Rev: May 07 -12
www.braycommercialdivision.comFax - 1-888-412-2720 Phone - 1-888-412-2729
Globe Valves
Glo
be
Va
lves
110
FeaturesGlobe Valve 2-Way & 3-Way Assembly Features:
DG Series Automated Globe ValvesApplications for Building Automation, Temperature Controls, HVAC
Two-Way and Three-Way Assemblies • Chilled Water • Hot Water • Steam
DG Series globe valves provide stable and accurate control of both water and steam heat exchangers on fan coil units, VAV reheat coils, and air handling units up to 900 GPM. These globe valves feature rangability of greater than 100:1 to provide precise control. Two way standard trim valves provide an equal percentage flow characteristic for use on hot water and chilled water.
Two way stainless trim valves - recommended for steam applications, and 3-way mixing valves provide a linear flow characteristic.
All DG series globe valves feature a cartridge style packing, which is easily replaceable while the valve is in line. Constant plug guiding and precision-machined metal to metal seating assures ANSI Class IV shutoff (.01%) which provides low leakage and energy conservation.
Features and Benefits:
Features
Valves
Benefits
Actuators
• Rangeability >100:1
• Cartridge Packing
• 2-Way and 3-Way bodies from 1/2" to 6"
• Stainless Steel Trim Option
• Broad range of spring return and non-spring return models
• Manual override capability
• Direct mount and linkage solutions
• Superior control accuracy
• Easily replaceable while valve is in line.
• Covers all applications from fan coil units to air handling units
• Applicable to steam inlet pressure up to 50 PSI
• Meets the requirements of virtually any heat exchanger control application
• Accommodates start-up commissioning and servicing
• More choices to meet more technical and economic requirements
www.braycommercialdivision.com Fax - 1-888-412-2720Phone - 1-888-412-2729
Glo
be V
alves
Globe Valves
111
SPECIFICATIONS
Globe Control Valves ½” through 2”Valves shall be cast bronze, ANSI 250 rating. Rangeability shall be 100:1 or greater. Connections shall be NPT.
Water valves shall have an equal percentage flow characteristic, brass plug and EPDM cartridge style packing which can be replaced with the valve in line. Steam valves shall have a linear flow characteristic, stainless steel plug, Teflon V-ring packings, and shall be suitable for up to 50 PSI steam inlet pressure.
Three way valves shall have a linear flow characteristic.
Globe Control valves 2-1/2” through 6”Valves shall be cast iron with ANSI 125 rating. Rangeability shall be 100:1 or greater. Connections shall be ANSI flanged.
Water valves shall have an equal percentage flow characteristic, brass plug and EPDM cartridge style packing which can be replaced with the valve in line. Steam valves shall have a linear flow characteristic, stainless steel plug, Teflon V-ring packings, and shall be suitable for up to 50 PSI steam inlet pressure.
Three way valves shall have a linear flow characteristic.
SpecificationsDG Automated Globe Valve Series Specifications
www.braycommercialdivision.comFax - 1-888-412-2720 Phone - 1-888-412-2729
Globe Valves
Glo
be
Va
lves
112
Globe ValveSpecification Charts
2-WAY & 3-WAY MIXING SIZES 1/2 ” - 2 ”, NPT
2-WAY & 3-WAY MIXING SIZES 2-1/2 ” - 6”, FLANGED
1/2” to 2” Screwed Valves, 2 & 3-Way Mixing 1/2” to 2” Screwed Valves, 2-Way
Bronze Body (UNS CA 844) Bronze Body (UNS CA 844)
Bronze (Standard Trim) Stainless Steel (noted by SS in the valve P/N)
Stainless Steel (ASTM A582 Type 303) Stainless Steel (ASTM A 582 Type 303)
EPDM O-Ring Teflon V-Ring/EPDM O-Ring
3/4” 3/4”
25 PSI (Water) / 15 PSI (Steam) 50 PSI Water or Steam
The flow characteristic is Equal Percentage for 2-Way valves with standard trim.
The flow characteristic is Linear for 3-Way valves and 2-Way valves with Stainless Steel trim.
Refer to Valve Selection Chart Refer to Valve Selection Chart
Class IV (0.01% of Cv) Class IV (0.01% of Cv)
>100:1 >100:1
2-1/2” to 6” Flanged Valves, 2 & 3-Way 2-1/2” to 6” Flanged Valves, 2-Way
Cast Iron Flanged Cast Iron Flanged
Bronze Stainless Steel (noted by SS in the valve P/N)
Stainless Steel (ASTM A582 Type 303) Stainless Steel (ASTM A582 Type 303)
EPDM O-Ring Teflon V-Ring/EPDM O-Ring
(3/4” stroke for 2-1/2“ & 3”valves) (3/4” stroke for 2-1/2“ & 3”valves)
( 1-1/2“ stroke for 4” - 6“ valves) ( 1-1/2“ stroke for 4” - 6“ valves)
25 PSI Water 50 PSI Water or Steam
The flow characteristic is Equal Percentage for 2-Way valves with standard trim.
The flow characteristic is Linear for 3-Way valves and 2-Way valves with Stainless Steel trim.
