Page 1: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

V e r s i o n N o 3 D a t e d 0 1 . 1 1 . 0 6

Page 2: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS2 Introduction

INTRODUCTION

The purpose of this Guide is to ensure that the ordering process is simple, clear and fast. It provides the customer and the supplier (TEE) with a common basis for understanding any Product Order. The products described in this Guide are divided into the following main groups:

Draw-Out UnitsThis type of product is intended for complete replacement of the obsolete draw-out units with the new ones.

Typical Adaptation Kits TKA/TELTKA/TEL are intended for Retrofit & Rehabilitation of obsolete stationary and withdrawable switchgear. The Kits include the parts for VCB mounting, for arranging the connection to the primary circuits and parts for interlock organization. Tavrida Electric has designed the typical adaptation kits for over 100 types of switchgear.

Typical Adaptation Kits TKA/TEESimplified typical adaptation kits consist of the basic essential units and plastic parts. These sets ensure proper installation of the ISM and interlock arrangement both for Retrofit purposes and for the manufacture of brand new switchgear using TEL Indoor Switching and Control Modules.

TEE Control PanelsThis group of products is intended for organizing auxiliary circuits and implementation of the Control Modules into the existing auxiliary circuits. They can also be used as a complete alternative to old relay protection.

Control CablesThe sets of the control cables simplify the interconnections between ISM/TEL, CM/TEL and the Relay Compartment for both stationary and withdrawable switchgear. The use of these cable sets ensures EMC and trouble-free installation of the auxiliary connections.

International retrofit projects TKA/TEEThese retrofit projects have been developed in cooperation with our regional partners.Complete sets of drawings and instruction manuals are available for all switchgear types from the list. The typical adaptation kits are intended to be produced locally.

Longitudinal VCB Module TE-1This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new stationary or withdrawable switchgear.

TM-2C CassetteTM-2C Cassette is designed for the replacement of ABB vacuum circuit breaker draw-out units of type VD4 (or its clones) or the application of brand-new cassette type switchgear.

Components for metal-clad switchgearThe basic components for swithgear manufacturing are listed.

Emergency Power Supply SetsBasic units for auxiliary power back-up and the Emergency Generator for closing ISM are presented.

Mounting KitsThe kits for mounting KTR series outdoor products on poles.

Page 3: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

3IntroductionTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Retrofit Core Components

Obsolete Switchgear Tavrida Electric Core Components Retrofitted Switchgear

Order Sample for retrofit of KRU2-10:

1. ISM/TEL-12-20/1000-0512. CM/TEL-100/220-12-01A3. TKA/TEL-2 630A 20kA VMP10K4. CK-08

Switching Module ISM/TEL

Tavrida Electric Switching Module numbering:

F

Index F (optional) meansthat ISM is intended for frequent CO operation

ISM/TEL Label sample:

Available ratings:

Rated Voltage, kV

Rated Current, A

Rated Short Circuit Breaking Current, kA

Pole centre distance, mm

12 24

630 1000 1250 1600 2000

16 25 31,520

150 200 210 250 275

Control Module CM/TEL

Tavrida Electric Control Module numbering: Available Voltage Ranges:

24/30/48/60 DC110/220 DC, 100/127/230 AC

Switching Module ISM/TELControl Module CM/TEL

Control cable kits CKTypical Adaptation Kit TKA/TEL

Page 4: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Selection of CM/TEL:

I/O interface for C M/TEL-X/X-12-01A modules

CM/TEL-X/X-12-02A When a Control Module is used in the switchgear p a n e l w i t h a u x i l i a r y D C p o w e r w i t h electromechanical relays and mP relays that do not provide the required signalling interface, the CM/TEL-X-X/X-12-02A can be used.

CM/TEL-X/X-12-01AWhen a Control Module is used in the switchgear panel with auxiliary DC power in combination with a modern mP relay, providing a signalling interface of its own, the CM/TEL-X-X/X-12-01A can be used.

CM/TEL-X/X-12-03A When a Control Module is used in the switchgear panel with auxiliary AC power and with electromechanical relays, the CM/TEL-X-X/X-12-03A can be used.

I/O interface for CM/TEL-X/X-12-03A modules

Values of the Resistors are to be chosen according to the table in the attachment 1.

The selection of all modules must be based on:- The required basic operating parameters. The parameters in the Technical Specification of the CM/TEL must not be exceeded under any circumstances.- The Control Voltages and the I/O Interface requirements.The following general selection rules with regard to the choice of interfaces are applicable.

Emergency Power Supply inputs allow the CM/TEL to be fed from a low-voltage source, such as a car-battery or an Emergency Generator. This feature ensures the closing ability of the ISM in the case of auxiliary power supply loss.

4 Introduction TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 5: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

CONTENTS1. DRAW-OUT UNITS 7

5Contents

7

8

VE/TEL Series 506

8

VE/TEL Series ST7

9

9

10

VE/TEL Series Shell

2. TYPICAL ADAPTATION KITS TKA/TEL

VE/TEL Series CSI

VE/TEE Series KRUV-10

7How to place an order for Draw-out Units

10

11

11

ТКА/TEL- 2 (К–XII, К–XIII, K–XXVI, К–37, КRU2–10)

12

ТКА/TEL- 3 (КRU2–10 E/E)

13

13

14

14

15

15

16

16

17

17

18

18

19

19

20

20

21

21

22

22

23

23

24

25

25

26

27

28

29

TKA/TEL – 18 (KRN–10)

TKA/TEL – 19 (MKFN)

TKA/TEL – 20 (21, 22) (KSO cubicles of concrete or stone width 1400 мм)

TKA/TEL – 23 (KRN–IV)

TKA/TEL– 9 (КE–6; КE–10)

TKA/TEL– 11 (KRUE–6(10)V)

TKA/TEL – 12 (KSO-266, -272, -85, -292)

TKA/TEL – 13 (14, 15) (KSO–2(UM); KSO–KP03; KSO–D13B; KSO–LP318; KSO–2200; KSO–MKVF)

TKA/TEL – 16 (KRN–II; KRN–III)

TKA/TEL – 31 (RSW-10)

