REPORT OF ASBESTOS AND PCB INSPECTION
Performed For: HA2F Consultants in Engineering 1 Van Patten Drive Clifton Park, New York 12065
Location of Inspection: Junius Ponds and Clifton Springs NYS Thruway Service Plazas
Material or Area Inspected: Service Plaza Roofs, Generator Building Roof (Clifton Springs)
Asbestos Material Found: Junius Ponds – None Clifton Springs Generator Building – Flashing, tar on deck, window caulk
PCBs Found: None
Non‐Asbestos Materials Tested: Junius Ponds Service Plaza Perlite insulation, built‐up roofing & flashing, parapet wall roofing, tar on
deck, flashing cement, seam cement, door caulk, metal flashing caulk, cap block caulk
Clifton Springs Service Plaza Perlite insulation, built‐up roofing & flashing, parapet wall roll roofing, seam
cement, tar on parapet wall, flashing cement, door caulk
Clifton Springs Service Plaza – Generator Building Built‐up roofing
Non‐PCB Materials Tested: Junius Ponds Service Plaza Roof 1E door caulk
Clifton Springs Service Plaza Roof 1D Door Caulk, roof insulation, generator building window caulk
Date(s) of Inspection: July 26&27 and August 30, 2012
Project Number: 12‐13058‐A
July 2012 Junius Ponds and Clifton Springs Service Plazas NYS Thruway
Page 2 of 5 1146 Central Ave. ● Albany, New York 12205 ● Phone: (518) 453‐0146
Inspection By: Alpine Environmental Services, Inc. 1146 Central Avenue Albany, New York 12205 Phone (518) 453‐0146
Inspector(s): Paul Van Zandt: NYSDOL Cert.#AH95‐02581
1.0 Asbestos Inspection
1.1 Scope and Purpose
This report is intended to document the pre‐renovation asbestos inspection of the roofs of the above‐mentioned New York State service plazas. The buildings are located within the Syracuse division of the New York State Thruway. “Asbestos containing materials”, as defined by the United States Environmental Protection Agency (EPA), is any material containing greater than 1% by weight of asbestos. Friable samples (samples easily crushed/pulverized by hand pressure), were analyzed via Polarized Light Microscopy (PLM) and Non‐Friable samples (samples not easily crushed/pulverized by hand pressure), were analyzed via Transmission Electron Microscopy (TEM) by EMSL Laboratory of New York, New York, a New York State Department of Health Approved Laboratory (ELAP #11506). 1.2 Description Junius Ponds and Clifton Springs both had multiple roof areas to be inspected. All of the service plaza roofs were built‐up. There was a generator building at the Clifton Springs service plaza. The roof of the generator building at the Clifton Springs Service Plaza was completely covered with water at the time of the initial inspection and therefore was not sampled. Roof Area 1D was not accessible at the Clifton Springs Plaza at the time of inspection. Alpine returned on August 30th and sampled the remaining roofs. The generator building roof was PVC over built‐up roofing that was adhered to the concrete deck. 1.3 Limitations Quantities of asbestos containing materials were estimated and the user must field verify all quantities. The atrium windows of the Junius Ponds and Clifton Springs Plazas were inaccessible at the time of inspection.
1.4 Results of Asbestos Inspection Bulk samples were collected throughout the subject areas, as prescribed by US EPA ASHARA protocols for the number and types of samples.
July 2012 Junius Ponds and Clifton Springs Service Plazas NYS Thruway
Page 3 of 5 1146 Central Ave. ● Albany, New York 12205 ● Phone: (518) 453‐0146
The following asbestos containing materials were found at the following locations:
Building
Location ACM
(Sample #’s) Quantity Substrate Friability Condition
Clifton Springs
Service Plaza
Generator Building Roof
Flashing (10‐01, 10‐02)
32 sq. ft. Concrete Non‐friable
Good
Tar on Deck (11‐01, 11‐02)
240 sq. ft. Concrete Non‐friable
Good
Generator Building
Window Caulk (12‐01, 12‐02)
8 sq. ft. Brick Non‐friable
Good
Quantities are estimates only and should be field verified by the user.
