Remote I/ORIO600Product Guide
Contents
1. Description.....................................................................3
2. Design............................................................................3
3. Configuration examples..................................................4
4. Self-supervision..............................................................5
5. Communication..............................................................5
6. Indication LEDs..............................................................5
7. Technical data................................................................6
8. Connection and terminal diagram.................................12
9. Dimensions and mounting............................................13
10. Assembly diagram.......................................................17
11. Ordering data..............................................................17
12. Tools...........................................................................17
13. Document revision history...........................................19
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2011 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Remote I/O 1MRS757487 ARIO600Product version: 1.0
2 ABB
1. DescriptionRIO600 is designed to expand the digital I/O ofABB’s Relion® series IEDs and to provide I/O forthe station automation device COM600 using theIEC 61850 communication. RIO600 allowsmaximum I/O flexibility and provides a seamlessIEC 61850 connectivity between the substationbinary input and output signals with IEDs ensuringimproved functionality and performance.
RIO600 helps in simplifying and decreasing thewiring inside the substation. The fully hardwiredtraditional medium voltage switchgear /substation control and protection system containsa centralized rack room approach resulting in
extensive I/O wiring, connecting devices forsignalling between the switchgear base andsignalling to and from the external systems forexample, to the RTU or other higher levelautomation systems.
RIO600 provides an additional I/O within theswitchgear itself, by using the Ethernet-based IEC61850 horizontal GOOSE communication. Thesignals can be transmitted within the switchgearand to the higher level automation systems.Similarly, signals from the upper level automationsystems can be executed through RIO600connected to numerical IEDs.
2. DesignRIO600 is built on the industrial hardwareplatform which provides the same reliability,performance, and real-time functionality as ABB
protection IEDs, withstanding extremetemperatures, electromagnetic interference andstringent industry standards.
IEC 61850-8-1
IEC 60870-5-104
ABBMicroSCADA
RET615 RET615 RIO600 REF630
IEC 61850-8-1
COM600Web HMI
COM600Web HMI
PCM600Ethernet switch
COM600
RIO600 RED615 RED615
RIO600
RIO600 REF615
COM600
Binary signaltransfer
PCM600Ethernet switch
Line differentialcommunication
GUID-F03EF024-C321-473D-B753-D7D490D99282 V1 EN
Figure 1. Connection overview of RIO600
Remote I/O 1MRS757487 ARIO600Product version: 1.0 Issued: 2011-12-23
Revision: A
ABB 3
RIO600 has modular architecture with specificfunctionality like inputs and outputs that are builton the modules. RIO600modules can be stackedon standard DIN rail to achieve the desiredconfiguration.
RIO600 consists of four module types.
• PSM_H - Power Supply Module• LECM - Communication Module• DIM8_H - Binary input module - 8 channels• DOM - Binary output module - 4 channels
Two power supplies can be used for redundancypurposes if there are less than 20 channels inRIO600.
3. Configuration examplesRIO600 can be configured to operate a maximumof 20 binary input/output signals using one powersupply module and up to 40 binary input/outputsignals using two power supply modules.
The user-specific configuration can be adapted asper application requirements by combiningdifferent modules.
PSM_H
Ready
DIM8_H
RIO600
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
LECM
Ready
IRF
Rx/Tx
10M/100M
DOM
Ready
IRF
DO1
DO2
DO3
DO4
RIO600 con�guration : 12 channels with 8 DI + 4 DO ( 1 * DIM8_H + 1 * DOM )
PSM_H
Ready
RIO600
LECM
Ready
IRF
Rx/Tx
10M/100M
DIM8_H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DIM8_H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DIM8_H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DIM8_H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DIM8_H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
PSM_H
Ready
RIO600 con�guration : 40 channels with 40 DI ( 5 * DIM8_H )
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN
Remote I/O 1MRS757487 ARIO600Product version: 1.0
4 ABB
PSM_H
Ready
RIO600
LECM
Ready
IRF
Rx/Tx
10M/100M
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
PSM_H
Ready
RIO600
LECM
Ready
IRF
Rx/Tx
10M/100M
DIM8_H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DIM8_H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DIM8_H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
DOM
Ready
IRF
DO1
DO2
DO3
DO4
PSM_H
Ready
RIO600 con�guration : 40 channels with 40 DO ( 10*DOM )
PSM_H
Ready
RIO600 con�guration : 40 channels with 24 DI + 16 DO ( 3*DIM8_H + 4*DOM )
GUID-FBC8542C-1954-4F29-BE46-34997C36F721 V1 EN
Figure 2. RIO600 remote I/O unit configuration examples
4. Self-supervisionRIO600 has built-in self-supervision feature whichcontinuously monitors the state of the RIO600hardware and the operation of the software. Anyfault or malfunction detected is used for alertingthe operator. The dedicated LED is provided toindicate the failure. RIO600 self-supervision statusis also distributed to the IEC 61850 station bus asone data entry in the published GOOSE frame.One of the output contact of DO module can alsobe configured to indicate the status of RIO600.
