1. Posttheinspectionreportcardonthejobsiteuntilthefinalinspectioniscompleted.2. NotifyInspectionswhentheiceprotectionmembraneisreadyforinspection.3. Scheduleafinalinspectionatleast24hoursinadvance(pleasehaveyourpermitnumberavailable).You can reach the Inspections Department between 8 am and 4 pm at 763-593-8090.
Three Inspection MustsOVER
CityofGoldenValleyInspectionsDepartment|7800GoldenValleyRoad,GoldenValley,MN55427|763-593-8090
Residential Roofing Information Sheet
B U I LD I N G PE R M ITS ENSURE THAT GOLDEN VALLEY MEETS LOCAL , STATE , AND FEDERAL BUILDING STANDARDS
AND CODES . THEY ALSO HELP PROTECT THE HEALTH , SAFETY, AND WELFARE OF THE COMMUNITY.
Tear-OffCompletelyremoveexistingshingles,underlayment(includingtheiceprotectionmembrane),flashing(ifrustedorinbadcondition),etcandinstallroofingasifitisnewconstruction.AccordingtotheNationalRoofingContractorsAssociation(NRCA),theexist-ingiceprotectionmembranecanremaininplaceifasecondlayerofmembraneisappliedoverit.Roofsheathingmustbecheckedbeforere-roofingandrepairedorreplacedifrottedorunsound.Replace-mentsheathingmustconformtotherequirementsoftheBuildingCode.OverlayingofsheathingmayrequireapprovalbyaMinnesotaregisteredengi-neer.Overlayofexistingshinglesisnolongerallowedbythecode.
Fasteners
Fastenersforasphaltshinglesmustbegalvanizedsteel,stainlesssteel,aluminum,orcopperroofingnailswithaminimum12-gage(0.105inch,or3mm)shankandaminimum3/8-inch(10mm)diameterhead.Theymustbelongenoughtopenetratethroughtheroofingmaterialsandaminimumof3/4inch(19mm)intotheroofsheathing.Wheretheroofsheathingislessthan3/4inchthick,thefasten-
ersmustpenetratethroughthesheathing.FastenersmustcomplywithATSMF1667.Note: Use of other types of fasteners must be approved by the City Inspections Department.
Roof SlopeDonotuseasphaltshinglesonroofswithlessthana2:12slope.Forroofswithslopeslessthan4:12,asphaltshinglesrequirespecialapplicationproce-dures.Alwaysfollowmanufacturer’sinstructionsonpackage.
UnderlaymentFor roof slopes of 2:12 to less than 4:12Applyiceprotectionmembraneaccordingtomanufacturersinstructionstoapointatleast24inchesinsidetheexteriorwallline(seeiceprotec-tionmembranerequirements).Overlaptheiceprotectionmembrane19incheshorizontallywith15#felt.Lapeachsubsequentlayerof15#felt19incheshorizontallyshinglefashiontopeak.Endlapsshallbeoffsetbysixfeet.For roof slopes of 4:12 and over Applyiceprotectionmembraneaccordingtomanufacturersinstructionstoapointatleast24inchesinsidetheexteriorwallline(seeiceprotec-tionmembranerequirements).Overlaptheiceprotectionmembraneaminimumoftwoincheshorizontallywith15#felt.Lapeachsubsequentlayerof15#felttwoincheshorizontallyshinglefashiontopeak.Endlapsshallbeoffsetbysixfeet.
Valley UnderlaymentBeforeapplyingshingles,installvalleyliningsperthemanufacturer’srequirements.
SHINGLE
DECK
Crooked Under-Driven
Over-Driven
PROPERNAILING
Valley FlashingValleyflashingshallconsistofnotlessthanNo.26-gaugecorrosion-resistant,galvanizedsheetmetal.Themetalmustextendatleast12inchesfromthecenterlineeachway.Sectionsofflashingshallhaveanendlapofnotlessthanfourinches.Alternately,thevalleymayconsistofwovenasphaltsinglesorclosed-cutstyleappliedinaccordancewiththemanufacturer’sinstructions.