The following materials were sampled and determined not to contain asbestos:
Building Non‐Asbestos
Material Locations Sample #’s
Junius Ponds Service Plaza
Built‐Up Roofing Roof Areas #1A, 1B, 1C, 1D, 1E
1‐01, 1‐02, 1‐03, 1‐04, 1‐05, 1‐06, 1‐07, 1‐08, 1‐09, 1‐10
Flashing Roof Area #1A, 1B, 1C, 1D, 1E
2‐01, 2‐02, 2‐03, 2‐04, 2‐05, 2‐06, 2‐07, 2‐08, 2‐09, 2‐10
Parapet Wall Roofing
Roof 1E Parapet Wall 3‐01, 3‐02
Tar on Deck Roofs 1A, 1E 4‐01, 4‐02, 4‐03, 4‐04
Flashing Cement Roof 1C Pitch Pocket 5‐01, 5‐02
Seam Cement Roofs 1A, 1D, 1E 6‐01, 6‐02, 6‐03, 6‐04
Door Caulk Roof 1E 7‐01, 7‐02 Flashing Caulk Roofs 1B, 1C Metal Flashing at Capblock 8‐01, 8‐02 Capblock Caulk Roof 1B 9‐01, 9‐02 Perlite Insulation Roofs 1A, 1E 10‐01, 10‐02
Clifton Springs Service Plaza
Built‐Up Roofing Roofs 1A, 1B, 1C, 1D
1‐01, 1‐02 1‐03, 1‐04 1‐05, 1‐06 3‐01, 3‐02*
Flashing Roofs 1A, 1B, 1C, 1D
2‐01, 2‐02 2‐03, 2‐04 2‐05, 2‐06 4‐01, 4‐02*
Parapet Wall Roofing
Roof 1B, Roof 1D 3‐01, 3‐02 5‐01, 5‐02*
July 2012 Junius Ponds and Clifton Springs Service Plazas NYS Thruway
Page 4 of 5 1146 Central Ave. ● Albany, New York 12205 ● Phone: (518) 453‐0146
Non‐Asbestos Materials Cont’d
Building Non‐Asbestos
Material Locations Sample #’s
Clifton Springs Service Plaza
Cont’d
Seam Cement Roof 1B on Parapet Wall, Roof 1D on Parapet Wall
4‐01, 4‐02 7‐01, 7‐02*
Tar on Wall Roof 1B Parapet Wall Under Roll Roofing 5‐01, 5‐02
Flashing Cement Roof 1B at Scupper, Roof 1C at Pitch Pocket,
Roof 1D at Scupper 6‐01, 6‐02 6‐01, 6‐02*
Perlite Insulation Roofs 1A, 1C 7‐01, 7‐02 Door Caulk Roof 1D 8‐01, 8‐02*
Clifton Springs Service Plaza Generator Building
Built‐up Roofing Generator Building Roof 9‐01, 9‐02*
*Samples taken on August 30, 2012. 1.5 Conclusion & Recommendations Any materials not sampled during this inspection should be considered suspect unless sampled and determined to be non‐asbestos. All asbestos containing materials must be abated prior to the demolition/renovation of any of the structures unless performed under a variance issued by the NYS Department of Labor. Disturbance/Abatement of any asbestos containing materials, as well as necessary air monitoring, must be performed by a NYS DOL licensed contractor, in accordance with state and federal regulations (NYS DOL ICR 56 and US EPA 40 CFR). 2.0 PCB Inspection: 2.1 Scope and Purpose An inspection was performed of the subject structures for possible PCB containing items. This inspection included only the sampling of window and door caulks and roofing insulation for PCB analysis. The roofing insulation samples were made into a composite sample. “PCBs”, or Polychlorinated Biphenyls contaminated material, as defined by the United States Environmental Protection Agency (EPA), is any material containing greater than 50ppm by weight of PCBs. 2.2 Conclusion Polychlorinated Biphenyls (PCBs)
Polychlorinated biphenyl (PCB) oils were commonly used as thermal insulating fluids in electrical and hydraulic equipment prior to a (approximately) 1977 manufacture date. Transformers and electrical ballasts are common places where PCB containing oils were used. Polychlorinated Biphenyls (PCBs) may be present in the caulk used in windows, doorframes, masonry columns, and other masonry building materials in many schools built or renovated between 1950 and 1978.
July 2012 Junius Ponds and Clifton Springs Service Plazas NYS Thruway
Page 5 of 5 1146 Central Ave. ● Albany, New York 12205 ● Phone: (518) 453‐0146
PCB Caulking Sample Analysis The purpose of sampling was to determine the Polychlorinated Biphenyls (PCB) content of the caulking at the roof doors, roofing insulation and window caulk.
Building Sample Location PCB Content
(ppm) Junius Ponds Svc
Plaza Roof Area #1E – Door Caulk None detected
Clifton Springs Roof Area #1D – Door Caulk None detected
Roof Area #1D – Roof Insulation Composite None detected Generator Building – Window Caulk None detected
If I can be of any further assistance to you on this, or any other matter, please do not hesitate to contact me (518) 453‐0146, ext. 314. Sincerely, Alpine Environmental Services, Inc.
