RHEEM COMMERCIAL WATER HEATING TRAINING. TRAINING COURSE OBJECTIVES. Introduction to Rheem Commercial Booklet Range appreciation Familiarise key design / installation criteria Introduction to manifolding Introduction to sizing Value added service. Commercial Water Heating course contents. - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/1.jpg)
RHEEM COMMERCIAL WATER HEATING TRAINING
![Page 2: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/2.jpg)
TRAINING COURSE OBJECTIVES
• Introduction to Rheem Commercial Booklet• Range appreciation• Familiarise key design / installation criteria• Introduction to manifolding• Introduction to sizing• Value added service
![Page 3: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/3.jpg)
Commercial Water Heating course contents
• Chapter 1 - Range overview - Commercial Booklet• Chapter 2 - Heat Pump • Chapter 3 - Commercial Solar• Chapter 4 - Equaflow Manifolding • Chapter 5 - Commercial Continuous Flow• Chapter 6 - Commercial Storage Gas systems• Chapter 7 - Raypak Heating and Hot Water• Chapter 8 - Commercial Electric• Chapter 9 - Guardian Warm Water • Chapter 10 – Pump Sets• Chapter 11 - Sizing and Selecting• Chapter 12 - Commercial installation and design
![Page 4: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/4.jpg)
Chapter 1
Range Overview&
Rheem Commercial Booklet
![Page 5: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/5.jpg)
Chapter 2 - Commercial Heat Pump
![Page 6: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/6.jpg)
COMMERCIAL HEAT PUMP LAYOUTS
![Page 7: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/7.jpg)
COMMERCIAL HEAT PUMP LAYOUTS
![Page 8: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/8.jpg)
Chapter 3 - Commercial Solar
![Page 9: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/9.jpg)
Commercial Solar
• Terminology– Split / Pumped / Loline– Close Coupled / Thermosiphon / Hiline– Direct / Indirect (Premier Hiline)
![Page 10: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/10.jpg)
Commercial Solar Loline
![Page 11: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/11.jpg)
Commercial Solar Loline
• Pumped system– Collectors and tank are split– Fluid is pumped between collectors and tanks– Can be on same level or different levels
• Direct system– Consumed water passes through the collectors– Partial frost protection
• In series boost
![Page 12: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/12.jpg)
![Page 13: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/13.jpg)
Commercial Solar Loline
• 325L and 410L vitreous enamel storage tanks– Manifold tanks as required
• NPT200 collector– Painted aluminium selective surface– 7 riser tubes– Good performance in all regions
![Page 14: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/14.jpg)
Commercial Solar Loline• Frost– Limited frost protection– Frost sensor strategy– Electric or gas frost heater
• Secondary Solar Recirculation– Maximum solar energy use– reduces energy use
• BMS output– Run and fail status
![Page 15: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/15.jpg)
Commercial Solar Premier Hiline
![Page 16: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/16.jpg)
Commercial Solar Premier Hiline• Thermosiphon system– Collectors and tank are close coupled– Fluid rises through collectors naturally to tank– Tank is always above collectors
• Indirect system– Transfer fluid passes through the collectors and
transfers heat to tank via heat exchanger– Full frost protection
• In series or in- tank electric boost
![Page 17: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/17.jpg)
Commercial Solar Premier Hiline
• 300L stainless steel tank• Manifold systems as required• 8 systems per array, multiple arrays possible• S200 collector– Steel collector– Painted selective surface– Good performance in all regions
![Page 18: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/18.jpg)
![Page 19: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/19.jpg)
Flat Plate vs Evacuated TubeCollectors
![Page 20: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/20.jpg)
EQUA-FLOW MANIFOLDING
Chapter 4
![Page 21: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/21.jpg)
EQUA-FLOW BASICS
![Page 22: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/22.jpg)
EQUA-FLOW BASICS
In Line
• Header diameters for cold/hot to be equal• Branch diameters for cold/hot to be equal• Hydraulic water flow “In one side, out the opposite”• Balanced performance per unit. Full delivery capacity from system
Flow direction In
Flow direction
Out
![Page 23: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/23.jpg)
Back to Back
Flow direction In
Flow direction
Out
EQUA-FLOW BASICS