Other FlashingAllotherflashingandroofventsshallbecheckedand,ifrustedorinbadcondition,replaced.ReplaceflashingwithnotlessthanNo.26-gaugecorrosion-resistantmetal.Roofventsandotherflashingsmustbeinstalledaccordingtomanufacturer’sinstructions.Anyreplace-mentofflashingatmasonrychimneysmustbeproperlycutinandre-tuckpointedorcaulkedwithanapprovedproduct.
Vertical Wall Flashing(26-Gauge)Applyshinglesuptheroofuntilacoursemustbetrimmedtofitatthebaseoftheverticalwall.Plantoadjusttheexposureslightly(andevenly)inthepreviouscourses,sothatthelastshingleisatleasteightincheswide(vertically).Thisallowsaminimumfive-inchexpo-sureofthetopcourseandathree-inchheadlap.Theflashingstripshouldbebent,usingametalbrake,toextendatleasttwoinchesuptheverticalwallandatleastthreeinchesontothelastshinglecourse(thatis,tothetopofthecutout).Embedtheflashinginasphaltplasticcementoranotherappropriateadhesive,andnailittotheroofevery12inches.Donotnailthestriptothewall.
Ifsidelapsarenecessary,overlapthepiecesatleastsixinches.Donotfasteninthisjointarea.
Shingle Application Around Flashing
Sidewall Flashing(26-Gauge)
Exhaust VentsCareshouldbetakentoensurethatkitchenandbath-roomexhaustfanpipesareconnectedtotheappropri-atedamperedexhaustroofventwithnoopeningsintotheatticthatwouldallowexhaustairbackintotheatticspace.Exhaustventsshallbeinstalledthesameasotheratticventsandventpipeflashings.Whenre-roofingaroundfurnaceflues,takecaretonotdislodgethejointsofthefluepipewithintheatticorwithininteriorchasesthispipemightpassthrough.Ifindoubt,consultalicensedheatingcontractor.
BRICKRe-mortaror caulkJOINT CAP
STEPFLASHING
SHINGLE
Fastenflashingto roof.
3"Min.2" Overlap
2"Min.
FLASHING
Kickout flashing is requiredwhere eaves meet wall plane.
Top and sides:SHINGLES overlap flangeand are set inasphalt plastic cement.
Bottom:FLANGE overlapsshingles. Exposedfastener heads are sealed.
UNDER-LAYMENT
ASPHALTPLASTICCEMENT
Gap similarto cutout
Min.2"
Flashing nailedover cutouts incourse below
Adhere shinglestrimmed to coverflashing strip
FLASHINGSTRIP
SIDING
Min.3"
OVER
InstallationInstalliceprotectionmembrane,oritscodeapprovedequivalent,accordingtomanufacturer’sinstructions.Theiceprotectionmembranemustextendfromthemetalorwooddripedgetoapointatleast24inchesinsidetheexteriorwalllineofthebuilding.Tworowsareusuallyrequired,butmorethantwomayberequireddependingonthesizeoftheoverhang.Theiceprotectionmembranemustextendtotheouteredgeatallfasciaboards.Whenapplyingiceprotectionmembrane,keeptheproductaswrinklefreeaspossible.Unrollitparallelwiththeeaves.Theiceprotectionmembraneshouldgoovertheeaves’dripedgeflashingbutundertherake’sdripedgeflashing.
Alternate Method
Where to Use Ice Protection MembraneAlwaysfollowmanufacturer’sinstallationinstructions.TheNRCArecommendsputtingnewiceprotectionmembraneovertheexisting.Topreventanyridgeeffect,extendituptheroofaminimumof12inches(heightofoneshinglecourse),pastthetopmostedgeoftheexistingmaterial.Realistically,thismeansmostcontractorswilluseanadditionalone-halforfull-rollwidth(18-inchor36-inch)ofmaterialalongtheeaves.Removaloftheexistingiceprotectionmembrane(whichisdifficultandultimatelyendsinadecisiontojustremovethedeckingalongtheeavesandinstallnewdecking)isgener-allyexcessive.
2" SIDE LAP
RAKE
EAVES
DRIPEDGE
DRIP EDGE
DECK
Start 1st coursewith full shingle
ICE PROTECTIONMEMBRANE
SHINGLES overhang dripedge 1/4" to 3/8". If no dripedge overhang is 1/2" to 3/4".
ICE PROTECTION MEMBRANE laps over fascia behind drip edge and gutter.