Paul Van Zandt NYS Dept. of Labor Asbestos Inspector Certificate # AH95‐02581
Enclosures: Samples Results, Chains of Custodies, Company License, Personal Certifications, Laboratory Certifications
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224199CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 07/31/2012 9:47 AM
12-13058-A/ JUNIUS PONDS SERVICE PLAZA/ PHELPS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/2/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
1-01031224199-0001
ROOF AREA #1A/ BOTTOM LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass7.0%
1-02031224199-0002
ROOF AREA #1A/ BOTTOM LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass5.3%
2-01031224199-0003
ROOF AREA #1A/ BOTTOM LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass1.9%
2-02031224199-0004
ROOF AREA #1A/ TOP LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass2.9%
1-03031224199-0005
ROOF AREA #1B/ BOTTOM LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass7.2%
1-04031224199-0006
ROOF AREA #1B/ TOP LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass6.6%
Page 1Test Report NY198w/A-7.21.0 Printed: 8/2/2012 7:16:49 PM
Initial Report From 08/02/2012 17:54:58
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224199CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 07/31/2012 9:47 AM
12-13058-A/ JUNIUS PONDS SERVICE PLAZA/ PHELPS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/2/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
2-03031224199-0007
ROOF AREA #1B - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass6.4%
2-04031224199-0008
ROOF AREA #1B - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass4.8%
1-05031224199-0009
ROOF AREA #1C/ BOTTOM LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass1.5%
1-06031224199-0010
ROOF AREA #1C/ TOP LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass2.3%
2-05031224199-0011
ROOF AREA #1C/ BOTTOM LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass4.5%
2-06031224199-0012
ROOF AREA #1A/ TOP LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass2.3%
1-07031224199-0013
ROOF AREA #1D/ BOTTOM LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass3.6%
Page 2Test Report NY198w/A-7.21.0 Printed: 8/2/2012 7:16:49 PM
Initial Report From 08/02/2012 17:54:58
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224199CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 07/31/2012 9:47 AM
12-13058-A/ JUNIUS PONDS SERVICE PLAZA/ PHELPS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/2/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
1-08031224199-0014
ROOF AREA #1D/ TOP LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass2.2%
2-07031224199-0015
ROOF AREA #1D - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass7.4%
2-08031224199-0016
ROOF AREA #1D - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass2.1%
1-09031224199-0017
ROOF AREA #1E/ BOTTOM LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass<1%
1-10031224199-0018
ROOF AREA #1E/ TOP LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass1.8%
2-09031224199-0019
ROOF AREA #1E - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass3.6%
2-10031224199-0020
ROOF AREA #1E/ TOP LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass2.6%
Page 3Test Report NY198w/A-7.21.0 Printed: 8/2/2012 7:16:49 PM
Initial Report From 08/02/2012 17:54:58
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224199CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 07/31/2012 9:47 AM
12-13058-A/ JUNIUS PONDS SERVICE PLAZA/ PHELPS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/2/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
3-01031224199-0021
ROOF AREA #1E/ PARAPET WALL - ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass1.8%
3-02031224199-0022
ROOF AREA # 1E PARAPET WALL - ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass<1%
4-01031224199-0023
ROOF AREA #1A - TAR ON DECK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
4-02031224199-0024
ROOF AREA #1A - TAR ON DECK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass<1%
4-03031224199-0025
ROOF AREA #1E - TAR ON DECK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass<1%
4-04031224199-0026
ROOF AREA #1E - TAR ON DECK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass2.8%
5-01031224199-0027
ROOF AREA #1C/ AT PITCH POCKET - FLASHING CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Page 4Test Report NY198w/A-7.21.0 Printed: 8/2/2012 7:16:49 PM
Initial Report From 08/02/2012 17:54:58
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224199CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 07/31/2012 9:47 AM
12-13058-A/ JUNIUS PONDS SERVICE PLAZA/ PHELPS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/2/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
5-02031224199-0028
ROOF AREA #1C/ AT PITCH POCKET - FLASHING CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
6-01031224199-0029
ROOF AREA #1A/ ON PARAPET WALL - SEAM CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
6-02031224199-0030
ROOF AREA #1D/ ON PARAPET WALL - SEAM CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
6-03031224199-0031
ROOF AREA #1E - SEAM CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
6-04031224199-0032
ROOF AREA #1E - SEAM CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
7-01031224199-0033
ROOF AREA #1E - DOOR CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
White
White
7-02031224199-0034
ROOF AREA #1E - DOOR CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
White
White
Page 5Test Report NY198w/A-7.21.0 Printed: 8/2/2012 7:16:49 PM
Initial Report From 08/02/2012 17:54:58
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224199CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 07/31/2012 9:47 AM
12-13058-A/ JUNIUS PONDS SERVICE PLAZA/ PHELPS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/2/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
8-01031224199-0035
ROOF AREA #1B/ METAL FLASHING AT CAPBLOCK - FLASH CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Gray
Gray
8-02031224199-0036
ROOF AREA #1C/ METAL FLASHING AT CAPBLOCK - FLASH CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Gray
Gray
9-01031224199-0037
ROOF AREA #1B - CAPBLOCK CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Gray
Gray
9-02031224199-0038
ROOF AREA #1B - CAPBLOCK CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Gray
Gray
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. The above test report relates only to the items tested. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The results in this report meet all requirements of the NELAC Standards unless otherwise noted. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM is not consistently reliable in detecting asbestos in floor coverings and similar NOB's. Quantitative TEM is currently the only method that can be used to determine if a NOB material can be considered or treated as non-asbestos containing.
