Using RealTime Data for Datacenter Operations, Energy & Sustainability initiatives Mark Peterson OSIsoft

Upload: vannguyet

Post on 21-Mar-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Using Real‐Time Data for Datacenter     Operations, Energy & Sustainability initiatives

Mark PetersonOSIsoft

Page 2: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

2 Empowering Business in Real Time. © Copyright 2012, OSIsoft , LLC. All rights Reserved.

• PI System overview

• Emerging Datacenter Operation Best Practices

• The Green Grid & the Datacenter maturity model

• Datacenter Benefits using PI

• Examples of PI use in Datacenters

• PI in Microsoft Datacenters

• Q&A

Agenda

Page 3: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

3 Empowering Business in Real Time. © Copyright 2012, OSIsoft , LLC. All rights Reserved.

Present

View data, identify problems, and take corrective action with familiar, easy‐to‐use graphical tools.

Visualisation

Analyze

Access  real‐time or historical role‐based data for the entire enterprise at any time.

Analytics

Connect

Collect data from hundreds of sources.

Interfaces

Manage

Gather and archive large volumes of data. Scale to meet your growing business needs. 

Real Time Data

The OSIsoft PI System

The OSIsoft PI System is the highly scalable and secure real-time and event infrastructure that connects people with the right operational and production

information at the right time to analyze, collaborate, and act.

Page 4: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

4 Empowering Business in Real Time. © Copyright 2012, OSIsoft , LLC. All rights Reserved.

OSIsoft: what we do

Page 5: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

5 Empowering Business in Real Time. © Copyright 2012, OSIsoft , LLC. All rights Reserved.

OSIsoft: what we also do

Page 6: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

6 Empowering Business in Real Time. © Copyright 2012, OSIsoft , LLC. All rights Reserved.

PI System: Real-time Data in to Actionable Information

PROBLEMS RESULTSTURN REAL-TIME DATA INTO ACTIONABLE INFORMATION

ENVIRONMENTAL REQUIREMENTS AND REGULATIONS

PROCESS CONDITIONS AND QUALITY

KNOWLEDGE LIFECYCLE

EQUIPMENT STATUS

ENERGY RESOURCES AND UTILISATION

CONDITION-BASED

MAINTENANCE

ENERGY AND RESOURCES

MANAGEMENT

KNOWLEDGE TRANSFER AND

RETENTION

PRODUCTION OPTIMIZATION

COMPLIANCE & REPORTING

DATA

PI INFRASTRUCTURE BUSINESS DECISIONS

INFORMATION ACTIONS

Challenges that apply in process industries also apply in Datacenter environments

Page 7: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

7 Empowering Business in Real Time. © Copyright 2011, OSIsoft , LLC. All rights Reserved.

Why PI in Datacenters?

Estimated consumption at 235.5 BkWh annually (2010). 

In the US total energy consumption % figure is closer to 2%.

Source: Jonathan Koomey, professor in the civil and environmental engineering department at Stanford University

Improving Uptime and Service levels are also primary 

Datacenter operation concerns

Page 8: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Green Grid: Data Center Maturity Model

Page 9: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Green Grid: Datacenter Maturity Model

Level 0 

•Minimal/No Progress

Level 1

•Part Best Practice

Level 2

•Best Practice

Level 3

•Reasonable Step (between Level 2 and 5)

Level 4

•Reasonable Step (between Level 2 and 5)

Level 5

•Visionary – 5 Year View

Page 10: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Data Center Maturity Model: Scope Includes

• Data Center Energy Efficiency– Energy demand– Energy supply – low carbon generation– Utilization / Effectiveness

• Data Center Sustainability– Carbon– Water – Waste heat– Materials management

– E-Waste– Cradle to cradle approach – lifecycle

– Building sustainability

• Data Center Monitoring/metrics

Page 11: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Datacenter: IT operations & Workload

Compute

Utilization

Workload Management

Operations

Power management

Server populations

Storage

Workload

Architecture

Operations

Technology

Provisioning

Network

Utilization

Workload

Operations

Technology

Base Performance

Provisioning

Management

Utilization

IT Sizing

Internal Power Supply

Service Catalogue/SLA’s

Incentivizing change for efficient behaviour

E-Waste

Procurement

Page 12: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Datacenter: Facilities Operations & Performance

Power

Critical Power Path Efficiency – Building Entrance to IT load

Architecture

Operations

Generation

Cooling

PUE – Cooling Contribution

RCI (hi) & RCI (lo) –if applicable

Mechanical/Refrigerant Cooling reduction

Environmental – set point range at inlet to IT

equipment

Environmental –monitoring and control

Operations

Other

Operational Resilience

Resilience vs. Need

Lighting

Building/Shell

M&E Waste

Procurement

Management

Monitoring

PUE

Waste heat reuse (as measured by ERF/ERE)

CUE

WUE

xUE/additional metrics

Real time Monitoring

Data Intensive

Page 13: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Data Center Maturity Model

• Provides clear goals and direction for Datacenter operators to improve energy efficiency and sustainability

• Provides guidelines by data center area such that operators can benchmark current performance, thereby:

• Understand how far they are from best practice

• Identify ongoing steps & innovations required to achieve greater energy efficiency & sustainability improvements, both today & into the future.

