Roll Paper ProtectionSeth Sienkiewicz
FM Global Research
![Page 2: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/2.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 2/22
FM Global
Outline
Meeting Evolving Needs
Roll Paper Hazard
Mitigating the Hazard
Large-Scale Fire Tests
Conclusions
![Page 3: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/3.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 3/22
FM Global
Meeting Evolving Needs
![Page 4: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/4.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 4/22
FM Global
![Page 5: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/5.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 5/22
FM Global
Roll Paper Hazard
Characteristics
Easily Ignitable
Extremely Fast Fire Growth
Intense Fire Plume
Contributors
Storage Configuration
Paper Type/Weight
Exfoliation
![Page 6: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/6.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 6/22
FM Global
Storage Configuration
H
a
z
a
r
d
S t a c k H e i g h t
![Page 7: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/7.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 7/22
FM Global
Storage Configuration
H
Pr
IgnitionLocation
Open Arra
Ignition
Location
PrimHoriz
FlaPropa
H
a
z
ar
d
F l u e S i z e
Standard A
![Page 8: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/8.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 8/22
FM Global
Paper Weight
H
a
z
a
r
d
P a p e r W e i g h t
![Page 9: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/9.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 9/22
FM Global
Exfoliation
Provides Virgin Fuel
Removes Pre-wetted
Paper
Spreads Fire to Adjacent Commodity
![Page 10: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/10.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 10/22
FM Global
Mitigating the Hazard
Stack Height
Paper Type
Flue Spaces
Banding
![Page 11: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/11.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 11/22
FM Global
Research Question
Can rolls of heavyweight paper, butted in one
direction, be protected the same regardless of
whether or not they are banded?
![Page 12: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/12.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 12/22
FM Global
![Page 13: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/13.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 13/22
FM Global
~24 ft
~19 ft
All Stacks
Butted In N-SDirection
Standard Array
![Page 14: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/14.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 14/22
FM Global
Ceiling Sprinkler Protection
K115 Upright Sprinklers
Standard Response
Temperature Rating – 141°C
Water Pressure – 1.0 Bar
Discharge Density – 14 lpm
Sprinkler Spacing – 3.0 m by 3.0 m
![Page 15: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/15.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 15/22
FM Global
Evaluation Criteria
No fire spread to the remote end of the array
Number of sprinkler activations acceptable
No excessive steel temperatures at ceiling
– ≥1,000°F for 1 minute duration – ≥1,200°F instantaneous
![Page 16: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/16.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 16/22
FM Global
Results
Banded
Un-Banded
~ 0 1
: 3 0
~ 0 3
: 3 0
![Page 17: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/17.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 17/22
FM Global
Results: 1st Sprinkler Activation
Banded Un-Banded
![Page 18: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/18.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 18/22
FM Global
Results: ~3:30 min
Banded Un-Banded
![Page 19: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/19.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 19/22
FM Global
Results: ~7:00 min
Banded Un-Banded
![Page 20: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/20.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 20/22
FM Global
Results
FIRE TEST RESULTS
Test ID Banded Un-B
Total Sprinklers Opened 18
First / Last Sprinkler Operation Times (min:s) 1:29 / 3:32 1:10
Maximum One Minute Average Gas Temperature (
C) [
F] 1014 (1858) 959
Maximum One Minute Average Steel Temperature (
C) [
F] 595 (1103) 631
Total Chemical Energy Released (30 minutes) (GJ) [BTUTH] 4.69 (4448) 11.36
Estimated Paper Consumed (kg) [lb] 335 (738) 812
Test Termination - Time After Ignition (min:s) 30:00 30
![Page 21: Roll paper fire protection](https://reader035.vdocument.in/reader035/viewer/2022062411/5695cf6b1a28ab9b028e0903/html5/thumbnails/21.jpg)
7/21/2019 Roll paper fire protection
http://slidepdf.com/reader/full/roll-paper-fire-protection 21/22
FM Global
Conclusions
Equivalent Protection for Banded and Un-Banded
– Standard Array
– 6.4 m High Storage under a 9.1 m High Ceiling
– 12 mm/min over 232 m2
Structural Steel Protection Required
Metal Bands Can be Removed from Standard Arrays
without Protection Upgrade
Allows Cost Savings and Alleviates Safety Concerns