James Hall, Laboratory Manageror other approved signatory
Analyst(s)
NOB = Non Friable Organically Bound N/A = Not Applicable
Derrick Young
Steve Jusczuk
Samples analyzed by EMSL Analytical, Inc. New York, NY NYS ELAP 11506
Page 6THIS IS THE LAST PAGE OF THE REPORT.Test Report NY198w/A-7.21.0 Printed: 8/2/2012 7:16:49 PM
Initial Report From 08/02/2012 17:54:58
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224225CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205Received: 07/31/12 9:46 AM
12-13058-A/ JUNIUS PONDS SERVICE PLAZA/ PHELPS, NY
Fax: (518) 453-0175Phone: (518) 453-0146
Project:
8/2/2012Analysis Date:7/26/2012Collected:
Sample Description Appearance % TypeAsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials by PLM via the NY State ELAP 198.1 Method
10-01031224225-0001
ROOF AREA #1A/ PERLITE INSULATION
Brown None DetectedFibrousHeterogeneous
Cellulose95.00% Non-fibrous (other)5.00%
10-02031224225-0002
ROOF AREA #1E/ PERLITE INSULATION
Brown None DetectedFibrousHeterogeneous
Cellulose95.00% Non-fibrous (other)5.00%
James Hall, Laboratory Manageror other approved signatory
Test Report PLMPTC-7.25.0 Printed: 8/2/2012 8:48:19 PM 1
Analyst(s)
THIS IS THE LAST PAGE OF THE REPORT.
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample.Samples analyzed by EMSL Analytical, Inc. New York, NY NYS ELAP 11506
Albert Grohmann (2)
Initial report from 08/02/2012 19:33:24
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224340CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 08/01/2012 10:19 AM
12-13058-A/ CLIFTON SPRINGS SVC PLAZA/ CLIFTON SPRINGS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/3/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
1-01031224340-0001
ROOF AREA #1A/ BOTTOM LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass6.2%
1-02031224340-0002
ROOF AREA #1A/ TOP LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
2-01031224340-0003
ROOF AREA #1A/ BOTTOM LAYER (UNDER INSULATION) - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
2-02031224340-0004
ROOF AREA #1A/ TOP LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass<1%
1-03031224340-0005
ROOF AREA #1B - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass3.2%
1-04031224340-0006
ROOF AREA #1B - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass4.4%
2-03031224340-0007
ROOF AREA #1B/ BOTTOM LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass<1%
Page 1Test Report NY198w/A-7.21.0 Printed: 8/3/2012 4:19:50 PM
Initial Report From 08/03/2012 16:19:50
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224340CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 08/01/2012 10:19 AM
12-13058-A/ CLIFTON SPRINGS SVC PLAZA/ CLIFTON SPRINGS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/3/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
2-04031224340-0008
ROOF AREA #1B/ TOP LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass2.7%
1-05031224340-0009
ROOF AREA #1C/ BOTTOM LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass5.6%
1-06031224340-0010
ROOF AREA #1C/ TOP LAYER - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass3.3%
2-05031224340-0011
ROOF AREA #1C/ BOTTOM LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass4.6%
2-06031224340-0012
ROOF AREA #1C/ TOP LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass1.2%
3-01031224340-0013
ROOF AREA #1B/ ON PARAPET WALL - ROLL ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass1.0%
Page 2Test Report NY198w/A-7.21.0 Printed: 8/3/2012 4:19:50 PM
Initial Report From 08/03/2012 16:19:50
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224340CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 08/01/2012 10:19 AM
12-13058-A/ CLIFTON SPRINGS SVC PLAZA/ CLIFTON SPRINGS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/3/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
3-02031224340-0014
ROOF AREA #1B/ ON PARAPET WALL - ROLL ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Glass6.9%
4-01031224340-0015
ROOF AREA #1B/ ON PARAPET WALL - SEAM CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
4-02031224340-0016
ROOF AREA #1B/ ON PARAPET WALL - SEAM CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
5-01031224340-0017
ROOF AREA #1B/ ON PARAPET WALL UNDER ROLL - TAR ON WALL
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
5-02031224340-0018
ROOF AREA #1B/ ON PARAPET WALL UNDER ROLL - TAR ON WALL
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
6-01031224340-0019
ROOF AREA #1B/ AT SCUPPER - FLASHING CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Page 3Test Report NY198w/A-7.21.0 Printed: 8/3/2012 4:19:50 PM
Initial Report From 08/03/2012 16:19:50
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224340CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 08/01/2012 10:19 AM
12-13058-A/ CLIFTON SPRINGS SVC PLAZA/ CLIFTON SPRINGS, NYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
8/3/2012Analysis Date:
Collected: 7/26/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
6-02031224340-0020
ROOF AREA #1C/ AT PITCH POCKET - FLASHING CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
8/2/2012
8/3/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. The above test report relates only to the items tested. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The results in this report meet all requirements of the NELAC Standards unless otherwise noted. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM is not consistently reliable in detecting asbestos in floor coverings and similar NOB's. Quantitative TEM is currently the only method that can be used to determine if a NOB material can be considered or treated as non-asbestos containing.