TKA/TEL – YAKNO

TKA/TEL – Minel

TKA/TEL – Rade Koncar

TKA/TEL – D4X, C4X Low Silhouette

TKA/TEL – D4X, C4X High Silhouette

TKA/TEL – BVP

TKA/TEL – LMT

TKA/TEL – 3AH, 3AF

TKA/TEL – HL4-7

TKA/TEL – K-34

ТКА/ТЕЕ-01

ТКА/ТЕЕ-02

ТКА/ТЕЕ-04

ТКА/ТЕЕ-05

TKA/TEE-07 (KRU2-10, К-XII, K-XIII, K-26, K-37), 630, 1000, 1600A

TKA/TEE-13 (RSW-10 630, 1250A)

12

3. TYPICAL ADAPTATION KITS TKA/TEE

TKA/TEL– 4 (К2–03; К3–02; KRU2–10 В)

TKA/TEL– 6 (CSIM 1–10)

TKA/TEL– 7 (К–IIIу; К–VIu; К–IIe)

TKA/TEL– 8 (КR–10U4, 4KVG9)

TKA/TEL – 17 (K–VI; SH–164)

TKA/TEL – 29 (ST–7; ST-8; ST–9)

10How to place an order for TKA/TEL

29

30

30

31

31

TKA/TEE-09 (VE/TEL-506, 1600A)

TKA/TEE-10 (KR-10U4, KVG4-10)

TKA/TEE-11 (VE/TEL-505, 630A, 1000A)

TKA/TEE-12 (KSO-266, -272, -285, -292, K-II, K-IIIu, K-IV, K-VIu 630А, 630A, 1000A, 1600A)

How to place an order for TKA/TEE 25

32

32

32

Control Box TEE-01, Control Box TEE-02

Relay Protection Panels RP/TEE-NDINF-01, RP/TEE-IM30T-02

4. TEE CONTROL PANELS TEE

TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 6: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

6 Contents

33

33

33

33

33

34

34

35

35

36

36

37

37

38

38

39

39

40

40

41

41

42

42

Cable Kit СК-01

Cable Kit СК-02

Cable Kit СК-03

Cable Kit СК-04

Cable Kit СК-05

Cable Kit СК-08 Harting

TKA/TEE-K11-Shell

TKA/TEE-SACE

TKA/TEE-Magrini

TKA/TEE-8BDE-LBS-Siemens

TKA/TEE-BBC

TKA/TEE-TSN

TKA/TEE-Pars Switch

TKA/TEE-EIB-NT

TKA/TEE-Alstom

TKA/TEE-Energoinvest

TKA/TEE-Minel-Shell

TKA/TEE-ICMP7

TKA/TEE-WMSWP

TKA/TEE-ROK6

TKA/TEE-SCI4

5. CONTROL CABLES

6. INTERNATIONAL RETROFIT PROJECTS TKA/TEE

44

44TE-1

45

46

46

46

46

46

46

46

46

46

46

8. TM-2C CASSETTE

TM-2C

Contact arm

Draw-out plate

7. LONGITUDINAL VCB MODULE, TE-1

9. COMPONENTS FOR METAL CLAD SWITCHGEAR MANUFACTURING

Moving contacts

Gear (umbrella) mechanism for earth switch

Earthing switch, EK-6 analogue, make type

Guide rails for draw-out plates

46

46

46

46

46

Fixed contacts insulator

Through insulator for single and double busbars

Ground line joint-lock mechanism

Joint-lock mechanism for Auxiliary Contacts drive

Set of the auxiliary contacts

Second plug joint-lock mechanism

Live gate mechanism. Shutters

47

47

47

47

47

TEE/EPSS-01 Generator, Varistors, Case, Handle, terminals, Fuses. Set of Wires, 30VDC

TEE/PSU-01 Genesis Battery, Oracle PSU + battery charger 24/220 VDC

TEE/RMK-02 Recloser Mounting Kit

TEE/VTMK-06 Voltage Transformer Mounting Kit

10. EMERGENCY POWER SUPPLY SETS

11. MOUNTING KITS (RMK, VTMK)

Attachment 1

48

47

Fixed primary contacts

TKA/TEE-EIB Transzvill Hungary

TKA/TEE-SACE D6.25 Hungary

43

43

46

How to place an order for TKA/TEE International Retrofit Projects 35

12. ACCESSORIES

49

TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 7: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

1. Draw-out Units

VE/TEL 506 series

For replacing the Draw-out Units of the following Switchgear types:

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 125

К–104 (К–204EP)КМ–1КМVКМ–1F(ZZVA)КМ–1F (LEMZ)

KRUN–6(10)LКМ–1МК–47К–49К–59

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

Cubicle Type (For KM-1F name of the factory ZZVA or LEMZ)

Main contact (Tulip) size, mm

7.2, 12

630, 1000, 1600

20 or 31.5

VK-10 or VKE-10

24, 36

Required Order Making Information:

How to place an order for Draw-out Units.

The following information is required:1. Rated Voltage, kV2. Rated Current, A3. Rated breaking current, kA4. Type of circuit breaker to be replaced5. Switchgear Type6. Main tulip contacts inner diameter, mm

The example of the order:

1. ISM/TEL-12-20/1000-051 2. CM/TEL-100/220-12-01A3. VE/TEL-506 12kV, 630A, 20kA, VK-10, KM-104, 24mm

7Draw-Out Units TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 8: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

VE/TEL Series SCI-6

For replacing the Draw-out Units of the following Switchgear types:

400, 800

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2

20

up to 115

CSIM-4-12 VEB Otto Bushwitz (DDR)

Applicable types of ISM and CM:ISM/TEL-12-20/1000-067CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:150 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2

400, 800

20

CSIM-4-12

Required Order Making Information:

VE/TEL Series ST7

For replacing the Draw-out Units of the following Switchgear types:

800, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

20

up to 115

ST-7

Applicable types of ISM and CM:ISM/TEL-12-20/1000-046CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

800, 1000

20

ST-7

Required Order Making Information:

8 Draw-Out Units TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 9: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

VE/TEL Series Shell

For replacing the Draw-out Units of the following Switchgear types:

1250, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

20, 31,5

up to 125

К–104 (К–204EP) КМ–1 КМV КМ–1F (ZZVA) КМ–1F (LEMZ)

KRUN–6(10)L КМ–1М К–47 К–49 К–59

Applicable types of ISM and CM:ISM/TEL-12-20/1250-108ISM/TEL-12-31,5/2000-110CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

Cubicle Type (For KM-1F name of the factory ZZVA or LEMZ)

Main contact (Tulip) size, mm

12

1250, 1600

20, 31,5

VK-10 or VKE-10

36

Required Order Making Information:

VE/TEE Series КRUV-10

Draw Out Units:KRUV-10

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 115

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000, 1600

20, 31.5

-

Required Order Making Information:

9Draw-Out Units TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 10: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

2. Typical Adaptation Kits TKA/TEL

TKA/TEL-2

Retrofit of the following switchgear types:

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 125

К–XII K-XIII К-26 К-37

КRU2-10 VMPE КRU2-10 VMPP КRU2-10 VMP-10K КRU2-10 VMP-10P

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000, 1600

20, 31.5

All VMPxxx series

Required Order Making Information:

How to make an order on Typical Adaptation Kits TKA/TEL.