5. CommunicationRIO600 supports the horizontal GOOSEcommunication of the IEC 61850 substationautomation standard.
RIO600 is designed to send and receive binary
signals to or from the ABB Relion® series IEDsand the station automation device COM600 usingthe IEC 61850-8-1 GOOSE (Generic ObjectOriented Substation Event) profile.
RIO600 communication module includes agalvanic Ethernet RJ-45 port for IEC 61850GOOSE communication. The used cable typemust be at least Shielded Twisted Pair (STP)CAT5e.
Using the same Ethernet port, RIO600 can beconnected in parallel to PCM600 and a Webbrowser over the same communication bus.
6. Indication LEDsRIO600 is equipped with different indication LEDsavailable on different modules.• Ready LED on all modules• Status indication LED for each binary input and
output• Communication diagnostic LED on the
communication module
Remote I/O 1MRS757487 ARIO600Product version: 1.0
ABB 5
7. Technical data
Table 1. Dimensions of the power supply module (PSM_H)
Description Value
Width 51.0 mm
Height 145.5 mm
Depth 99.0 mm
Weight 235.0 g
Table 2. Dimensions of the communication module (LECM)
Description Value
Width 32.5 mm
Height 145.5 mm
Depth 81.0 mm
Weight 123.0 g
Table 3. Dimensions of the digital input module (DIM8_H)
Description Value
Width 51.0 mm
Height 145.5 mm
Depth 99.0 mm
Weight 206.0 g
Table 4. Dimensions of the digital output module (DOM)
Description Value
Width 32.5 mm
Height 145.5 mm
Depth 99.0 mm
Weight 163.0 g
Table 5. Dimensions of the end clamp (EW 35, Weidmuller)
Description Value
Width 8.5 mm (To be fixed on ends of assembled modules)
Remote I/O 1MRS757487 ARIO600Product version: 1.0
6 ABB
Table 6. Power supply
Description Value
Uaux nominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz
110, 125, 220, 250 V DC
Uaux variation 85...264 V AC
88...300 V DC
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Maximum interruption time in theauxiliary DC without resetting the RIOmodules
100 ms at Uaux nominal
Burden on auxiliary voltage supply at 240V AC
Module configuration Condition Consumption in VA
PSM_H + LECM + DIM8_H No DI activated 15.41
All DI activated at 90V DC 15.52
PSM_H + LECM + DOM No DO activated 15.52
All DO activated 16.23
PSM_H + LECM + DOM (5) All DO activated 23.00
PSM_H(2) + LECM + DOM(10) No DO activated 35.65
All 40 DO activated 43.24
Load sharing with other PSM in caseof two power supply used
Equal
Table 7. Binary inputs (Digital input module DIM8_H)
Description Value
Operating range ±20% of the rated voltage
Rated voltage 110...250 V DC
Current drain 1.8...2.6 mA
Power consumption/input channel 200...750 mW
Threshold voltage 78 V DC
Reaction time 0.3 ms + 1 ms...4.0 s filtering time
Remote I/O 1MRS757487 ARIO600Product version: 1.0
ABB 7
Table 8. Signal outputs (Digital output module DOM)
Description Value
Rated voltage 250V AC/DC
Continuous contact carry 5A
Make and carry for 3.0 s 10A
Make and carry for 0.5 s 15A
Breaking capacity when the control-circuit time constant L/R < 40 ms, at 48/110/220V DC
1A / 0.25A / 0.15A
Table 9. Communication interface (Communication module LECM)
Cable Data transfer
Shielded twisted pait cable, at minimum CAT5e withRJ-45 connector