James Hall, Laboratory Manageror other approved signatory
Analyst(s)
NOB = Non Friable Organically Bound N/A = Not Applicable
Derrick Young
Steve Jusczuk
Samples analyzed by EMSL Analytical, Inc. New York, NY NYS ELAP 11506
Page 4THIS IS THE LAST PAGE OF THE REPORT.Test Report NY198w/A-7.21.0 Printed: 8/3/2012 4:19:50 PM
Initial Report From 08/03/2012 16:19:50
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031224350CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205Received: 08/01/12 10:11 AM
12-13058-A/ CLIFTON SPRINGS SVC PLAZA/ CLIFTON SPRINGS, NY
Fax: (518) 453-0175Phone: (518) 453-0146
Project:
8/2/2012Analysis Date:7/26/2012Collected:
Sample Description Appearance % TypeAsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials by PLM via the NY State ELAP 198.1 Method
7-01031224350-0001
ROOF AREA #1A - PERLITE INSULATION
Brown None DetectedNon-FibrousHeterogeneous
Cellulose65.00% Non-fibrous (other)35.00%
7-02031224350-0002
ROOF AREA #1C - PERLITE INSULATION
Brown None DetectedFibrousHomogeneous
Cellulose55.00% Non-fibrous (other)20.00%Perlite25.00%
James Hall, Laboratory Manageror other approved signatory
Test Report PLMPTC-7.25.0 Printed: 8/2/2012 10:33:36 PM 1
Analyst(s)
THIS IS THE LAST PAGE OF THE REPORT.
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample.Samples analyzed by EMSL Analytical, Inc. New York, NY NYS ELAP 11506
Emily Myint (1)Kamel Alawawda (1)
Initial report from 08/02/2012 22:07:10
Analytical Sample Results
Job Number: 12080151Fax: 518.381.6055Phone: 518.346.4592Schenectady, NY 123082190 Technology DrivePace Analytical Services, Inc.
Client Sample ID:Sample Matrix:Received Date:
Collection Date:
1-ROOF 1E DOOR CAULKCAULK
08/08/2012 17:47
07/26/2012
Lab Sample ID: 12080151-01 (AP23287)
ALPINE ENVIRONMENTAL SERVICES, INCClient:
Batch ID AnalystDate Init Wt./Vol.Method Final Vol. ColumnGC20F-1354-52 SW-846 8082 (PCB) JKA08/14/2012 23:33 NAAnalysis 1: NA Phenomenex, Zebron ZB-1, 30 m, 0.25 mm ID, 0.25 µm
19424 EPA 3540C JWO08/13/2012 15:31 1.02 gPrep 1: 25.0 mL NA
N/APercent Solid:
JUNIUS PONDS SERVICE STN WARNERS NY 12-13058-AProject:
Analyte CAS No. Result (ug/g) PQL Dilution Factor Flags File IDNDAroclor 1016 0.488 1.00 GC20F-1354-52U12674-11-2NDAroclor 1221 0.488 1.00 GC20F-1354-52U11104-28-2NDAroclor 1232 0.488 1.00 GC20F-1354-52U11141-16-5NDAroclor 1242 0.488 1.00 GC20F-1354-52U53469-21-9NDAroclor 1248 0.488 1.00 GC20F-1354-52U12672-29-6NDAroclor 1254 0.488 1.00 GC20F-1354-52U11097-69-1NDAroclor 1260 0.488 1.00 GC20F-1354-52U11096-82-5NDAroclor 1262 0.488 1.00 GC20F-1354-52U37324-23-5NDAroclor 1268 0.488 1.00 GC20F-1354-52U11100-14-4NDTotal PCB Amount > RL 1.00 GC20F-1354-52U1336-36-3
SurrogateLimits
Q File ID% RecoveryCAS No.1
(%)Tetrachloro-meta-xylene 95.8 60.0-140 GC20F-1354-52877-09-8Decachlorobiphenyl 104 60.0-140 GC20F-1354-522051-24-3Qualifier column where '*' denotes value outside the control limits or 'D' denotes value was diluted out. 1
ND: Denotes analyte not detected at a concentration greater than the PQL.PQL (Practical Quantitation Limit). Denotes lowest analyte concentration reportable for the sample.
2190 Technology Drive | Schenectady, NY 12308 | Phone 518.346.4592 | Fax 518.381.6055 | www.pacelabs.comThis report may not be reproduced except in full, without the written approval of Pace Analytical Services, Inc.