The following information is required:1. Rated Voltage, kV2. Rated Current, A3. Rated breaking current, kA4. Type of circuit breaker to be replaced5. Switchgear Type

The example of order:

1. ISM/TEL-12-20/1000-051 2. CM/TEL-100/220-12-01A3. TKA/TEL-2 12kV, 630A, 20kA, VMPE, K-XII

10 Typical Adaptation Kits TKA/TEL TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 11: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL-4

Retrofit of the following switchgear types:

630, 1250, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 125

K2-03 К3-02

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1250, 1600

20, 31.5

АК 10/800/20, АК 10/1250/20, АК 10/2000/20

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

TKA/TEL-3

Retrofit of the following switchgear types:

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 125

KRU2-10 E/E

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000, 1600

20, 31.5

VEM-10E

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

11Typical Adaptation Kits TKA/TELTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 12: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL-7

Retrofit of the following switchgear types:

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 125

К–IIIu K-II K-IV K-VIu

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000, 1600

20, 31.5

VMG-133, VMP-10K, VMPP-10, VMPE-10

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052ISM/TEL-12-31,5/1600-083CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

TKA/TEL-6

Retrofit of the following switchgear types:

800, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

up to 115

CSIM 1–10/350 VEB Otto Bushwitz (DDR)

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

800, 1000

20

CSI 1–20/350

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

12 Typical Adaptation Kits TKA/TEL TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 13: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL-9

Retrofit of the following switchgear types:

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 125

КЕ-6 КЕ-9

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000, 1600

20, 31.5

VE-6, VE-10

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

630, 1000, 1600

7.2, 12

20, 31.5

up to 125

7.2, 12

630, 1000, 1600

20, 31.5

VMG-133, VMP-10K, VMPP-10, VMPE-10

Distance between poles:250 mm

TKA/TEL-8

Retrofit of the following switchgear types:

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

KR-10U4 KVG4-10 4KVS-9

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052ISM/TEL-12-31,5/1600-083CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

13Typical Adaptation Kits TKA/TELTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 14: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL-12

Retrofit of the following stationary type cubicles:

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

КSО-266 КSО-272 КSО-285 КSО-292

Rated Voltage, kV

Rated Current, A

Breaking current, kA

7.2, 12

630, 1000, 1600

20, 31.5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052ISM/TEL-12-31,5/1600-083CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

Type of the breaker to be replaced VMG–10, VMG–133, VMGP–10, VMPP–10, VMPE–10

TKA/TEL-11

Retrofit of the following switchgear types:

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

up to 115

KRUE-6V KRUE-10V

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VBCH-SP-10 or VVTP-10 or VVM–10

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

14 Typical Adaptation Kits TKA/TEL TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 15: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL-16

Retrofit of the following outdoor stationary type cubicles:

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

КRN-II КRN-III

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VMG–10, VMG–133, VMP–10

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

TKA/TEL-13, 14, 15

Retrofit of the following stationary type cubicles:

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

КSО-2 КSО-2UM КSО-2200 КSО-D13B

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

КSО-LP318 КSО-KP03 КSО-MKFV

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VMG–10, VMG–133, VMP–10

15Typical Adaptation Kits TKA/TELTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 16: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL-18

Retrofit of the following outdoor stationary type cubicles:

KRN-10

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VMG–10, VMGP–10, VMG–133, VMP–10

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

TKA/TEL-17

Retrofit of the following outdoor stationary type cubicles:

К-VI SH-164

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VMG–10, VMG–133

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

16 Typical Adaptation Kits TKA/TEL TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 17: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL-20, 21, 22

Retrofit of the following outdoor stationary type cubicles:

KSO with the front covered with metal sheet or wire mesh and the sides of concrete, brick or high-density plasterboard. Only for Russia-made stationary type cubicles . Width 1400mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VMG–10, VMG–133

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

TKA/TEL-19

Retrofit of the following outdoor stationary type cubicles:

KRUN-MKFN

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VMG–10, VMG–133

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

17Typical Adaptation Kits TKA/TELTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 18: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL-29

Retrofit of the following switchgear types:

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

up to 115

ST-7 ST-8 ST-9

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

WMPWZ/S ZWAR

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

TKA/TEL-23

Retrofit of the following outdoor stationary type cubicles:

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

KRN–IV

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VK-10

18 Typical Adaptation Kits TKA/TEL TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 19: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Retrofit of the following outdoor stationary type cubicles:

630

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

YAKNO

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630

20

VMG

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

TKA/TEL- YAKNO

TKA/TEL-31

Retrofit of the following switchgear types:

630, 1000, 1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 125

RSW-10/I

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000, 1250

20, 31.5

ZWAR: WMSWPI-10/6/3,5 WMSWPI-10/12/3,5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31.5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

19Typical Adaptation Kits TKA/TELTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 20: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL- Rade Končar

Retrofit of the following switchgear types:

1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

20, 31.5

125

Rade Koncar, Croatia OR1 pg12-1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

1250

20, 31.5

M12-20-12S, M12-25-12SE

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/1600-081CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

TKA/TEL- MINEL

Retrofit of the following stationary type cubicles:

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12, 24

16, 20

up to 70

RO Minel Elektrooprema BEOGRAD Serbia Energoinvest Sarajevo

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12, 24

630, 1000

16, 20

PU, PUB, PUD

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-055ISM/TEL-24-16/800-058CM/TEL-XX/XX-12-02A

