report.pdf

23
Simulation of Inverter and Rectifier under different fault conditions for NX- APL UPS 2014 VIKALP DHIMAN GRADUATE ENGINEER TRAINEE EMERSON NETWORK POWER INDIA

Upload: vikalp2005

Post on 17-Nov-2015

14 views

Category:

Documents


0 download

TRANSCRIPT

  • 0 | P a g e

    Simulation of Inverter and Rectifier

    under different fault conditions for NX-

    APL UPS

    2014

    VIKALP DHIMAN

    GRADUATE ENGINEER TRAINEE

    EMERSON NETWORK POWER

    INDIA

  • 1 | P a g e

    PROJECT REPORT

    ON

    SIMULATION OF INVERTER &

    RECTIFIER UNDER DIFFERENT FAULT

    CONDITIONS FOR NX-APL UPS

    BY

    VIKALP DHIMAN

    GUIDED BY MENTOR

    Mr. KAMLESH KEHARIA Mr. VASUDEVAN R

    SPECIAL THANKS TO

    Mr. SUPRIYA GHORAI

    Mr. NITISH KUMAR

    ENGINEERING DEPARTMENT

    EMERSON NETWORK POWER INDIA

    THANE

  • 2 | P a g e

    Table of Contents

    INTRODUCTION ......................................................................................... 3

    TYPE OF INVERTER ................................................................................... 4

    CONTROL CIRCUIT .................................................................................... 5

    PWM GENERATION ............................................................................................ 5

    SIMULATING MODEL OF PWM GENERATOR ................................................ 6

    SIMULATION RESULT OF PWM GENERATOR ................................................ 7

    WORKING OF THREE LEVEL INVERTER ................................................... 8

    POWER CIRCUIT ...................................................................................... 10

    o UNFILTERED OUTPUT VOLTAGE WAVEFORMS .................................................. 11

    FILTER CIRCUIT ...................................................................................... 13

    SIMULATION MODEL OF FILTER CIRCUIT .................................................. 13

    o FILTERED OUTPUT VOLTAGE WAVEFORMS ....................................................... 13

    INTEGRATED SIMULATION MODEL........................................................ 15

    FAULT ANALYSIS ..................................................................................... 16

    TYPES OF FAULT: ............................................................................................. 16

    o ANGLE DELAY IN PWM GENERATION .................................................................. 17

    o NEUTRAL MISSING .................................................................................................. 17

    o L-G FAULT ................................................................................................................. 18

    o L-L FAULT .................................................................................................................. 19

    o SHORT CIRCUITING OF IGBT LEG ........................................................................ 20

    FAULT CONTROL CIRCUIT ...................................................................... 21

    CONCLUSION ........................................................................................... 22

  • 3 | P a g e

    INTRODUCTION

    Uninterruptible Power Supply is an electrical apparatus that provides emergency power to a load when the input power source fails.

    Main components of UPS are:

    Rectifier

    Inverter

    Battery

    Maintenance bypass

    Static Switches

    Fig.1 Block Diagram of UPS

    At any type of power disturbances, any part of UPS doesnt work properly. High magnitude and peaky nature of currents during fault can demolish the each component and hence UPS. So special protection against faults are mandatory and should be implemented in UPS.

    To apply these protections against faults, behavior of each component of UPS must be understood during fault. Hence simulating each part under different fault conditions can describe the behavior of UPS during fault.

    However aim of our project is to examine the behavior of Inverter & Rectifier only under different fault conditions with the help of MATLAB simulation.

  • 4 | P a g e

    TYPE OF INVERTER (Neutral point-clamped three-level inverter)

    Multi-level inverter type inverters provide an output waveform that exhibits multiple steps at several voltage levels. Hence no need of transformers. Multilevel converters can operate at both fundamental switching frequency and high switching frequency PWM. Lower switching frequency usually means lower switching loss and higher efficiency.

    Multi-level inverter provides multiple voltage levels through connection of the phases to a series bank of capacitors. The concept can be extended to any number of levels by increasing the number of capacitors. Early descriptions of this topology were limited to three-levels where two capacitors are connected across the dc bus resulting in one additional level. Here we are using three-level inverter. Two levels are provided by two capacitors and one level by neutral point which is clamped between capacitors and diodes.

    Fig.2 Power circuit of three-level inverter

    Three phase three level inverter has three legs having four IGBTs which are connected with anti-parallel diode. To provide pulses to the IGBTs control circuit is used.

  • 5 | P a g e

    CONTROL CIRCUIT

    (Sinusoidal pulse width modulation scheme)

    Control circuit is used to provide pulses to the corresponding IGBTs in power circuit. Pulses are generated with the help of PWM generator.

    PWM GENERATION

    PWM generator consists of:

    Three sinusoidal reference signals having phase difference of 120*.

    A triangular modulating signal of higher frequency.

