REM 610Technical Presentation
REM 610Motor Protection
©AB
B AG
-2-
The Motor Protection Relay REM 610
Based on the success of
the famous SPAM series
Introduction
REM 610Motor Protection
©AB
B AG
-3-
Introduction
Area of application Medium.sized and large MV asynchronous (induction) motors (motors started direct on line, 50 Hz or 60 Hz)
Back-up protection of or integrated in protection schemes for synchronous motors
Circuit-breaker and contactor controlled drives
Feeder cables, power transformers and other requiring thermal overload protection and functionality included in the relay
REM 610Motor Protection
©AB
B AG
-4-
Introduction
Area of application cont. Low-voltage motors, typical power range 500 kW - 4 MW
Drives for ventilation & fans, crushers, conveyors, pumps, mills, etc. and applications in marine, offshore, mining and other demanding environments
Due to large number of protection functions integrated, the reliability protects the motor against damage
REM 610Motor Protection
©AB
B AG
-5-
Mechanical design
Basic parts
Metal case
Plastic front plate
Metal rear plate
REM 610Motor Protection
©AB
B AG
-6-
Mechanical design
Withdrawable relay unit
Case unit
Plug-in unit
REM 610Motor Protection
©AB
B AG
-7-
Mechanical design
Front plate
2 x 16 character alphanumericdisplay (LCD)
6-button keypadLocal communication port,wireless or via cable
3 pre-assigned LEDs
8 programmable LEDs
REM 610Motor Protection
©AB
B AG
-8-
Mechanical design
Inputs and outputs
Remote communication card
CT secondary current inputs prepared for ring-lug and scew-compression type wire connection.
Binary inputs and outputsRTD/Thermistor inputsPower supplyetc.
REM 610Motor Protection
©AB
B AG
-9-
Mechanical design
The CT secondaries are automatically short-circuited when the relay unit is withdrawn from the case
No need for separate short-circuiting arrangements
REM 610Motor Protection
©AB
B AG
-10-
Mechanical design
REM 610 product information under the handle
Easy access of type specifications and ratings
REM 610Motor Protection
©AB
B AG
-11-
Battery backup of the real-time clock (RTC) and memory circuits, disturbance recorder (DR), etc.
Automatically supervised and easy to change
Mechanical design
REM 610Motor Protection
©AB
B AG
-12-
Flush, semi-flush or surface mounting using suitable mounting accessories
Mechanical design
50 mm raising frame for semi-flush mounting
REM 610Motor Protection
©AB
B AG
-13-
Mechanical design
1. Left side + right side+18c rails
2. Left side x 2 + 12c rails
3. Right side x 2 + 24c rails
Mounting alternatives in COMBIFLEX equipment frames
REM 610Motor Protection
©AB
B AG
-14-
Mechanical design
Withdrawable mechanical designEasy to install and handleAutomatic short-circuiting of CT secondariesCommunication maintained even when relay unit withdrawnMechanical coding for identification of plug-in unit
Height 4U (~177 mm)Depth behind the panel only about 150 mm (100 mm possible!)Easy mounting - no loose mounting accessoriesBoth compression type connection and ring-lug terminal connection of CT secondary wiresIP 54 degree of protection by enclosure of the relay case when flush-mounted.