Distance between poles:210 mm 275 mm

20 Typical Adaptation Kits TKA/TEL TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 21: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL- D4X High Silhouette

Retrofit of the following switchgear types:

400

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

11

20

155

C4X (D4X) High Silhouette type, Hawker Siddeley Co, Blackwood, UK

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

11

400

20

C4X, D4X Hawker Siddeley Co, Blackwood, UK

Required Order Making Information:

Applicable types of ISM and CM:ISM/TELCM/TEL

Specialities:Modules are supplied fully-assembledModules are supplied fully-assembled

TKA/TEL- D4X Low Silhouette

Retrofit of the following switchgear types:

400

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

11

20

155

C4X (D4X) Low Silhouette type, Hawker Siddeley Co, Blackwood, UK

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

11

400

20

C4X, D4X Hawker Siddeley Co, Blackwood, UK

Required Order Making Information:

Applicable types of ISM and CM:ISM/TELCM/TEL

Specialities:Modules are supplied fully-assembledModules are supplied fully-assembled

21Typical Adaptation Kits TKA/TELTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 22: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL- LMT

Retrofit of the following switchgear types:

400

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

20

200

LMT, A. Reyrolle Co., UK

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

400

20

LMT 2

Required Order Making Information:

Applicable types of ISM and CM:ISM/TELCM/TEL

Specialities:Modules are supplied fully-assembledModules are supplied fully-assembled

TKA/TEL- BVP

Retrofit of the following switchgear types:

400

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

11

20

155

BVP type AEI Ltd. Manchester, UK

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

11

400

20

BVP-17, GEC Swithgear Ltd., Manchester, UK

Required Order Making Information:

Applicable types of ISM and CM:ISM/TELCM/TEL

Specialities:Modules are supplied fully-assembledModules are supplied fully-assembled

22 Typical Adaptation Kits TKA/TEL TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 23: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL- HL4-7

Retrofit of the following switchgear types:

630, 1000, 1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

20, 31.5

up to 125

HL4-7, Czech Republic

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

630, 1000, 1250

20, 31.5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12- /1600-082ISM/TEL-12-20/1000-051CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

31,5

Distance between poles:200 mm

TKA/TEL- 3AH, 3AF

Retrofit of the following switchgear types:

400, 630, 800, 1000, 1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

24

25, 31.5

up to 125

8BK-20, Siemens

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

24

800, 1000, 1250

25, 31.5

3AF, 3AH

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/1600-081CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

23Typical Adaptation Kits TKA/TELTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 24: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEL- K34

Retrofit of the following outdoor truck types:

630

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

10

up to 115

K-34

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

630

20

VMM-10

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

24 Typical Adaptation Kits TKA/TEL TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 25: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

3. Typical Adaptation Kits TKA/TEE

TKA/TEE-01-12, TKA/TEE-01-24

ITEA 685422.527-01 Manual trip and indication unit 1

ITEA 711671.004 Housing 3

ITEA 714323.001 Cover 3

ITEA 711121.002 Cap 3

ITEA 754152.002 Disc 3

ITEA 754463.016 Sticker Earth 2

ITEA 754342.056 Sticker "O” 1

ISO 7380 ISO 4032 ISO 8738 DIN 6796

Bolt M10x35 Nut M10

Washer 10 Washer 10

6666

How to choose:

Components:

Nominal Voltage, kV 12 TKA/TEE-01-12

Nominal Voltage, kV TKA/TEE-01-24 Insulating caps included

On request TEE can design a retrofit solution for any type of switchgear not mentioned in this guide. The design can be tailored to particular local manufacturing capabilities.

>12kV or insuficient clearances between live parts and from earth.

25Typical Adaptation Kits TKA/TEETEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 26: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEE-02-12, TKA/TEE-02-24

ITEA 301652.001 Manual trip and indication unit 1

ITEA 711671.004 Housing 3

ITEA 714323.001 Cover 3

ITEA 711121.002 Cap 3

ITEA 754152.002 Disc 3

ITEA 754463.016 Sticker Earth 2

ISO 7380 ISO 4032 ISO 8738 DIN 6796

Bolt M10x35 Nut M10

Washer 10 Washer 10

6666

How to choose:

Nominal Voltage, kV 12 TKA/TEE-02-12

Nominal Voltage, kV TKA/TEE-02-24 Insulating caps included

Components:

>12kV or insuficient clearances between live parts and from earth.

26 Typical Adaptation Kits TKA/TEE TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 27: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEE-04-12, TKA/TEE-04-24

ITEA 442611.024 Manual trip and indication unit 1

ITEA 711671.004 Housing 3

ITEA 714323.001 Cover 3

ITEA 711121.002 Cap 3

ITEA 754152.002 Disc 3

ITEA 754463.016 Sticker Earth 2

АРТА442611.004-01 Shaft extention unit 1

ITEA 713232.527 Coupler 1

How to choose:

Nominal Voltage, kV 12 TKA/TEE-04-12

Nominal Voltage, kV TKA/TEE-04-24 Insulating caps included

ITEA 304281.012 Compensator 1

Components:

>12kV or insuficient clearances between live parts and from earth.

27Typical Adaptation Kits TKA/TEETEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 28: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEE-05-12, TKA/TEE-05-24

ITEA 442611.024-01 Manual trip and indication unit 1

ITEA 711671.004 Housing 3

ITEA 714323.001 Cover 3

ITEA 711121.002 Cap 3

ITEA 754152.002 Disc 3

ITEA 754463.016 Sticker Earth 2

АРТА442611.004-01 Shaft extention unit 1

ITEA 713232.527 Coupler 1

How to choose:

Nominal Voltage, kV 12 TKA/TEE-05-12

Nominal Voltage, kV TKA/TEE-05-24 Insulating caps included

ITEA 304281.012 Compensator 1

Components:

>12kV or insuficient clearances between live parts and from earth.

