‐30111 09 30122‐30126 10 30137‐30141 11 30152‐30156 12 30167‐30171 13 30182‐30186 14 30197‐30201 15 30212‐30216 16 30227‐30231 Calculation of the Gas Value: (Gas Level x Range) / 1000 = Value
Modbus function 03,06,16
Holding Registers :
Channel Register addresses 01 40007‐40016 02 40022‐40031 03 40037‐40046 04 40052‐40061 05 40067‐40076 06 40082‐40081 07 40097‐40106 08 40112‐40121 09 40127‐40136 10 40142‐40151 11 40157‐40166 12 40172‐40181 13 40187‐40196 14 40202‐40211 15 40217‐40226 16 40232‐40241 ComError CAN Bus Gateway Register address 30242 The Alarm Accept signal is generated when the Modbus Master writes data value 1 to address 40251.
Information Register addresses
Gas Level 30002
Range 30003
Resolution 30004
Decimal Places 30005
Status 30006
Gas Name 40007‐40010
Gas Unit 40011‐40014
Reserved 40015
Reserved 40016
The alarm status byte contains the alarm and channel status bits: The High Byte reflects the Low Byte
11
Measurment Range Dec.Place Resolution
1 2 1
2 2 1
3 2 1
4 2 1
5 2 1
6 2 1
7 2 1
8 2 1
9 2 1
10 1 1
11 1 1
12 1 1
15 1 1
20 1 1
25 1 1
30 1 1
50 1 1
75 1 1
100 0 1
200 0 1
250 0 1
300 0 1
500 0 1
1000 0 5
2000 0 5
3000 0 10
5000 0 10
9999 0 25
12
Technical Data Standard: ISO 11898 / ISO.IEC 11801 Ports: 1 x CAN 2.0
1 x RS485 1 x RS262 Max Distance: CAN: 5.000 m. for 10K bps
CAN: 25 m for 1M bps RS 485 Modbus RTU side: 1200 m for 115K bps
Data Rates: CAN: From 10K up to 1M bps ModBUS: up to 115K bps Isolation: >2000 VDC LED: 1 x Power indicator
2 x Signal indicator Power: 24 VDC 200mA
12/18V AC; 50/60 Hz;200mA Temperature: Operating: ‐30° to +70° (‐22°F to +158°F) Storage: ‐40° to 80° (‐40°F to +176°F) Humidity: Operating:10% to 80%, non‐condensing Storage: 5% to 90%, non‐condensing EMI Compliance: EN 61000‐6‐2
FCC part 15 of Class A Dimensions: 120x23x107 (DxWxH) Weight: 200 g approx Mechanical Fixing: DIN 35 mm Rail mounting