REM 610Motor Protection
©AB
B AG
-15-
Functionality
General50/60 Hz rated frequency
Real-time clock (chip) for time stamps
Non-volatile memory for settings (EEPROM)
Non-volatile memory for recorded fault values (battery back-up)
CT inputs for screw-compression or ring-lug type wire connection
Signal connectors for screw-compression type wire connection
Withdrawable design with automatic short-circuiting of CT secondaries
Five fault recordings with time stamps, 100 event codes for SCADA
Disturbance recorder, 5 seconds, one recording
Self-supervision of hardware and software
REM 610Motor Protection
©AB
B AG
-16-
Functionality
Protection functionsThermal overload protection (49)Temperature supervision based on RTDs (49/38)Motor startup supervision (48)Cumulative motor start-up time counter (66)Short-circuit protection (50)Overcurrent protection (51)Earth-fault protection (50N/51N)Phase unbalance / phase reversal protection (46)Undercurrent (loss of load) protection (37)Circuit-breaker failure protection (62BF)Electrically latched lockout relay (86)Emergency restart
REM 610Motor Protection
©AB
B AG
-17-
Functionality
Inputs4 analog inputs for current measurement (IL1, IL2, IL3 and I0)6 RTD inputs in two groups available with optional RTD module
RTD types can be mixed in the same module, e.g. Pt-100 and Ni-1202 thermistor (PTC) inputs can be used instead of RTDsRTDs and PTCs can be mixed, e.g. up to 4 RTDs + 2 PTCs
2 binary inputs (+ 3 additional in the optional RTD module)
Output contacts3 heavy-duty contacts capable of operating a circuit-breaker2 freely assignable signalling contacts1 pre-assigned signalling contact for IRF alarm
REM 610Motor Protection
©AB
B AG
-18-
Functionality
LCD, 2 x 16 charactersBuilt-in support for 7 languages: English, Finnish, Swedish, German, Spanish, French, ItalianIEC symbols / ANSI codes selectableFault indications5 fault recordings with time stampMeasurements and displays
Currents and temperaturesCalculated motor thermal capacity used and cooling time required before next motor start, etc.Historical data since commissioning, running hours, etc.
Settings in units of the motor full load current (FLC), 2 groupsConfigurations such as protocol settings, etc.Product information, identification, etc.
REM 610Motor Protection
©AB
B AG
-19-
Functionality
3 dedicated and 8 user-assignable LEDs + 1 dedicated LED indicating communication
Fast fault location and clearance (20 signals can be freely associated with 8 user-assignable LEDs), BI status, Restart Inhibit, Alarms, Trips…
3 dedicated LEDs for Ready, Start and Trip indication
1 dedicated LED for indicating local communication activity
Local communication port
6 push buttons
Arrow keys, Enter/Edit, Cancel/Clear
REM 610Motor Protection
©AB
B AG
-20-
Functionality
Self-supervision and alarmsContinuous testing of memory circuits, RAM, ROM, EEPROMSupervision of CT secondary circuits, MPX, ADCWatchdog functions for monitoring CPU operation and program excecutionInternal trip path continuity checkInternal power supply voltage drop-out check
External Trip Circuit Supervision (TCS)Temperature sensor (RTD) circuit open or short-circuitedRTD card alarmCommunication card alarmLow memory backup battery alarm Overtemperature alarm of internal power supply
REM 610Motor Protection
©AB
B AG
-21-
Functionality
Communication ProtocolsSPA bus communication (via front and rear port )
IEC 60870-103-5 communication (via rear port only)
Modbus communication (via rear port only)
REM 610Motor Protection
©AB
B AG
-22-
Communication: P = plastic fibre, R = RS - 485, N = none
RTD / thermistor card: M = included, N = noneTerminals: C = compression typePower supply: H = 100-240 Vac / 110-250 VdcEarth-fault current input: 5 = 5 A, 1 = 1 A Phase current inputs: 5 = 5 A, 1 = 1 ARevision
Ordering
Ordering key:
REM610A55HCMP
REM 610Motor Protection
©AB
B AG
-23-
Connections
REM 610Motor Protection
©AB
B AG
-24-
Setting calculation tool
REM 610Motor Protection
©AB
B AG
-25-
Required information
Motor settingsMotor rated current, starting current and starting time
CT ratings
Ambient temperature in degrees Celsius or Fahrenheit
REM 610Motor Protection
©AB
B AG
-26-
Relay settingsNumber of hot/cold starts allowed
Type of motor: p and kc settings
Protection principles: I>> doubling, use of I2 protection, etc
Protection requirements: I>> operation time, E/F sensitivity, etc
Required information
REM 610Motor Protection
©AB
B AG
-27-
The software guides the user through the settings and executes the calculations required
Faster and easier calculation and selection of settings
Outputs
REM 610Motor Protection
©AB
B AG
-28-
Outputs
The software allows the thermal behaviour of the motor to be simulated
Verification of settings
Better understanding of protection and settings
REM 610Motor Protection
©AB
B AG
-29-
Graphical visualization of trip curvesHardcopy report including settings and graphs
Outputs