residential ventilation: a review of established … · 4.3.1 test set up and methodology ..... 22...

79
Residential Ventilation: A Review of Established Systems and a Laboratory Investigation of the Fine Wire Heat Recovery Ventilator by Samuel van Berkel A thesis submitted in conformity with the requirements for the degree of Master of Applied Science Department of Civil Engineering University of Toronto © Copyright by Samuel van Berkel 2014

Upload: hoangthuan

Post on 09-Sep-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Residential Ventilation: A Review of Established Systems and a Laboratory Investigation of the Fine Wire Heat

Recovery Ventilator

by

Samuel van Berkel

A thesis submitted in conformity with the requirements for the degree of Master of Applied Science

Department of Civil Engineering University of Toronto

© Copyright by Samuel van Berkel 2014

ii

Residential Ventilation: A Review of Established Systems and a

Laboratory Investigation of the Fine Wire Heat Recovery

Ventilator

Samuel van Berkel

Master of Applied Science

Department of Civil Engineering

University of Toronto

2014

Abstract

The fine wire HRV is a novel concept for decentralized residential ventilation heat recovery

using thin copper wires to transfer sensible energy between supply and exhaust airstreams. The

HRV can be incorporated into the building envelope, in effect creating a “breathing wall” ideally

suited to demand controlled ventilation.

Performance testing conducted in the laboratory indicates that fan electricity consumption was as

low as 1.1 W per L/s, while sensible heat recovery efficiency was as high as 82%. Overall, the

fine wire HRV is comparable to the top 5% of HRVs available in North America. When used in

conjunction with demand controlled ventilation, the modeled ventilation heating load was

reduced by 61% and the total heating load was reduced by 17%. Fan electricity consumption was

also reduced by 61%, corresponding to a reduction in household electricity use of roughly 5%.

Additional modeling and field installations are recommended.

iii

Acknowledgments

I would like to thank Professor K.D. Pressnail and Professor J. Siegel for their ideas, support and

guidance in writing this thesis. I would also like to thank Doug Hart for encouraging me to

continue my studies and first bringing the fine wire heat exchanger to my attention. Finally I

would like to thank Eur van Andel, inventor of the fine wire heat exchanger, for supplying a heat

exchanger sample and for his guidance constructing a prototype heat recovery ventilator.

iv

Table of Contents

1 Introduction ................................................................................................................................ 1

2 Review of Existing Technologies .............................................................................................. 3

2.1 Distribution System ............................................................................................................ 3

2.1.1 Centralized Ventilation ........................................................................................... 4

2.1.2 Decentralized Ventilation ....................................................................................... 5

2.2 Ventilation Control ............................................................................................................. 6

2.3 Energy Recovery Technology ............................................................................................. 8

2.3.1 Plate ......................................................................................................................... 9

2.3.2 Rotary .................................................................................................................... 10

2.3.3 Run-Around .......................................................................................................... 10

2.3.4 Heat Pipe ............................................................................................................... 11

2.3.5 Alternating Flow Regenerators ............................................................................. 11

3 The Fine Wire HRV ................................................................................................................. 12

3.1 Heat Recovery Technology ............................................................................................... 12

3.2 Enclosure and Manifold Design ........................................................................................ 13

3.3 Distribution System .......................................................................................................... 15

3.4 Ventilation Control ........................................................................................................... 16

4 Performance Measurements ..................................................................................................... 17

4.1 Pressure Drop .................................................................................................................... 17

4.2 Fan Electricity Consumption ............................................................................................ 19

4.3 Airstream Cross-Leakage .................................................................................................. 22

4.3.1 Test Set Up and Methodology .............................................................................. 22

4.3.2 Measurements ....................................................................................................... 23

4.3.3 Estimating Cross-Leakage .................................................................................... 25

4.3.4 Limitations ............................................................................................................ 27

4.4 Sensible Heat Recovery Efficiency .................................................................................. 27

4.4.1 Measurement Standards ........................................................................................ 27

v

4.4.2 Test Set Up and Methodology .............................................................................. 29

4.4.3 Results ................................................................................................................... 31

5 Preliminary CFD Model ........................................................................................................... 34

6 Whole-Building Model ............................................................................................................ 36

6.1 Indoor Air Quality Metrics ............................................................................................... 36

6.1.1 Fine Particulate Matter (PM2.5) ............................................................................. 36

6.1.2 Formaldehyde (HCHO) ........................................................................................ 37

6.1.3 Ozone (O3) ............................................................................................................ 37

6.2 Methodology: Energy Use ................................................................................................ 38

6.3 Methodology: Indoor Air Quality ..................................................................................... 39

6.3.1 Fine Particulate Matter (PM2.5) ............................................................................. 41

6.3.2 Formaldehyde (HCHO) ........................................................................................ 41

6.3.3 Ozone (O3) ............................................................................................................ 42

6.4 Analysis ............................................................................................................................. 43

6.4.1 Constant Ventilation Rate ..................................................................................... 43

6.4.2 Variable Ventilation Strategy ............................................................................... 43

6.4.3 Occupancy Schedules ........................................................................................... 46

6.5 Results ............................................................................................................................... 48

6.5.1 Energy Consumption ............................................................................................ 48

6.5.2 Indoor Air Quality ................................................................................................. 50

6.6 Limitations ........................................................................................................................ 51

7 Discussion ................................................................................................................................ 52

8 Conclusions .............................................................................................................................. 54

9 Future Research ........................................................................................................................ 55

9.1 Condensation and Freezing ............................................................................................... 55

9.2 Field Installation ............................................................................................................... 56

Appendix A: Photos of Prototype, Testing and Installations ....................................................... 62

Appendix B: Sensible Heat Recovery Efficiency Test Data ....................................................... 66

vi

List of Tables

Table 1. Mass balance model parameter values ............................................................................ 40

Table 2. Pollutant concentrations at constant ventilation rates ..................................................... 43

vii

List of Figures

Figure 1. Common residential ventilation systems ......................................................................... 1

Figure 2. Conventional heat/energy recovery ventilator ................................................................. 2

Figure 3. Types of heat/energy recovery ventilators ...................................................................... 9

Figure 4. Fine wire heat exchanger and manifold ......................................................................... 12

Figure 5. Heat exchanger and heat recovery process .................................................................... 13

Figure 6. Photos of variable speed brushless DC centrifugal fans and air sealing ....................... 14

Figure 7. HRV enclosure and heat exchanger manifold ............................................................... 14

Figure 8. Typical use of the fine wire HRV in a bedroom ........................................................... 15

Figure 9. Fine wire HRV concept and distribution system ........................................................... 16

Figure 10. Test setup for pressure and flow rate measurements ................................................... 18

Figure 11. Pressure and flow rate measurements used to develop system curve ......................... 19

Figure 12. Fine wire HRV electrical power consumption at different flow rates ......................... 20

Figure 13. Fine wire HRV ventilation electrical efficiency at different flow rates ...................... 21

Figure 14. Distribution of electrical power consumption of HRVs .............................................. 21

Figure 15. Dry ice and configuration of leakage testing using CO2 ............................................. 23

Figure 16. CO2 concentrations in Airstreams A and B ................................................................. 24

Figure 17. CO2 concentrations in Airstream B before and after heat exchanger .......................... 24

Figure 18. Process for estimating CO2 concentrations in Airstream A ........................................ 26

Figure 19. Location of temperature measurements in standard test procedures ........................... 29

Figure 20. Heat recovery efficiency test setup and location of thermocouples ............................ 30

Figure 21. Temperature measurements at two airflow rates ......................................................... 31

Figure 22. Effect of heat loss through the HRV enclosure ........................................................... 32

Figure 23. Sensible heat recovery efficiency test results .............................................................. 33

Figure 24. Distribution of sensible heat recovery efficiencies of HRVs ...................................... 34

viii

Figure 25. Initial CFD modeling results ....................................................................................... 35

Figure 26. Variable ventilation strategy ........................................................................................ 44

Figure 27. Required duration of increased mechanical ventilation .............................................. 45

Figure 28. Occupancy schedules ................................................................................................... 46

Figure 29. Living room pollutant concentrations resulting from occupancy schedules ............... 47

Figure 30. Bedroom pollutant concentrations resulting from occupancy schedules .................... 48

Figure 31. Energy use of constant and variable ventilation strategies .......................................... 49

Figure 32. Pollutant concentrations of constant and variable ventilation strategies ..................... 50

1

1 Introduction

The energy efficiency of buildings has steadily increased since the energy crisis of the 1970’s

prompted improvements in construction methods and HVAC technology (Wray et al. 2000). A

major component of this improvement in energy efficiency has come as a result of reduced

uncontrolled air leakage through the building envelope. Over the same period, changes in

building materials, appliances, home furnishings and manufactured products have resulted in

new types of indoor pollutants and increased emissions levels (Sherman and Walker 2007). As a

result, operable windows and air leakage can no longer be relied upon to provide adequate

residential ventilation, particularly in cold climates during the winter.

In order to provide a healthy indoor environment for building occupants, most jurisdictions

prescribe residential ventilation rates based on the size of the space and the number of

anticipated occupants. These ventilation rates are intended “to provide indoor air quality that is

acceptable to human occupants and that minimizes adverse health effects” (ANSI/ASHRAE

2013). Builders have traditionally met the requirements with central exhaust-only systems, which

are relatively simple to install and have a low initial cost (Wray et al. 2000). As interest in energy

conservation grows, balanced supply and exhaust systems are becoming increasingly popular in

cold climates because they allow for heat to be recaptured from the exhaust air. Without

ventilation heat recovery, energy savings from improvements in the air-tightness of the building

envelope are offset by heat losses due to increased mechanical ventilation. Balanced ventilation

systems also allow for pre-filtration of supply air and prevent depressurization, which can have

negative effects on indoor air quality (Russell et al. 2005).

(a) Exhaust-only (b) Balanced supply & exhaust

Figure 1. Common residential ventilation systems (Oikos Green Building Source 1995)

2

Balanced ventilation systems recover energy from the exhaust air using a heat recovery

ventilator (HRV) or energy recovery ventilator (ERV). The difference between HRVs and ERVs

is described in Section 2.3. Both are packaged ventilation units which provide both supply and

exhaust airflows while using a heat exchanger to transfer energy between the two airstreams, as

illustrated in Figure 2. In cold outdoor conditions, the energy captured from the outgoing exhaust

airstream pre-heats the incoming supply airstream, reducing the additional space heating load

created by the ventilation air.

Figure 2. Conventional heat/energy recovery ventilator

HRVs and ERVs provide a solution for maintaining indoor air quality while achieving the energy

benefits of an increasingly airtight building envelope. However, they have also introduced a new

set of challenges. Additional electricity is required to power fans, and in some cases this

electricity consumption can partially or wholly offset the energy benefits of reduced space

heating and cooling, particularly if the system is run continuously (El Fouih et al. 2012). Even in

the winter, when fan electricity can partially offsets space heating requirements, the high cost of

electricity relative to natural gas results in increased energy costs. Energy recovery efficiency

also varies widely between commercially available units, with many HRVs recovering less than

60% of the available heat (Home Ventilation Institute 2014). In houses without forced air heating

systems, additional ductwork is required, utilizing space and creating interconnections which

allow noise to travel between rooms. HRV and ERV controls can also be confusing for home

owners, leading to over- or under-ventilation in some circumstances.

While these challenges are being partially addressed by performance improvements of

conventional HRVs and ERVs, further progress may require completely reimagining residential

ventilation and energy recovery. This thesis was motivated by one such effort in the Netherlands.

Indoor Air

(warm & stale)

Pre-Heated

Supply Air

(warm & fresh)

Outdoor Air

(cold & fresh)

Exhaust Air

(cold & stale)

Heat Exchanger Supply Fan

Exhaust Fan

3

In the 1990s a Dutch company called Fiwihex developed an HRV which uses thin copper wires

to transfer sensible energy between supply and exhaust airstreams and termed their invention a

fine wire heat exchanger (2006). Because of the efficient heat transfer mechanism, the heat

exchanger profile can be constructed thin enough to allow the HRV to be incorporated into the

building envelope, in effect creating a “breathing wall” ventilation system without ductwork.

In this initial investigation of the fine wire HRV, its efficiency and performance are measured in

the laboratory and its potential application for decentralized ventilation heat recovery in

residential buildings is evaluated. Other ventilation technologies and strategies are also reviewed

to provide the reader with perspective and a basis for comparison.

2 Review of Existing Technologies

Ventilation and air leakage are estimated to account for a third of all energy used for space

conditioning (Liddament and Orme 1998). In North America, ventilation rates are established by

ANSI/ASHRAE Standard 62.1-2013 – Ventilation for Acceptable Indoor Air Quality and

ANSI/ASHRAE Standard 62.2-2013 – Ventilation and Acceptable Indoor Air Quality in Low-

Rise Residential Buildings. Although these standards are well established, there remains

significant variation in how much energy ventilation systems use and the quality of indoor air

they provide. Sherman and Walker (2007) compared common residential ventilation systems

meeting ANSI/ASHRAE Standard 62.2 and found differences of two or three times in total

ventilation energy use, suggesting that there are still significant improvements that can be made

to residential ventilation design, both by optimizing existing systems and by exploring new

concepts in residential ventilation. This section provides a review of existing residential

ventilation technologies by focusing on three key areas: distribution system, ventilation control,

and energy recovery technology.

2.1 Distribution System

Russell et al. (2005) provide a thorough review of existing residential ventilation strategies.

Mechanical ventilation may be exhaust-only, supply-only or balanced supply and exhaust, and

may be operated either continuously or intermittently. Natural ventilation strategies include

operable windows, passive stack ventilation and solar chimneys. Limited energy recovery is

possible in naturally ventilated systems while a heat pump can be used to recapture energy from

4

exhaust-only mechanical systems. However, for most practical applications ventilation heat

recovery is limited to balanced supply and exhaust mechanical systems (Russell et al. 2005).

Balanced supply and exhaust systems may be centralized, having a single set of supply and

exhaust fans for the whole single family detached house. In the case of multi-unit residential

buildings, multiple centralized supply and exhaust fans are used and each serves a number of

suites. Decentralized ventilation makes use of individual supply and exhaust fans to ventilate

individual rooms or zones of the house, or in the case of multi-unit residential buildings,

individual supply and exhaust fans for each suite.

2.1.1 Centralized Ventilation

In multi-unit residential buildings, the most common balanced ventilation strategy in older

buildings is to have central air handlers supply air to the corridors and exhaust air from

bathrooms and kitchens. Although some portion of the supply air is expected to enter suites

through the pressurized corridors, these systems are mostly designed to prevent the movement of

contaminants into the corridors and between suites. Infiltration through walls and operable

windows is required to supply much of the fresh air for these buildings, often leading to

inadequate indoor air quality and comfort. In newer multi-unit residential buildings, fresh air is

typically delivered directly to suites in addition to corridors, improving indoor air quality but

increasing cost and space required for ductwork. In either case, centralized systems rely on

interconnections between suites, making it more difficult to control pressure differences induced

by stack effect, as well as the spread of odours, sound, pests, fire and smoke (CMHC 2003).