Refer to Valve Selection Chart Refer to Valve Selection Chart
Class IV (0.01% of Cv) Class IV (0.01% of Cv)
>100:1 >100:1
SizesValve Body -ANSI Class 250Valve Trim Required
Stem MaterialPackingStem LiftMaximum Recommended Differential
Flow Characteristic
Maximum Close-Off PressureLeakage RateRangeability
SizesValve Body -ANSI Class 125Valve Trim Required
Stem MaterialPackingStem Lift
Maximum Recommended Differential
Flow Characteristic
Maximum Close-Off PressureLeakage RateRangeability
FOR CHILLED/HOT WATER AND STEAM SERVICE: Chilled / Hot Water Steam (0-50 PSI Inlet)
FOR CHILLED/HOT WATER AND STEAM SERVICE:
Chilled / Hot Water Steam (0 PSI to 50 PSI Inlet)
˚F PSI
-20 to 150 400
-20 to 200 385
-20 to 250 365
-20 to 300 335
-20 to 350 300
-20 to 400 250
˚F PSI
-20 to 150 200
200 190
250 175
300 165
400 140
450 125
˚F PSI
-20 to 150 200
200 190
250 175
300 165
400 140
450 125
˚F PSI
-20 to 150 200
200 190
250 175
300 165
400 140
450 125
Maximum Fluid Temperature and Pressure
Maximum Fluid Temperature and Pressure
www.braycommercialdivision.com Fax - 1-888-412-2720Phone - 1-888-412-2729
Glo
be V
alves
Globe Valves
113
A
D E
C
B
3-W
AY M
IXIN
G&
DIV
ERTI
NG
2-W
AY
CA BCv D EConnection
GLOBEVALVE
MODEL#DG Size-Way-Cv
2.22.12.51/2 15DG05-2-03 15.0 4.9 7.4 188125381414409406404404414419422427417424
565656565866666674767979
5386
102127130160748699
125130160
125125125125125125125125125125125
188188188188188188188188188188188
2.23.46.33/4 20DG75-2-07 16.3 4.9 7.42.24.0101DG1-2-10 16.1 4.9 7.42.25.0161-1/4DG125-2-16 16.0 4.9 7.42.35.1251-1/2DG150-2-25 15.9 4.9 7.42.66.3402DG2-2-40 15.9 4.9 7.42.62.92.51/2DG05-3-03 16.3 4.9 7.42.63.46.33/4DG75-3-07 16.5 4.9 7.42.93.9101DG1-3-10 16.6 4.9 7.43.04.9161-1/4DG125-3-16 16.8 4.9 7.43.15.1251-1/2DG150-3-25 16.4 4.9 7.43.16.3402
25324050152025324050DG2-3-40 16.7 4.9 7.4
DIMENSIONS, 1/2 ” - 2 ”Please reference illustration above
in. mm in. mmin. mmin. mm in. mm in. mm
Globe Valve Dimensions1/2" - 2", 2 & 3-Way
Largest actuator dimension shownmultiple Cvs are available for 1/2" valves.
www.braycommercialdivision.comFax - 1-888-412-2720 Phone - 1-888-412-2729
Globe Valves
Glo
be
Va
lves
114
A
DETandem
C
B
3-W
AY M
IXIN
G&
DIV
ERTI
NG
2-W
AY
CA BCv D EConnection
GLOBEVALVE
MODEL#DG Size-Way-Cv
4.910.92-1/2 65DG250-2-63 24.8 4.9 4.9/8.6**4.9/8.6**4.9/8.6**4.9/8.6**4.9/8.6**4.9/8.6**4.9/8.6**4.9/8.6**4.9/8.6**4.9/8.6**
125/218**125/218**125/218**125/218**125/218**125/218**125/218**125/218**125/218**
125/218**
125630660699701724546622660787
820
12513516017820197
112130147
168
277300353401452277300353401
452
125125125125125125125125
125
5.311.83 80DG3-2-100 26.0 4.96.313.94DG4-2-160 27.5 4.97.015.85DG5-2-250 27.6 4.97.917.86DG6-2-400 28.5 4.93.810.92-1/2DG250-3-63 21.5 4.94.411.83DG3-3-100 24.5 4.95.113.94DG4-3-160 26.0 4.95.815.85DG5-3-250 31.0 4.9
6.617.86DG6-3-400 32.3 4.9
1001251506580
100125
150
6310016025040063
100160250
400
DIMENSIONS, 2-1/2 ” - 6”Please reference illustration above
in. mm in. mmin. mmin. mm in. mm in. mm
Globe Valve Dimensions2-1/2" - 6", 2 & 3-Way
Largest actuator dimension shown** indicates tandem mounted actuators
www.braycommercialdivision.com Fax - 1-888-412-2720Phone - 1-888-412-2729
Glo
be V
alves
Globe Valves
115Normally Closed (PDTO) Diverting View (3-Way)Normally Open (PDTC)
N.C. N.C.
N.O. N.O.
COM COM
Mixing (3-Way)
CommonPort
UpperPort
BottomPort
(NC)(C)
(NO)
CommonPort
UpperPort
BottomPort
(NC) (C)
(NO)
3-Way Mixing Globe Valve Set-Up for Diverting1) Non Spring Return valves are shipped B to AB (C to L on 2-1/2" through 6") at 0VDC.
2) Spring Return valves are shipped B to AB (C to L on 2-1/2" through 6") at 0VDC will fail B to AB.
Any configuration of fail open, fail closed, reverse acting or direct acting can be set up upon special request. All diverting globe valves will ship in the above configuration unless otherwise specified.