KSO-2UM

28 Typical Adaptation Kits TKA/TEE TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 29: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEE-07

Retrofit of the following switchgear types:

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

К–XII K-XIII К-26 К-37

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

up to 125

КRU2-10 VMPE КRU2-10 VMPP КRU2-10 VMP-10K КRU2-10 VMP-10P

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000, 1600

20, 31.5

All VMPxxx series

TKA/TEE TKA/TEE-07

TKA/TEE-09 Adopted for manufacturing at TEL Asia

For replacing the Draw Out Units of the following types:

1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

31.5

up to 125

К–104 (К–204EP) КМ–1 КМV КМ–1F (ZZVA) КМ–1F (LEMZ)

КRUN–6(10)L КМ–1М К–47 К–49К–59

Applicable types of ISM and CM:ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

Cubicle Type (For KM-1F name of the factory ZZVA or LEMZ)

Main contact (Tulip) size, mm

7.2, 12

1600

31.5

VK-10 or VKE-10

36

Required Order Making Information:

29Typical Adaptation Kits TKA/TEETEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 30: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEE-10

Retrofit of the following switchgear types:

630, 1000, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

KR-10U4 KVG4-10 4КVS-9

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Interlock Type:

7.2, 12

630, 1000, 1600

20, 31.5

Interlockong unit ITEA442611.004 (UOBI)

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052ISM/TEL-12-31,5/1600-083CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

Type of the breaker to be replaced VMG-133, VMP-10K, VMPP-10, VMPE-10

up to 125

TKA/TEE-11

For replacing the Draw Out Units of the following types:

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

up to 115

К–104 (К–204EP) КМ–1 КМV КМ–1F (ZZVA) КМ–1F (LEMZ)

КRUN–6(10)L КМ–1М К–47 К–49К–59

Applicable types of ISM and CM:ISM/TEL-12-20/1000-046CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

Cubicle Type (For KM-1F name of the factory ZZVA or LEMZ)

Main contact (Tulip) size, mm

7.2, 12

630, 1000

20

VK-10 or VKE-10

24, 36

Required Order Making Information:

30 Typical Adaptation Kits TKA/TEE TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 31: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

TKA/TEE-12

Retrofit of the following type cubicles:

630, 1000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20

KSO-266KSO-272KSO-285KSO-292

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-052CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:250 mm

Based on TKA/TEL-12

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000

20

VMG–10, VMG–133, VMGP–10, VMPP–10, VMPE–10

TKA/TEE TKA/TEE-12

TKA/TEE-13

Retrofit of the following switchgear types:

630, 1000, 1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

up to 125

RSW-10/I

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

630, 1000, 1250

20, 31.5

ZWAR: WMSWPI-10/6/3,5 WMSWPI-10/12/3,5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-051ISM/TEL-12-31,5/1600-082CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:200 mm

31Typical Adaptation Kits TKA/TEE

K-IIIu,K-II,K-IV,K-VIu

TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 32: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Use of ТЕЕ Control Boxes provides customers with the following advantages:1. Compact placement of the Control Module and auxiliary wiring within the cubicle2. Simple and convenient interconnection to the existing auxiliary wiring3. Presence of the local control and main contacts position indication4. Protection of the CM/TEL from electromagnetic interference A control box with CM/TEL inside can be mounted on the front panel of a truck or a stationary cubicle.

PLEASE NOTE, THAT THE INSTALLATION OF THE CM/TEL WITHOUT A METAL COVER ON A FRONT PANEL IS PROHIBITED.

4. TEE Control Panels

Control Box TEE-01, Control Box TEE-02

Basic functions:

Control Box TEE-01with CM/TEL-X/X-12-01A

Control Box TEE-02with CM/TEL-X/X-12-03A

Dry contacts ON, OFF

Signalization FAILURE

Dry contacts ON, OFF

Signalization FAILURE

Signalization READYLocal control ON, OFF

Lamps OPEN, CLOSE

Emergency Power Supply

Current Power Supply

Close & Trip Supervisory

Emergency Trip & Reset

Signalization READY

Lamps OPEN, CLOSELocal control ON, OFF

Required Order Making Information:

Auxiliary Voltage, V

Resistor R1, R2, R3 nominals:

Model of CM/TEL: CM/TEL-X/X-12-01A

Control Box TEE Control Box TEE-01

CM/TEL-X/X-12-03A

Control Box TEE-02

Values to be chosen from Attachment 1

Metal 1,5mm thick

Auxiliary Voltage, V

Enclosure:

Dimensions, mm

Weight, kg

~230, =110,220

400x300x150

15

RP/TEE-NDINF-01, RP/TEE-IM30T-02 Relay Panels

Basic functions:RP/TEE-NDINF-01 RP/TEE-IM30T-02

Remote control ON, OFF

Local control ON, OFF

Remote control ON, OFF

Local control ON, OFF

Lamps OPEN, CLOSERemote lamps OPEN, CLOSE

Power supply changeover system

Protection relay IM30T

Local Lamps OPEN, CLOSE

Power supply changeover systemRemote lamps OPEN, CLOSE

Metal

Auxiliary Voltage, V

Enclosure:

Dimensions, mm

Weight, kg

220 DC

400x500x150

Required Order Making Information:

Auxiliary Voltage, VDC

Relay Panel RP/TEE-NDINF-01 RP/TEE-IM30T-02

10

Protection relay N-DIN-F

220 220

Protection Relay: N-DIN-F IM30T

Relay Protection Panels are designed for complete replacement of obsolete electromechnical protection relays in switchgear. Panels include CM/TEL and Protection Relays N-DIN-F or IM30T by Microelettrica Scientifica.

I>, I>>, TCC, Io>, Io>>, tw, I2>

32 TEE Control Panels TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 33: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

5. TEE Control Cables

CK-01 Cable Kit

1. LAPPKABEL OLFLEX-110 СY 30G0,5

Application: Designed for the interconnection between ISM and CM-01A. The CM-01A is installed inside the Control Box TEE - 01 which is mounted on the front of a draw-out unit.

Content Length, m Connector Shielded Cable

2. LAPPKABEL H07V-K 1x0,5(30)

3. LAPPKABEL OLFLEX-110 СY 30G0,5

4. HELUKABEL JZ-500 2x0,5

5. HELUKABEL JZ-500 16x0,5

6. LAPPKABEL H07V-K 1x2,5 Y/G

7. LAPPKABEL H07V-K 1x0,5

8. Cramp

2,4

1,5

2,5

2,5

2,5

0,5

20

SSHR-55

SSHR-55

YES

YES

CK-02 Cable Kit

1. LAPPKABEL OLFLEX-110 СY 30G0,5

Application: Designed for the interconnection between ISM and CM-01A. The CM-01A is installed inside the Control Box TEE - 01 which is mounted on the front of a stationary switchgear.