    The reference signal (Uref input), also called the modulating signal, is naturally sampled and compared with two symmetrical level-shifted triangle carriers.

    Fig.3 Generated PWM pulses for single phase inverter

  • 6 | P a g e

    SIMULATING MODEL OF PWM GENERATOR

    Fig.4 Simulation diagram

    Three reference signals which are 120* out of phase and two carrier signals. Modulation Index to control the amplitude of the fundamental component of the output voltage of the converter. The modulation index must be greater than 0 and lower than or equal to 1.

    [Peak magnitude of reference signal] / [Peak magnitude of carrier signal] = 0.85

    Carrier wave frequency = 20 KHz Note: Higher the modulation index, higher will be total harmonic distortion in output.

  • 7 | P a g e

    SIMULATION RESULT OF PWM GENERATOR

    There are 12 IGBTs in power circuit and each IGBT triggers with a PWM pulse. Output of PWM generator consists of twelve PWM pulses.

    Fig.5 Twelve IGBT pulses waveform The PWM Generator (3-Level) block generates pulses for carrier-based pulse-width modulation (PWM) converters using three-level topology. The block can control switching devices (IGBTs) of three-phase Bridge (three arms). The converter arm can have three states: +1, 0, or 1. When the reference signal is greater than the positive carrier, the state of the arm is +1; when the reference signal is smaller than the negative carrier, the state of the arm is 1.Otherwise, the state is 0.

    One reference signal is required to generate the four pulses of an arm. For a single-phase full-bridge converter, a second reference signal is required to generate the four pulses of the second arm. This signal is internally generated by phase-shifting the original reference signal by 180 degrees. For a three-phase bridge, three reference signals are required to generate the 12 pulses.

  • 8 | P a g e

    WORKING OF THREE LEVEL INVERTER

    The inverter is controlled in open loop. PWM Generator blocks generates sets of 12 pulses. For one inverter module:

    An m level inverter leg requires 2(m-1) switching devices and (m-1)*(m-2) clamping diodes. For a three-level inverter, m=3, so it needs four switching devices and two clamping diodes per leg.

    Fig.6 Inverter circuit

    Table.1

    State condition 1 means the switch is ON, and state 0 means the switch is OFF. Table.1 is showing switching states and correspondingly voltage level for A phase. It is also mentioned that switch pair (1, 3) and (2, 4) are complementary.

  • 9 | P a g e

    Thus, if one of the complementary switch pairs is turned ON, the other of the same pair must be OFF. Two switches are always turned ON at the same time. For m-level Diode Clamped inverter, each switching device is only required to block a voltage level of

    Vdc/(m-1). Unequal conduction duty requires different current ratings for switching devices. Therefore, if the inverter design uses the average duty cycle to find the device ratings, the upper switches may be over sized, and the lower switches may be undersized.

    Fig.7 Output voltage waveform

    From Fig.7 we can see that there are three levels of output voltage. A diode clamped inverter is mostly used because control method is simple. Also, when the number of levels is high enough, the harmonic content is low enough to avoid the need for filters. But, it is limited by the increase in number of clamping diodes as the number of levels increases. Also, it is difficult to control the real power flow of the individual converter in multi-converter systems.

  • 10 | P a g e

    POWER CIRCUIT

    (BLOCK DIAGRAM)

    Power circuit includes three modules of Inverter, connected in parallel followed by filter circuits. DC supply to inverters is provided by rectifier. Block diagram for power circuit is

    shown below:

    Fig.8 Block diagram of power circuit

    DATA:

    Rating of each inverter module = 150 KVA

    DC supply voltage = 760 V

  • 11 | P a g e

    SIMULATION MODEL OF INVERTER MODULE

    Fig.9 Inverter simulation diagram

    UNFILTERED OUTPUT VOLTAGE WAVEFORMS

    Fig.9 Unfiltered Output phase voltage (A, B, C) waveform of a inverter module simulation

  • 12 | P a g e

    Fig.10 Unfiltered Output line voltage (AB, BC, CA) waveform of a inverter module simulation

    Peak magnitude of phase voltage = (m*Vdc)

    (M is modulation index)

  • 13 | P a g e

    FILTER CIRCUIT

    In fig.9 and fig.10 we have seen that output voltage are not sinusoidal. To achieve

    sinusoidal waveforms we use LC low-pass filter circuits.