Note: 1/2" through 2" are labeled A, B, and AB. 2-1/2" through 6" are labeled U, C, and L.
3-Way Globe Valve Piping Schematics
Valve Operation
3-Way Mixing:Stem down = Flow from NC to C.
Stem up = Flow from NO to C.
Mixing Application - fluid enters through two inlets and exits through one outlet.
Diverting Application - fluid enters through one inlet and exits through two outlets.
3-Way Diverting:Stem down = Flow from C to NC.
Stem up = Flow from C to NO.
2-Way Valves:
1) Non Spring Return valves are shipped normally closed (stem down) at 0VDC.
2) Spring Return valves are shipped normally open (stem up) at 0VDC (fail open). 3-Way Mixing Valves: 1) Non Spring Return valves are shipped NO to C at 0VDC and will fail in last position.
2) Spring Return valves are shipped NO to C at 0VDC and will fail to NO to C.
Optional 3-Way Spring Return Valve Set-up:
1) Flow from NO to C at 0VDC with flow from NC to C at 10VDC. Fail with flow from NO to C.
2) Flow from NO to C at 10VDC with flow from NC to C at 0VDC. Fail with flow from NO to C.
3) Flow from NC to C at 0VDC with flow from NO to C at 10VDC. Fail with flow from NC to C.
4) Flow from NC to C at 10VDC with flow from NO to C at 0VDC. Fail with flow from NC to C.
Globe Valve Set-Up and Overview2 & 3-Way Mixing
www.braycommercialdivision.comFax - 1-888-412-2720 Phone - 1-888-412-2729
Globe Valves
Glo
be
Va
lves
116
VALVE SIZING STEPS - Liquid
STEP ONE
STEP TWO
STEP THREE
STEP FOUR
Determine the designed Cv by using the following equation.
Cv = Q G
Where = Flow in gallons per minute (GPM) required to pass through the valve= Specific gravity of fluid *= Designed pressure drop across the valve in PSI= Flow coefficient
QG
Cv
OPT
ION
1
LINE SIZE SIZE FOR PRECISE CONTROL
Determine whether the valve should be line size or sized to match the designed pressure drop(typical for modulating applications where precise control is required.)
Determine the actual pressure drop using the below equation.
Go to page 91, 92, Globe Valve Close-Off Charts. Using the line size, find a valve of the same size with a Cv that best matches the one calculated in Step 1.
Go to page 88 (2-way or 3-way), Globe Valve Piping Geometry Charts. Find the line size at the top of the chart. Scan down the page to the Cv that best matches the one calculated in Step 1.
OPT
ION
2
CvQ G
=2
Check to be sure that the close-off requirements are met. Refer to Pages 122 & 123
If the pressure drop is acceptable*, go to Step 4. If not, repeat Steps 2 and 3, selecting an alternate valve.
NO
TES * Specific gravity is negligible (equal to 1) for water below 200˚ F. Use actual specific gravity
of pure fluids other than water. In most cases, the valve selected for a H2O mixture will not be affected by the specific gravity.
EXA
MP
LE The Specific Gravity of 50% Water (Compound 1) and 50% Ethylene Glycol Solution (Compound 2):
Specific Gravity (G)wt% of Compound 2Specific Gravity (G)
= +1
G soln
wt% of Compound 1
1 0.51.0
0.51.113
1.05+= =Specific Gravity
Globe ValveLiquid Sizing
* Recommended to be no higher than 25 PSI or match the designed pressure drop, 3, 4, 5, and 6 PSI are commonly accepted for modulating applications.
www.braycommercialdivision.com Fax - 1-888-412-2720Phone - 1-888-412-2729
Glo
be V
alves
Globe Valves
117
VALVE SIZING STEPS - Steam
STEP ONE
STEP ONE
STEP TWO
When sizing a globe valve for a steam application, there are two methods of calculating the required Cv. The first method is to use the Steam Tables on pages 125 abd 126.The tables are based on the steam pressure and pounds per hour. These tables use the standard rule of an 80% pressure drop for modulating applications and a 10% pressure drop for on/off control. If the exact inlet pressure of the system is not referenced on the charts or a different pressure drop is desired, the following equations can also be used to calculate the required valve Cv.
Determine the proper pressure drop.For low pressure steam (15 PSIG or less) use a pressure drop that is 80% of the gauge inlet pressure.
Calculate the absolute outlet pressure (Po).
For higher pressure steam (greater than 15 PSIG) use a pressure drop that is 42% of the absolute inlet pressure.
= 0.8 x Pi (inlet pressure in PSIG)
Note: The below equations are designed for sizing globe valves please consult Bray if you desire to use a ball or butterfly valve.
Modulating Control:
On/Off Control:
For higher pressure steam (greater than 15 PSIG) use a pressure drop that is 10% of the absolute inlet pressure.
= 0.1 x Pi (inlet pressure in PSIG)
= 0.42 x Pi (inlet pressure in PSIA) Pi = Absolute Inlet Pressure = Gauge Pressure + 14.7
= 0.1 x Pi (inlet pressure in PSIA) Pi = Absolute Inlet Pressure = Gauge Pressure + 14.7
Po = Pi - Pi = Absolute Inlet Pressure = Gauge Pressure + 14.7
Po = Pi - Pi = Absolute Inlet Pressure = Gauge Pressure + 14.7
STEP TWO
Determine the proper pressure drop.For low pressure steam (15 PSIG or less) use a pressure drop that is 10% of the gauge inlet pressure.