In single family homes, balanced supply and exhaust systems with ventilation heat recovery can

be installed in a number of ways, each having advantages and disadvantages as described by

Building Science Corporation (2013). In a single-point system, air is typically delivered to a

single room, and exhausted from another room. This system requires the least ductwork and the

simplest controls, making it the most economical. It does not distribute air throughout the house

or provide mixing however, important factors in achieving adequate indoor air quality in all

areas of the home (Rudd and Lstiburek 2000). A multi-point system typically delivers air to each

bedroom and living room, and exhausts air from bathrooms and kitchens. Although the multi-

point system achieves good air distribution, it has a high installation cost because of the

extensive ductwork required. In houses with a central air handler, fresh air can be delivered to

5

the air handler’s supply trunk, and exhaust air can be extracted from return trunk. This integrated

system provides the distribution benefits of a fully ducted system, without the additional

ductwork costs. An integrated system is more vulnerable to control issues since the ventilation

control must be interconnected with the air handler control (Building Science Corporation 2013).

2.1.2 Decentralized Ventilation

Decentralized ventilation has a number of advantages over centralized ventilation. From the

perspective of indoor air quality, decentralization allows a ventilation system to meet the specific

demand of each zone without having to balance different requirements throughout the building.

Such systems can respond to increased occupant-related pollutant emission rates by increasing

ventilation rates when occupancy is high and can conserve energy by reducing ventilation rates

when the zone is unoccupied. By providing increased ventilation near pollutant sources,

decentralized systems can also achieve higher ventilation effectiveness than mixed ventilation

systems, reducing the volume of supply air required and the energy required to condition and

deliver that air. By compartmentalizing buildings into zones, decentralized ventilation also

allows for increased temperature variation in unoccupied spaces, further reducing space

conditioning requirements (Knoll 1992). In multi-unit buildings, compartmentalizing individual

suites reduces horizontal and vertical air movement, reducing air leakage through the building

envelope, improving comfort, and reducing space conditioning requirements (CMHC 2005).

By decentralizing ventilation systems, building occupants are able to have greater control over

their indoor environment, improving comfort and overall satisfaction. Elimination of a central air

distribution network also reduces space requirements for ductwork. It can mean reduced sound

transmission between rooms or suites (Knoll 1992), and in the case of multi-unit buildings, better

control over the spread of pests, fire, and smoke (CMHC 2003).

Since individual ventilation systems are required for each room or suite, decentralized ventilation

is typically more expensive to install and to maintain than a centralized system. Further,

depending on the location of ventilation units and the types of fans used, occupants may be

exposed to greater noise levels.

6

2.2 Ventilation Control

Residential ventilation requirements calculated using ANSI/ASHRAE Standard 62.1 and 62.2

include minimum constant whole-building ventilation rates based on the floor area and the

number of intended residents. The simplicity of this constant ventilation approach makes it

relatively straight forward for builders to understand and implement, and ensures adequate

indoor air quality is provided under most circumstances.

At the same time, because of the significant energy cost associated with the delivery and

conditioning of ventilation air, there has long been an interest in finding strategies to reduce

overall ventilation rates while maintaining adequate indoor air quality. Because pollutant

emission rates vary, and spaces are not continuously occupied, constant ventilation inevitably

means ventilating more than necessary at some times. As early as 1990, the need for demand-

controlled ventilation (DCV) had been identified (International Energy Agency 1990), as it was

clear that by continuously adjusting the fresh air delivery to meet the demand, energy

consumption could be reduced while indoor air quality could be maintained or even improved.

In some cases, DCV can be achieved by increasing or decreasing ventilation based on a simple

schedule. Scheduled ventilation is appropriate in buildings with predictable occupancy patterns,

such as retail spaces or office buildings which are unoccupied at night or during the weekends,

and is uncommon in residences. Scheduled ventilation is the lowest cost DCV strategy, but is

limited by how much energy it can save because it must make fairly conservative assumptions

about how long and to what fraction spaces are occupied. Scheduled ventilation may also fail to

provide adequate indoor air quality if the programming does not consider atypical occupants

such as nighttime cleaners, or if there is an unexpected deviation from the assigned schedule.

Sensor-based demand-controlled ventilation (SBDCV) provides a more adaptable option than

simple ventilation scheduling. Fisk and De Almeida (1998) identified three characteristics of

applications best suited to air quality SBDCV: (1) a pollutant or ‘indicator’ exists which is

relatively easy to measure and which dominates such that reducing its concentration with

ventilation will provide sufficient control of all other pollutants; (2) large spaces where pollutant

emission rates or occupancy are unpredictable and vary with time; and (3) locations with high

heating or cooling loads and high energy costs.

7

The most common parameters used for SBDCV is carbon dioxide (CO2), which is continuously

exhaled by humans and is relatively inexpensive to monitor. While recent research by (Satish et

al. 2012) suggests CO2 may impair cognitive performance at concentrations as low as 1000 ppm,

it has traditionally been used as an indicator of bioeffluents and other emissions related to

occupant activity, rather than a pollutant itself (Fisk and De Almeida). The ventilation rate per

person roughly correlates to the steady state CO2 concentration in a space, and this principle is

used to estimate the number of occupants and set the ventilation rate accordingly. Since CO2

sensors have some lag time, and ventilation rates and occupancy are highly dynamic processes, a

basic set-point control strategy is often ineffective, and a proportional or exponential control

strategy is preferable (Schell et al. 1998). Recent updates to ANSI/ASHRAE Standard 62.1 only

permit a basic CO2 set-point control strategy when used very conservatively, resulting in

significant over-ventilation (Dougan and Damiano 2011).

Dougan and Damiano identify several challenges in implementing CO2-based SBDCV, most

significantly sensor precision (±50 ppm or greater sampling error), drift and time lag, but also

ventilation airflow rate accuracy and changes in outdoor CO2 concentration. They note that this

can lead to an accumulated root-mean-square error of up to 50%. As a result, many designers act

conservatively, leading to over-ventilation and increased energy consumption, often wholly or

partially defeating the benefits of DCV. CO2-based SBDCV is also unable to respond to

pollutant emissions which are not correlated with occupancy, such as emissions from building

materials and furniture (Fisk and De Almeida 1998).

Because of the limitations of CO2-based SBDCV, a number of alternative strategies for detecting

occupancy and controlling occupant-generated pollutants have been developed. Naghiyev et al.

(2014) compared three unobtrusive occupant detection techniques in a residential setting include

CO2, passive infra-red (PIR) and device-free localization (DfL). PIR technology functions by

sensing human body temperature against the temperature of background objects. The main

advantage of PIR sensors is that they are low cost, easy to use and offer immediate feedback.

The main disadvantage is that they cannot be used to estimate the number of occupants. DfL

functions by detecting the absorption of radio signals by the human body. It is possible, although

difficult, to estimate the density of occupants using DfL.

8

The study by Naghiyev et al. (2014) found that all three occupancy detection techniques

functioned to some degree. The CO2 sensors suffered from slow response times, while the PIR

sensors failed to detect reduced-movement occupants in some circumstances. DfL technology is

promising, but further research is required to determine how best to configure the sensors and

analyze the data. CO2 and PIR sensors can be used in combination, although both are influenced

by the metabolic rate of occupants.

In residential settings, humidity-based DCV can be effective for controlling moisture. It is most

often implemented in bathrooms or kitchens, and used to activate exhaust fans. Humidity-based

SBDCV must be combined with another ventilation strategy, as humidity is not a good indicator

for most residential pollutants (Fisk and De Almeida 1998).

Total volatile organic compound (TVOC) sensors can offer more precise control of non-

occupant-based emissions, such as those from building materials and furniture. Unfortunately,

controlling ventilation based on TVOCs is problematic because of the large variability in toxicity

of individual VOCs relative to each other (Fisk and De Almeida). In residential settings,

emissions from building materials and furniture are typically stable enough that TVOC-based

SBDCV has limited benefit.

2.3 Energy Recovery Technology

As described by Kakaç and Liu (2002), heat exchangers can be classified into two basic

categories based on the process of heat transfer: recuperative and regenerative. Recuperative heat

exchangers are characterized by one fluid continuously recovering heat directly from the other

fluid, either by direct contact between the fluids or, in the case of ventilation heat recovery,

through a separating wall. Regenerative heat exchangers use an intermediate storage medium to

transfer energy to and from the two airstreams. The airstreams may alternately occupy a single

flow passage containing the storage medium or the storage medium may move between the two

airstreams.

Heat exchangers used for ventilation heat recovery can be further classified into those which

recover sensible energy only (referred to as “heat recovery ventilators” or HRVs) and those

which recover sensible energy and latent energy (referred to as “energy recovery ventilators” or

9

ERVs). ERVs are most commonly used in hot climates where the latent portion of the cooling

load dominates, while HRVs are more common in cold climates where heating load dominates.

Plate, rotary and run-around heat exchangers are the conventional technologies most commonly

used to recover energy from ventilation air. Of the three conventional technologies, plate heat

exchangers are the most common technology, due largely to their simplicity and relatively low

cost. Rotary heat exchangers are most common where space is available and significant latent

energy recovery is desired. Run-around systems have lower efficiencies, but allow for heat

recovery between physically separated air streams.

Heat pipes and alternating flow regenerators are examples of more experimental technologies

which may be appropriate for specific applications, but have not been widely adopted in North

America. While alternating flow regenerators are promising for decentralized ventilation, there

has been limited peer-reviewed study of the technology.

Plate Source: www.innergytech.com

Rotary Source: www.innergytech.com

Run-Around Source: www.immak.eu

Heat Pipe Source: www.immak.eu

Alternating Flow

Regenerator Source: www.lunos.de

Figure 3. Types of heat/energy recovery ventilators

2.3.1 Plate

The most common form of HRV for buildings is a recuperative plate heat exchanger, sometimes

referred to as a cross-flow heat exchanger because the two airstreams are brought together in a

cross or counter-flow arrangement. Plate heat exchangers have the advantage of being relatively

compact, low-cost and free of moving parts. Plate heat exchangers designed to recover sensible

energy only are typically constructed from aluminum or polypropylene. Although aluminum has

the advantage of higher thermal conductivity, polypropylene cores weigh less, are more

corrosion and chemical resistant, and collect fewer fouling particles (Mardiana and Riffat 2013).

10

Flat plate ERVs designed to recover both sensible and latent energy have been built from

vapour-permeable paper sheets for over 30 years (Osamu 1984). Zhang and Jiang (1999) tested

membrane-based flat plate heat exchangers and concluded that, under hot and humid conditions,

they could recover twice as much latent energy as the existing paper systems. Both technologies

allow the movement of water vapour between air streams, while preventing the transfer of

pollutants. Today both vapour-permeable paper and membrane plate technologies are in use, but

are less common than rotary heat exchangers when moisture transfer is desired.

2.3.2 Rotary

Rotary heat exchangers, often referred to as heat wheels or energy wheels, are the most common

form of regenerative heat exchangers used for ventilation heat recovery. The matrix or storage

medium is in constant movement, passing periodically from the hot airstream to the cold

airstream. Early rotary heat exchangers used steel wool to store sensible energy, while newer

models make use of silica-gel desiccants to store both sensible and latent energy (Nóbrega and

Brum 2009).

Rotary heat exchangers generally provide the highest heat recovery efficiencies of any HRV or

ERV, and are less prone to fouling because air flowing in one direction removes particles

deposited by air flowing in the opposite direction. Rotary heat exchangers may be more

expensive to install and maintain because they require a lot of room, having moving parts, and

require a separate motor and control to provide rotation. Cross contamination of the airstreams is

also a concern, although a purge section can be used to reduce the amount of exhaust air entering

the supply air stream (Ruan et al. 2012).

2.3.3 Run-Around

Run-around heat exchangers are another form of regenerative heat recovery. Energy is

transferred from one air stream to a water-glycol mix, which is circulated by a pump to the other

airstream where the energy is released. Although less efficient than plate or rotary heat

exchangers, run-around heat exchangers have the advantage of being able to transfer energy

between two airstreams which may not be in close physical proximity. This can be particularly

important in building retrofits where the existing ventilation system was not designed with heat

recovery in mind. Another advantage of run-around systems over rotary heat exchangers is that

there is no airstream cross-leakage and, other than the pump, there are no moving parts.

11

Although traditional run-around systems were limited to sensible energy recovery, some

researchers (Seyed-Ahmadi et al. 2009) have proposed using semi-permeable membranes in

combination with an aqueous salt solution to transfer both sensible and latent energy between the

two airstreams. A heat pump can be added to run-around systems to increase heat recovery

efficiency from 50% to nearly 70%, although installation costs and electricity consumption are

also increased (Wallin et al. 2012).

2.3.4 Heat Pipe

Heat pipes are growing in popularity for ventilation air dehumidification and reheating (Zhang

and Lee 2011). They are not commonly used for recovering energy from exhaust ventilation air

however, because they are limited to sensible energy only and are more expensive than other

types of heat exchangers. As outlined by Shao and Riffat (1997), heat pipes may be useful for

applications where a very low pressure drop is desired, such as with natural ventilation systems.

2.3.5 Alternating Flow Regenerators

Alternating flow regenerative HRVs function by moving air through an energy storage medium

in alternating directions. The energy storage medium stays in a fixed position, and the direction

of airflow alternates to capture energy from one airstream, and then deposit it into the other

airstream. Because each unit allows for airflow in a single direction, an even number of

synchronized ventilation units are required to achieve balanced airflow. There exist at least two

commercial variations of the reversible regenerator, one with an aluminum sheet energy storage

medium (Manz et al. 2000) and one with a ceramic energy storage medium (Schmidt and Klein

2011). To the authors’ knowledge there have been no peer-reviewed studies of the newer product

with ceramic storage medium.

For both products, the cycle lengths between changes in airflow direction are in the range of 75

to 80 seconds. Sensible efficiencies appear to be comparable to those achieved by plate heat

exchangers, and it is possible to recover latent energy, depending on the storage material.

Computational fluid dynamics models by Manz et al. (2000) indicate air change efficiencies of

0.63-0.83 (1.0 corresponds to complete mixing), depending on the location of the units relative to

each other. The air change efficiencies measured in this study suggest significant short circuiting

of fresh supply airstream back into the exhaust airstream, which may reduce overall ventilation

effectiveness.

12

3 The Fine Wire HRV

The review of existing heat recovery technologies indicates that further study of decentralized

ventilation systems with heat recovery would be beneficial. The fine wire HRV represents a

novel concept for decentralized ventilation with heat recovery. The ventilator uses copper wires

to transfer sensible energy between the supply and exhaust airstreams. Although the heat

exchanger technology was first patented in North America in 1998 (Van Andel), it has yet to be

successfully commercialized. This section describes the heat recovery technology in more detail

and outlines a potential decentralized ventilation strategy for residential buildings.