4
Pace Analytical Services, Inc. 12080151 Page 11 of 14
3
Pace Analytical Services, Inc. 12080151 Page 9 of 14
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031228043CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 09/01/2012 8:57 AM
12-13058-A/ CLIFTON SPRINGS SERVICE AREA/ NYS THRUWAYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
9/1/2012Analysis Date:
Collected: 8/30/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
1-01031228043-0001
ROOF/ AREA 1D AT ROOF CORE - PERLITE INSULATION
PLM NYS 198.1 Friable 9/1/2012
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
Not Analyzed
Not Analyzed
N/A
N/A
None DetectedBrown 25%Cellulose75.00%
1-02031228043-0002
ROOF/ AREA 1D AT FLASH CORE - PERLITE INSULATION
PLM NYS 198.1 Friable 9/2/2012
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
Not Analyzed
Not Analyzed
N/A
N/A
None DetectedBrown 60%Cellulose40.00%
2-01031228043-0003
GENERATOR BUILDING ROOF AT ROOF CORE - CONCRETE DECK
PLM NYS 198.1 Friable 9/1/2012
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
Not Analyzed
Not Analyzed
N/A
N/A
None DetectedGray/Black 100%
2-02031228043-0004
GENERATOR BUILDING ROOF AT FLASH CORE - CONCRETE DECL
PLM NYS 198.1 Friable 9/2/2012
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
Not Analyzed
Not Analyzed
N/A
N/A
None DetectedGray/Black 100%
Page 1Test Report NY198w/A-7.21.0 Printed: 9/2/2012 5:42:38 AM
Initial Report From 09/02/2012 05:41:46
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031228043CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 09/01/2012 8:57 AM
12-13058-A/ CLIFTON SPRINGS SERVICE AREA/ NYS THRUWAYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
9/1/2012Analysis Date:
Collected: 8/30/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. The above test report relates only to the items tested. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The results in this report meet all requirements of the NELAC Standards unless otherwise noted. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM is not consistently reliable in detecting asbestos in floor coverings and similar NOB's. Quantitative TEM is currently the only method that can be used to determine if a NOB material can be considered or treated as non-asbestos containing.
James Hall, Laboratory Manageror other approved signatory
Analyst(s)
NOB = Non Friable Organically Bound N/A = Not Applicable
Steve Jusczuk
Sean Scales
Page 2THIS IS THE LAST PAGE OF THE REPORT.Test Report NY198w/A-7.21.0 Printed: 9/2/2012 5:42:38 AM
Initial Report From 09/02/2012 05:41:46
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031228041CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 09/01/2012 8:56 AM
12-13058-A/ CLIFTON SPRINGS SERVICE AREA NYS THRUWAYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
9/4/2012Analysis Date:
Collected: 8/30/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
3-01031228041-0001
ROOF AREA 1D - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
3-02031228041-0002
ROOF AREA 1D - BUILT-UP ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
4-01031228041-0003
ROOF AREA 1D - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
4-02031228041-0004
ROOF AREA 1D - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Brown
Brown
5-01031228041-0005
ROOF AREA 1D ON PARAPET WALL - ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
5-02031228041-0006
ROOF AREA 1D ON PARAPET WALL - ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
6-01031228041-0007
ROOF AREA 1D AT SCUPPER - FLASHING CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Page 1Test Report NY198w/A-7.21.0 Printed: 9/4/2012 7:02:11 PM
Report Amended 09/04/2012 18:52:57 Replaces Report Amended 09/02/2012 12:59:56. Reason Code: Data Entry-Samples Added
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031228041CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 09/01/2012 8:56 AM
12-13058-A/ CLIFTON SPRINGS SERVICE AREA NYS THRUWAYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
9/4/2012Analysis Date:
Collected: 8/30/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
6-02031228041-0008
ROOF AREA 1D AT SCUPPER - FLASHING CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
7-01031228041-0009
ROOF AREA 1D ON PARAPET WALL - SEAM CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
7-02031228041-0010
ROOF AREA 1D ON PARAPET WALL - SEAM CEMENT
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
8-01031228041-0011
ROOF AREA 1D - DOOR CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Clear
Clear
8-02031228041-0012
ROOF AREA 1D - DOOR CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Clear
Clear
9-01031228041-0013
GENERATOR BUILDING BOTTOM LAYER - ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
9-02031228041-0014
GENERATOR BUILDING TOP LAYER - ROOFING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Inconclusive: None Detected
None Detected
Black
Black
Page 2Test Report NY198w/A-7.21.0 Printed: 9/4/2012 7:02:11 PM
Report Amended 09/04/2012 18:52:57 Replaces Report Amended 09/02/2012 12:59:56. Reason Code: Data Entry-Samples Added
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031228041CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 09/01/2012 8:56 AM
12-13058-A/ CLIFTON SPRINGS SERVICE AREA NYS THRUWAYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
9/4/2012Analysis Date:
Collected: 8/30/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
10-01031228041-0015
GENERATOR BUILDING BOTTOM LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A Positive Stop (Not Analyzed)
Black
Black
6.0% Chrysotile
6.0% Total
10-02031228041-0016
GENERATOR BUILDING TOP LAYER - FLASHING
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Positive Stop (Not Analyzed)
Positive Stop (Not Analyzed)
11-01031228041-0017
GENERATOR BUILDING AT ROOF CORE - TAR ON DECK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A Positive Stop (Not Analyzed)
Black
Black
8.2% Chrysotile
8.2% Total
11-02031228041-0018
GENERATOR BUILDING AT FLASH CORE - TAR ON DECK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Positive Stop (Not Analyzed)
Positive Stop (Not Analyzed)
12-01031228041-0019
GENERATOR BUILDING REAR WINDOW - WINDOW CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A Positive Stop (Not Analyzed)
Gray
Gray
5.0% Chrysotile
5.0% Total
12-02031228041-0020
GENERATOR BUILDING SIDE WINDOW - WINDOW CAULK
PLM NYS 198.1 Friable
PLM NYS 198.6 NOB
TEM NYS 198.4 NOB
9/4/2012
9/2/2012
Not Analyzed
N/A
N/A
Positive Stop (Not Analyzed)
Positive Stop (Not Analyzed)
Page 3Test Report NY198w/A-7.21.0 Printed: 9/4/2012 7:02:11 PM
Report Amended 09/04/2012 18:52:57 Replaces Report Amended 09/02/2012 12:59:56. Reason Code: Data Entry-Samples Added
EMSL Analytical, Inc.307 West 38th Street, New York, NY 10018Phone/Fax: (212) 290-0051 / (212) 290-0058http://www.emsl.com [email protected]
031228041CustomerID: ALPI50CustomerPO:ProjectID:
EMSL Order:
Attn: Alpine Environmental Services1146 Central Avenue
Albany, NY 12205 Received: 09/01/2012 8:56 AM
12-13058-A/ CLIFTON SPRINGS SERVICE AREA NYS THRUWAYFax: (518) 453-0175
Phone: (518) 453-0146 Project:
9/4/2012Analysis Date:
Collected: 8/30/2012
AnalyzedDate Sample Description Asbestos Fibrous Non-FibrousTest CommentsColor
Non Asbestos
Test Report:Asbestos Analysis of Bulk Material
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. The above test report relates only to the items tested. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The results in this report meet all requirements of the NELAC Standards unless otherwise noted. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM is not consistently reliable in detecting asbestos in floor coverings and similar NOB's. Quantitative TEM is currently the only method that can be used to determine if a NOB material can be considered or treated as non-asbestos containing.