Calculate the absolute outlet pressure (Po).
STEP THREE Calculate the valve coefficient (Cv) of flow.
Where:Cv = Valve coefficient of flowQ = Pounds per hour of steam = #/hr = Pressure drop across open valvePo = Outlet pressure in PSIA
STEP FOUR Refer to the below chart to select the proper trim for the application.
STEP THREE Calculate the valve coefficient (Cv) of flow.
Cv =Q
Where:Cv = Valve coefficient of flowQ = Pounds per hour of steam = #/hr = Pressure drop across open valvePo = Outlet pressure in PSIA
x Po
Cv =
3
3Q
x Po
GLO
BE V
ALV
E TR
IM S
ELEC
TIO
N
FLOWING MEDIA
Chilled / Hot Water
Low-Pressure Steam(0 - 15 PSI Intet)
Medium-Pressure Steam(16 - 50 PSI Intet)
High-Pressure Steam(51 PSI Intet and Greater)
GLOBE VALVE
Standard Trim
Stainless Steel Trim - SS
Stainless Steel Trim - SS
Consult Bray for Assistance
Globe Valve SizingSteam Application
www.braycommercialdivision.comFax - 1-888-412-2720 Phone - 1-888-412-2729
Globe Valves
Glo
be
Va
lves
118
- Globe ValvesAdjusted Cv 2-WAY 1/2” 3/4” 1” 1-1/4” 1-1/2” 2” 2-1/2” 3” 4” 5” 6” 8” 10”
DG05-2-01 1.00 1.00 1.00 1.00 --- --- --- --- --- --- --- --- ---
DG75-2-07 --- 6.30 6.20 6.10 6.10 --- --- --- --- --- --- --- ---DG1-2-10 --- --- 10.00 9.90 9.80 9.70 --- --- --- --- --- --- ---DG125-2-16 --- --- --- 16.00 15.90 15.70 15.50 --- --- --- --- --- ---DG150-2-25 --- --- --- --- 25.00 24.70 24.30 24.10 --- --- --- --- ---DG2-2-40 --- --- --- --- --- 40.00 39.70 39.30 38.80 --- --- --- ---DG250-2-63 --- --- --- --- --- --- 63.00 62.70 61.70 61.10 --- --- ---DG3-2-100 --- --- --- --- --- --- --- 100.00 98.70 97.30 96.30 --- ---DG4-2-160 --- --- --- --- --- --- --- --- 160.00 158.90 157.30 155.20 ---DG5-2-250 --- --- --- --- --- --- --- --- --- 250.00 248.70 245.00 242.50DG6-2-400 --- --- --- --- --- --- --- --- --- --- 400.00 394.80 389.10
1/2”
DG05-2-03 2.50 2.50 2.40 2.40 --- --- --- --- --- --- --- --- ---1/2”
DG05-2-04 4.00 3.80 3.70 3.60 --- --- --- --- --- --- --- --- ---1/2”
3/4”1”
1-1/4”1-1/2”
2”2-1/2”
3”
4”5”
6”
ValveSize
ValveModel
Number
Pipe Size
- Mixing & Diverting Globe ValvesAdjusted Cv 3-WAY 1/2” 3/4” 1” 1-1/4” 1-1/2” 2” 2-1/2” 3” 4” 5” 6” 8” 10”
1/2” DG05-3-01 1.00 1.00 1.00 1.00 --- --- --- --- --- --- --- --- ---
3/4” 6.10 6.10 --- --- --- --- --- --- --- ---1” DG1-3-10 --- --- 10.00 9.90 9.80 9.70 --- --- --- --- --- --- ---
1-1/4” DG125-3-16 --- --- --- 16.00 15.90 15.70 15.50 --- --- --- --- --- ---1-1/2” DG150-3-25 --- --- --- --- 25.00 24.70 24.30 24.10 --- --- --- --- ---
2” DG2-3-40 --- --- --- --- --- 40.00 39.70 39.30 38.80 --- --- --- ---2-1/2” DG250-3-63 --- --- --- --- --- --- 63.00 62.70 61.70 61.10 --- --- ---
3” DG3-3-100 --- --- --- --- --- --- --- 100.00 98.70 97.30 96.30 --- ---4” DG4-3-160 --- --- --- --- --- --- --- --- 160.00 158.90 157.30 155.20 ---5” DG5-3-250 --- --- --- --- --- --- --- --- --- 250.00 248.70 245.00 242.506” DG6-3-400 --- --- --- --- --- --- --- --- --- --- 400.00 394.80 389.10
1/2” DG05-3-03 2.50 2.50 2.40 2.40 --- --- --- --- --- --- --- --- ---
1/2” DG05-3-04 4.00 3.80 3.70 3.60 --- --- --- --- --- --- --- --- ---
ValveSize
Pipe Size
EXAMPLE
DG75-3-07 --- 6.30 6.20
ValveModel
Number
Globe ValvesAdjusted Cv Charts for Piping Geometry Charts Fp
What is the correct Cv rating for a DG 75-3-07 valve when placed in a 1” pipe?Look a the 1” pipe column and cross over to the valve model #. As you can see the correct Cv rating is 6.20.These values also apply to Stainless Steel trim valves where applicable.
