Required vs. Non-required
Fire Protection SystemsDan Austin
Chief Fire Code Consultant/State Fire Protection Engineer
![Page 2: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/2.jpg)
What are we going to cover?
▪What makes a system required?
▪What to do when a non-required system is
installed?
▪Examples, lots of examples.
2
![Page 3: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/3.jpg)
Chapter 9 – Section 901
▪ 901.4 Installation. Fire protection systems shall be maintained
in accordance with the original installation standards for that
system. Required systems shall be extended, altered or
augmented as necessary to maintain and continue protection
whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in
accordance with applicable standards.
3
![Page 4: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/4.jpg)
Chapter 9 – Section 901
▪ 901.4 Installation. Fire protection systems shall be maintained
in accordance with the original installation standards for that
system. Required systems shall be extended, altered or
augmented as necessary to maintain and continue protection
whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in
accordance with applicable standards.
4
![Page 5: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/5.jpg)
Chapter 9 – Section 901
▪ 901.4.1 Required fire protection systems. Fire protection
systems required by this code or the International Building Code
shall be installed, repaired, operated, tested and maintained in
accordance with this code.
▪ Clarification: Any system required by the Codes becomes a
required system. For example, if sprinkler systems are needed
for height or area increase, they are now a required system
5
![Page 6: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/6.jpg)
Chapter 9 – Section 901
▪ 901.4.2 Nonrequired fire protection systems. Any fire
protection system or portion thereof not required by this code or
the International Building Code shall be allowed to be furnished
for partial or complete protection provided such installed system
meets the requirements of this code and the International
Building Code.
▪ Clarification: System not required by any code section or
exception.
6
![Page 7: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/7.jpg)
Chapter 9 – Section 901
▪ 901.4.2 Nonrequired fire protection systems. Any fire
protection system or portion thereof not required by this code or
the International Building Code shall be allowed to be furnished
for partial or complete protection provided such installed system
meets the requirements of this code and the International
Building Code.
7
![Page 8: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/8.jpg)
Chapter 9 – Section 901
▪ 901.4.2 Nonrequired fire protection systems. Any fire
protection system or portion thereof not required by this code or
the International Building Code shall be allowed to be furnished
for partial or complete protection provided such installed system
meets the requirements of this code and the International
Building Code.
▪ Clarification: Designed intent, what is the purpose.
8
![Page 9: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/9.jpg)
Chapter 9 – Section 901
▪ 901.4.2 Nonrequired fire protection systems. Any fire
protection system or portion thereof not required by this code or
the International Building Code shall be allowed to be furnished
for partial or complete protection provided such installed system
meets the requirements of this code and the International
Building Code.
▪ Clarification: Devices installed meet the installation
requirements of the North Carolina Codes and referenced
standards
9
![Page 10: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/10.jpg)
NFPA 13 – General
▪ 4.2 Limited Area Systems.
▪ 4.2.1 When partial sprinkler systems are installed, the
requirements of this standard shall be used insofar as they are
applicable.
▪ 4.2.2 The authority having jurisdiction shall be consulted in each
case.
▪ Clarification: Not limited to 20 heads, unless fed from domestic
service.
10
![Page 11: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/11.jpg)
NFPA 72 – Definitions
▪ 3.3.171* Nonrequired. A system component or group of components that
is installed at the option of the owner, and is not installed due to a building
or fire code requirement. (SIG-FUN)
11
![Page 12: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/12.jpg)
NFPA 72 – Annex
▪ A.3.3.171 Nonrequired. There are situations where the applicable building
or fire code does not require the installation of a fire alarm system or
specific fire alarm system components, but the building owner wants to
install a fire alarm system or component to meet site-specific needs or
objectives. A building owner always has the option of installing protection
that is above the minimum requirements of the Code.
12
![Page 13: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/13.jpg)
NFPA 72 – Annex
▪ A.3.3.171 Nonrequired.(Continued) It is the intent of the Code that any
fire alarm system, or fire alarm system components installed voluntarily by
a building owner, meet the requirements of the applicable portions of the
Code. However, it is not the intent of the Code that the installation of a
nonrequired fire alarm system, or fire alarm system components, trigger
requirements for the installation of additional fire alarm system components
or features.
13
![Page 14: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/14.jpg)
NFPA 72 – Annex
▪ A.3.3.171 Nonrequired. (Continued) For example, the installation of a fire
alarm control unit and fire detectors to service a specific area, such as a
computer room or flammable liquid storage room, does not trigger a
requirement for audible or visible notification appliances, manual fire alarm
boxes, or other fire alarm system features in other parts of the building.