Content Length, m Connector Shielded Cable

2. LAPPKABEL OLFLEX-110 СY 30G0,5

3. HELUKABEL JZ-500 2x0,5

4. HELUKABEL JZ-500 16x0,5

5. LAPPKABEL H07V-K 1x2,5 Y/G

6. LAPPKABEL H07V-K 1x0,5

7. Cramp

2,4

2

2,5

0,65

0,5

20

YES

YES

CK-03 Cable Kit

1. LAPPKABEL OLFLEX-110 СY 30G0,5

Application: Designed for the interconnection between ISM and CM-01A/03A. The CM-01A/03A is installed inside the Relay Compartment. Applicable to draw-out units only.

Content Length, m Connector Shielded Cable

2. LAPPKABEL OLFLEX-110 30G0,5

3. HELUKABEL JZ-500 2x0,5

4. LAPPKABEL OLFLEX-110 18G0,5

5. LAPPKABEL H07V-K 1x2,5 Y/G

6. Cramp

2,4

2

2,5

2

0,5

SSHR-55

SSHR-55

YES

CK-04 Cable Kit

1. LAPPKABEL OLFLEX-110 СY 30G0,5

Application: Designed for the interconnection between ISM and CM-03A. The CM-03A is installed inside the Control Box TEE - 02 which is mounted on the front of a draw-out unit.

Content Length, m Connector Shielded Cable

2. LAPPKABEL H07V-K 1x0,5(30)

3. LAPPKABEL OLFLEX-110 СY 30G0,5

4. HELUKABEL JZ-500 2x0,5

5. HELUKABEL JZ-500 16x0,5

6. LAPPKABEL H07V-K 1x2,5 Y/G

7. LAPPKABEL H07V-K 1x0,5

8. LAPPKABEL OLFLEX-110 СY 5G2,5

2,4

1,5

2

2,5

0,65

0,5

20

SSHR-55

SSHR-55

YES

YES

9. LAPPKABEL OLFLEX-110 СY 18G0,5

10. LAPPKABEL H07V-K 1x0,5(18)

11. Cramp

2,4

1,5

2,5

SSHR-55

SSHR-55

YES

YES

33TEE Control CablesTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 34: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

CK-05 Cable Kit

1. LAPPKABEL OLFLEX-110 СY 30G0,5

Application: Designed for the interconnection between ISM and CM-03A. The CM-03A is installed inside the Control Box TEE - 02 which is mounted on the front of a stationary switchgear.

Content Length, m Connector Shielded Cable

3. LAPPKABEL OLFLEX-110 СY 18G0,5

3. LAPPKABEL OLFLEX-110 СY 30G0,5

4. HELUKABEL JZ-500 2x0,5

5. HELUKABEL JZ-500 16x0,5

6. LAPPKABEL H07V-K 1x2,5 Y/G

7. LAPPKABEL H07V-K 1x0,5

8. LAPPKABEL OLFLEX-110 СY 5G2,5

4

4

2,5

2,5

0,65

0,5

20

YES

YES

9. Cramp

2,5 YES

YES

CK-08 Cable Kit

1. LAPPKABEL OLFLEX-110 СY 30G0,5

Application: Designed for the interconnection between ISM and CM-01A/03A. The CM-01A/03A is installed inside the Relay Compartment. Applicable to draw-out units.

Content Length, m Connector Shielded Cable

2. LAPPKABEL OLFLEX-110 30G0,5

3. HELUKABEL JZ-500 2x0,5

4. LAPPKABEL OLFLEX-110 18G0,5

5. LAPPKABEL H07V-K 1x2,5 Y/G

6. Cramp

2,5

2

2,5

2

0,5

HARTING

HARTING

YES

34 TEE Control Cables TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 35: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

6. TKA/TEE International Retrofit Projects

Retrofit of the stationary cubicle of type:

2000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

31,5

К–11

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/2000-096CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:275 mm

TKA/TEE-K11

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

2000

31,5

VMGG

Interlocking Type Padlock and inner non-removable key-lock

How to place an order for TKA/TEE International Retrofit Projects.

The following information is required:1. Rated Voltage, kV2. Rated Current, A3. Rated breaking current, kA4. Type of circuit breaker to be replaced5. Switchgear Type6. Main tulip contacts inner diameter, mm

The example of order:

1. ISM/TEL-12-31,5/2000-096 2. CM/TEL-100/220-12-01A3. TKA/TEE is to be coordinated with Product Manager TEE

TEE has developed a set of drawings and instruction manuals for the switchgear types presented below. On request TEE can design a retrofit project for any particular type of switchgear. The design and the delivery kit of components can be tailored to customer manufacturing capabilities.

35TKA/TEE International Retrofit ProjectsTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 36: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Retrofit of the switchgear of type:

1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

31.5

Nuova Magrini

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/1600-066CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:150 mm

TKA/TEE-Nuova Magrini

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

1600

31.5

up to 125

Nuova Magrini

1250, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

31.5

Distance between poles:200 mm 250 mm

up to 125

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12

1250

31.5

RGSE12-50-1250

TKA/TEE TKA/TEE-SACE-1250

7.2, 12

1600

31.5

RGSE12-50-1600

TKA/TEE-SACE-1600

TKA/TEE-SACE Pergamo

Retrofit of the following switchgear types:

SACE Pergamo RGSE12-50-1250 SACE Pergamo RGSE12-50-1600

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/1250-082ISM/TEL-12-31,5/1600-083CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

36 TKA/TEE International Retrofit Projects TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 37: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Retrofit of the switchgear of type:

1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

31,5

BBC

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/1250-081CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

TKA/TEE-BBC

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

1250

31,5

up to 125

BBC (exact type should be specified)

Retrofit of the following switchgear types:

400, 630

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

-

8BDE LBS Fused 8BDE LBS

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-067CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:150 mm

TKA/TEE-8BDE-LBS-Siemens

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

400, 630

20

up to 125

3CB044 LBS with Fuses, 3CB044 LBS No fuses

37TKA/TEE International Retrofit ProjectsTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 38: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Replacement of the Draw-out Units of type FP BLRM

630, 1000, 1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12, 24

16, 20, 25, 31,5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-055ISM/TEL-24-16/800-057ISM/TEL-12-31,5/1250-081CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

TKA/TEE - Pars Switch

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12, 24

630, 1000, 1250

16, 20, 25, 31,5

up to 125

FP series BLRM

Draw-out Retrofit of the switchgear of type TSN

630

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

24

16

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-24-16/800-057CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

TKA/TEE-TSN

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

24

630

16

up to 115

TSN, Energoivest (the exact type should be specified)

* - For 24kV the max rated current is 800A

*

*

38 TKA/TEE International Retrofit Projects TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 39: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Replacement of the Cassette type DOU.