www.braycommercialdivision.com Fax - 1-888-412-2720Phone - 1-888-412-2729
Glo
be V
alves
Globe Valves
119
Globe Valve Close-Off Chart2-Way
- Close-Off Chart (PSI)2-WAY DG Series
25025025013090806533
25018016013066201610
SIZE Cv MODEL #
200 20095402926
2-WAYModulating
NON SPRING RETURN ACTUATORS SPRING RETURN ACTUATORS
SIZE Cv MODEL #
NON SPRING RETURN ACTUATORS SPRING RETURN ACTUATORS
DCS24-62-P DS24-180
On/Off24VAC/DC
On/Off24VAC/DC
0(2)-10VDC0(4)-20mA •24VAC/DC
0-10VDC0-20mA •
24VAC/DC
DMS24-180DCMS24-62-P
Floating24VAC/DC
Floating24VAC/DC
DS24-180-TDS24-180D
On/Off24VAC/DC
0(2)-10VDC0(4)-20mA •24VAC/DC
DMS24-180D
Floating24VAC/DC
DS24-180-TDDCS24-62-TP
2-WAYOn/Off & Floating
100 20050 100
302416
11555
230110342818
170 230 250170 230 25080 110 235 25035 50 105 210155 23525 34 70 140105 155
30 60 12595 14050 75
DM24-53
0(2)-10VDC0(4)-20mA
24VAC
DM24-70
0(2)-10VDC0(4)-20mA24VAC/DC
0(2)-10VDC0(4)-20mA24VAC/DC
DM24-140
0(2)-10VDC0(4)-20mA24VAC/DC
DM24-210
0(2)-10VDC0(4)-20mA24VAC/DC
DM24-280 DCM24-310-P
0-10VDC0-20mA •
24VAC/DC
D24-53-T
Floating24VAC
D24-70
On/OffFloating
24VAC/DC
D24-140
On/OffFloating
24VAC/DC
D24-210
On/OffFloating
24VAC/DC
D24-280
On/OffFloating
24VAC/DC
0(2)-10VDC0(4)-20mA24VAC/DC
DM24-280D
D24-280D
On/OffFloating
24VAC/DC
DC24-310-TP
Floating24VAC/DC
DCM24-310-PD
0-10VDC0-20mA •
24VAC/DC
DC24-310-TPD
Floating24VAC/DC
1/2” 2.5 DG05-2-03X3/4” 6.3 DG75-2-07X
1” 10 DG1-2-10X1-1/4” 16 DG125-2-16X1-1/2” 25 DG150-2-25X
2” 40 DG2-2-40X2-1/2” 63 DG250-2-63X
3” 100 DG3-2-100X4” 160 DG4-2-160X5” 250 DG5-2-250X6” 400 DG6-2-400X
- Close-Off Chart (PSI)2-WAY VAL-SRS Series
SIZE Cv MODEL #
2-WAYVAL-SRS Series
Spring Return Actuators
NORMALLY OPEN NORMALLY CLOSED
9715363101
3925
654229 17
VAL-SRS07P VAL-SRS15P VAL-SRS07P VAL-SRS15P
2-1/2” 63 DG250-2-63XX/VAL-SRS07P
DG4-2-160XX/VAL-SRS15PDG5-2-250XX/VAL-SRS15PDG6-2-400XX/VAL-SRS15P
DG3-2-100XX/VAL-SRS07P3” 1004” 1605” 2506” 400
0-10VDC4-20mA24VAC
0-10VDC4-20mA24VAC
0-10VDC4-20mA24VAC
0-10VDC4-20mA24VAC
* Available in 120VAC.• Requiresfieldfurnished500Ohmresistor.D Indicates tandem mounted actuators are standard for higher close-off.XIndicates"N=NormallyOpen"or"C=NormallyClosed". Refer to the Actuator Section for a list of actuators with additional options (i.e. auxiliary switches etc.). When used in a Diverting Application, Differential Pressure should not exceed 22.5 PSI when fully open
XIndicates"N=NormallyOpen"or"C=NormallyClosed".