Figure 4. Fine wire heat exchanger and manifold

3.1 Heat Recovery Technology

Manufactured by in the Netherlands Fiwihex (2006), the fine wire heat exchanger is composed

of 28 layers of 0.1 mm diameter copper wire. The wires are spaced at 0.6 mm parallel to the

direction of airflow, and 0.4 mm perpendicular to the direction of airflow. Adjacent air streams

are separated by 2 mm thick layers of glue. The copper wires extend between supply and exhaust

airstreams, through the glue, allowing for heat transfer via conduction. A thin lacquer protects

the copper from corrosion without significantly limiting heat transfer.

The copper wires form a matt roughly 454 mm long, 217 mm wide and 16 mm thick, which is

divided into 17 channels along the width (Figure 5a). The heat exchanger area is roughly 0.05 m2

in each direction of airflow. A single fine wire heat exchanger is composed of approximately

30,000 copper wires with a combined mass of roughly 500 g.

13

The narrow diameter of the copper wire reduces the thickness of the boundary layer of air

formed at the surface, resulting in a high heat transfer coefficient between the copper and the air.

Because the copper wires are very conductive, efficient heat transfer between adjacent airstreams

is achieved, as illustrated in Figure 5b.

(a) Elevation (b) Section with details

Figure 5. Heat exchanger and heat recovery process

3.2 Enclosure and Manifold Design

An enclosure was built for the heat exchanger out of a combination of wood and transparent

acrylic plastic, with clear caulking and sheathing housewrap tape used for air sealing. Two

centrifugal fans were mounted back-to-back at the top of the enclosure, as shown in Figure 6.

The thickness of the enclosure (roughly 150 mm) was dictated by the depth of the fans. At this

thickness, the enclosure fits within the width of most conventional wall systems. For testing

purposes, the speed of each fan was controlled using a potentiometer and standard resistors to

create an adjustable 0-10 V output. Additional photos of the fans, control, enclosure and

manifold can be found in Appendix A.

High efficiency fans with brushless direct current (DC) motors were used. Electronically

commutated motors (ECMs) are brushless DC motors with an internal rectifier to convert

alternating current (AC) to DC. ECMs do not require an external DC power source, making them

popular for residential HVAC applications. For the purposes of testing, two 100 W variable

speed fans with non-electronically commutated brushless DC motors were used, requiring two

48 VDC power supplies.

Pre-Heated

Supply Air

Warm

Indoor Air

Cooled

Exhaust Air

Cold

Outdoor Air

28 L

ayers o

f Co

pp

er

Wire (ø

=0

.1m

m)

16mm

13mm Glue Boundary

Heat Transfer

via Conduction

454mm

217mm

Section Cut

14

Figure 6. Photos of variable speed brushless DC centrifugal fans and air sealing

A manifold was supplied with the heat exchanger provided by Fiwihex. A manifold is required

on both sides to keep the two airstreams separate as they enter and exit the heat exchanger. The

design is tapered such that the height is reduced at the top and bottom of the heat exchanger,

which likely reduces the airflow rate and alters the airflow direction the airflow at these

locations. With a maximum centre height of 40 mm, the manifold easily fits within the enclosure

depth. The enclosure and manifold are illustrated in Figure 7.

(a) Enclosure elevation (b) Enclosure section (c) Manifold airflow detail

Figure 7. HRV enclosure and heat exchanger manifold

Outlet

Copper Wires

Manifold

From Inlet

Centrifugal

Fans

Manifold

15

3.3 Distribution System

By integrating the fine wire HRV ventilation into the façade to create a “breathing wall”, the

extensive ductwork and space requirements of conventional ventilation systems can be avoided.

By using a system of individual ventilation units in each room, rather than a single centralized

unit, air can be distributed more efficiency and airflow to each room can be controlled

independently. This independent control is particularly beneficial when individual rooms are

unoccupied for extended periods, as it allows ventilation to be reduced without increasing

occupant pollutant exposure. Ventilation rates can also be increased if higher than normal

occupancy is detected in a room, better controlling occupant-generated pollutant levels and

improving indoor air quality. Although ventilation noise levels may be higher because of the

proximity of the HRV to occupied spaces, eliminating central air distribution ductwork can

reduce sound transmission between rooms. A typical installation of the fine wire HRV in a

bedroom is illustrated in Figure 8.

Figure 8. Typical use of the fine wire HRV in a bedroom

Balanced airflow to each room is recommended to maximize overall ventilation heat recovery.

Balanced airflow also helps prevent air movement through the building envelope, which can

result in moisture issues depending on the relative indoor and outdoor temperature and relative

humidity. A separate occupant-controlled exhaust fan is recommended for the bathroom and

16

kitchen range, as the high levels of moisture and pollutants at these locations would increase the

HRV cleaning and maintenance requirements. Make up air for the bathroom and kitchen is

provided through infiltration, or through temporary imbalances in airflow at the HRVs in

adjacent spaces. This concept is illustrated in Figure 9.

Figure 9. Fine wire HRV concept and distribution system

3.4 Ventilation Control

The current design for the heat exchanger assembly utilizes two variable speed fans to allow

independent control of the supply and exhaust airstreams. Although for testing purposes the fans

were controlled using a simple potentiometer, a site installation would benefit from a more

sophisticated programmable logic controller with pressure and temperature sensors in each

airstream. Using this control configuration, the speed of one fan can be modulated to maintain

equal pressure drop across the heat exchanger for both air streams, resulting in balanced supply

and exhaust airflow rates, even if the space is positively or negatively pressurized due to stack

effect, wind or the operation of other mechanical systems. By automatically balancing the two

airflows, overall heat recovery efficiency can be maximized.

Since the fine wire HRV can be integrated into the wall and used to provide decentralized

ventilation, it is ideally suited to DCV. In a residential setting, a preset schedule will provide

good control for rooms with relatively predictable occupancy patterns, such as bedrooms. The

addition of a manual override or PIR sensor may be helpful to activate the ventilation system if

the room is occupied outside of the normal schedule. In other areas of the home where the

number of people and their schedules are less predictable, such as the living room, PIR

occupancy sensors should be used in combination with CO2 sensors. This allows the ventilation

system to be activated as soon as the space is occupied, but also allows the system to estimate

17

occupancy levels, and increase ventilation accordingly. The ventilation control strategy is

explored further in Section 6.4.2. Further refinement of the occupancy detection and control

strategy requires study of an installed prototype in an occupied home.

Optionally, reversible fans can be used to allow for cross ventilation and free cooling during

favourable outdoor conditions. In this configuration, HRVs on the windward side of the building

would be set to supply air only, with one fan operating in reverse such that both fans are

pressuring the space. On the leeward side of the building the HRVs would be operating in a

similar manner, but would be depressurizing the space. Working in combination, significant

cross ventilation could be achieved. This increased ventilation would be beneficial when there is

a desire for cooling and outdoor temperatures are lower than indoor temperatures.

4 Performance Measurements

Third-party performance data for the fine wire HRV is not published by the manufacturer and to

the author’s knowledge there have been no peer-reviewed studies of the technology. To address

this gap, laboratory tests were conducted to assess performance in a number of areas. Efforts

were made to quantify the pressure drop, DC fan electricity consumption, airstream cross-flow

leakage and sensible heat recovery efficiency at varying flow rates.

4.1 Pressure Drop

A system curve relating static pressure drop to flow rate was developed for the heat exchanger.

The system curve is an important parameter when selecting fans and can be a significant factor in

fan electricity consumption. Knowing the system curve also simplifies future testing by allowing

airflow rates to be calculated indirectly from static pressure measurements. Static pressure drop

and flow rate were measured using a calibrated axial fan in combination with a digital

differential pressure and flow gauge. To simplify the process, the fine wire HRV’s centrifugal

fans were not operated during the test, and the calibrated axial fan was used to generate airflow.

Static pressure probes were inserted through the side of the enclosure and located away from the

surface of the heat exchanger in an area of low air velocity. The test setup, equipment and

location of pressure sensors are shown in Figure 10.

18

Figure 10. Test setup for pressure and flow rate measurements

The system curve can be expressed using Equation 1 (adapted from ASHRAE 2013).

(1)

where,

Q is the airflow rate through the heat exchanger [L/s]

C is the flow coefficient

ΔP is the static pressure difference across the heat exchanger [Pa]

n is the flow exponent

Measurements of static pressure drop were made at flow rates ranging from 5 L/s to 50 L/s. By

taking natural logarithms of both sets of values and doing a linear regression, the flow coefficient

and flow exponent could be estimated as shown in Figure 11a. Using these values, the system

curve could be generated, as shown in Figure 11b.

19

(a) Estimating flow coefficient and exponent (a) Measured values and system curve

Figure 11. Pressure and flow rate measurements used to develop system curve

The difference in static pressure drop measured across the two sides of the heat exchanger at a

given flow rate was less than 5% and the system curve shown in Figure 11b was considered

accurate for both sides.

4.2 Fan Electricity Consumption

HRV electricity consumption is an important factor in overall ventilation energy use. Some

North American HRVs make use of inefficient permanent split capacity (PSC) motors which

result in excessive fan electricity consumption, although the industry is moving towards more

efficient fans with brushless DC motors (Straube 2009). More efficient air-to-air heat exchangers

generally result in larger pressure losses and require more fan power to move the same volume of

air. As a result, there is often a tradeoff between higher heat recovery efficiency and lower fan

electricity consumption. Depending on the climate, the energy benefit of selecting a more

expensive HRV with higher heat recovery efficiency may be wholly or partially offset by

increased fan power (El Fouih et al. 2012).

The electrical power consumption of the fine wire HRV was measured using an outlet electricity

meter. Static pressure drop across the heat exchanger was measured and converted to airflow rate

using Equation 11. Power consumption measurements were taken with both fans operating, with

one fan operating and with both fans off as shown in Figure 12.

R² = 0.9988

0

1

2

3

4

5

6

0 1 2 3 4 5

ln(Δ

P)

ln(Q)

ln(ΔP) = 1.649 ln(Q) - 1.0638ln(ΔP) = ln(Q)/0.606 - 0.649/0.606ΔP = (Q/1.91)1/0.61

0

50

100

150

200

250

0 10 20 30 40 50

Stat

ic P

ress

ure

Dro

p, Δ

P(P

a)

Airflow Rate, Q (L/s)

Measured Values

System Curve

ΔP = (Q/1.91)1/0.61

20

Figure 12. Fine wire HRV electrical power consumption at different flow rates

Comparing electricity consumption of the fine wire HRV with one and two fans operating

suggests that there is an overhead power supply electricity consumption of about 12 W,

regardless of fan speed. At low flow rates, this is as much as 65% of total electricity

consumption. Considerable electricity savings may be possible by using a smaller power supply,

although this would limit the HRV’s maximum airflow capacity. If the fine wire HRV is to be

operated intermittently the control should cut power to the power supply when the fans are not

operating. A separate power source would be required for the control components.

Total electrical power per unit flow rate was calculated to illustrate ventilation efficiency at

varying flow rates and allow for comparison to conventional HRVs. The results are illustrated in

Figure 13.

0

20

40

60

80

100

120

140

160

10 20 30 40 50 60 70

Ele

ctri

cal

Po

we

r C

on

sum

pti

on

(W

)

Airflow Rate in Each Direction (L/s)

2 Fans Operating

1 Fan Operating

Power Supply Only

21

Figure 13. Fine wire HRV ventilation electrical efficiency at different flow rates

Power consumption per unit flow rate is minimized to 1.1 W per L/s at flow rates around 25 L/s.

This results from the overhead electricity consumption of the power supply, which has a greater

relative penalty at low flow rates. Using a smaller power supply would shift the optimal

operating point to a lower flow rate.

Fan electricity consumption of the fine wire HRV was compared to conventional HRVs listed in

the Home Ventilation Institute Certified Products Directory (2014). Where performance data was

given at multiple flow rates, the fan electricity consumption at the highest sensible heat recovery

efficiency was used. The mean electricity consumption of the conventional HRVs was 2.2 W per

L/s. At 1.1 W per L/s, only the top 5% of conventional HRVs consume less electricity than the

fine wire HRV. The distribution of conventional units is shown in Figure 14.

Figure 14. Distribution of electrical power consumption of HRVs

0.0

0.5

1.0

1.5

2.0

2.5

3.0

10 20 30 40 50 60 70

Ele

ctri

cal

Po

we

r C

on

sum

pti

on

(W p

er

L/s)

Airflow Rate in each Direction (L/s)

0%

10%

20%

30%

40%

50%

<=1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 >4.5

Pe

rce

nta

ge o

f C

on

ven

tio

nal

HR

V U

nit

s

Electrical Power Consumption (W per L/s)

Fine WireHRV1.1 W per L/s

Source: Home Ventilation Institute 2014

22

It is important to note that the distribution shown in Figure 14 is based on all HRVs certified by

the Home Ventilation Institute and is not adjusted to account for the number of units sold. As

such, the distribution of HRVs in use in North American homes may differ.

4.3 Airstream Cross-Leakage

The Canadian Standards Association (CSA) standard C439, Standard laboratory methods of test

for rating the performance of heat/energy-recovery ventilators (2010) requires cross-leakage

between the exhaust and supply airstreams be measured using a tracer gas. Although a particular

tracer gas is not specified, the standard states that the tracer gas injection rate must be sufficient

such that a cross-leakage of 0.1% is within the range of the measurement device being used.

Sherman (1990) identified five ideal characteristics of tracer gases for determining ventilation

rates: safety, non-reactivity, insensibility, uniqueness and measurability. While early researchers

experimented with many different tracer gases, sulfur hexafluoride (SF6) has become the most

popular choice in recent years. While SF6 exhibits the five ideal characteristics defined by

Sherman and functions well as a tracer gas, it also has an extremely high global warming

potential, causing many to question the ethics of its use in research and leading some

jurisdictions to control its availability. As the use of SF6 becomes increasingly problematic,

researchers are exploring more environmentally friendly tracer gases (Burke et al. 2014).

For the purposes of this study, airstream cross-leakage testing was performed using CO2 as a

tracer gas. The decision was made based on the accessibility of CO2 (in the form of dry ice) and

CO2 sensors. While CO2 is not unique, background concentrations in the test room were

considered stable enough that they would not have a significant impact on the test results. The

measurability of CO2 using the sensors available also presented a challenge, both in terms of

sensor noise and range, but these issues were managed as described in Section 4.3.3.