14
![Page 15: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/15.jpg)
NFPA 72 – Initiating Devices
▪ 17.5.3.3* Nonrequired Coverage.
▪ 17.5.3.3.1 Detection installed for reasons of achieving specific fire safety
objectives, but not required by any laws, codes, or standards, shall meet all
of the requirements of this Code, with the exception of the prescriptive
spacing criteria of Chapter 17.
▪ 17.5.3.3.2 Where nonrequired detectors are installed for achieving specific
fire safety objectives, additional detectors not necessary to achieve the
objectives shall not be required.
15
![Page 16: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/16.jpg)
NFPA 72 – Protected Premises Fire Alarm Systems
▪ 23.3.2* Nonrequired (Voluntary) Systems and Components.
▪ The features for a nonrequired system shall be established by the system
designer on the basis of the goals and objectives intended by the system
owner.
▪ 23.3.2.1 Nonrequired protected premises systems and components shall
meet the requirements of this Code.
▪ 23.3.2.2 Nonrequired systems and components shall be identified on the
record drawings required in 7.2.1(12).
16
![Page 17: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/17.jpg)
NFPA 72 – Annex
▪ A.23.3.2 Nonrequired fire alarm features are defined in 3.3.171. These are
fire alarm systems or components that are not required by the building or
fire codes and are installed voluntarily by a building owner to meet site-
specific fire safety objectives. There is a need to properly document the
nonrequired system and components. Nonrequired components must be
operationally compatible in harmony with other required components and
must not be detrimental to the overall system performance.
17
![Page 18: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/18.jpg)
NFPA 72 – Annex
▪ A.23.3.2 It is for this reason that 23.3.2.1 mandates that nonrequired
(voluntary) systems and components meet the applicable installation,
testing, and maintenance requirements of this Code. It is not the intent of
the Code to have the installation of nonrequired (voluntary) systems or
components trigger a requirement for the installation of additional fire alarm
components or features in the building.
18
![Page 19: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/19.jpg)
NFPA 72 – Annex
▪ A.23.3.2 For example, if a building owner voluntarily installs a fire alarm
control unit to transmit sprinkler waterflow signals to a central station, that
does not trigger a requirement to install other fire alarm system
components or features, such as manual fire alarm boxes, occupant
notification, or electronic supervision of sprinkler control valves. See also
A.17.5.3.3 and A.18.1.5.
▪ Alternatively, supervision and power requirements are required to be taken
into account for the nonrequired components/systems on the required fire
alarm systems.
19
![Page 20: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/20.jpg)
NFPA 72 – Emergency Communication Systems
▪ 24.3.4* Nonrequired (Voluntary) Emergency Communications
Systems.
▪ 24.3.4.1 Nonrequired emergency communications systems and
components shall meet the requirements of this chapter.
▪ 24.3.4.2 Nonrequired emergency communications systems and
components shall be identified on the record drawings.
▪ A.24.3.4 The features for a nonrequired system should be established by
the system designer on the basis of the goals and objectives intended by
the system owner.
20
![Page 21: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/21.jpg)
GOT IT?
21
![Page 22: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/22.jpg)
Something is better than Nothing, Right?
▪ Not always.
▪ Would a person feel that in the event of an emergency they
would be notified?
▪ Does the system perform the intent as designed?
22
![Page 23: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/23.jpg)
LETS LOOK AT SOME EXAMPLES
23
![Page 24: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/24.jpg)
Example 1
▪ Fire station:
▪ Non-separated
▪ Sleeping areas
▪ Kitchen area
▪ What would be required?
▪ Sprinkler system, 903.2.8
▪ Type?
– NFPA 13
▪ Hood system, commercial cooking 507.2.3 NCMC
▪ Smoke alarms, 907.2.9.2- 907.2.11
▪ Dialer – 903.4
24
![Page 25: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/25.jpg)
25
![Page 26: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/26.jpg)
Smoke Alarm Smoke Detector Waterflow Bell
FACP Hood System DACT/Dialer
![Page 27: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/27.jpg)
Example 1
▪ Is anything else required?
▪ Is the Fire Sprinkler Panel required to monitor the Hood System?
▪ Are manual pull stations required?
▪ Is occupant notification required?