1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

25

Alstom

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-25/1250-081CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

TKA/TEE-Alstom

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

1250

25

up to 95

DOU

Replacement of the Draw-out Units of the following types:

800, 1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

31.5

NT10-108 NT10-203

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/800-066ISM/TEL-12-31,5/1250-081CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:150 mm 210 mm

TKA/TEE-EIB-NT

Rated Voltage, kV

Nomina l Current, ARated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2,12

800, 1250

31.5

up to 125

EIB Series VAV Union

39TKA/TEE International Retrofit ProjectsTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 40: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Retrofit of the switchgear of type Minel

2000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

31,5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/2000-095CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

TKA/TEE-Minel-Shell

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12

2000

31,5

up to 95

PU, PUD, PUC by Minel

Retrofit of the switchgear of type

1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

31,5

Energoinvest

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/1250-081CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

TKA/TEE-Energoinvest

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

6,12

1250

31,5

up to 125

Energoinvest

40 TKA/TEE International Retrofit Projects TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 41: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Retrofit of the switchgear of type

630

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2

20

ZWAR truck with WMSWP

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-055CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:210 mm

TKA/TEE-WMSWP

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2

1000

20

up to 115

WMSWP Pneumatic Drive, by ZWAR

Retrofit of the following switchgear types:

1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12

31.5

Electroputere ICMP7 CELPI

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/1250-066CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:150 mm

TKA/TEE-ICMP7

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2,12

1250

31.5

up to 125

ICMP Series

41TKA/TEE International Retrofit ProjectsTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 42: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Replacement of the Draw-out Units of types

630, 1000, 1250, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12, 24

20, 25, 31,5

CSI4

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/1600-081ISM/TEL-12-20/1000-055ISM/TEL-24-16/800-057CM/TEL-XX/XX-12-03ACM/TEL-XX/XX-12-02ACM/TEL-XX/XX-12-01A

Distance between poles:210 mm

TKA/TEE-CSI4

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

12, 24

630, 1000, 1250, 1600

20, 25, 31,5

up to 95

CSI4, by ZWAR

Retrofit of ROK Switchgear for Mining Industry of type

400

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2

20

ZEG ROK6 IP54

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-067CM/TEL-XX/XX-12-01A

Distance between poles:150 mm

TKA/TEE-ROK6

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of Conventional Load Break Switch

7.2

400

20

up to 1000

Load Break Switch

42 TKA/TEE International Retrofit Projects TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 43: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Retrofit of the switchgear of type

1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7,2

25

SACE Pergamo D6.25

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-25/1250-066CM/TEL-XX/XX-12-02A

Distance between poles:150 mm

TKA/TEE-SACE D6.25 Hungary

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7,2

1250

25

up to 100

SACE D6.25 air-blast type

Retrofit of the switchgear of type BOTO12 by Vertesz DOU by Transzvill under EIB licence

800, 1250

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12

20, 31.5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-055ISM/TEL-12-31,5/1250-081

Distance between poles:210 mm

TKA/TEE-EIB Transzvill Hungary

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of Conventional Load Break Switch

6, 12

800, 1250

20, 31.5

up to 140

EIB А/10/500/B

43TKA/TEE International Retrofit ProjectsTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 44: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

7. TE-1 Longitudinal Module

Replacement of ABB circuit breakers of types VD4R and HD4R or for new installations

630, 1000, 1250, 1600

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

7.2, 12, 24

16, 20, 31.5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-20/1000-067ISM/TEL-12-20/1000-055ISM/TEL-12-31,5/1250-066ISM/TEL-12-31,5/1600-081ISM/TEL-24-16/800-057ISM/TEL-24-16/800-058CM/TEL-XX/XX-12-01ACM/TEL-XX/XX-12-03A

Distance between poles:150 mm 210 mm 275 mm

TE-1

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Type of the breaker to be replaced

7.2, 12, 24

630, 1000, 1250, 1600

16, 20, 31.5

VD4R, HD4R

Interlocking Type Padlock and inner non-removable key-lock

up to 75

44 TE-1 Longitudinal Module TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 45: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

8. TM-XC Series Cassette

Replacement of ABB circuit breakers of type VD4.

630, 1250 and 2000

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Weight, kg

12, 17.5

25, 31.5

Required Order Making Information:

Applicable types of ISM and CM:ISM/TEL-12-31,5/2000-094ISM/TEL-12-31,5/2000-095ISM/TEL-12-31,5/2000-096ISM/TEL-17.5-25/2000-095ISM/TEL-17.5-25/2000-096CM/TEL-XX/XX-12-01A

Distance between poles:150 mm 210 mm 275 mm

TM-2C

Rated Voltage, kV

Rated Current, A

Breaking current, kA

Additional interlock

12, 17.5

630, 1250 and 2000

25, 31.5

Type of the breaker to be replaced VD4

up to 75

45TM-XC Series Cassette TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 46: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

9. Components for metal clad switchgear manufacturing

Draw Out Plates

Distance between poles :150, 210, 275

, mm

Contact ArmsRated current, A: 1250, 1600-2500, 3150Dimensions, mm:Ф50x158Ф50x209Ф80x180Ф115x182

Moving Contact

Rated current, A: 400, 630, 1250, 1600, 1600-2500Inner Diameter, mm:Ф18, Ф24, Ф33.2, Ф35, Ф36, Ф47.2, Ф77.2, Ф107.2

46 Components

Ground line joint-lock mechanism

Left or right side

Gear (umbrella) mechanism for an earthing switch

Earthing switch, EK-6 analogue, make type

12kV, 31.5, 40kA, 4 secDistance between poles : 150, 210, 275

, mm

Joint-lock mechanism for Auxiliary Contacts drive

12kV, 31.5, 40kA, 4 secDistance between poles :150, 210, 275

, mm

Set of the auxiliary contacts

FK series

Second plug joint-lock mechanism

Interlock for auxiliary circuits connector

Guide rails for draw-out plates

right slideleft slideSlide joint-lock

Live gate mechanism. Shutters

Distance per pole : 150, 210, 275

, mm

Fixed primary contacts

Rated current, A: 1250, 2500, 3150Dimensions, mm:Ф35x78Ф49x82Ф79x117Ф109x112

Fixed contacts insulator

Rated current, A:1250, 2500, 2500-3150, 4000

Through insulator for single and double busbarsRated current, A: 1250, 2500Dimensions, mm:Ф35x72Ф79x117

TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 47: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

10. Emergency Power Supply Sets

TEE-EPSS-01The Emergency Generator is manually operated by rotating the handle.