10/100 MBits/s
Table 10. Degree of protection by enclosure
Description value
Degree of protection IP20
Table 11. Environmental conditions
Description Value
Operating temperature range -40...+70ºC
Relative humidity < 93%
Atmospheric pressure 86...106 kPa
Altitude up to 2000 m
Transport and storage temperature range -40...+85ºC
Table 12. Environmental tests
Description Type test value Reference
Dry heat test • 96 h at +70ºC IEC 60068-2-2
Dry cold test • 96 h at -40ºC IEC 60068-2-1
Damp heat test, cyclic • 6 cycles at +25...55ºC, humidity >93%
IEC 60068-2-30
Storage test • 96 h at +85ºC
• 96 h at -40ºC
IEC 60068-2-48
Remote I/O 1MRS757487 ARIO600Product version: 1.0
8 ABB
Table 13. Electromagnetic compatibility and immunity tests
Description Type test value Reference
Electrostatic discharge IEC 61000-4-2, Level 3 and IEC60255-22-2
• Contact discharge 6 kV
• Air discharge 8 kV
Radio-frequency electromagneticfield (amplitude modulated)
10 V/m (rms)f= 80 - 1000 MHz
IEC 61000-4-3, Level 3 and IEC60255-22-3
Radio-frequency electromagneticfield from digital radio telephones(pulse modulated)
10 V/m (rms)f = 900 MHz
IEC 61000-4-3, Level 3 and IEC60255-22-3
Power-frequency (50 Hz) magneticfield
IEC 61000-4-8, Level 5
• Continuous 100 A(rms)/m
• 1 second 1000 A(rms)/m
Pulse magnetic field 1000A/m; 1.2/50 (8/20) μs Tr/Th; 5pulses positive/negative; 10 s (timeinterval)
IEC 61000-4-9, Level 5
Conducted disturbance induced byradio frequency fields, Amplitudemodulated
0.15 – 80 MHz - 10 V (unmod., rms);80% AM (1 kHz); 150 Ohms sourceimpedance; 27 and 68 MHz (spotfrequencies); 10 V (unmod., rms);80% AM (1 kHz); 150 Ohms sourceimpedance
IEC 61000-4-6, Level 3 and IEC60255-22-6
Fast low energy transient (EFT)(including functional earth port)
5/50 ns Tr/Th; 2.5 kHz repetitionfrequency; 4 kV (peak) for powersupply and input/output ports; 2 kV(peak) for communication port
IEC 61000-4-4, Level 4 and IEC60255-22-4
Damped oscillatory waves (HFD) 1MHz burst
1MHz frequency; 75ns Tr; 400 Hzrepetition frequency; 200 Ohmssource impedance; power supply andInput/output ports :- Differentialmode : 1 kV (peak); Common mode :2.5 kV (peak); For communicationport :- differential mode : notapplicable ; common mode : 1 kV(peak)
IEC 61000-4-12, Level 3 and IEC60255-22-1
Slow high energy transient(surge1.2/50 us voltage pulse)
Auxiliary power supply and input/output ports - ± 4 kVp (L-Gnd) ± 2kVp (L-L); Communication port - ± 2kVp (L-Gnd) while no L-L test isapplicable.; 1.2/50 μs Tr/Th (opencircuit); 8/20 μs Tr/Th (short circuit)
IEC61000-4-5, Level 4 and IEC60255-22-5
Voltage interruption 100% reduction; 2, 5, 10, 20, 50,100, 200 ms
IEC 60255-11
Remote I/O 1MRS757487 ARIO600Product version: 1.0
ABB 9
Table 13. Electromagnetic compatibility and immunity tests, continued
Description Type test value Reference
Voltage dips, short interruptions andvoltage variation immunity tests (AC50 Hz and 60 Hz)
30 % reduction for 1 period60% reduction for 50 periods100% reduction for 5 periods100% reduction for 50 periods
IEC 61000-4-11 and IEC 61000-6-5,level 5
Voltage drop, supply Interruption andvoltage variations on d.c. input powerport (immunity tests)