James Hall, Laboratory Manageror other approved signatory
Analyst(s)
NOB = Non Friable Organically Bound N/A = Not Applicable
Daena Charles
Robert Georgens
Samples analyzed by EMSL Analytical, Inc. New York, NY NYS ELAP 11506
Page 4THIS IS THE LAST PAGE OF THE REPORT.Test Report NY198w/A-7.21.0 Printed: 9/4/2012 7:02:11 PM
Report Amended 09/04/2012 18:52:57 Replaces Report Amended 09/02/2012 12:59:56. Reason Code: Data Entry-Samples Added
Analytical Sample Results
Job Number: 12080562Fax: 518.381.6055Phone: 518.346.4592Schenectady, NY 123082190 Technology DrivePace Analytical Services, Inc.
Client Sample ID:Sample Matrix:Received Date:
Collection Date:
1-ROOF AREA 1D DOOR CAULKCAULK
08/31/2012 10:40
08/30/2012 08:00
Lab Sample ID: 12080562-01 (AP26331)
ALPINE ENVIRONMENTAL SERVICES, INCClient:
Batch ID AnalystDate Init Wt./Vol.Method Final Vol. ColumnGC20F-1379-40 SW-846 8082 (PCB) JKA09/06/2012 22:08 NAAnalysis 1: NA Phenomenex, Zebron ZB-1, 30 m, 0.25 mm ID, 0.25 µm
19745 EPA 3540C DKA09/04/2012 10:00 1.05 gPrep 1: 25.0 mL NA
N/APercent Solid:
CLIFTON SPRINGS SERVICE AREA NYS THRUWAYProject:
Analyte CAS No. Result (ug/g) PQL Dilution Factor Flags File IDNDAroclor 1016 0.478 1.00 GC20F-1379-40U12674-11-2NDAroclor 1221 0.478 1.00 GC20F-1379-40U11104-28-2NDAroclor 1232 0.478 1.00 GC20F-1379-40U11141-16-5NDAroclor 1242 0.478 1.00 GC20F-1379-40U53469-21-9NDAroclor 1248 0.478 1.00 GC20F-1379-40U12672-29-6NDAroclor 1254 0.478 1.00 GC20F-1379-40U11097-69-1NDAroclor 1260 0.478 1.00 GC20F-1379-40U11096-82-5NDAroclor 1262 0.478 1.00 GC20F-1379-40U37324-23-5NDAroclor 1268 0.478 1.00 GC20F-1379-40U11100-14-4NDTotal PCB Amount > RL 1.00 GC20F-1379-40U1336-36-3
SurrogateLimits
Q File ID% RecoveryCAS No.1
(%)Tetrachloro-meta-xylene 93.7 60.0-140 GC20F-1379-40877-09-8Decachlorobiphenyl 108 60.0-140 GC20F-1379-402051-24-3Qualifier column where '*' denotes value outside the control limits or 'D' denotes value was diluted out. 1
ND: Denotes analyte not detected at a concentration greater than the PQL.PQL (Practical Quantitation Limit). Denotes lowest analyte concentration reportable for the sample.
2190 Technology Drive | Schenectady, NY 12308 | Phone 518.346.4592 | Fax 518.381.6055 | www.pacelabs.comThis report may not be reproduced except in full, without the written approval of Pace Analytical Services, Inc.
Analytical Sample Results
Job Number: 12080562Fax: 518.381.6055Phone: 518.346.4592Schenectady, NY 123082190 Technology DrivePace Analytical Services, Inc.