www.braycommercialdivision.comFax - 1-888-412-2720 Phone - 1-888-412-2729
Globe Valves
Glo
be
Va
lves
120
- Close-Off Chart (PSI)3-WAY VAL-SRS Series
SIZE Cv MODEL #
3-WAYVAL-SRS Series
Spring Return Actuators
NORMALLY OPEN - (Lower Port) NORMALLY CLOSED - (Upper Port)
9715363101
3925
654229 17
VAL-SRS07P VAL-SRS15P VAL-SRS07P VAL-SRS15P
2-1/2” 633” 1004” 1605” 2506” 400
DG250-3-63/VAL-SRS07P
DG4-3-160/VAL-SRS15PDG5-3-250/VAL-SRS15PDG6-3-400/VAL-SRS15P
DG3-3-100/VAL-SRS07P
0-10VDC4-20mA24VAC
0-10VDC4-20mA24VAC
0-10VDC4-20mA24VAC
0-10VDC4-20mA24VAC
- Close-Off Chart (PSI)3-WAY DG Series
25025025013090806533
25018016013066201610
SIZE Cv MODEL #
200 20095402926
3-WAYModulating
NON SPRING RETURN ACTUATORS SPRING RETURN ACTUATORS
SIZE Cv MODEL #
NON SPRING RETURN ACTUATORS SPRING RETURN ACTUATORS
DCS24-62-P DS24-180
On/Off24VAC/DC
On/Off24VAC/DC
0(2)-10VDC0(4)-20mA •24VAC/DC
0-10VDC0-20mA •
24VAC/DC
DMS24-180DCMS24-62-P
Floating24VAC/DC
Floating24VAC/DC
DS24-180-TDS24-180D
On/Off24VAC/DC
0(2)-10VDC0(4)-20mA •24VAC/DC
DMS24-180D
Floating24VAC/DC
DS24-180-TDDCS24-62-TP
3-WAYOn/Off & Floating
100 20050 100
302416
11555
230110342818
170 230 250170 230 25080 110 235 25035 50 105 210155 23525 34 70 140105 155
30 60 12595 14050 75
DM24-53
0(2)-10VDC0(4)-20mA
24VAC
DM24-70
0(2)-10VDC0(4)-20mA24VAC/DC
0(2)-10VDC0(4)-20mA24VAC/DC
DM24-140
0(2)-10VDC0(4)-20mA24VAC/DC
DM24-210
0(2)-10VDC0(4)-20mA24VAC/DC
DM24-280 DCM24-310-P
0-10VDC0-20mA •
24VAC/DC
D24-53-T
Floating24VAC
D24-70
On/OffFloating
24VAC/DC
D24-140
On/OffFloating
24VAC/DC
D24-210
On/OffFloating
24VAC/DC
D24-280
On/OffFloating
24VAC/DC
0(2)-10VDC0(4)-20mA24VAC/DC
DM24-280D
D24-280D
On/OffFloating
24VAC/DC
DC24-310-TP
Floating24VAC/DC
DCM24-310-PD
0-10VDC0-20mA •
24VAC/DC
DC24-310-TPD
Floating24VAC/DC
1/2” 2.5 DG05-3-03X3/4” 6.3 DG75-3-07X
1” 10 DG1-3-10X1-1/4” 16 DG125-3-16X1-1/2” 25 DG150-3-25X
2” 40 DG2-3-40X2-1/2” 63 DG250-3-63X
3” 100 DG3-3-100X4” 160 DG4-3-160X5” 250 DG5-3-250X6” 400 DG6-3-400X
Globe Valve Close-Off Chart3-Way
* Available in 120VAC.• Requiresfieldfurnished500Ohmresistor.D Indicates tandem mounted actuators are standard for higher close-off.XIndicates"N=NormallyOpen"or"C=NormallyClosed". Refer to the Actuator Section for a list of actuators with additional options (i.e. auxiliary switches etc.). When used in a Diverting Application, Differential Pressure should not exceed 22.5 PSI when fully open
www.braycommercialdivision.com Fax - 1-888-412-2720Phone - 1-888-412-2729
Glo
be V
alves
Globe Valves
121
Globe Valve - VAL-SRS07P & VAL-SRS15PFeatures and Benefits
The VAL-SRS07 and VAL-SRS15P Spring Return Electro Hydraulic Actuators provide precise modulating control of Bray SDF Series cast iron globe valves.
These actuators use electro hydraulic force to achieve superior close-off pressure ratings. The stroke of these actuators is up at the low input signal condition, and down in the high signal input condition.
A weather shield is available to offer a degree of protection against rain, sleet and damage from external ice formation.
Features and Benefits:• Provides high close-off pressure ratings
• Eases installation and minimizes space requirements
• Returns valve to the open or closed position upon loss of power
• Accepts current or voltage inputs
• Allows manual positioning during set-up or balancing
• Provides position feedback and provides for remote monitoring
High Output Force
Manual Override Handle
Visual and Electronic Position Indication
Spring Return Operation
User-Selectable Input Signals
Direct Mount to Bray SDF and STF Series Globe Valves
www.braycommercialdivision.comFax - 1-888-412-2720 Phone - 1-888-412-2729
Globe Valves
Glo
be
Va
lves
122
4 (100)
8 (200)
MINIMUM ACCESSSPACE REQUIRED
(24mm)
1-1/4 in.(44mm)
(10 or 14mm)
14-3/4 in.(375mm)
9-1/4 in.(235mm)
7 in.(178mm)
KNOCKOUTS FORSTANDARD 1/2"
CONDUIT CONNECTOR
3-1/2 in.(89mm)
5-1/2 in.(140mm)
3-1/2in.(89mm)
5-13/32 in.(137mm)
3 in.(76mm)
KNOCKOUTS FORSTANDARD 1/2"
CONDUIT CONNECTOR
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Bray office. Bray Controls shall not be liable for damages resulting from misapplication or misuse of its products.