30% reduction for 0.1 s60% reduction for 0.1 s100% reduction for 0.05 s
IEC 61000-4-29 and IEC 61000-6-5
Ripple voltage 10 % Un, 50 and 60 Hz (frequenciesof ripple)
IEC 61000-4-17 and IEC 61000-6-5
Power frequency voltage 50 Hz and60 Hz
For Input/output port :- Differentialmode ;- 150 V r.m.s., 100 Ω couplingresistor, 0.1μF coupling capacitor ;Common mode;- 300V r.m.s., 220Ωcoupling resistor, 0,47 μF couplingcapacitor
IEC 61000-4-16 and IEC 60255-22-7
Emission tests IEC 60255-25
• Radiated
30...230 MHz < 40 dB (μV/m) quasi peak,measured at 10 m distance
230...1000 MHz < 47 dB (μV/m) quasi peak,measured at 10 m distance
• Conducted
0.15...0.50 MHz < 79 dB (μV) quasi peak< 66 dB (μV) average
0.5...30 MHz < 73 dB (μV) quasi peak< 60 dB (μV) average
Table 14. Insulation tests
Description Type test value Reference
Dielectric testsTest voltage
2 kV, 50 Hz, 1 min500V, 50 Hz, 1 min, communication
IEC 60255-5 and IEC 60255-27
Impulse voltage testsTest voltage
5 kV, 1.2/50 μs, 0.5 J,1 kV, 1.2/50 μs, 0.5 J, communication
IEC 60255-5 and IEC 60255-27
Insulation resistance measurementInsulation resistance
>100 MΩ, 500 V DC
IEC 60255-5 and IEC 60255-27
Earth leaking current test < 3.5 mA AC10 mA DC
IEC 60255-27
Mechanical durability of plug-in relays 200 withdrawals and insertions underdeenergized conditions
IEC 60255-6
Remote I/O 1MRS757487 ARIO600Product version: 1.0
10 ABB
Table 15. Mechanical tests
Description Reference Requirement
Vibration tests (sinusoidal) IEC 60255-21-1 Class 2Vibration response test: - f = 10…150Hz - ± 0.075 mm/1.0 g - 1 sweepcycle in each axis Vibrationendurance test:- f = 10…150 Hz - 2.0g - 20 sweep cycles in each axis
Shock and bump test IEC 60255-21-2 Class 2Shock response test:- peakacceleration 10 g - duration of thepulse 11 ms - number of pulses ineach direction: 3 .Shock withstand test: - peakacceleration 30 g - duration of thepulse 11 ms - number of pulses ineach dir3 Bump test:- peakacceleration 20 g - duration of thepulse 16 ms - number of pulses ineach direction: 1000
Table 16. Contact tests
Description Type test value Reference
Make and carry Signalling contacts:5 A, continuous; 8 A for 3 s; 10 A for0.5 s
IEC 60255-23 and IEC 60255-27
Breaking capacity for d.c., L/R ≤ 40 ms Signalling contacts:48 V, 1 A; 110 V, 0.25 A; 220 V, 0.15A
IEC 60255-23 and IEC 60255-27
Mechanical durability 10000 operations IEC 60255-6
Table 17. EMC compliance
Description Reference
EMC directive 2004/108/IEC
Standard EN 50263 (2000)EN 60255-26 (2007)
Table 18. RoHS compliance
Description
Complies with RoHS directive 2002/95/EC
Remote I/O 1MRS757487 ARIO600Product version: 1.0
ABB 11
8. Connection and terminal diagram
Uaux
X1
1 ( PE )
2 ( NC )
3 ( N/- )
4 ( L/+ )
5 ( NC )
5 ( PE )
PSM_H DIM8_H
DI 1
DI 2
DI 3
DI 4
1 ( 0V + )
2 ( DI1 )
3 ( DI2 )
4 ( DI3 )
5 ( DI4 )
6 ( 0V + )
X1
DI 5
DI 6
DI 7
DI 8
1 ( 0V + )
2 ( DI5 )
3 ( DI6 )
4 ( DI7 )
5 ( DI8 )
6 ( 0V + )
X2
X1
DO 1
DO 2
DO 3
DO 4
1 ( COM )
2 ( DO1 )
3 ( DO2 )
4 ( DO3 )
5 ( DO4 )
6 ( COM )
DOM
GUID-6E6D23B5-5AB7-4BE8-891D-44685DA9769E V1 EN
Figure 3. Connection and terminal diagram of RIO600 modules
Remote I/O 1MRS757487 ARIO600Product version: 1.0
12 ABB
9. Dimensions and mounting
A B D
E
F