4.3.1 Test Set Up and Methodology

Three CO2 sensors were installed as shown in Figure 15. CO2 was produced by crushing dry ice

and placing it within a capture hood, through which Airstream A was circulated. Sublimation of

the dry ice quickly increased the CO2 concentration within Airstream A, which was recirculated

through the heat exchanger in a closed loop. The CO2 concentration in Airstream A was

measured on the inlet side of the heat exchanger (CO2 Sensor 1). At the same time, ambient air

23

was circulated through Airstream B, with CO2 concentrations being measured on the inlet side

(CO2 Sensor 2) and outlet side (CO2 Sensor 3) of the heat exchanger. The elevated concentration

of CO2 in Airstream A was allowed to decay slowly while Airstream B was monitored for an

increase in CO2 concentration. An increase in CO2 concentration in Airstream B is indicative of

air leakage between the two airstreams.

Figure 15. Dry ice and configuration of leakage testing using CO2

Roughly 1-2 g of crushed dry ice was used to increase the CO2 concentration in Airstream A.

Since CO2 concentrations were measured directly, an accurate measurement of the mass of dry

ice used was unnecessary. The CO2 sensors used had a range of 0-5000 ppm and an accuracy of

+/- 50 ppm or +/- 3% of reading. The sensors were calibrated prior to the test using their internal

calibration function with outdoor air as a reference, and were recalibrated relative to each other

based on the ambient CO2 concentration measured during the test. A high degree of absolute

accuracy was unnecessary, as the test methodology relied on the relative CO2 concentrations

between the two airstreams. Measurements were taken every 10 seconds and converted to

average concentrations per minute to reduce the inherent CO2 sensor noise.

4.3.2 Measurements

The cross-leakage test was conducted at three airflow rates: 6.9 L/s, 11.7 L/s and 20.6 m3/h. The

measured CO2 concentrations are shown in Figure 16. Airflows were balanced using differential

pressure measurements across the heat exchanger in both airflow directions. Airflow rate was

calculated from differential pressure using the system curve developed in Section 4.1.

24

a) 6.9 L/s b) 11.7 L/s c) 20.6 L/s

Figure 16. CO2 concentrations in Airstreams A and B

The mass of dry ice used and the relatively small volume of the closed duct system mean that the

CO2 concentration in Airstream A quickly surpassed the upper limit of the sensor’s range (5000

ppm or approximately 4500 ppm above the ambient CO2 concentration). In all three tests, the

CO2 concentration in Airstream B showed a small but discernible increase correlating with the

sharp increase in CO2 concentration in Airstream A, indicating cross-leakage between the two

airstreams. While this increase was most pronounced at Sensor 3, there was also an observable

increase in the CO2 concentration measured at Sensor 2, as shown in Figure 17.

a) 6.9 L/s b) 11.7 L/s c) 20.6 L/s

Figure 17. CO2 concentrations in Airstream B before and after heat exchanger

0

1000

2000

3000

4000

5000

0 20 40 60

CO

2C

on

c. (

pp

m a

bo

ve a

mb

ien

t)

Time (minutes)

0

1000

2000

3000

4000

5000

0 20 40 60

CO

2C

on

c. (

pp

m a

bo

ve a

mb

ien

t)

Time (minutes)

0

1000

2000

3000

4000

5000

0 20

CO

2C

on

c. (

pp

m a

bo

ve a

mb

ien

t)

Time (minutes)

0

50

100

150

200

250

0 20 40 60

CO

2C

on

cen

trat

ion

(pp

m a

bo

ve a

mb

ien

t)

Time (minutes)

0

50

100

150

200

250

0 20 40 60

CO

2C

on

cen

trat

ion

(pp

m a

bo

ve a

mb

ien

t)

Time (minutes)

0

50

100

150

200

250

0 20

CO

2C

on

cen

trat

ion

(pp

m a

bo

ve a

mb

ien

t)

Time (minutes)

25

Because Sensor 2 was located on the inlet side of the heat exchanger, the increase in CO2

concentration measured at this location is not a result of air leakage through the heat exchanger

itself. The most probable explanation is that air leakage occurred elsewhere in the enclosure

before Sensor 2, likely at the bases of the centrifugal fans which penetrate the surface dividing

Airstreams A and B. Although it is also possible that the ambient CO2 concentration in the test

room became elevated as a result of CO2 produced during the experiment, it is unlikely given the

large volume of the room and relatively small mass of CO2 used.

4.3.3 Estimating Cross-Leakage

Although leakage through the heat exchanger is most accurately represented by the increase in

CO2 concentration between Sensor 2 and Sensor 3, comparing CO2 concentration at Sensor 3 to

ambient levels provides an estimate of cross-leakage through the complete enclosure and heat

exchanger. The higher CO2 concentration at Sensor 3 also makes the trend easier to distinguish

against the background noise. For this reason, CO2 concentration in Airstream B was based on

the increase in CO2 concentration above ambient levels at Sensor 3.

Because the CO2 concentration in Airstream A is outside the sensor’s range during the period in

which there is an observable increase in CO2 concentration in Airstream B, the CO2

concentration in Airstream A must be estimated. This can be accomplished using Equation 2a

(adapted from ASHRAE 2013).

(2a)

where,

t time from the start of the test [min]

C(t) CO2 concentration above the ambient concentration at time t [ppm]

C0 CO2 concentration above the ambient concentration at time zero [ppm]

S CO2 source rate [ppm/min]

L CO2 loss rate [min-1

]

By assuming that the dry ice sublimates quickly enough to result in a net increase in CO2

concentration in Airstream A throughout the sublimation process, it follows that the peak CO2

concentration (Cpeak) in Airstream A coincides with the time at which sublimation is complete.

After the peak time (tpeak), the CO2 source rate, S, is zero, reducing Equation 2a to Equation 2b.

26

(2b)

Although the point of peak CO2 concentration for Airstream A is unknown because the

concentration is above the sensor’s upper limit, it corresponds with the point of peak CO2

concentration in Airstream B, which is within the sensor’s limits. The CO2 loss rate, L, can be

determined from the declining period of CO2 concentration (after the peak time), which is only

measurable once concentrations are below the sensor’s upper limit. The CO2 concentration in

Airstream A can then be estimated for the period after sublimation of the dry ice is complete and

before concentrations are within the range of Sensor 1. This process is illustrated in Figure 18 for

the test conducted at 11.7 L/s.

Figure 18. Process for estimating CO2 concentrations in Airstream A

Following the same process for the other two tested airflow rates, CO2 concentration in

Airstream A can be approximated and compared to CO2 concentrations in Airstream B to

estimate air leakage using Equation 3 (adapted from Canadian Standards Association 2010).

(3)

Using the estimated CO2 concentration in Airstream A and the measured CO2 concentration

Airstream B, the cross-leakage rate for the three tested airflows varied from 0.5% to 1.5%.

0

200

400

600

800

1000

1200

1400

1600

1800

2000

0

2000

4000

6000

8000

10000

12000

14000

16000

18000

20000

0 10 20 30 40 50

CO

2C

on

c. -

Air

stre

am B

(p

pm

ab

ove

am

bie

nt)

CO

2C

on

c. -

Air

stre

am A

(p

pm

ab

ove

am

bie

nt)

Time (minutes)

Airstream A (Sensor 1)

Airstream A (estimated)

Airstream B (Sensor 3)

tpeak = 11 miny = -0.1403x + 9.8123

R² = 0.9954

L = 0.1403 min-1

Cpeak = e9.8123 = 18256 ppm

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10 20 30 40 50

ln (C

O2

con

cen

trat

ion

)

t - tpeak (minutes)

27

4.3.4 Limitations

The results obtained for air leakage between the two airstream are estimates, limited by the noise

and range of the CO2 sensors. In addition, Equations 2a and 2b assume uniform CO2

concentration within each airstream, which may not be true, particularly if air leakage through

the heat exchanger is localized. More accurate measurements could be obtained by using a

combination of tracer gas and multiple sensors with increased sensitivity and range. While

estimates, these preliminary results do indicate that the fine wire heat exchanger and enclosure

are relatively air tight, and that cross contamination of the two airstreams is unlikely to have a

significant impact on energy efficiency or indoor air quality. It can also be concluded that air

leakage between the two airstreams is not a major factor affecting heat recovery efficiency.

4.4 Sensible Heat Recovery Efficiency

In cold climates, the main benefit of installing a more expensive balanced HRV system over a

lower cost exhaust-only ventilation system is the capacity to recover heat and reduce the

ventilation heating load. It follows that the heat recovery efficiency of an HRV is an important

parameter in assessing its overall value and is often the first performance characteristic

considered when selecting an HRV.

4.4.1 Measurement Standards

There are a number of ways of measuring sensible heat recovery efficiency. The compact design

of most HRVs requires that temperatures be measured at the main inlet and outlet ducts, with the

fans located between the points of measurement. As a result, heat generated by the fans increases

measured temperatures, often inflating the apparent efficiency. Most reputable measurement

standards correct for heat generated by fans and other factors which may distort the results.

The North America-based Heating Ventilation Institute publishes results based on CSA C439,

Standard laboratory methods of test for rating the performance of heat/energy-recovery

ventilators (2010). Sensible heat recovery efficiency is calculated using Equation 4.

(4)

28

where,

n total number of measurements

i ith

time that data are recorded

Ms net mass flow rate of the supply air, after accounting for cross-leakage [kg/s]

Cp specific heat of the air [kJ/kg°C]

t5 net temperature at the supply air outlet, after correcting for cross-leakage [°C]

t1 dry-bulb temperature of supply air inlet [°C]

t3 dry-bulb temperature of exhaust air inlet [°C]

Δϴ time between flow measurements [s]

QSF energy input into supply airstream attributed to fan(s) [kJ]

QSH energy used by heater and compressor in supply airstream [kJ]

QC casing heat transfer [kJ]

QD energy used for defrost [kJ]

QL heat loss due to casing leakage [kJ]

Mmax greater of the net mass flow rate of the exhaust and supply air [kg/s]

QEF energy input into exhaust airstream attributed to fan(s) [kJ]

QEH energy used by heater in exhaust airstream [kJ]

CSA C439 also defines an additional parameter called apparent sensible effectiveness, which

does not correct for fan heat or cross-leakage. As a result, it is typically higher than the sensible

heat recovery efficiency, particularly for HRVs with inefficient fans. Although of less technical

relevance than sensible heat recovery efficiency, apparent sensible effectiveness may be quoted

by manufacturers to increase the perceived performance of their product.

The German-based Passive House Institute has also developed a standard for calculating sensible

heat recovery efficiency, using Equation 5 (Passivhaus Institut 2009).

(5)

where,

Pel exhaust air fan electrical power [W]

ṁ mass flow rate of the exhaust air [kg/s]

Cp specific heat of the air [kJ/kg°C]

t1 dry-bulb temperature of supply air inlet [°C]

t3 dry-bulb temperature of exhaust air inlet [°C]

t4 dry-bulb temperature of exhaust air outlet [°C]

Equation 5 assumes balanced flow rates and negligeable air leakage. The correction factor for

fan energy also makes the assumption that the supply air fan is located on the outlet side of the

heat exchanger, as shown in Figure 19. Equation 5 will slightly under calculate sensible heat

recovery efficiency if the supply air fan is located on the inlet side of the heat exchanger.

29

Figure 19. Location of temperature measurements in standard test procedures

4.4.2 Test Set Up and Methodology

The sensible heat recovery efficiency of the fine wire HRV was measured in an indoor

laboratory using the setup illustrated in Figure 20. A calibrated axial fan was used to generate the

supply airflow, while a variable speed centrifugal fan was used to generate the exhaust airflow.

Static pressures were measured on the inlet and outlet sides of the heat exchanger in both

airstreams, at the same locations used to generate the system curve in Section 4.1. Temperature

measurements were taken at 10 second intervals with sets of three Type T thermocouples

(resolution 0.1 °C) located at each inlet and outlet.

Indoor air at approximately 21 °C was used for the supply airstream. Two 200 W incandescent

light bulbs connected to a dimmer switch were used to heat the exhaust airstream, creating a

temperature difference of 10-20 °C between the two inlets. The measurements described in

Section 4.1 indicate that pressure drop across the two sides of heat exchanger is approximately

equal for a given airflow rate. Based on this observation, airflow rates were balanced by

equalizing the pressure drop across the heat exchanger and airflow rate was recorded using the

calibrated axial fan located at the supply air inlet.

Indoors

Exhaust Inlet

t1

t2 (t5)

t3

t4

Outdoors

Exhaust Outlet

Supply Inlet

Supply Outlet

30

(a) Test setup and airflows (b) Location of thermocouples

Figure 20. Heat recovery efficiency test setup and location of thermocouples

Since it was possible to take temperature measurements between the heat exchanger and the fans,

it was not necessary to correct for waste heat. Cross-leakage was assumed negligible based on

the tracer gas measurements described in Section 4.3. Heat transfer through the HRV enclosure

was also assumed to have a negligible effect given the close proximity of the temperature

measurements to the heat exchanger, as well as the low temperature differences between the

airstreams and the ambient air in the laboratory. Under these conditions Equation 4 from CSA

C439 and Equation 5 from the Passive House Institute can be reduced to just the temperature

variables. The numerator is different in the two equations, with Equation 4 using the increase in

temperature of the supply airstream and Equation 5 using the decrease in temperature of the

exhaust airstream. If airflows are balanced, the reduced forms of the two equations give the same

result. To achieve the most reliable results and account for any airflow imbalances during testing,

the increase in temperature of the supply airstream and decrease in temperature of the exhaust

airstream were averaged using Equation 6 (proposed by the author based on Equations 4 & 5).

(6)

where,

t1 average dry-bulb temperature of supply air inlet [°C]

t2 average dry-bulb temperature of supply air outlet [°C]

t3 average dry-bulb temperature of exhaust air inlet [°C]

t4 average dry-bulb temperature of exhaust air outlet [°C]

Cardboard Warming Hood

Calibrated Axial FanCentrifugal Fan

Exhaust Inlet Supply Inlet

Supply Outlet Exhaust Outlet

Heat exchanger and manifold

Supply InletExhaust Inlet

Supply Outlet

Exhaust Outlet

t1t3

Thermocouples

t4t2

31

4.4.3 Results

A series of nine tests was conducted to measure the sensible heat recovery efficiency of the fine

wire HRV at airflow rates ranging from 5.7 L/s to 26.4 L/s. The heat output at the exhaust inlet

was increased with increasing flow rate to maintain a temperature rise of 10-20 °C over the

supply inlet. Temperatures were averaged over a 5-10 min period after they had stabilized. The

results for airflow rates of 9.7 L/s and 18.4 L/s are shown in Figure 21. The complete set of

temperature measurements can be found in Appendix B.

(a) Airflow rate of 9.7 L/s (b) Airflow rate of 18.4 L/s

Figure 21. Temperature measurements at two airflow rates

The temperature measurements consistently show a larger decrease in temperature of the exhaust

airstream than increase in temperature of the supply airstream. The difference is greatest at low

airflow rates and gradually decreases with increasing airflow rate. It is unknown exactly why this

difference occurred. The measurements described in Section 4.3 indicate that cross-leakage is

unlikely to be a significant factor. Temperature measurements were taken with sets of three

thermocouples at each location. The difference between thermocouple readings does not suggest

significant variation across the airstream section or malfunctioning sensors.