VAL-SRS07P/SRS15P SERIES SPECIFICATIONS
Model NumberVAL-SRS07P 2-1/2” to 3“ valvesVAL-SRS15P 4” to 6“ valves
VAL-SRS07P 18.5 lb. (8.4 kg)VAL-SRS15P 21.4 lb. (9.7 kg)
VAL-SRS07P
24 VAC (±20%), 50/60 Hz
3/4" (20 mm)VAL-SRS15P 1-1/2" (40 mm)
VAL-SRS07P 18 VA NominalVAL-SRS15P 28 VA Nominal
Power Requirements
Control Input Signal
Input Impedance
Feedback Signal
Mechanical Output
Stroke Range
Nominal Stroke Timing
Ambient Operating Conditions
Current
Voltage 4 to 20 mA
0 to 10 VDC
CurrentVoltage 250 Ω
100,000 Ω
Input YInput R 4 to 20 mA
0 to 10 VDC
Stem Up 610 lb. (2684 N) (Spring return stroke)
Stem Down 1000 lb. (4400 N) (Power stroke)
Agency Compliance UL 873 Listed, C-UL C22.2 No. 24-93
Enclosure Rating NEMA 1, Weather shield available
Shipping Weight
Power Stroke 120 seconds
Return Stroke15 seconds for VAL-SRS07P20 seconds for VAL-SRS15P
5 to 130°F (-15 to 55°C), 10 to 90% RH, non-condensing,86°F (30°C) maximum dew point
Globe Valve - VAL-SRS07P & VAL-SRS15PActuator Dimensions
www.braycommercialdivision.com Fax - 1-888-412-2720Phone - 1-888-412-2729
Glo
be V
alves
Globe Valves
123
Globe Valve SizingUsing Steam Tables
* Indicates 2-Position Control Applications. Higher Pressure Drop for Modulating Control Applications. Note: Steam Capacity in Pounds per Hour. Table is Based on Saturated Steam.
0.4
0.95
0.99
1.1
1.3
1.8
2.2
2.5
3.3
3.6
3.8
4.0
5.0
5.5
6.0
6.2
7.4
7.5
8.2
8.5
9.0
10.5
11.0
15.0
16.0
17.4
25.0
35.8
40.0
45.0
0.5*
3.7
8.8
9.2
10.2
12.2
18.7
20.4
23
31
34
35
37
47
51
56
58
69
70
76
79
84
98
102
139
149
162
232
333
372
418
4
9.5
22.6
23.5
26.2
31
43
52
59
79
86
90
95
119
131
143
147
176
178
195
202
214
250
262
357
380
414
594
851
951
1070
1*
5.9
13.9
14.5
16.1
19
26.3
32
37
48
53
56
58
73
80
88
91
108
110
120
124
131
153
161
219
234
254
365
523
584
657
8
13.9
32.9
34.3
38.1
45.1
62.4
76
87
114
125
132
139
173
191
208
215
257
260
284
295
312
364
381
520
555
603
867
1241
1387
1560
1.5*
7.8
18.5
19.3
21.5
25.4
35.1
43
49
64
70
74
78
98
107
117
121
144
146
160
166
176
205
215
293
312
340
488
699
780
878
12
17.5
41.5
43.3
48.1
56.8
78.7
96
109
144
157
166
175
219
240
262
271
324
328
359
372
393
459
481
656
700
761
1093
1565
1749
1967
2*
9.7
23
24
26.7
31.5
43.7
53
61
80
87
92
97
121
134
146
150
180
182
199
206
218
255
267
304
388
422
607
867
970
1092
14
20.4
48.5
50.6
56.2
66.4
91.9
112
128
169
184
194
204
255
281
306
317
378
383
419
434
460
536
562
766
817
889
1277
1828
2043
2298
2.5*
11.6
27.5
28.6
31.8
37.6
52.1
63.6
72
95
104
110
116
145
159
174
179
214
217
237
246
260
304
318
434
463
503
723
1036
1157
1302
16
23.4
55.5
57.8
64.3
75.9
105.2
128.5
146
193
210
222
234
292
321
351
362
432
438
479
497
526
613
643
876
935
1016
1460
2091
2337
2629
4*
17.1
40.6
42.3
47
55.5
76.9
94
107
141
154
162
171
214
235
256
265
316
320
350
363
385
449
470
641
684
743
1068
1529
1709
1923
23
32.4
77
80.2
89.1
105.3
145.8
178
203
267
292
308
324
405
446
486
502
599
608
664
689
729
851
891
1215
1296
1409
2025
2900
3240
3645
5*
20.7
49.2
51.3
57
67.4
93.3
114
130
171
187
197
207
259
285
311
321
384
389
425
441
466
544
570
777
829
902
1296
1856
2073
2332
27
38.3
90.9
94.8
105.3
124.4
172.3
210.3
239
316
345
364
383
479
526
574
593
708
718
785
814
861
1005
1053
1436
1531
1665
2393
3427
3829
4307
7.5*
29.8
70.8
73.7
81.9
96.8
134.1
164
186
246
268
283
298
372
410
447
462
551
559
811
633
670
782
819
1117
1192
1296
1862
2667
2980
3352
37
53
126
131
146
172
238
291
331
437
477
503
530
662
728
795
821
980
994
1086
1126
1192
1391
1457
1987
2120
2305
3312
4742
5299
5961
10*
38.8
92.2
96.1
106.8
126.2
174.7
213.6
342
320
349
369
388
485
534
582
602
718
728
796
825
874
1019
1068
1456
1553
1689
2427
3475
3883
4368
48
68
161
168
187
221
306
373
424
560
611
645
679
848
934
1018
1052
1256
1273
1392
1443
1528
1782
1867
2546
2716
2954
4244
6077
6790
7639
2 5 10 15 20 25 40 50 75 100
Inlet Pressure (PSIG)Low-Pressure Steam (SSBS)
Inlet Pressure (PSIG)Medium-Pressure Steam (SS3) High-Pressure Steam (SS3)
Inlet Pressure (PSIG)
Cv0.2*