CGUID-907D3C00-52C3-464F-B37E-044C89D1C344 V1 EN
Figure 4. Dimension and mounting details of RIO600 Power supply module PSM_H
A 46 mm
B 4.5 mm
C 51mm
D 99 mm
E 81 mm
F 145.5 mm
Remote I/O 1MRS757487 ARIO600Product version: 1.0
ABB 13
GUID-B5C4052E-7782-4E23-9A45-0706B1EF3E51 V1 EN
Figure 5. Dimension and mounting details of RIO600 Digital Input module DIM8_H
A 46 mm
B 4.5 mm
C 51 mm
D 99 mm
E 81 mm
F 145.5 mm
Remote I/O 1MRS757487 ARIO600Product version: 1.0
14 ABB
A B D
F
E
CGUID-3C54DC2F-92F6-4B6C-A457-2F1F0403D871 V1 EN
Figure 6. Dimension and mounting details of RIO600 Digital Output module DOM
A 27.5 mm
B 4.5 mm
C 32.5 mm
D 99 mm
E 81 mm
F 145.5 mm
Remote I/O 1MRS757487 ARIO600Product version: 1.0
ABB 15
BA D
E
CGUID-7770857A-8B26-4B64-95E4-5ADDB579D4C8 V1 EN
Figure 7. Dimension and mounting details of RIO600 Communication module LECM
A 27.5 mm
B 4.5 mm
C 32.5 mm
D 81 mm
E 145.5 mm
Remote I/O 1MRS757487 ARIO600Product version: 1.0
16 ABB
10. Assembly diagram
2
3 4 5 6
7
1 1
2
GUID-57402DEF-96C5-4555-9254-BD644C9D5B40 V1 EN
Figure 8. Assembly drawings of RIO600 modules
1 Rubber cap
2 End clamp
3 PSM module
4 LECM module
5 Digital Input module
6 Digital Ouptput module
7 DIN Rail
The total length of the assembly can becalculated by adding together length of allmodules.
The length of the end clamp depends on theselected part. This mounting uses the Weidmullerpart EW 35 which is 8.5 mm wide.
11. Ordering data
Table 19. RIO600 module ordering details
Item Order number
Digital input module with 8 inputs MOD600ADIM8H
Digital output module with 4 outputs MOD600ADOM4R
Power supply module MOD600APSMH07
Communication module with RJ-45 port MOD600ALECMIR
12. ToolsThe present status information of RIO600 can beviewed from the Web-browser based userinterface (Web HMI) and the parameter setting
values can be viewed or changed from thePCM600 tool in combination with the RIO600-specific connectivity package.
Remote I/O 1MRS757487 ARIO600Product version: 1.0
ABB 17
The Protection and Control IED Manager PCM600is available in three different variants, that isPCM600, PCM600 Engineering and PCM600Engineering Pro. PCM600 Engineering Pro withthe RIO600 connectivity package is used forconfiguring RIO600 in offline or online mode toconnect to the other IEDs in IEC 61850 stationbus. When the Web-browser based user interfaceis used, RIO600 can be accessed remotely usinga Web browser (IE 7.0 or later).
The RIO600 connectivity package is a collectionof software and specific device information, whichenable system products and tools to connect andinteract with RIO600. The connectivity packagesreduce the risk of errors in system integration,minimizing device configuration and set-up times.
Table 20. Tools
Configuration and setting tools Version
PCM600 2.3 or later
Web-browser based user interface IE 7.0 or later
RIO600 Connectivity Package 1.0 or later
GUID-1857CDEE-7790-47E7-ABDA-720D2A80DFF6 V1 EN
Figure 9. General view of RIO600 WHMI
Remote I/O 1MRS757487 ARIO600Product version: 1.0
18 ABB
13. Document revision history
Document revision/date Product version History
A/2011-12-23 1.0 First release
Remote I/O 1MRS757487 ARIO600Product version: 1.0
ABB 19