Despite the measurements described in Section 4.1 which indicate very similar system curves for

both sides of the heat exchanger, it is possible that the geometry of the exhaust side creates a

higher pressure drop, resulting in a slightly lower exhaust airflow rate. Air density may also be a

factor, as the exhaust airstream is warmer and less dense, resulting in a slightly lower mass flow

20

22

24

26

28

30

32

34

36

38

40

0 100 200 300 400

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t3

t2

t4

t1

ExhaustΔt = 15.1 °C

SupplyΔt = 12.1 °C

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250 300

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t3

t2

t4

t1

ExhaustΔt = 11.2 °C

SupplyΔt = 9.8 °C

32

rate at equal volume flow rates. Based on conservation of energy, unequal mass flow rates would

result in different temperature changes for the two airstreams.

Another possibility is that heat transfer through the enclosure is causing a reduction in airstream

temperature as it travels between the heat exchanger and the thermocouples. Since the exhaust

outlet and supply inlet airstreams are roughly the same temperature as the ambient air, any heat

transfer through the enclosure at these locations should be negligible. In contrast, both the

exhaust inlet and supply outlet airstreams are 10-20 °C warmer than the ambient air and

significant heat loss through the enclosure is possible, as shown in Figure 22.

Figure 22. Effect of heat loss through the HRV enclosure

Assuming a surface film conductance of 8 W/m2/K for the exterior of the enclosure, and

negligible thermal resistance for the interior surface film (high air velocity) and enclosure itself,

as much as 22 W of heat could be lost from each of the exhaust inlet and supply outlet

airstreams. At an airflow rate of 9.7 L/s this heat loss could result in a 2 °C change in

temperature in each airstream, which is sufficient to explain the discrepancy shown in Figure

21a. It would also explain why the magnitude of the discrepancy decreases with increasing

airflow rate, as the same rate of heat loss is being distributed over a larger volume of air.

Supply InletExhaust Inlet

Supply Outlet

Exhaust Outlet

t1t3

Thermocouples

t4t2

Small Δt between airstreams and ambient air results in negligible

heat loss

Large Δt between airstreams and ambient air results in significant

heat loss

33

A preliminary attempt to test this theory was made by thermally insulating the enclosure and

repeating the test, but a difference in temperature changes of the two airstreams was still

observed. As the test was done in haste and without careful documentation, the results are

considered inconclusive. Future testing should be done using an insulated enclosure to minimize

heat transfer.

The potential for bias introduced by unbalanced mass flow rates is addressed by using Equation

6 to average the decrease in temperature of the exhaust airstream with the increase in

temperature of the supply airstream. This approach also addresses the issue of heat loss through

the enclosure, assuming that the heat lost in the exhaust inlet and supply outlet airstreams is

approximately equal. More reliable results could be obtained by using two calibrated fans to

more accurately balance airflow rates and by better insulating the HRV enclosure during testing

to reduce heat loss. The resulting sensible heat recovery efficiencies are shown in Figure 23.

Figure 23. Sensible heat recovery efficiency test results

A maximum sensible heat recovery efficiency of 82% was achieved at airflow rates of 7-10 L/s.

Efficiency declined linearly at higher airflow rates, with each 2 L/s increase in airflow resulting

in a 1% reduction in sensible heat recovery efficiency.

0.0 0.1 0.2 0.3 0.4 0.5 0.6

70%

75%

80%

85%

90%

0.0 5.0 10.0 15.0 20.0 25.0 30.0

Average Surface Air Velocity (m/s)

Sen

sib

le H

eat

Re

cove

ry E

ffic

ien

cy

Airflow Rate (L/s)

34

The maximum sensible heat recovery efficiency of the fine wire HRV was compared to

conventional HRVs listed in the Home Ventilation Institute Certified Products Directory (2014).

Where the directory provides performance data at multiple flow rates, the highest value was

used. The mean sensible heat recovery efficiency of the conventional HRVs is 68%. Only 2.5%

of conventional HRVs have higher sensible efficiencies than the fine wire HRV. The distribution

is shown in Figure 24.

Figure 24. Distribution of sensible heat recovery efficiencies of HRVs

The distribution shown in Figure 24 is based on all HRVs certified by the Home Ventilation

Institute and is not adjusted to account for the number of units sold. As such, the distribution of

HRVs in use in North American homes may differ.

5 Preliminary CFD Model

As part of this study of the fine wire heat exchanger, a preliminary investigation using

computational fluid dynamics (CFD) modeling was started. CFD uses equations of fluid

dynamics in combination with numerical methods to predict fluid flows. OpenFOAM, an open-

source CFD modeling software, was used to model a single copper wire extending between two

adjacent airstreams, as shown in Figure 25. The model space was divided into a mesh, with

increasing numbers of mesh elements at the intersection of the different materials.

0%

10%

20%

30%

40%

55% 60% 65% 70% 75% 80% 85% 90% 95%

Pe

rce

nt

of

Co

nve

nti

on

al H

RV

Un

its

Maximum Sensible Heat Recovery Efficiency

Fine Wire HRV82%

Source: Home Ventilation Institute 2014

35

(a) Geometry used in model (b) Section showing temperatures and velocities

Figure 25. Initial CFD modeling results

A solver was selected which could calculate both turbulent flow of incompressible fluids, as well

as heat transfer between solid and fluid regions. In this way it was possible to model heat transfer

from one airstream to another via the copper wire. Had more time been available, the next step

would be to expand the model to include a full cross-section of 28 copper wires. This would

allow for parametric modeling to analyze the effect of different numbers, sizes and spacings of

copper wires on pressure drop and heat recovery efficiency of the heat exchanger.

CFD would also be a valuable tool for better understanding airflow through the heat exchanger

manifold. From the shape of the manifold, it seems that air velocities through the heat exchanger

are likely to be higher at the centre, and lower near the top and bottom. Since testing has revealed

different sensible heat recovery efficiencies at different total airflow rates, it seems likely that the

distribution of air velocities through the heat exchanger would influence its performance. CFD

could be used to analyze this effect in more detail.

Due to the many variables which can greatly influence the results of a CFD model, reliability can

only be achieved when physical measurements are used to calibrate and validate the model. One

challenge encountered in the early stages of CFD modeling of the fine wire heat exchanger was

the scale. With airstream channels of little more than 10 mm in width, it was difficult to

accurately measure air velocities using a standard hot-wire anemometer. It was also difficult to

locate the thermocouples in a specific location, as the size of the thermocouples was substantial

in comparison to the width of the channels. These challenges will need to be addressed in any

future modeling efforts.

Copper wire

Separating layer

36

6 Whole-Building Model

To evaluate the potential for whole-building energy savings, a model of ventilation energy usage

and indoor air quality was developed and used to test a variable ventilation strategy. The model

was based on a new energy-efficient three-bedroom home in Toronto. The variable ventilation

strategy consisted of four fine wire HRVs operating at adjustable ventilation rates in each zone

of the home, utilizing demand controlled ventilation principles. A conventional HRV operating

at a constant ventilation rate in the same home was also modeled for comparison purposes.

6.1 Indoor Air Quality Metrics

In proposing an alternative ventilation strategy, it is important to understand the impact on

indoor air quality. This was done by using a transient mass balance model to track concentrations

of three important residential pollutants: fine particulate matter less than 2.5 μm in aerodynamic

diameter (PM2.5), formaldehyde (HCHO), and ozone (O3). Based on research by Logue et al.

(2012), these three pollutants are among the six most costly, in terms of daily adjusted life years

(DALYs) lost, due to chronic inhalation in US residences. The three pollutants were chosen

based on their widespread presence in almost all homes and because sufficient measurement data

exists to model their behavior in a residential environment. They also present a balanced

combination of sources including predominately indoor (HCHO), predominately outdoor (O3),

and both indoor and outdoor (PM2.5). Other pollutants which top the list produced by Logue et

al., such as secondhand smoke and radon, also have considerable societal health costs but are

best approached by controlling the pollutant source, rather than through ventilation.

6.1.1 Fine Particulate Matter (PM2.5)

A number of studies have linked PM2.5 with adverse health effects. Dominici et al. (2006)

studied hospital emission rates and ambient PM2.5 levels in 204 urban communities throughout

the US and found statistically significant effects for many respiratory and cardiovascular

diseases. The greatest association was found for heart failure, which increased in risk by 1.28%

for every 10 μg/m3 increase in ambient PM2.5 levels. Franklin et al. (2007) studied the link

between ambient PM2.5 and reported deaths in 27 US communities, and found a 1.78% increase

in respiratory related mortality and a 1.03% increase in stroke related mortality for every 10

μg/m3 increase. There is no recognized threshold below which PM2.5 levels do not have health

37

effects and Health Canada (2014) recommends reducing concentrations as much as possible.

Outdoor PM2.5, which is generated by combustion (largely from electricity generation and

transportation), can be a significant source of indoor PM2.5. PM2.5 can also be generated indoors

directly by combustion activities such as smoking or cooking, by re-suspension of settled

particles and by reactions between other components of indoor air (Health Canada 2014).

6.1.2 Formaldehyde (HCHO)

HCHO is a volatile organic compound which has respiratory and allergic health effects and may

contribute to the development of asthma. Research of 148 children in 80 Australian houses by

Garrett et al. (1999) found a relationship between HCHO in homes and incidences of atopy, as

well as the severity of allergy symptoms. Other studies have found increases in nose, throat and

eye irritation with increasing indoor HCHO levels (Health Canada 2005). While there is

evidence that HCHO may cause cancer in the nasal cavity, these effects have only been observed

at concentrations higher than those found in most residential environments (Health Canada

2014). Health Canada (2014) sets a residential short-term (1 hr) HCHO exposure limit of 123

µg/m3 and a long-term (8 hr) exposure limit of 50 µg/m

3. In non-smoking households, the main

source of HCHO is off-gassing of formaldehyde-containing building materials and furnishing

such as particle board, paint and carpeting (Health Canada 2014). HCHO may also be produced

by reactions of other volatile organic compounds with O3 (Weschler et al. 1992).

6.1.3 Ozone (O3)

Ambient O3 has been linked to respiratory and cardiovascular health effects, including

exacerbation of asthma (Stephens et al. 2012). Controlled human exposure studies have shown

prolonged exposure to O3 at concentrations as low as 240 µg/m3 results in decreased lung

function and subjective respiratory symptoms (Health Canada 2014). O3 can also react with

substances in the indoor environment to generate volatile organic compounds, including HCHO,

ultrafine particles and other pollutants which further contribute to adverse health effects

(Weschler et al. 1992, Zhao et al. 2007). Health Canada (2014) sets a residential long-term (8 hr)

O3 exposure limit of 40 µg/m3. The main source of indoor O3 is from photochemical reactions

outdoors. People spend up to 90% of their time indoors, and a large portion of overall exposure

occurs within residences (Lee et al. 1999). Indoor sources of ozone were not considered in the

model as they are relatively rare in a residential environment.

38

6.2 Methodology: Energy Use

The study home was modeled with a floor area of 186 m2 based on the average single-family

detached house reported in a survey by the Canadian Home Builders’ Association (2013). The

house was assumed to have a ceiling height of 2.5 m and a volume of 465 m3. A whole-house

infiltration rate was chosen based on CONTAM software modeling of annual infiltration rates

for US houses conducted by Persily et al. (2010). The results of the study indicate a typical

infiltration air change rate of 0.09 hr-1

for the tightest 10% of single-family detached houses built

in 1990 or later. This value was used in the model and assumed to be a reasonable approximation

of infiltration rates for energy efficient housing constructed in Canada today.

The energy consumption of a conventional HRV operating at a constant ventilation rate was

compared to four fine wire HRVs operating at variable ventilation rates. The conventional HRV

model was based on a single ventilation zone. The sensible heat recovery efficiency and fan

electricity consumption were obtained from the Home Ventilation Institute Certified Products

Directory (2014). Values were averaged over models with net supply airflow rates between 30

L/s and 60 L/s (80 models). Where the directory provided multiple values at different airflow

rates for the same model, the values at airflow rates closest to 30 L/s were used. The mean

sensible heat recovery efficiency and fan electricity consumption of the sample were 61% and

1.99 W per L/s, respectively.

The fine wire HRV model was split into four ventilation zones: the main living space zone,

including an open concept kitchen and living room, and three separate bedroom zones. The main

living zone occupied half the total floor area and was ventilated by two fine wire HRVs. The

bedrooms each occupied a sixth of the floor area and were ventilated with a single fine wire

HRV. To maximize the benefits of decentralized ventilation and to simplify the model, it was

assumed that the partitions between zones were airtight and that bedroom doors were kept

closed, making air movement between the zones negligible. The infiltration rate was assumed to

be the same in each zone.

The heat recovery efficiency and fan electricity consumption of the fine wire HRV were based

on the measurements described in Section 4. In order to model variable airflow rates, linear

regressions with the measured data points were used to create equations relating airflow rate to

sensible heat recovery efficiency and fan electricity consumption. At the minimum airflow rate

39

of 15 L/s, a sensible heat recovery efficiency of 80% and a fan electricity consumption of 1.14 W

per L/s were used for the fine wire heat exchanger. For those periods when a lower ventilation

rate was desired, the unit was assumed to operate intermittently at the minimum airflow rate.

Fan electricity consumption was not adjusted to account for filters as data for conventional

HRVs is not published in the Home Ventilation Institute Certified Products Directory. Studies

have also shown that the energy cost of more efficient filters in residential and light-commercial

HVAC systems to be negligible (Stephens et al. 2010). The contribution of fan electricity to the

heating load was not considered. Although separate bathroom and kitchen exhaust ventilation is

recommended, they were assumed to operate intermittently and to contribute little to the overall

ventilation rate.

The impact of sensible heat recovery efficiency on annual ventilation heating load was assessed

using Equation 7 (adapted from ASHRAE 2013).

(7)

where,

Heat Loss is the annual heat loss due to mechanical ventilation [kJ]

q is the annual average ventilation rate [m3/day]

cP is the specific heat capacity of air [1.005 kJ/kg.°C]

ρ is the density of air [1.3 kg/m3]

HDD is the annual number of heating degree days [3734 °C.days]

η is the annual average sensible heat recovery efficiency

A value of 3734 heating degree days (HDD) per year was used, based on the October to May

degree days below 18 °C for Toronto Pearson International Airport measured from 1981 to 2010

(Environment Canada 2014). The impact of ventilation on energy for cooling was not considered

as the fine wire HRV is only capable of recovering sensible heat and is not well suited to

cooling-dominated climates.

6.3 Methodology: Indoor Air Quality

Indoor air quality was determined using a transient mass balance air pollutant model which

tracked concentrations of PM2.5, HCHO and O3. Pollutant concentrations were modeled at 5-

minute intervals over a 24-hour period using Equation 8 (adapted from ASHRAE 2013).