Used only with CM/TEL-XX/XX-03A

TEE-PSU-01An ORACLE Power Supply unit and a HAWKER Battery form a 12V UPS that provides VCB tripping and closing operations when the auxiliary supply is cut off.

Used together with CM/TEL-XX/XX-03A

11. Mounting Kits

TEE/RMK-02 Recloser Mounting Kit

Designation:

OSM/TEL-15,5-XXX-204 1, 2 sets of SA

OSM/TEL-27-XXX-205 1, 2 sets of SA

Pole types:

Round Wooden

Trapezoidal, Concrete

TEE/VTMK-06 Voltage Transformer Mounting Kit

Designation:

SADTEM OVF-12-1 / VE6

WTW VZF 12-03 / VZF 24-03

Pole types:

Round Wooden

Trapezoidal, Concrete

Emergency Power Supply inputs allow CM/TEL-XX/12-03A to be fed via a low-voltage source, such as a car-battery or the Emergency Generator. This feature ensures the closing ability of the ISM in case of the loss of the auxiliary power supply.

47ComponentsTEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 48: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

12. Accessories

Use of heat sinks is obligatory for ISM/TEL-12-20/1000 when rated current is above 800A. Please refer to Instruction Manual ver.4 dated 01.01.06 for details of installation.

Heatsinks set ITEA442611.010–01

Set content:

Heatsink ITEA 741394.006-01 6 pcs.

Plastic Head Bolts ITEA.301611.004-03

Set of fittings

12 pcs

12 sets

Use insulation hoods for ISM/TEL-12-20/1000 when isolation distance is not sufficient.The use of insulation hoods for rated voltages above 12kV is obligatory.

Insulation hoods set АRТА 305621.001

Set content:

Cover ITEA714323.001 3 pcs.

Hood IТЕА711671.004

Washer IТЕА754152.002

Disc IТЕА711121.002

3 pcs.

3 pcs.

3 pcs.

Use shaft extension for acquiring additional distance essential for some interlock arrangements. 280мм.

Shaft extention set ITEA442611.007

Set content:

Coupler IТЕА715112.007-01 1 pc.

Support IТЕА742133.010

Shaft IТЕА723116.050-01

Set of fittings

1 pc.

1 pc.

1 set

Please refer to Attachment 1 of the current document.All resistance values are available. Aluminum case. Pi = 5 x Nom

Arcol Resistors

Use the shaft interface for side interlock or manual trip arrangements.Shaft interface set АRТА 442611.004

Set content:

Fork IТЕА.751746.004 1 pc.

Coupler

Interface IТЕА.763176.004

Tapper washer

1 pc.

1 pc.

1 pc.

Set of fittings 1 pc.

Nominal Power, W:25, 50, 100, 200

Please refer to Attachment 5 of the current Instruction Manual for installation and usage details.Interference Suppressive Power Filters series F/TEL

Used for protection of ISM/TEL actuator coil circuit F/TEL-03

Used for protection of CM/TEL power supply circuitF/TEL-04

48 Accessories TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 49: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

Adjustment of the control inputs

This procedure is applicable for CM/TEL-X/X-12-02A,CM/TEL-X/X-12-03A.“Close & Supervision”, “Trip & Supervision”,“Alternative Trip & Supervision” inputs shall beadjusted to the required control voltage and cur-rent. This adjustment is achieved by the connec-tion of a proper external resistor to the relevantinputs (also see section “Control ModulesOperation”) and by selection of the control cur-rent with the aid of relevant selection switches(also see Section “Control Modules Design”).

For rated voltages not exceeding 60 V the criticalparameter of the external resistor (in addition to itsvalue R) is its rated power P.For rated voltages exceeding 60 V the critical param-eter is impulse power Pi , that can be absorbed bythe resistor during a 100 ms current pulse.These values are determined by rated voltage andcurrent of the input and shall be chosen in accor-dance with the following table. (See also Notesbelow the table.)

Note 1: The power ratings shown above ensure reliable operation of the external resistor in a static condition. Some resistors have extra sensitivity to temporary overloads caused by frequent switching operations or application of high energy lightning impulses. In these cases, the required rated power may exceed that shown in the table above.In case of doubt please contact the manufacture.Note 2: When choosing the value of R insure that it is less than the combined value of the resistors R, R1 and R3 connected in series with the supervision relays by at least 3.5 times ( also see Section “Destination and operation of inputs”). If this is not achieved then failure of a supervision relay coil to a short circuit condition could result in an uninstructed circuit breaker operation.Note 3: External resistors used shall be wire type and shall have a tolerance of ± 5% or better.

Rated voltage, V Parameter Rated control current, А

Ohm

W

Ohm

W

W

W

Ohm

W

W

Ohm

W

W

Ohm

W

W

Ohm

W

W

Ohm

W

W

Ohm

W

W

Ohm

W

W

49Attachment 1TEE PRODUCTS GUIDE FOR RETROFIT AND NEW INSTALLATIONS

Page 50: Retrofit Guide Eng3-2zam - LBT · This Module is designed for the replacement of ABB vacuum circuit breakers of type VD4 in the longitudinal switchgear or the application of brand-new

This document is copyright and is intended for users and distributors of Tavrida Electric product. It contains information that is the intellectual property of Tavrida Electric and the document, or any part thereof, should not be copied or reproduced in any form without prior permission from Tavrida Electric.Tavrida Electric applies a policy of ongoing development and reserves the right to change product without notice. Tavrida Electric does not accept any responsibility for loss or damage incurred as a result of acting or refraining from action based on information in this document.