![Page 24: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/24.jpg)
1 1
0A
B
0+1+1=2
EQUA-FLOW BASICS
![Page 25: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/25.jpg)
11
A
B 1 1
PATH of LEAST RESISTANCE
![Page 26: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/26.jpg)
MORE EQUA-FLOW PRINCIPLES
21
2
1
A
B
0+2+1+1+2=6 1+2+1+2=6 1+2+2+1+0=6
![Page 27: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/27.jpg)
ANGLED MANIFOLD 3 + bend1
1 3 + bend
B
A
![Page 28: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/28.jpg)
BACK TO BACK MANIFOLD
0.75
H6:0.75+1+1 = 2.75
H4:0.75+1+1 = 2.75
H2:0.75+1+1 = 2.75
11
H1:0+1+1+0.75 = 2.75
H3:1+1+0.75= 2.75
H5:1+1+0.75 = 2.75
A
B
10.75 1
![Page 29: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/29.jpg)
EQUAFLOW PRINCIPLES IN PRACTICE
![Page 30: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/30.jpg)
When designing/ inspecting complicated manifolds consideration must be given to primary loops as well as hot and cold headers
COMPLICATED EQUAFLOW PRINCIPLES IN PRACTICE
![Page 31: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/31.jpg)
EQUAFLOW PRINCIPLES IN PRACTICE
![Page 32: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/32.jpg)
COMPLICATED EQUAFLOW PRINCIPLES IN PRACTICE
![Page 33: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/33.jpg)
BRANCHES• NEVER use non-return valves or pressure
limiting valves in the branch– These create imbalance in the branches
• Non-return and pressure reducing valves must be in a train on the cold water inlet
COLD WATER SUPPLY
TO WATER HEATER MANIFOLD
![Page 34: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/34.jpg)
BRANCHES• Last branch should be
a T piece, not an elbow, to maintain equal resistance in all branches
T PIECE
![Page 35: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/35.jpg)
Chapter 5 - Commercial CFWH
![Page 36: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/36.jpg)
RHEEM INDOOR CFWH – FLUE SYSTEMSUSE MM AND FF ADAPTERS IF HORIZONTAL LENGTH OF HORIZONTAL TERMINATING FLUE EXCEEDS 2.7M
TRIM
RING
USE CONDENSATE DRAIN & TRAP IF VERTICAL SECTION OF HORIZONTAL TERMINATING FLUE EXCEEDS 2M
![Page 37: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/37.jpg)
Rheem Multipak, Tankpak, Commpak and Commpak PlusCommercial Continuous Flow
Hot Water Solutions
![Page 38: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/38.jpg)
![Page 39: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/39.jpg)
Chapter 6 - Commercial Gas Storage
![Page 40: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/40.jpg)
RHEEM Commercial Gas Storage
• Work horse of the industry• 3 input sizes – 50, 110, 200MJ/hr• Indoor and outdoor models• Multi-fin flue technology• Flue damper• Hot Surface Ignition• Up to 82oC• Room sealed flue
![Page 41: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/41.jpg)
HD Gas Layout
![Page 42: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/42.jpg)
631275 Room Sealed Flue• Converts outdoor model to indoor room sealed• Ideal where no ventilation, contaminated air
supply or fluing to roof impractical• 3m and 3 x 90o bends• Re-use flue terminal• Kit P/No 299135
![Page 43: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/43.jpg)
![Page 44: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/44.jpg)
Chapter 7 – Raypak Heating and Hot Water
![Page 45: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/45.jpg)
Raypak Layouts
![Page 46: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/46.jpg)
Chapter 8 - Commercial Electric Storage
![Page 47: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/47.jpg)
RHEEM Commercial Electric Storage
• Work horse of the industry• 2 x 3 element models – 50 & 315L• 1 x 6 element model – 315L• Up to 36kW output• Indoor and outdoor installation• Heavy Duty enamel• Larger anode• Models up to 82oC
![Page 48: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/48.jpg)
HD Electric Layout
![Page 49: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/49.jpg)
Chapter 9 - Rheem Guardian Warm Water
![Page 50: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/50.jpg)
Chapter 10 - Pump Sets
![Page 51: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/51.jpg)
Deluxe Pump Sets
• Deluxe Models• UPS 20-60N and 32-80N pumps• Individual Auto, Off, Manual switches• Individual Run and Fail indicators• Timer control• Isolation and check valves included• BMS output
![Page 52: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/52.jpg)
Standard Pump Sets
• Standard Models• UPS 20-60N and 32-80N pumps• Single Auto, Off, Manual switch• Timer control• Isolation and check valves included
![Page 53: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/53.jpg)
Chapter 11
• Sizing and selecting...