40

(8)

where,

C(t) is the pollutant concentration at the end of the time interval [μg/m3]

Co is the pollutant concentration at the beginning of the time interval [μg/m3]

t is the length of the time interval [hr]

L is the average pollutant loss rate over the time interval [hr-1

]

S is the average pollutant source rate over the time interval [μg/m3/hr]

The pollutant loss rate and source rate were calculated using Equation 9a and Equation 9b,

respectively (adapted from ASHRAE 2013).

(9a)

(9b)

where,

λinf is the infiltration rate [hr-1

]

λmech is the mechanical ventilation rate [hr-1

]

β is the pollutant deposition loss rate [hr-1

]

E is the indoor pollutant emission rate [μg/m3/hr]

Cout is the outdoor pollutant concentration [μg/m3]

P is the pollutant penetration factor

η is the filter efficiency

Parameter estimates were obtained from the literature and are discussed further in the following

sections. Except for the mechanical ventilation rate, the same parameter values were used in both

the conventional and variable ventilation models. The values are summarized in Table 1.

Table 1. Mass balance model parameter values

Parameter PM2.5 HCHO O3

Cout, Outdoor Concentration [μg/m3] 8.3 0 26.2

E, Indoor Emission Rate [μg/m3/hr] 10.3 18.2 0

β, Deposition Loss Rate [hr-1

]

With ventilation on 0.42 0 5.6

With ventilation off 0.21 0 2.8

P, Penetration Factor 0.72 NA 0.79

η, Filter Efficiency 19% NA 10%

The model assumes that each zone is completely mixed, and that there is no mixing between

zones. The model also assumes that all indoor sources are accounted for in the indoor emission

rates and that the deposition loss rates account for chemical reactions between pollutants.

41

6.3.1 Fine Particulate Matter (PM2.5)

Outdoor concentrations of PM2.5 were based on ambient measurements taken in downtown

Toronto by the Ontario Ministry of Environment and Climate Change (2014). A typical outdoor

level of 8.3 μg/m3 was used in the model based on the 2013 annual mean concentration.

Indoor source emission, deposition loss and penetration rates used for PM2.5 were based on the

research conducted by Williams et al. (2003). The study measured PM2.5 in 37 North Carolina

residences over a one-year period. Based on the indoor-generated PM2.5 concentrations,

deposition loss rates and air exchange rates measured in the study, an indoor source emission rate

of 10.3 μg/m3/hr was used in the model. The study found a penetration rate of 0.72, which agreed

well with the summer rate of 1.11 and winter rate of 0.54 measured by Long et al. (2001). A

PM2.5 penetration rate of 0.72 was used in the model.

The study by Williams et al. also found a mean deposition loss rate of 0.42 hr-1

. Of the

residences in the sample, 70.2% had central forced air mechanical systems and only reported

using natural ventilation 23% of the time. As a result, the PM2.5 deposition loss rate measured by

Williams et al. was used for periods when the HVAC system was running. Emmerich and

Nabinger (2001) found that deposition loss rates for PM2.5 were approximately halved when

ventilation systems were not running, and so a PM2.5 deposition loss rate of 0.21 hr-1

was used

for those periods. While other studies (eg. Long et al.) have found lower deposition loss rates for

PM2.5, they generally included fewer residences and shorter study periods. A standard filter

efficiency of 19% was used in the model, based on the value used by Riley et al. (2002) for

loaded residential furnace filters.

6.3.2 Formaldehyde (HCHO)

An indoor source emission rate of 18.2 μg/m3/hr was assumed for HCHO based on the mean

value of 14 US houses analyzed by Sherman and Hodgson (2004). This emission rate was

calculated from a steady-state mass balance as the product of the air exchange rate and indoor

minus outdoor concentration. As such, the emission rate reflects the net generation of HCHO

after accounting for emissions and deposition losses and an additional deposition loss rate was

not included in the model.

42

Following Sherman and Hodgson, a number of simplifying assumptions were made in modeling

HCHO concentrations. The emission rate was assumed to be independent of concentration,

which may over-predict HCHO levels at high concentrations as emissions tend to be lower under

these conditions. This assumption is necessary as the relationship between HCHO emission rate

and concentration varies by source and is not easily modeled. This assumption is also

conservative in the sense that it over-predicts the buildup of HCHO when the ventilation rate is

reduced, underestimating the benefits of a variable ventilation rate. As outdoor concentrations of

HCHO are generally much lower than indoor concentrations, they were assumed to be

negligible. This assumption eliminates the need for an HCHO penetration factor or filter removal

efficiency.

6.3.3 Ozone (O3)

Outdoor concentrations of O3 were based on ambient measurements taken in downtown Toronto

by the Ontario Ministry of Environment and Climate Change. A typical outdoor level of 26.2

μg/m3 was used in the model based on the 2013 annual mean concentration. While some indoor

sources of O3 do exist such as air cleaners and photocopiers, they are uncommon in residential

settings and were not considered in the model. Therefore, a negligible O3 indoor source emission

rate was assumed.

Lee et al. measured O3 deposition loss rates in 43 Southern California homes and recorded a

mean value of 2.8 hr-1

. Nearly all of the homes included in the study were single family detached

houses without central forced air mechanical systems. Stephens et al. and Mueller et al. (1973)

measured O3 deposition loss rates two to four times larger than those measured by Lee et al., but

conducted the measurements while fans were operating which provided mixing and increased

mass transfer. This variation agrees well with measurements conducted by Sabersky et al. (1973)

showing residential O3 deposition loss rates approximately doubled with internal air circulation.

Values of 5.6 hr-1

and 2.8 hr-1

were used in the model for periods with and without ventilation

running, respectively. An O3 penetration rate of 0.72 was used in the model, based on

measurements of eight homes by Stephens et al. Zhao et al. (2007) measured O3 filter removal

efficiencies for eight residential filters and obtained a mean value of 10%, which was used in the

model.

43

6.4 Analysis

6.4.1 Constant Ventilation Rate

In order to evaluate the benefits of the variable ventilation strategy, indoor air quality was

modeled at a constant ventilation rate. The constant ventilation rate was first calculated based on

ANSI/ASHRAE Standard 62.2-2013. Based on a floor area of 186 m2 and three bedrooms, the

design ventilation rate, including infiltration, was 42 L/s (0.32 hr-1

). The standard allows for up

to two thirds of the total ventilation rate to be made up of infiltration. Since an infiltration rate of

5.8 L/s (0.09 hr-1

) was used in the model, the design mechanical ventilation rate was reduced to

30 L/s (0.23 hr-1

).

The concentrations of the three pollutants resulting from the ANSI/ASHRAE 62.2-2013

ventilation rate are shown in Table 2. As this rate, HCHO concentrations exceed the Health

Canada guideline by 12%. To allow the Health Canada guidelines to be used as a minimum

requirement for both the variable and constant ventilation models, the constant ventilation rate

was increased by 17% to 35.3 L/s (0.27 hr-1

). This adjustment brought the steady-state HCHO

concentrations to the Health Canada guideline level of 50 μg/m3.

Table 2. Pollutant concentrations at constant ventilation rates

Constant Ventilation Rate Steady-State Concentration [μg/m

3]

PM2.5 HCHO O3

30.3 L/s (0.23 hr-1

) [ASHRAE 62.2] 17 56 1.2

35.3 L/s (0.27 hr-1

) 16 50 0.7

Health Canada Guideline - 50 40

The low steady-state concentrations of O3 relative to the Health Canada guideline suggest that it

does not have a significant impact on indoor air quality, at least for typical residences located in

Toronto. As a result, HCHO and PM2.5 will be the primary indoor air quality outputs used to

compare ventilation models.

6.4.2 Variable Ventilation Strategy

While the fine wire HRV requires less fan electrical energy and recovers more thermal energy

than most conventional HRVs, further energy savings can be achieved by taking advantage of

DCV in different zones. Based on this assertion, a ventilation control strategy was developed that

44

maximizes energy savings while maintaining pollutant concentrations within the guideline levels

established by Health Canada. As outdoor O3 concentrations in Toronto are too low to pose

indoor air quality concerns, and Health Canada does not publish specific limits for PM2.5, the

variable ventilation strategy focused on maintaining acceptable levels of HCHO. Although not

analyzed in this study, CO2 may also function as a practical basis for designing a DCV strategy.

As reviewed in Section 2.2, there are a number of technologies available for detecting

occupancy. While these technologies currently vary in their reliability, they are expected to

continue to improve over time. For the purposes of this simplified model it is assumed that

occupancy can be accurately detected in each of the four zones. When zones are unoccupied,

maximum energy savings can be achieved by turning off mechanical ventilation. This results in a

buildup of indoor-generated pollutants. In order to meet the Health Canada guidelines,

ventilation must then be increased when the zone is re-occupied. Increased ventilation is most

effective immediately after the zone is re-occupied, as pollutant concentrations are higher. Once

the initial buildup of pollutants has been removed, the constant mechanical ventilation rate

calculated in Section 6.4.1 can be restored. This process is illustrated in Figure 26.

Figure 26. Variable ventilation strategy

The Health Canada short-term guideline recommends one-hour HCHO concentrations be kept

below 123 μg/m3. Since Health Canada does not publish guidelines for exposures shorter than

one hour, an overall maximum HCHO limit of 123 μg/m3 was used, which corresponds to just

over seven hours without mechanical ventilation in the modeled home. After these first seven

45

hours, the minimum mechanical ventilation rate required to keep HCHO concentrations below

123 μg/m3 indefinitely is 0.06 hr

-1. To keep HCHO concentrations from exceeding 123 μg/m

3,

this reduced mechanical ventilation rate of 0.06 hr-1

is recommended after the first seven

unoccupied hours. To simplify operation, the reduced mechanical ventilation rate of 0.06 hr-1

could be applied from the start of the unoccupied period, but would result in slightly lower

energy savings.

To meet the Health Canada long-term guideline, the average concentration of HCHO measured

over the first eight hours after the zone is reoccupied must be below 50 μg/m3. The duration of

increased ventilation required to meet this targets depends on the length of the preceding

unoccupied period as well as the increased ventilation rate. Although heat recovery and fan

efficiency of the fine wire HRV are lower at higher flow rates, more pollutant can be removed

for each unit of ventilation air when concentrations are higher. The result is greater overall

pollutant removal efficiency at higher ventilation rates immediately after the space is reoccupied.

The ventilation rate during this period is limited by the airflow capacity of the fans, the ability of

the space heating system to meet the additional ventilation load and comfort of occupants

exposed to higher air velocities and resulting noise. Further modeling and experimentation is

required to develop an increased ventilation rate that optimizes all these factors. For modeling

purposes, the increased ventilation rate immediately after the zone is reoccupied was arbitrarily

set to 0.82 hr-1

, three times the constant ventilation rate. Based on this ventilation rate, the

required duration of increased ventilation can be determined, as shown in Figure 27.

Figure 27. Required duration of increased mechanical ventilation

0.0

0.5

1.0

1.5

2.0

2.5

0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0

Re

qu

ire

d D

ura

tio

n o

f In

cre

ase

d

Me

chan

ical

Ve

nti

lati

on

(h

ou

rs)

Duration of Unoccupied Period (hours)

2 hours increased ventilation required for unoccupied

periods greater than 7 hours

46

For unoccupied periods of less than 60 minutes, the increased mechanical ventilation must run

for 40-45% of the time that the space was unoccupied. This ratio decreases with increasingly

long unoccupied periods, resulting in greater energy savings. Because HCHO concentration

buildup is capped at 123 μg/m3 in the unoccupied period, a maximum of two hours of increased

ventilation is required, even for extended unoccupied periods.

6.4.3 Occupancy Schedules

The impact of the decentralized ventilation strategy on annual energy usage is difficult to

quantify without knowing the occupancy pattern of each zone. Without developing a detailed set

of statistically representative residential occupancy scenarios, a conservative estimate of energy

savings can be made by identifying those periods which are likely to be unoccupied for most

homes, most days of the year.

The main living zone was assumed to be occupied from 7AM to 9AM and 6PM to 11PM,

Monday to Friday, and from 7AM to 11PM Saturday and Sunday. The bedrooms were assumed

to be occupied from 9PM to 8AM every day of the week. The schedules are illustrated in Figure

28. The ventilation rate in each zone was modeled based on these schedules and the control

strategy described in Section 6.4.2. The resulting concentrations of PM2.5, HCHO and O3 are

shown in Figure 29 and Figure 30.

Figure 28. Occupancy schedules

Main Living Zone

Bedroom Zones

Occupied

Unoccupied

Main Living Zone

Bedroom Zones

(b) Weekends

(a) Weekdays

4 PM 6 PM 8 PM 10 PM 12 AM

12 AM

12 AM 2 AM 4 AM 6 AM 8 AM 10 AM 12 PM 2 PM

12 PM 2 PM 4 PM 6 PM 8 PM 10 PM12 AM 2 AM 4 AM 6 AM 8 AM 10 AM

47

Fig

ure

29. L

ivin

g r

oom

poll

uta

nt

con

cen

trati

on

s re

sult

ing f

rom

occu

pan

cy s

ched

ule

s

48

Figure 30. Bedroom pollutant concentrations resulting from occupancy schedules

6.5 Results

6.5.1 Energy Consumption

The ventilation heating load and fan electricity consumption were calculated for each ventilation

schedule developed in Section 6.4.3. The results were time- and area-weighted to calculate

whole-house annual energy use for the variable ventilation strategy. For comparison purposes,

the whole-house ventilation heating load and fan electricity consumption was also modeled as a

base case at the constant ventilation rate of 35.3 L/s (0.27 hr-1

). Both heat exchanger technologies

were modeled at the constant ventilation rate to identify the energy savings associated with the

increased sensible heat recovery efficiency and reduced fan electricity consumption of the fine

wire HRV. The results for the three ventilation strategies are shown in Figure 31.

49

(a) Ventilation heat loss (b) Fan electricity consumption

Figure 31. Energy use of constant and variable ventilation strategies

Based on the constant ventilation rate of 35.3 L/s (0.27 hr-1

), the fine wire HRV reduces the

ventilation heat loss and fan electricity consumption by 45% and 43%, respectively.

Implementing the variable ventilation rate strategy described in Section 6.4.3 results in additional

energy savings, reducing both ventilation heat loss and fan electricity consumption by 61% as

compared to a typical conventional HRV operating at the constant ventilation rate.

Di Placido et al. (2014) modeled energy use of a Toronto home built to the R-2000 standard

which is representative of new energy-efficient home construction in Canada. The modeling by

Di Placido et al. indicates an annual space heating intensity of 72 MJ/m2, with 28% of the

heating load coming from ventilation. This is about 30% lower than the ventilation heating load

calculated in this study for a conventional HRV operating at constant ventilation rate. Part of this

discrepancy can be explained by the 17% higher ventilation rate use in this study, as described in

Section 6.4.1. Di Placido et al. also utilized different weather data and included waste heat

produced by fans in the thermal balance. Equation 7, which was used to calculate ventilation heat

loss in Figure 31a, is also limited in that it does not consider interaction between mechanical

systems, building thermal mass or other environmental condition factors such as solar gains.