27
![Page 28: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/28.jpg)
Smoke Alarm Smoke Detector Waterflow Bell
FACP Hood System DACT/Dialer Pull station
Strobe
![Page 29: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/29.jpg)
Smoke Alarm Smoke Detector Waterflow Bell
FACP Hood System DACT/Dialer Pull station
Horn/StrobeStrobe
![Page 30: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/30.jpg)
Smoke Alarm Smoke Detector Waterflow Bell
FACP Hood System DACT/Dialer Pull station
Horn/StrobeStrobe
![Page 31: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/31.jpg)
Smoke Alarm Smoke Detector Waterflow Bell
FACP Hood System DACT/Dialer Pull station
Horn/StrobeStrobe
![Page 32: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/32.jpg)
Example 2
▪ Strip shopping center
▪ Up fit of tenant space
▪ What is required by code?
▪ Group B occupancy
32
![Page 33: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/33.jpg)
Example 2
![Page 34: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/34.jpg)
Smoke Detector
FACP
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 2
![Page 35: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/35.jpg)
Smoke Detector
FACP
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 2
![Page 36: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/36.jpg)
Smoke Detector
FACP
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 2
![Page 37: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/37.jpg)
Smoke Detector
FACP
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 2
![Page 38: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/38.jpg)
Example 2
▪ What if we added sprinkler?
▪ Does it need to dial out?
Smoke Detector
FACP
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Waterflow Bell
![Page 39: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/39.jpg)
Example 3 – First floor Business occupancy
▪ Facts:
▪ No occupancy in the building requires sprinkler or alarm per NC Codes.
![Page 40: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/40.jpg)
![Page 41: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/41.jpg)
Smoke Alarm Smoke Detector Waterflow Bell
FACP Hood System DACT/Dialer Pull station
Horn/StrobeStrobe
Example 3
![Page 42: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/42.jpg)
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 3
▪ Design: Only notify occupants in waiting area.
▪ Staff will evacuate other occupants.
![Page 43: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/43.jpg)
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 3
▪ Just sprinkler in the Tenant space
![Page 44: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/44.jpg)
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 3
▪ Just a hood system
![Page 45: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/45.jpg)
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 3
▪ Just a hood system
![Page 46: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/46.jpg)
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
Example 3
▪ Just a hood system
![Page 47: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/47.jpg)
Example 4
47
▪ Storage occupancy with Business
▪ Total 11,999ft2 exterior wall to exterior wall.
▪ 1,500ft2 of I – IV Commodity high-piled storage area
▪ 1,000ft2 of High Hazard high-piled storage area.
▪ Break room, 2 commercial 6-eye ranges.
▪ What is required?
▪ Hood system for ranges.
▪ Alarm for high-piled storage areas.
![Page 48: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/48.jpg)
Example 4
48
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
![Page 49: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/49.jpg)
Example 4
49
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
![Page 50: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/50.jpg)
Example 4
50
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
![Page 51: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/51.jpg)
Example 5
51
▪ One of my FAVORIATE occupancies:
▪ Sweepstakes
![Page 52: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/52.jpg)
Example 5
52
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
![Page 53: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/53.jpg)
Example 5
▪ Just notification in gaming area?
▪ What is the design intent?
53
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
![Page 54: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/54.jpg)
Example 5
▪ Just pull stations?
▪ No DACT, No Alarms? What is the intent?
▪ What can you require?
▪ Signs – 907.5.2.4
▪ What can you suggest?
54
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
![Page 55: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/55.jpg)
Example 6
55
▪ Two tenant spaces:
▪ Code compliant separation to
make separated mixed use.
![Page 56: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/56.jpg)
Example 6
56
▪ Sprinkler west side.
▪ Bell outside.
▪ Supervision?
▪ Monitoring?
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe
![Page 57: Required vs. Non-required Fire Protection Systems...notification, or electronic supervision of sprinkler control valves. See also A.17.5.3.3 and A.18.1.5. Alternatively, supervision](https://reader033.vdocument.in/reader033/viewer/2022041810/5e571a5d48f18b6f60287afd/html5/thumbnails/57.jpg)
Example 6
57
▪ Fire alarm west side.
▪ Panel
▪ Monitoring?
▪ Initiating Devices
▪ Smoke/Heat
▪ Pull
Smoke Alarm
Smoke Detector
Waterflow Bell
FACP
Hood System
DACT/Dialer
Pull station
Horn/Strobe
Strobe