![Page 54: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/54.jpg)
Energy Consumption It takes 4.2kJ of heat energy to raise 1litre of water (or 1 kg)
of water 1 degreeE = L x 4.2 x dT
Example : To raise 500 litres by 32 degrees (from 10C to 42C)Energy consumption = 500 x 4.2 x 32 = 67,200kJ or 67.2MJ
Plant efficiency must also be considered. If the plant operates at 80% efficiency, then;Energy required = 67.2 / 0.8 = 84MJ
![Page 55: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/55.jpg)
Typical Hot Water Usage Assumptions
OfficesOffice peak period 60 minutes– Water per person 0.5 litres – Area per person 10m2
– Occupants
Gymnasium peak period 30 minutes– Water per person 25 litres
![Page 56: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/56.jpg)
Typical Hot Water Usage AssumptionsFood ServiceRestaurant Peak Period – 2 hours(temperature requirements) – Bistro per Meal 5.0 litres– Coffee Shop per Meal 3.5 litres– Auditorium per Meal 3.0 litres– Restaurant per Meal 5.5 litres– Takeaway Shop per Meal– Café per Meal 3.0 litres– Hotel Kitchen per Meal 6.0 litres
![Page 57: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/57.jpg)
Typical Hot Water Usage Assumptions
ApartmentsPeak period 60 minutes
– Bed-sitter 25 litres– 1 Bedroom 40 litres– 2 Bedroom 70 litres– 2 Bedroom w/en suite 75 litres– 3 Bedroom 80 litres– 3 Bedroom w/en suite 90 litres– 4 Bedroom 100 litres– Penthouse 150 litres
![Page 58: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/58.jpg)
![Page 59: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/59.jpg)
Typical Hot Water Usage Assumptions
MotelMotel peak period 60 minutes(Assume 2 people per room)– Shower 1 & 2 Star 20 litres /person– Shower 3 Star 25 litres /person– Shower 4 Star 30 litres /person– Shower 5 Star 45 litres /person– Shower Family/Spa 100 litres /person
![Page 60: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/60.jpg)
Sizing example...
• Motel• 100 rooms• 5 star accommodation• Central electric plant• Moderate climate• Refer to commercial booklet...
![Page 61: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/61.jpg)
Sizing example... Motel
• Showers = 50 x 2x 45 = 4,500L/1hr peak• Moderate climate = 50oC rise• Central electric plant:– 5 x 616315 with 6 x 6kW elements
![Page 62: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/62.jpg)
Hot Water Usage Assumptions
Nursing HomePeak period 180 minutes– Bedpan 2.5 litres / bed– Shower 25 litres / bed– Cleaning water 10 litres / bed– Water per meal 5.5 litres
Laundry peak 300 minutes– Laundry (1.2kg per bed) 10 litres / kg
![Page 63: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/63.jpg)
Selecting a water heating system
• Usage profiles...Have they changed?• Peak Period in Litres/hr (e.g. 1hr)• Redundancy• Daily Load in Litres (Solar)...• Water delivery Temperatures• Plant Location - Indoor or Outdoor• Flue location & termination (room sealed?)• Circulation Systems...considerations
![Page 64: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/64.jpg)
Sporting Facility Case StudyFootball Club - Tasmania
![Page 65: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/65.jpg)
Sizing example...
• Local football club• 15 shower outlets @ 6 litres per minute (hot)• 35 players inc umpires• Commercial heat pump system• Refer booklet...