The analysis done by Di Placido et al. utilized more sophisticated energy modeling software and

the resulting ventilation heating load is considered more accurate. The results of this study are

still useful in that they illustrate the relative benefits of the fine wire HRV and DCV. Since the

model constructed by Di Placido et al. used a conventional HRV with similar performance to the

0

1000

2000

3000

4000

5000

6000

7000

Consant, Convent. HRV

Constant, Fine Wire HRV

Variable, Fine Wire HRV

Ve

nti

lati

on

He

at L

oss

(M

J/ye

ar)

0

100

200

300

400

500

600

700

Consant, Convent. HRV

Constant, Fine Wire HRV

Variable, Fine Wire HRV

Fan

Ele

ctri

city

Use

(kW

h/y

ear

)

-45% -61% -43% -61%

50

one used in the this study’s baseline model, comparable percentile energy savings can likely be

achieved. Applying a 61% reduction in ventilation heating load to the results obtained by Di

Placido et al. indicates that the overall energy required for space heating of an R-2000 home

could be reduced by 17%. Thus, using the fine wire HRV in combination with DCV can be

expected to reduce annual heating fuel consumption by 12.3 MJ/m2.

Statistics Canada (2011) lists the average Ontario household’s annual electricity consumption as

8333 kWh. Although this is an average across houses of different sizes and ages, it provides a

rough approximation of electricity consumption in the house modeled in this study. Assuming an

annual household electricity consumption of 8333 kWh, the fine wire HRV and DCV have the

potential to reduce total household electricity consumption by approximately 5%. This

percentage may be higher for energy efficient housing with lower overall electricity consumption

due to high efficiency appliances and lighting.

6.5.2 Indoor Air Quality

Pollutant concentrations resulting from the constant and variable ventilation strategies were also

compared. Concentrations were averaged over the occupied periods and are shown in Figure 32.

(a) PM2.5 (b) HCHO (b) O3

Figure 32. Pollutant concentrations of constant and variable ventilation strategies

The average concentration of PM2.5 during the occupied periods is reduced by 21% in the

variable ventilation strategy. As PM2.5 is suspected of having adverse health effects even at low

concentrations (Health Canada), this reduction is significant in improvement in occupant health.

0

2

4

6

8

10

12

14

16

18

Constant Ventilation

Variable Ventilation

PM

2.5

(μg/

m3)

0

10

20

30

40

50

60

Constant Ventilation

Variable Ventilation

HC

HO

g/m

3)

0.0

0.5

1.0

1.5

2.0

2.5

Constant Ventilation

Variable Ventilation

O3

(μg/

m3)

-21% +41% +3%

51

There is a 3% increase in average HCHO concentrations during occupied periods in the variable

ventilation strategy. This increase results from the short occupancy periods in the main living

space during the weekday mornings and evenings. HCHO concentration builds up during the

unoccupied period and results in high initial HCHO levels when the space is first occupied. Since

these occupied periods are short, the high initial concentration results in higher average

concentrations, even though HCHO concentration is reduced quickly over the first two hours.

Since these are short events by definition, they are unlikely to contribute significantly to an

individual’s overall HCHO exposure.

Although there is a 41% increase in average O3 concentration during occupied periods due to an

increase in the average ventilation rate, the concentration is still more than an order of magnitude

less than the Health Canada (2014) guideline. Given the very low O3 concentration in both

strategies, the increase is not expected to have a significant impact on health.

6.6 Limitations

There are a number of limitations to the modeling approach. The parameters used to model

indoor air quality are mean values, and do not capture the distributions of values. Furthermore,

parameters are assumed constant over time which may not capture important relationships

between different parameters. For example, indoor HCHO emission rates likely decrease with

increasing concentration. Similarly, indoor PM2.5 emissions are likely higher during occupied

periods due to activities such as cooking or cleaning which generate particles. In both of these

examples the assumptions are conservative in that they underestimate the benefits of the

decentralized ventilation system, but there may be other less understood relationships with

unknown implications.

Because the proposed variable ventilation strategy is based on the mean HCHO emission rate

used in the model, it is not optimized for homes with different HCHO emission levels. In cases

where emissions are lower, the proposed strategy may result in wasted energy, while in cases

where emissions are higher it may result in HCHO concentrations exceeding the Health Canada

(2014) guidelines. This challenge is also faced by constant ventilation rate guidelines and is

largely unavoidable. Sensitivity analysis of the relative impact of HCHO emission rates on the

optimized ventilation strategy would help quantify the significance of this concern.

52

The outdoor pollutant concentrations used in the model are based on average conditions in

Toronto. While Toronto has relatively low average ambient levels of O3 and PM2.5, outdoor

concentrations of these pollutants can be higher during particular times of the day. For example,

traffic-generated outdoor pollutant levels may peak during the morning and afternoon rush hours.

If the afternoon peak coincides with occupants returning home and increased ventilation rates, it

may introduce higher levels of these traffic-generated pollutants into the indoor environment.

Similarly, for those locations in the world where outdoor pollution levels are very high, the

proposed strategy of increasing the ventilation rate when a zone is initially occupied may

actually expose occupants to worse indoor air quality. Care should be taken to consider

differences in outdoor air quality when extrapolating these results to other locations.

The calculations of ventilation heat loss are based on a simplified equation which does not

consider the building systems in detail or the effects of other environmental factors such as solar

gains. More accurate results could be obtained by performing a whole-building energy model.

The occupancy schedules assumed in the model also limit the relevance of the results, which

may differ under different occupancy scenarios.

The many limitations and unknown variables inherent to the modeling approach mean that there

is some uncertainty associated with the results. Although the results may not be representative of

all installations of the fine wire HRV, they do illustrate the potential for significant reductions in

ventilation heating load and fan electricity consumption. Further modeling and field testing is

necessary to provide more reliable and representative results.

7 Discussion

The results of this study indicate that the fine wire HRV, in combination with a variable and

demand controlled ventilation strategy, may offer significant benefits over conventional

ventilation systems. The apparent effectiveness of the technology raises the question of why it

has not been successfully commercialized yet. Although the fine wire heat exchanger was first

patented in North America over 15 years ago, it is not yet commercially available and to the

author’s knowledge has received limited industry attention. This may be in part a reality of trying

to manufacture and promote an unconventional product with limited resources. That being said,

it is also important to consider some of the challenges which may impact the technology’s uptake

in the residential market.

53

Unlike a conventional ventilation system, the fine wire HRV is designed to be located in close

proximity to building occupants. Similar to a window air conditioner or portable air cleaner, the

noise generated by fans and air movement may be disruptive, particularly in bedrooms. This

issue is likely most significant in Northern Europe, where people are generally less tolerant of

noise, as evidenced by the importance of acoustics in European ventilation standards (eg.

Passivhaus Institut 2009). Even in North America, some building owners, particularly those

interested in high-end energy efficient housing, may find the fine wire HRV less attractive as a

result. Further investigation should be conducted to quantify noise levels and explore options for

dampening sound or locating the HRV to minimize acoustical impacts.

The cost of installation and maintenance is another issue which may dissuade home owners from

installing the fine wire HRV. Although the final retail price of the unit itself should be

comparable to conventional HRVs, a greater number of units are required to take advantage of

decentralized ventilation, increasing the installation cost. This increased cost will be partly offset

by reduced ductwork requirements. Maintenance costs will also be higher, as there are a larger

number of fans, electrical components and filters to be serviced.

The challenge of providing multiple HRVs is further compounded by the need for condensate

drainage in cold climates. Moisture is produced in buildings by activities such as showering and

cooking, as well as by the biological processes of occupants themselves. The result is relatively

warm and moist indoor air, regardless of outdoor humidity levels. When outdoor temperatures

are low, HRVs function by extracting energy from the warm exhaust air to heat the cool supply

air. If the exhaust air is cooled below its dew point it will not be able to contain the water vapour,

resulting in condensation which must be drained away. Providing drains to multiple HRVs

located on exterior walls throughout the home may be costly, particularly in a retrofit situation.

The fine wire heat exchanger is only capable of recovering sensible heat, making it most relevant

for heating dominated climates. Given the fundamental heat recovery concept, an option for

latent heat recovery does not appear feasible. Although the layers separating adjacent airstreams

could potentially be made vapour permeable, the very small surface area would likely still make

significant latent heat transfer difficult. Thus, the technology has a smaller potential market than

rotary and plate heat exchangers which can be designed to recover both sensible and latent heat.

54

8 Conclusions

The fine wire HRV represents a novel concept for decentralized ventilation with heat recovery.

The ventilator uses copper wires to transfer sensible energy between the supply and exhaust

airstreams. By integrating the fine wire HRV into the façade to create a “breathing wall”, the

extensive ductwork and associated space requirements of conventional ventilation systems can

be avoided. This also allows each room or zone of the home to have its own ventilator,

facilitating demand controlled ventilation. This initial scientific review of the fine wire HRV

evaluated its performance in several areas as well as its suitability for decentralized and demand

controlled ventilation heat recovery in residential buildings.

Performance testing was conducted in an indoor laboratory. Fan electricity consumption using

brushless DC motors was found to be 1.1 W per L/s for airflow rates below 30 L/s, putting the

fine wire HRV within the top 5% of North American HRVs with respect to fan energy. The fine

wire HRV was also found to have a sensible heat recovery efficiency as high as 82% for airflow

rates of 7-10 L/s. At this performance level, it is within the top 2.5% of North American HRVs

with respect to heat recovery. Airstream cross-leakage was found to be 0.5-1.5% and not to have

a significant impact on performance.

A model of ventilation energy usage and indoor air quality was developed and used to compare a

conventional HRV to the fine wire HRV. The model results indicate that the fine wire HRV in

conjunction with demand controlled ventilation could reduce the ventilation heating load by 61%

and the total heating load by 17%. Fan electricity consumption was also reduced by 61%,

corresponding to a 5% reduction in total household electricity use. Indoor air quality was also

improved, with a 21% reduction in average PM2.5 concentrations.

The technology has yet to be successfully commercialized and there are a number of challenges

which may slow adoption of the fine wire HRV. Due to the proximity to building occupants,

noise generated by fans and air movement may be disruptive, particularly in bedrooms. The cost

of installation and maintenance of multiple ventilation units is another issue which may dissuade

home owners. Finally, the inability to recover latent heat means that the fine wire HRV is only

appropriate for heating dominated climates.

55

9 Future Research

9.1 Condensation and Freezing

One issue that has not been investigated in this study is the fine wire HRV’s capacity to handle

condensation and freezing. During moderate winter weather, water vapour will condense on the

heat exchanger surface and can be drained away. High efficiency heat exchangers and cold

outdoor temperatures mean exhaust air may be cooled below 0 ⁰C however, resulting in freezing

and an accumulation of ice on the heat exchanger surface. This ice eventually obstructs airflow

and results in fouling of the HRV. Different HRV designs address ice accumulation in different

ways. In North America, the most common approach is to preheat the supply air inlet above a

minimum temperature so that freezing does not occur in the exhaust airstream. To simplify

installation, this preheating is often done with electric resistance heat, making it a costly process

relative to heating with natural gas. Preheating the supply air inlet also reduce the total heat that

can be recovered from the exhaust airstream, making the HRV less efficient. Other HRV designs

either stop or reduce supply airflow temporarily, increasing the temperature of the exhaust

airstream and allowing the ice to melt. This must be done periodically as ice re-accumulates,

reducing the HRVs overall heat recovery efficiency in cold weather.

The impact of condensation and freezing of water vapour on the fine wire heat exchanger has not

been explored in this study. The developer has suggested that the very rapid cooling of the

exhaust air as it passes through the 16 mm thick heat exchanger results in air exiting in a super-

saturated state. If this is true, it could mean reduced condensation and ice accumulation and

improved performance in cold weather. Tests should be conducted to determine under what

conditions ice begins to accumulate, and how much supply airflow must be reduced to defrost

the heat exchanger. These results can then inform an effective control strategy and an energy

modeling effort which accounts for the reduction in annual efficiency due to freezing.

56

9.2 Field Installation

The model of whole-building energy use and indoor air quality provides an indication of the

potential of the fine wire HRV. As with any modeling exercise, increased confidence in the

results requires field validation. Ideally this would be done by installing a number of fine wire

HRVs in a typical new home which also had a conventional HRV system and associated

ductwork. The house could then be operated intermittently with the two systems, and the effects

on energy consumption and indoor air quality could be measured.

Undoubtedly many of the assumptions made in the model will have to be refined. The

performance measurements taken in the lab may also have to be adjusted, as technology often

behaves differently in the field. For example, all the performance measurements taken as part of

this study were conducted under steady-state conditions. It is unclear what effect continuously

changing airflows in the field might have on performance. Occupancy may also be a challenge to

accurately detect, and some level of control failure may have to be incorporated into the model.

57

References

ANSI/ASHRAE. 2013. ANSI/ASHRAE Standard 62.1 – Ventilation for Acceptable Indoor Air

Quality. American Society of Heating, Refrigerating and Air-Conditioning Engineers,

Atlanta, GA.

ANSI/ASHRAE. 2013. ANSI/ASHRAE Standard 62.2 – Ventilation and Acceptable Indoor Air-

Quality in Low-Rise Residential Buildings. American Society of Heating, Refrigerating and

Air-Conditioning Engineers, Atlanta, GA.

ASHRAE. 2013. ASHRAE Handbook—Fundamentals. American Society of Heating,

Refrigerating and Air-Conditioning Engineers, Atlanta, GA.

Building Science Corporation. 2013. Balanced Ventilation Systems (HRVs and ERVs). Info-611,

BuildingScience.com, Somerville, MA.

Burke, M., Wong, L., Gonzales, B.A., and Knutson, G. 2014. Nitrous Oxide as a Tracer Gas in

the ASHRAE 110-1995 Standard. Journal of Occupational and Environmental Hygiene,

11(1): 32-39. doi: 10.1080/15459624.2013.839881.

Canadian Home Builders' Association. 2013. 46th Pulse Survey. Retrieved 15 July 2014 from

http://chba.ca/uploads/pulse%20survey%20results/main%20report2013.pdf

Canadian Standards Association 2010. C439-09 - Standard laboratory methods of test for rating

the performance of heat/energy-recovery ventilators.

CMHC. 2003. Ventilation Systems for Multi-Unit Residential Buildings: Performance

Requirements and Alternative Approaches. Technical Series 03-121.

CMHC. 2005. Assessment of Suite Compartmentalization and Depressurization in New High-

Rise Residential Buildings. Technical Series 05-112.

Di Placido, A.M., Pressnail, K.D., and Touchie, M.F. 2014. Exceeding the Ontario Building

Code for low-rise residential buildings: Economic and environmental implications. Building

and Environment, 77(0): 40. doi: 10.1016/j.buildenv.2014.03.015.