1st course SHINGLE
STARTERSHINGLE
EAVE DRIPEDGE FLASHINGlaps into gutter
SOFFIT VENT
GUTTER
Crickets and SaddlesAcricketorsaddlemustbeinstalledontheridgesideofanychimneyorpenetrationmorethan30inches(762mm)wideasmeasuredperpendiculartotheslope.Cricketorsaddlecoveringsmustbesheetmetalorofthesamematerialastheroofcovering.
METAL COVERED SADDLE
Ice Protection MembraneIceprotectionmembraneisrequiredonallbuildings,exceptunconditioneddetachedaccessorystructures.Itconsistsofatleasttwolayersof15#feltunderlaymentcementedtogetheroraself-adheringpolymermodifiedbitumensheet.Iceprotectionmembraneisknownbyavarietyofgenericandtradenames,including:iceprotectionunderlayment,self-adheredmembrane,self-adheringmodifiedbitumensheetmaterial,WeatherLock®,Ice&WaterShield®,WeatherWatch®,MoistureGuardPlus®,Titanium-UDL™,Titanium-PSU™,GraceSelect®,EaveGuard®,andWinterGuard™.
Shingle ApplicationFive-Inch Method Skylight (Basic Sheet Metal Components)
All dimensions approximate.
Start3rd coursewith 10"removed
4" End lap
ICE PROTECTIONMEMBRANE
DECK EAVESFLASHING
(If required)
DRIPEDGE
STARTERSHINGLE
SHINGLES overhang dripedge 1/4" to 3/8". If no dripedge overhang is 1/2" to 3/4".
5" Exposure
Start1st coursewith full shingle
Start2nd coursewith 5"removed
2" Top lapDRIPEDGE
SELF-SEALINGADHESIVE
INTEGRAL COUNTER FLASHING with hemmed drip edge
COUNTER FLASHING over base and step flashing approx. 2" min.
APRON FLASHING with lower edge hemmed under
RAISED CURB2" x 8" suggested as minimum to attain flashing clearance
ICE PROTECTION MEMBRANEturned up on curb
STEPFLASHING
BACKER FLASHING under shingles minimum three courses. Where necessary (depending upon anticipated debris and/or snow accumulation), holdshingles up one course and nail high.
SKYLIGHT
1 to 3001. 1512=5.04squarefeetofrequiredventarea
3002. 5.04x144=725.76squareinches3. Ifbothroofventsandsoffitventsprovidedper
Code,dividebytwo.725.76=362.88squareinches2
4. 362.88=8 roof vents required with balance50of ventilation in soffits
Enclosed SpacesEnclosedatticsandenclosedrafterspacesformedwhereceilingsareapplieddirectlytotheundersideofroofraftersshallhavecrossventilationfor each separate space.
Mechanical Venting DevicesUseofpoweredroofventilators,windturbines,orothermechanicalventingdeviceswillallowcreditforthesizeoftheroof opening onlyduetothepotentialformechanicalfailureofthedevice.Re-useofpow-eredroofventilatorsrequiresproofofoperation.
Roof and Soffit VentsIfnecessary,additionalroofandsoffitventsmustbeinstalled.
Minimum area Thetotalnetfreeventilationareashallnotbelessthan1to150oftheareaofthespaceventilated,ornotlessthan1to300if50to80percentoftheventilationisprovidedinthethreefeetaboveeaveorcornicevents,withthebalanceoftherequiredventilationprovidedbyeaveorcornicevents.Asanalternative,thenetfreecross-ventilationareamaybereducedto1to300whenavaporbarrierhavingatransmissionratenotexceeding1permisinstalledonthewarmsideoftheceiling.
Roof Vent Calculation ExamplesForahousewithfoundation(ceilingarea)measuring42feetx36feet(1,512squarefeet)andadesiredroofventnetareaof50squareinches:
1 to 1501. Dividethefoundationsize(insquarefeet)bythe
ratiodeterminedbyguidelinesabove.1,512=10.08squarefeetofrequiredventarea150
2. Multiplyresultby144todeterminesquareinches.10.08x144=1,451.52squareinches
3. Dividebythedesiredroofventnetarea.1,451.52=30 roof vents if no soffit vents 50