![Page 66: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/66.jpg)
Sizing example...
• Players and Umpires = 35• Shower time, say 10 mins• Peak duration = 30mins• Showers = 35 x 6L/min x 10 = 2,100 litres• Plant selection:• 6 x 610430 storage tanks• 1 x 953022 heat pump• Recovery @10C ambient =244L/hr = 9hrs
![Page 67: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/67.jpg)
SELECTION & SIZING...
• Diversity...• The difference between the maximum possible load on
a water heating system if all outlets were in use at once and the “likely” load at any given time.
• Example... • In a multi story accommodation building, only a
predictable percentage of taps will be turned on at any given time, however it can be expected that all taps in a shower block of a sporting facility can be turned on at once and will require full heated water flow.
![Page 68: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/68.jpg)
SELECTION & SIZING
CFWH PLANT or STORAGE PLANT... What to consider?• Footprint availability e.g. solar• Storage volume?• Maintenance/removal• Flow rates• Gas and water pressure• Fluing• Energy/fuel types
![Page 69: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/69.jpg)
Chapter 12
• Commercial Installation and Design Requirements
![Page 70: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/70.jpg)
82oC Dead Leg Operation
![Page 71: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/71.jpg)
Primary Pump Requirements• Used for Raypak, Solar and Heat Pump• Non return valve is not required after primary pump.• Spindle must be horizontal• Pump is not weather proof – must be covered
Primary Pump
Isolation Valve
Note: Pump
shaft must be
horizontal
![Page 72: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/72.jpg)
NOT EQUA-FLOW
PUMP SPINDLE VERTICAL
![Page 73: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/73.jpg)
Clearances
![Page 74: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/74.jpg)
CASE STUDY #2Rheem Commercial Water Heating Systems
Rheem Solar preheated, gas storage with a warm water system.
![Page 75: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/75.jpg)
Commercial application – Large nursing home
![Page 76: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/76.jpg)
Including a commercial laundry
![Page 77: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/77.jpg)
Commercial kitchen
![Page 78: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/78.jpg)
Commercial sinks
![Page 79: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/79.jpg)
Electric boost on sink
![Page 80: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/80.jpg)
Commercial dishwashing machine
![Page 81: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/81.jpg)
Water must be at sanitizing temperature i.e. 77 degrees
![Page 82: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/82.jpg)
The solar arrayTo achieve the energy rating for the building, solar has been chosen.
Often solar is a preferred method to achieve the energy reduction on site.
Note - north facing collectors
Note - the fall protection
The panels are set in two arrays of 8 collectors
![Page 83: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/83.jpg)
16 Rheem solar panels – ‘primary source of heat’
Each square meter(approx) of panel requires approx. 60 litres of solar storage tank capacity!
![Page 84: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/84.jpg)
Collector connections
![Page 85: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/85.jpg)
Primary flow and return to solar panels.
![Page 86: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/86.jpg)
Temperature probe wired to solar controller and to the circulating pump. It works on a 8 degree C differential.
![Page 87: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/87.jpg)
Automatic air eliminator on the return line out of the panels.
![Page 88: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/88.jpg)
The return hot water line to storage tanks
Note the pipe insulation to reduce heat loss which is measured in ‘ watts ‘ per meter
Lagging must be UV resistant and meet AS3500.4
![Page 89: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/89.jpg)
Four Rheem 430 litre solar storage cylinders
( 1720 litre capacity )
![Page 90: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/90.jpg)
Rheem Gas boost mains pressure storage units.
![Page 91: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/91.jpg)
Rheem Solar controller
Green light indication of system cycle.
Note - the solar return pipe work from the panels.
![Page 92: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/92.jpg)
Primary flow and return from solar panels
Note – the isolation valves
Note – the pipe lagging
![Page 93: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/93.jpg)
Commercial site assistance
![Page 94: RHEEM COMMERCIAL WATER HEATING TRAINING](https://reader035.vdocument.in/reader035/viewer/2022070414/56814e3e550346895dbba8a3/html5/thumbnails/94.jpg)
THANK YOU FOR YOUR TIME TODAY
• We trust you have enjoyed and benefited from this training course...