Dominici, F., Peng, R.D., Bell, M.L., Pham, L., McDermott, A., Zeger, S.L., and Samet, J.M.

2006. FIne particulate air pollution and hospital admission for cardiovascular and respiratory

diseases. The Journal of the American Medical Association, 295(10): 1127-1134. doi:

10.1001/jama.295.10.1127.

Dougan, D.S. and Damiano, L.A. 2011. ANSI/ASHRAE Standard 62.1 - 2010, Ventilation for

Acceptable Indoor Air Quality - Update, Analysis and Recommendations, EBTRON Inc.,

Loris, SC.

El Fouih, Y., Stabat, P., Rivière, P., Hoang, P., and Archambault, V. 2012. Adequacy of air-to-

air heat recovery ventilation system applied in low energy buildings. Energy and Buildings,

54(0): 29-39. doi: 10.1016/j.enbuild.2012.08.008.

58

Emmerich, S.J., and Nabinger, S.J. 2001. Measurement and simulation of the IAQ impact of

particle air cleaners in a single-zone building. HVAC&R Research, 7(3): 223.

Environment Canada 2014. Canadian Climate Normals 1981-2010 Station Data (TORONTO

LESTER B. PEARSON INT'L A) 2014(07/18). Retrieved from

http://climate.weather.gc.ca/climate_normals/results_1981_2010_e.html

Fisk, W.J., and De Almeida, A.T. 1998. Sensor-based demand-controlled ventilation: a review.

Energy and Buildings, 29(1): 35-45. doi: 10.1016/S0378-7788(98)00029-2.

Fiwihex 2006. Fine Wire Heat Exchangers 2014(04/14). Retrieved from

http://fiwihex.home.xs4all.nl/english/

Franklin, M., Zeka, A., and Schwartz, J. 2007. Association between PM2.5 and all-cause and

specific-cause mortality in 27 US communities. Journal of Exposure Science and

Environmental Epidemiology, 17(3): 279-87. doi: 10.1038/sj.jes.7500530.

Garrett, M., Hooper, M., Hooper, B., Rayment, P., and Abramson, M. 1999. Increased risk of

allergy in children due to formaldehyde exposure in homes. Allergy, 54(4): 330-337. doi:

10.1034/j.1398-9995.1999.00763.x.

Health Canada. 2005. Proposed residential indoor air quality guidelines for formaldehyde.

Retrieved 1 September 2014 from http://www.hc-sc.gc.ca/ewh-semt/pubs/air/formaldehyde/

index-eng.php

Health Canada 2014. Residential Indoor Air Quality Guidelines 2014(07/14). Retrieved from

http://www.hc-sc.gc.ca/ewh-semt/air/in/res-in/index-eng.php

Home Ventilation Institute 2014. Certified Products Directory 2014(08/14). Retrieved from

http://www.hvi.org/proddirectory/

International Energy Agency. 1990. Demand Controlled Ventilation - State of the Art Review.

Energy Conservation in Buildings and Community Systems Programme, Annex 18, Swedish

Council for Building Research, Stockholm, Sweden.

Kakaç, S. and Liu, H. 2002. Heat exchangers : selection, rating, and thermal design. CRC Press,

Boca Raton.

Knoll, B. 1992. Advanced ventilation systems - state of the art and trends. Technical Note 35,

Air Infiltration and Ventilation Centre, Coventry, UK.

Lee, K., Vallarino, J., Dumyahn, T., Ozkaynak, H., and Spengler, J.D. 1999. Ozone Decay Rates

in Residences. Journal of the Air & Waste Management Association, 49(10): 1238-1244.

doi: 10.1080/10473289.1999.10463913.

Liddament, M.W., and Orme, M. 1998. Energy and ventilation. Applied Thermal Engineering,

18(11): 1101-1109. doi: 10.1016/S1359-4311(98)00040-4.

59

Logue, J.M., Price, P.N., Sherman, M.H., and Singer, B.C. 2012. A Method to Estimate the

Chronic Health Impact of Air Pollutants in U.S. Residences. Environmental Health

Perspectives, 120(2): 216-22.

Long, C.M., Suh, H.H., Catalano, P.J., and Koutrakis, P. 2001. Using Time- and Size-Resolved

Particulate Data To Quantify Indoor Penetration and Deposition Behavior. Environmental

Science & Technology, 35(10): 2089-2099. doi: 10.1021/es001477d.

Manz, H., Huber, H., Schälin, A., Weber, A., Ferrazzini, M., and Studer, M. 2000. Performance

of single room ventilation units with recuperative or regenerative heat recovery. Energy and

Buildings, 31(1): 37-47. doi: 10.1016/S0378-7788(98)00077-2.

Mardiana, A., and Riffat, S.B. 2013. Review on physical and performance parameters of heat

recovery systems for building applications. Renewable and Sustainable Energy Reviews,

28(0): 174-190. doi: 10.1016/j.rser.2013.07.016.

Mueller, F.X., Loeb, L., and Mapes, W.H. 1973. Decomposition rates of ozone in living areas.

Environmental Science & Technology, 7(4): 342-346. doi: 10.1021/es60076a003.

Naghiyev, E., Gillott, M., and Wilson, R. 2014. Three unobtrusive domestic occupancy

measurement technologies under qualitative review. Energy and Buildings, 69(0): 507-514.

doi: 10.1016/j.enbuild.2013.11.033.

Nóbrega, C.E.L., and Brum, N.C.L. 2009. Modeling and simulation of heat and enthalpy

recovery wheels. Energy; ECOS 2007, 34(12): 2063-2068. doi:

10.1016/j.energy.2008.08.016.

Oikos Green Building Source 1995. Home Ventilation Options for Home Builders. Source

Builder Newsletter. no. 39.

Ontario Ministry of Environment and Climate Change 2014. Pollutant Concentrations

2014(07/14). Retrieved from http://airqualityontario.com/history/

Osamu, T. 1984. An analysis of simultaneous heat and water vapor exchange through a flat paper

plate crossflow total heat exchanger. International Journal of Heat and Mass Transfer,

27(12): 2259-2265. doi: 10.1016/0017-9310(84)90084-X.

Passivhaus Institut. 2009. Requirements and testing procedures for energetic and acoustical

assessment of Passive House ventilation systems for Certification as “Passive House suitable

components”. Passivhaus Institut, Darmstadt, Germany. Retrieved 1 September 2014 from

http://passiv.de/downloads/03_Reqs_and_testing_procedures_ventilation_en.pdf

Persily, A., Musser, A., and Emmerich, S.J. 2010. Modeled infiltration rate distributions for U.S.

housing. Indoor Air, 20(6): 473-485. doi: 10.1111/j.1600-0668.2010.00669.x.

Riley, W.J., McKone, T.E., Lai, A.C.K., and Nazaroff, W.W. 2002. Indoor Particulate Matter of

Outdoor Origin: Importance of Size-Dependent Removal Mechanisms. Environmental

Science & Technology, 36(2): 200-207. doi: 10.1021/es010723y.

60

Ruan, W., Qu, M., and Horton, W.T. 2012. Modeling analysis of an enthalpy recovery wheel

with purge air. International Journal of Heat and Mass Transfer, 55(17): 4665-4672. doi:

10.1016/j.ijheatmasstransfer.2012.04.025.

Rudd, A.F., and Lstiburek, J.W. 2000. Measurement of ventilation and interzonal distribution in

single-family homes. ASHRAE Transactions, 106: 709.

Russell, M., Sherman, M. and Rudd, A. 2005. Review of Residential Ventilation Technologies.

LBNL 57730, Lawrence Berkeley National Laboratory.

Sabersky, R.H., Sinema, D.A., and Shair, F.H. 1973. Concentrations, decay rates, and removal of

ozone and their relation to establishing clean indoor air. Environmental Science &

Technology, 7(4): 347-353. doi: 10.1021/es60076a001.

Satish, U., Mendell, M.J., Shekhar, K., Hotchi, T., Sullivan, D., Streufert, S., and Fisk, W.J.

2012. Is CO2 an indoor pollutant? Direct effects of low-to-moderate CO2 concentrations on

human decision-making performance. Environmental Health Perspectives, 120(12): 1671-

1677. doi: 10.1289/ehp.1104789.

Schell, M.B., Turner, S.C., and Shim, O.R. 1998. Application of CO2-based demand-controlled

ventilation using ASHRAE standard 62: Optimizing energy use and ventilation. ASHRAE

Transactions, 104: 1213.

Schmidt, M. and Klein, B. 2011. Prüfbericht über die Prüfung von Wohnungslüftungsgeräten mit

Wärmerückgewinnung nach DIBt. Nr. PL.11.WLG.91, Institut für Gebäude Energetik,

University of Stuttgart, Stuttgart.

Seyed-Ahmadi, M., Erb, B., Simonson, C.J., and Besant, R.W. 2009. Transient behavior of run-

around heat and moisture exchanger system. Part 1: Model formulation and verification.

International Journal of Heat and Mass Transfer, 52(25): 6000-6011. doi:

10.1016/j.ijheatmasstransfer.2009.07.012.

Shao, L., and Riffat, S.B. 1997. Flow loss caused by heat pipes in natural ventilation stacks.

Applied Thermal Engineering, 17(4): 393-399. doi: 10.1016/S1359-4311(96)00029-4.

Sherman, M.H. 1990. Tracer-gas techniques for measuring ventilation in a single zone. Building

and Environment, 25(4): 365-374. doi: 10.1016/0360-1323(90)90010-O.

Sherman, M.H., and Hodgson, A.T. 2004. Formaldehyde as a basis for residential ventilation

rates. Indoor Air, 14(1): 2-8. doi: 10.1046/j.1600-0668.2003.00188.x.

Sherman, M. and Walker, I. 2007. Energy Impact of Residential Ventilation Norms in the United

States. LBNL 62341, Lawrence Berkeley National Laboratory, Environmental Energy

Technologies Division.

Statistics Canada. 2011. Households and the Environment: Energy Use. Catalogue no. 11-526-S.

Retrieved from http://www.statcan.gc.ca/pub/11-526-s/11-526-s2013002-eng.pdf

61

Stephens, B., Siegel, J.A., PhD, and Novoselac, A., PhD 2010. Energy Implications of Filtration

in Residential and Light-Commercial Buildings. ASHRAE Transactions, 116: 346-357.

Stephens, B., Gall, E.T., and Siegel, J.A. 2012. Measuring the Penetration of Ambient Ozone

into Residential Buildings. Environmental Science & Technology, 46(2): 929-936. doi:

10.1021/es2028795.

Straube, J. 2009. The Passive House (Passivhaus) Standard: A comparison to other cold climate

low-energy houses. Building Science Insights, BSI-025.

Van Andel, E. 1998. US5832992: Heat exchanger and method for manufacturing same.

Wallin, J., Madani, H., and Claesson, J. 2012. Run-around coil ventilation heat recovery system:

A comparative study between different system configurations. Applied Energy; Energy

Solutions for a Sustainable World, Special Issue of International Conference of Applied

Energy, ICA2010, April 21-23, 2010, Singapore, 90(1): 258-265. doi:

10.1016/j.apenergy.2011.05.012.

Weschler, C., Hodgson, A., and Wooley, J. 1992. Indoor Chemistry - Ozone, Volatile Organic-

Compounds, and Carpets. Environmental Science & Technology, 26(12): 2371-2377. doi:

10.1021/es00036a006.

Williams, R., Suggs, J., Rea, A., Sheldon, L., Rodes, C., and Thornburg, J. 2003. The Research

Triangle Park particulate matter panel study: modeling ambient source contribution to

personal and residential PM mass concentrations. Atmospheric Environment, 37(38): 5365-

5378. doi: 10.1016/j.atmosenv.2003.09.010.

Wray, C.P., Matson, N.E., and Sherman, M.H. 2000. Selecting whole-house ventilation

strategies to meet proposed Standard 62.2: Energy cost considerations. ASHRAE

Transactions, 106: 681.

Zhang, L.Z., and Jiang, Y. 1999. Heat and mass transfer in a membrane-based energy recovery

ventilator. Journal of Membrane Science, 163(1): 29-38. doi: 10.1016/S0376-

7388(99)00150-7.

Zhang, L., and Lee, W.L. 2011. Evaluating the use heat pipe for dedicated ventilation of office

buildings in Hong Kong. Energy Conversion and Management, 52(4): 1983-1989. doi:

10.1016/j.enconman.2010.10.046.

Zhao, P., Siegel, J.A., and Corsi, R.L. 2007. Ozone removal by HVAC filters. Atmospheric

Environment, 41(15): 3151-3160. doi: 10.1016/j.atmosenv.2006.06.059.

62

Appendix A:

Photos of Prototype, Testing and Installations

63

Manifold (back side) Manifold (front side)

Heat exchanger core without manifold Heat exchanger core detail

64

Fans mounted back-to-back Plywood sandwich layer with wiring

Installed fan Fan power supplies and controls

Location of static pressure probe Test setup with calibrated fan

65

Completed prototype Prototype with thermocouples

Example installation (by others) Example installation (by others)

66

Appendix B:

Sensible Heat Recovery Efficiency Test Data

67

Test 1 – Airflow rate: 12 cfm (5.7 L/s) – Heat at exhaust inlet: 200 W

Test 2 – Airflow rate: 15 cfm (7.1 L/s) – Heat at exhaust inlet: 215 W

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250 300 350 400 450

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250 300 350 400 450

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1

68

Test 3 – Airflow rate: 20.5 cfm (9.7 L/s) – Heat at exhaust inlet: 260 W

Test 4 – Airflow rate: 26 cfm (12.3 L/s) – Heat at exhaust inlet: 300 W

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250 300 350

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1

20

22

24

26

28

30

32

34

36

38

40

0 100 200 300 400 500

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1

69

Test 5 – Airflow rate: 28.5 cfm (13.5 L/s) – Heat at exhaust inlet: 300 W

Test 6 – Airflow rate: 33 cfm (15.6 L/s) – Heat at exhaust inlet: 320 W

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250 300 350 400

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1

70

Test 7 – Airflow rate: 39 cfm (18.4 L/s) – Heat at exhaust inlet: 345 W

Test 8 – Airflow rate: 48 cfm (22.7 L/s) – Heat at exhaust inlet: 370 W

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250 300 350 400

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1

71

Test 9 – Airflow rate: 56 cfm (26.4 L/s) – Heat at exhaust inlet: 370 W

20

22

24

26

28

30

32

34

36

38

40

0 50 100 150 200 250 300 350 400 450

Me

asu

red

Te

mp

era

ture

(°C)

Time (seconds)

t1(a)

t1(b)

t1(c)

t2(a)

t2(b)

t2(c)

t3(a)

t3(b)

t3(c)

t4(a)

t4(b)

t4(c)

t3

t2

t4

t1