    SIMULATION MODEL OF FILTER CIRCUIT

    Fig.11 Simulation diagram

    Inductance value = 63 H

    Capacitance value = 200 F

    FILTERED OUTPUT VOLTAGE WAVEFORMS

    Fig.12 Filtered Output phase voltage (A, B, C) waveform of a inverter module simulation

  • 14 | P a g e

    Fig.11 Filtered Output line voltage (AB, BC, CA) waveform of a inverter module simulation

    A low pass filter is a filter that passes signals with a frequency lower than a

    certain cutoff frequency and attenuates signals with frequencies higher than the

    cutoff frequency. The amount of attenuation for each frequency depends on the

    filter design. Basically, an electrical filter is a circuit that can be designed to modify,

    reshape or reject all unwanted frequencies of an electrical signal and accept or pass

    only those signals wanted by the circuits designer. In other words they filter-out

    unwanted signals and an ideal filter will separate and pass sinusoidal input signals

    based upon their frequency.

    http://en.wikipedia.org/wiki/Filter_(signal_processing)http://en.wikipedia.org/wiki/Signal_(electrical_engineering)http://en.wikipedia.org/wiki/Frequencyhttp://en.wikipedia.org/wiki/Cutoff_frequencyhttp://en.wikipedia.org/wiki/Attenuatehttp://en.wikipedia.org/wiki/Attenuation

  • 15 | P a g e

    INTEGRATED SIMULATION MODEL

    Fig.12

    All modules must be in -

    o Frequency synchronization.

    o Amplitude synchronization.

    o Phase synchronization.

    Parallel operation of voltage source inverters with other inverters or with the grid, are sensitive to disturbances from the load or other sources and can easily be damaged by overcurrent.

  • 16 | P a g e

    FAULT ANALYSIS

    In an electric power system, a fault is any abnormal electric current. For example, a short circuit is a fault in which current bypasses the normal load. An open-circuit fault occurs

    if a circuit is interrupted by some failure. In three phase systems, a fault may involve one

    or more phases and ground, or may occur only between phases. In a "ground fault" or

    "earth fault", charge flows into the earth. The prospective short circuit current of a fault

    can be calculated for power systems. In power systems, protective devices detect fault

    conditions and operate circuit breakers and other devices to limit the loss of service due

    to a failure.

    TYPES OF FAULT:

    Angle delay in PWM generation

    Neutral Missing

    L-G fault

    L-L fault

    Short circuiting of IGBT leg

    We generated the all faults with the help of MATLAB simulation and analyze the effect of

    each fault on DC bus bar, output current and output load current. Outcomes after

    generating the each fault are given below. We also provided a controlling circuitry to

    control the effect of particular fault.

    Below given table is a brief overview of fault effects and type of fault.

    Table.2

    http://en.wikipedia.org/wiki/Electric_power_systemhttp://en.wikipedia.org/wiki/Prospective_short_circuit_currenthttp://en.wikipedia.org/wiki/Circuit_breaker

  • 17 | P a g e

    ANGLE DELAY IN PWM GENERATION:

    OUTPUT CURRENT OF HIGH MAGNITUDE

    NEUTRAL MISSING :

    When there is a sudden loss of neutral connection, neutral

    point shifts and output voltage waveform distorts. Neutral missing type fault can be only

    examined if load is unbalanced.

    OUTPUT CURRENT

    NEUTRAL MISSING

  • 18 | P a g e

    DC BUS BAR CURRENT

    NOTE: Magnitude of current varies according to corresponding load.

    L-G FAULT :

    Fault between phase A and neutral

    OUTPUT CURRENT

    DC BUS BAR CURRENT

    NOTE: High magnitude of current flows as expected.

    Phase A to Neutral

  • 19 | P a g e

    L-L FAULT :

    Fault between phase A and phase B.

    OUTPUT CURRENT

    DC BUS BAR CURRENT

    NOTE: High magnitude of current flows through output terminals of inverter and DC

    bus bar as expected.

    PHASE A to PHASE B

  • 20 | P a g e

    SHORT CIRCUITING OF IGBT LEG :

    OUTPUT CURRENT

    DC BUS BAR CURRENT

    During above all faults, a circulating current flows through corresponding faulty phase

    and through DC bus bar. It is a current of high magnitude (in thousands).

  • 21 | P a g e

    FAULT CONTROL CIRCUIT

    The circulating current can damage power electronics devices used in power circuit. To

    prevent this damage fault control circuit is used. This circuit detects the particular fault

    point and disconnect that source from rest of the circuit.

    Fig.14 Fault control circuit

    NOTE: Iabc1, Iabc2, Iabc3 are circulating current. These currents first should be rectified and

    then allow to flow through relay circuit, relay output would be zero if value of current is

    not within the limits of relay.

    A1, A2, A3 are connected to PWM Generator 1

    B1, B2, B3 are connected to PWM Generator 2

    C1, C2, C3 are connected to PWM Generator 3

    Three currents Iabc1, Iabc2, Iabc3 are detected by this control circuit and corresponding

    Inverter module turns off.

  • 22 | P a g e

    CONCLUSION

    We understand the effects of several possible faults by this Inverter simulation and

    according to that effects, we provide a fault controlling circuit to prevent damage

    of power electronics devices by fault current.