• Using the higher levels of the model to inform data center and IT strategy.

• Roadmap for the industry to significantly improve efficiency and sustainability

Page 14: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

14 Empowering Business in Real Time. © Copyright 2012, OSIsoft , LLC. All rights Reserved.

Value Now, Value Over Time…

Valu

e an

d Ef

fort

InitialSoftware

Investment{

Incremental effort yields sustainable gains

Effort

Target(time, value) Capacity Planning

TimeCollect, Aggregate, Visualize

Branch Circuit MonitoringCondition Based MaintenancePower  Distribution Analysis

Cooling System AnalysisEnvironmental ComplianceEnergy Management

Collect

Aggregate

Visualize

Value of Historical  Data

Page 15: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Data Center Benefits using PI

BenefitsDecrease equipment downtime & preventative maintenance via condition‐based maintenance.

Improve Strategic Asset Management & Outage Prevention by analyzing real time and historical data to identify root cause of anomalies & equipment failure.

Provide real‐time/ historic data records and trend analysis to support planning.

Support cost reduction by monitoring and improving efficiency (PUE); reducing carbon footprint (future regulation). Assess design criteria to actual demands

Establish real time alarming and response plans to reduce off‐spec impacts, optimize corrective action. Develop condition assessment algorithms & equipment alarms.

Increase effectiveness by aggregating time‐critical information at Enterprise level in Single Dashboard. Display KPI and facility performance. 

Use Real Time data to support performance claims (validate availability)

CorporatePlanning

Operations/Maintenance

IT

Marketing/Sales

Benefit Map by Role/Function

Engineering

D

E

AC

B

G

C

D

C

B

F

G

Page 16: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

16 Empowering Business in Real Time. © Copyright 2012, OSIsoft , LLC. All rights Reserved.

• Branch Circuit Monitoring

• Capacity planning

• Bill back to business units

• Corporate Dashboards

• Carbon Foot Print, PUE / Energy Efficiency, other metrics

• Benchmark against state-of-the-art facilities

• Proactive Maintenance of Assets within the Facility

• Create a condition based maintenance program vs. a calendar

• Manager of Managers/NOC

• Alarming• Troubleshooting

• Multi-site data aggregation

• Correlation between IT load & the power consumed by IT equipment

• Uncontrolled cooling

• Air blockages

• Air recirculation

• Chiller efficiency

• CRAC unit efficiency

• Cooling tower efficiency

• UPS efficiency

• Reactive power loss

• Correlation between energy cost and energy use

Data Center Monitoring and Metrics

Page 17: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

17 Empowering Business in Real Time. © Copyright 2011, OSIsoft , LLC. All rights Reserved.

Example: PI System Energy Dashboard

Page 18: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Example: Real Time Power Usage & Energy Cost

Page 19: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Example: Data Center Transformer load over time

Page 20: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Example: UPS Monitoring

Page 21: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

Example: Root-Cause Analysis: Trend Analysis

High CPU and increases in NetFlow traffic are correlated with the time that Jitter reached an unacceptable level.

Network traffic has not increased proportionally to the number of flows.

This is unusual as it means more connections are traversing the network but the network is not transporting more data.

Page 22: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

22 Value now. Value over time. © Copyright 2012, OSIsoft Inc. All rights Reserved.

Datacenters & Critical Facilities

Process Industries Utilities

Customers

Page 23: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

23 Value now. Value over time. © Copyright 2012, OSIsoft Inc. All rights Reserved.

Newark, NJ

Amsterdam, NL

Sydney, AU

Hong Kong, HK

Miami, FL

Bay Area, CALos Angeles, CA

Paris, FRZurich, CH

Vienna, AT

São Paulo, BR

Singapore, SG

Taipei, TWN

Seoul, KR

Stockholm, SE

Ashburn, VA

Tokyo, JP

Des Moines, IA

PI System in Microsoft Datacenter’s

San Antonio

Dublin

QuincyChicago

Page 24: RS ZA 2012 03 OSIsoft Data Centres - OSIsoft, Mark Petersoncdn.osisoft.com/corp/en/media/presentations/2012/RegionalSeminars/... · Mark Peterson OSIsoft. ... Establish real time

© Copyright 2012

Q&A