2.2
5.2
5.4
6
7.1
9.8
12
13.6
18
19.6
20.7
22
27
30
33
34
40
41
45
46
49
57
60
82
87
95
136
195
218
245
1.6
5.9
14
14.6
16.2
19.2
27
32.4
37
49
53
56
59
74
81
89
91
109
111
121
125
133
155
162
221
236
257
369
528
590
664
STEAM SIZING TABLE 1
www.braycommercialdivision.comFax - 1-888-412-2720 Phone - 1-888-412-2729
Globe Valves
Glo
be
Va
lves
124
Globe Valve SizingUsing Steam Tables
0.5* 4 1* 8 1.5* 12 2* 14 2.5* 16 4* 23 5* 27 7.5* 37
2 5 10 15 20 25 40 50 75
10* 48
100
0.2*
56
65
70
75
85
100
115
145
170
200
235
275
350
425
440
640
680
1125
1150
1750
1850
2600
2650
3400
4500
5400
7000
10000
521 1331 818 1942 1093 2448 1359 2860 1620 3271 2392 4536 2903 5360 4171 7418 5436 9506305 826
604 1545 949 2254 1268 2842 1577 3320 1881 3797 2777 5265 3369 6221 4842 8611 6310 11034354 958
651 1664 1022 2427 1366 3061 1698 3575 2025 4089 2991 5670 3628 6670 5214 9273 6795 11882381 1032
697 1783 1095 2601 1463 3279 1820 3830 2170 4381 3204 6075 3887 7179 5587 9935 7280 12731409 1106
790 2021 1241 2947 1658 3716 2062 4341 2459 4966 3631 6885 4406 8136 6332 11260 8251 14429463 1253
930 2377 1460 3468 1951 4372 2426 5107 2893 5842 4272 8101 5183 9571 7449 13247 9707 16975545 1475
1069 2734 1680 3988 2244 5028 2790 5873 3327 6718 4913 9316 5961 11007 8566 15234 11163 19521627 1696
1348 3447 2118 5028 2829 6340 3518 7405 4195 8471 6195 11746 7516 13878 10801 19208 14075 24613790 2138
1580 4042 2483 5895 3177 7433 4124 8682 4918 9931 7263 13771 8811 16271 12663 22519 16502 28857926 2507
1859 4755 2921 6935 3902 8744 4852 10214 5786 11684 8544 16201 10366 19143 14898 26494 19414 339501090 2949
2184 5587 3432 8149 4585 10275 5701 12002 6799 13729 10040 19036 12180 22493 17505 31130 22812 398911281 3465
2556 6538 4016 9536 5366 12024 6672 14044 7956 16065 11749 22277 14254 26321 20484 36429 26695 466811499 4055
3253 8321 5112 12136 6829 15303 8491 17875 10126 20447 14953 28352 18141 33500 26071 46264 33975 594121907 5161
3950 10104 6207 14737 8292 18582 10311 21705 12296 24828 18157 34427 22028 40678 31658 56300 41256 721432316 6267
4090 10461 6426 15257 8585 19238 10675 22471 12730 25704 18798 35642 22806 42114 32775 58287 42712 746892398 6488
5949 15215 9347 22192 12487 27982 15527 32685 18516 37388 27342 51844 33172 61257 47672 84781 62126 1086393488 9437
6321 16166 9931 23579 13268 29731 16498 34728 19673 39725 29051 55084 35245 65085 50652 90080 66009 1154293706 10027
10457 26746 16430 39010 21950 49187 27294 57454 32547 65722 48063 91131 58310 107678 83799 149029 109206 1909676131 16589
10689 27340 16796 39877 22438 50280 27900 58731 33271 67182 49131 93156 59606 110071 85661 152341 111633 1952106267 16958
16267 41604 25558 60682 34145 76513 42457 89373 50629 102234 74764 141760 90705 167499 130354 231823 169876 2970599537 25805
17196 43982 27019 64150 36096 80885 44883 94481 53522 108076 79036 149860 95888 177070 137803 245070 179583 31403410082 27280
24167 61812 37972 90157 50730 113677 63079 132783 75220 151890 111078 210614 134762 248855 193669 344422 252388 44134514169 38339
24632 63001 38703 91890 51706 115863 64292 135337 76667 154811 113214 214665 137353 253641 197394 351046 257241 44983214442 39076
31604 80831 49656 117897 66339 148654 82488 173640 98365 198625 145256 275419 176227 325426 253260 450398 330045 57714318529 50136
41828 --- 65722 --- 87802 --- 109175 --- 130189 --- --- --- --- --- --- --- --- ---24524 66356
50194 --- 78866 --- 105362 --- --- --- --- --- --- --- --- --- --- --- --- ---29429 79628
65066 --- 102234 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---38148 ---
92952 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---54498 ---
1.6
STEAM SIZING TABLE 2
Inlet Pressure (PSIG)Low-Pressure Steam (SSBS)
Inlet Pressure (PSIG)Medium-Pressure Steam (SS3) High-Pressure Steam (SS3)
Inlet Pressure (PSIG)
Cv
* Indicates 2-Position Control Applications. Higher Pressure Drop for Modulating Control Applications. Note: Steam Capacity in Pounds per Hour. Table is Based on Saturated Steam.