Client Sample ID:Sample Matrix:Received Date:
Collection Date:
2-GENERATOR BUILDING WINDOW CAULKCAULK
08/31/2012 10:40
08/30/2012 08:00
Lab Sample ID: 12080562-02 (AP26332)
ALPINE ENVIRONMENTAL SERVICES, INCClient:
Batch ID AnalystDate Init Wt./Vol.Method Final Vol. ColumnGC20F-1379-41 SW-846 8082 (PCB) JKA09/06/2012 22:20 NAAnalysis 1: NA Phenomenex, Zebron ZB-1, 30 m, 0.25 mm ID, 0.25 µm
19745 EPA 3540C DKA09/04/2012 10:00 1.42 gPrep 1: 25.0 mL NA
N/APercent Solid:
CLIFTON SPRINGS SERVICE AREA NYS THRUWAYProject:
Analyte CAS No. Result (ug/g) PQL Dilution Factor Flags File IDNDAroclor 1016 0.351 1.00 GC20F-1379-41U12674-11-2NDAroclor 1221 0.351 1.00 GC20F-1379-41U11104-28-2NDAroclor 1232 0.351 1.00 GC20F-1379-41U11141-16-5NDAroclor 1242 0.351 1.00 GC20F-1379-41U53469-21-9NDAroclor 1248 0.351 1.00 GC20F-1379-41U12672-29-6NDAroclor 1254 0.351 1.00 GC20F-1379-41U11097-69-1NDAroclor 1260 0.351 1.00 GC20F-1379-41U11096-82-5NDAroclor 1262 0.351 1.00 GC20F-1379-41U37324-23-5NDAroclor 1268 0.351 1.00 GC20F-1379-41U11100-14-4NDTotal PCB Amount > RL 1.00 GC20F-1379-41U1336-36-3
SurrogateLimits
Q File ID% RecoveryCAS No.1
(%)Tetrachloro-meta-xylene 90.7 60.0-140 GC20F-1379-41877-09-8Decachlorobiphenyl 106 60.0-140 GC20F-1379-412051-24-3Qualifier column where '*' denotes value outside the control limits or 'D' denotes value was diluted out. 1
ND: Denotes analyte not detected at a concentration greater than the PQL.PQL (Practical Quantitation Limit). Denotes lowest analyte concentration reportable for the sample.
2190 Technology Drive | Schenectady, NY 12308 | Phone 518.346.4592 | Fax 518.381.6055 | www.pacelabs.comThis report may not be reproduced except in full, without the written approval of Pace Analytical Services, Inc.
Analytical Sample Results
Job Number: 12080562Fax: 518.381.6055Phone: 518.346.4592Schenectady, NY 123082190 Technology DrivePace Analytical Services, Inc.
Client Sample ID:Sample Matrix:Received Date:
Collection Date:
ROOF INSULATIONSOLID
08/31/2012 10:40
08/30/2012 08:00
Lab Sample ID: 12080562-07 (AP26337)
ALPINE ENVIRONMENTAL SERVICES, INCClient:
Batch ID AnalystDate Init Wt./Vol.Method Final Vol. ColumnGC20F-1378-22 SW-846 8082 (PCB) JES09/05/2012 13:47 NAAnalysis 1: NA Phenomenex, Zebron ZB-1, 30 m, 0.25 mm ID, 0.25 µm
19752 EPA 3540C TJH09/04/2012 09:35 2.00 gPrep 1: 25.0 mL NA
100 - Results are based on dry weight unless otherwise noted.Percent Solid:
CLIFTON SPRINGS SERVICE AREA NYS THRUWAYProject:
Analyte CAS No. Result (ug/g) PQL Dilution Factor Flags File IDNDAroclor 1016 0.250 1.00 GC20F-1378-22U12674-11-2NDAroclor 1221 0.250 1.00 GC20F-1378-22U11104-28-2NDAroclor 1232 0.250 1.00 GC20F-1378-22U11141-16-5NDAroclor 1242 0.250 1.00 GC20F-1378-22U53469-21-9NDAroclor 1248 0.250 1.00 GC20F-1378-22U12672-29-6NDAroclor 1254 0.250 1.00 GC20F-1378-22U11097-69-1NDAroclor 1260 0.250 1.00 GC20F-1378-22U11096-82-5NDAroclor 1262 0.250 1.00 GC20F-1378-22U37324-23-5NDAroclor 1268 0.250 1.00 GC20F-1378-22U11100-14-4NDTotal PCB Amount > RL 1.00 GC20F-1378-22U1336-36-3
SurrogateLimits
Q File ID% RecoveryCAS No.1
(%)Tetrachloro-meta-xylene 91.0 60.0-140 GC20F-1378-22877-09-8Decachlorobiphenyl 104 60.0-140 GC20F-1378-222051-24-3Qualifier column where '*' denotes value outside the control limits or 'D' denotes value was diluted out. 1
ND: Denotes analyte not detected at a concentration greater than the PQL.PQL (Practical Quantitation Limit). Denotes lowest analyte concentration reportable for the sample.
2190 Technology Drive | Schenectady, NY 12308 | Phone 518.346.4592 | Fax 518.381.6055 | www.pacelabs.comThis report may not be reproduced except in full, without the written approval of Pace Analytical Services, Inc.