8
Description and operating instructions Industrial ETHERNET Rail Switch The Rail Switches RS2-5TX and RS2-5TX/FX have been especially designed for use in industrial environments. They support ETHERNET 10 MBit/s and Fast ETHERNET 100 MBit/s. The Rail Switch modules support switched ETHERNET networks in accordance with IEEE standard 802.3 using copper and fiber optic technology. The switch modules are plugged onto the standard DIN rail. Because of their compact design the modules can be mounted in a terminal box. The RS2-5TX modules have five 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up to five DTEs (data terminal equipment) or other TP/TX network segments to these ports using twisted pair cabling. The RS2-5TX/FX modules have four 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors) and one 100 MBit/s fiber optic port (100BASE-FX, MTRJ connector). It is possible to connect up to four DTEs or other TP/TX network segments to the TP/TX ports using twisted pair cabling. One further DTE or an optical network component can be connected to the fiber port. The TP ports support auto negotiation and autopolarity. The operating mode of the FX port is full duplex. RS2-5TX Order No. 943 732-003 RS2-5TX/FX Order No. 943 732-103 Hirschmann. Simply a good Connection.

Upload: others

Post on 05-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RSP Supply Industrial Automation SCADA Hardware - Description … · 2015. 9. 5. · 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up

Description and operating instructionsIndustrial ETHERNET Rail Switch

The Rail Switches RS2-5TX and RS2-5TX/FXhave been especially designed for use inindustrial environments. They supportETHERNET 10 MBit/s and Fast ETHERNET100 MBit/s.

The Rail Switch modules support switchedETHERNET networks in accordance withIEEE standard 802.3 using copper and fiberoptic technology. The switch modules areplugged onto the standard DIN rail. Becauseof their compact design the modules can bemounted in a terminal box.

The RS2-5TX modules have five10/100 MBit/s twisted pair ports(10/100BASE-TX, RJ45 connectors). It is possible to connect up to five DTEs(data terminal equipment) or other TP/TXnetwork segments to these ports using twisted pair cabling.

The RS2-5TX/FX modules have four 10/100 MBit/s twisted pair ports(10/100BASE-TX, RJ45 connectors) and one100 MBit/s fiber optic port (100BASE-FX,MTRJ connector).It is possible to connect up to four DTEs orother TP/TX network segments to the TP/TXports using twisted pair cabling. One furtherDTE or an optical network component canbe connected to the fiber port.

The TP ports support auto negotiation andautopolarity.The operating mode of the FX port is fullduplex.

RS2-5TXOrder No.

943 732-003RS2-5TX/FXOrder No.

943 732-103

Hirschmann. Simply a good Connection.

Page 2: RSP Supply Industrial Automation SCADA Hardware - Description … · 2015. 9. 5. · 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up

2

The performance features described hereare binding only if they have been expresslyguaranteed in the contract. We havechecked that the contents of the technicalpublication agree with the hardware andsoftware described. However, it is not possi-ble to rule out deviations completely, so weare unable to guarantee complete agree-ment. However, the details in the technicalpublication are checked regularly. Any cor-rections which prove necessary are contai-ned in subsequent editions. We are gratefulfor suggestions for improvement.

We reserve the right to make technicalmodifications.

Permission is not given for the circulationor reproduction of this document, its use orthe passing on of its contents unless gran-ted expressly. Contravention renders theperpetrator liable for compensation fordamages. All rights reserved, in particularin the case of patent grant or registration ofa utility or design.

Copyright © Hirschmann Automation and Control GmbH 2012All Rights Reserved

NoteWe would point out that the content ofthese operating instructions is not part of,nor is it intended to amend an earlier or exi-sting agreement, permit or legal relation-ship. All obligations on Hirschmann arisefrom the respective purchasing agreementwhich also contains the full warranty condi-tions which have sole applicability. Thesecontractual warranty conditions are neitherextended nor restricted by comments inthese operating instructions.

We would furthermore point out that forreasons of simplicity, these operatinginstructions cannot describe every conceivable problem associated with theuse of this equipment. Should you requirefurther information or should particular problems occur which are not treated insufficient detail in the operating instruc-tions, you can request the necessary infor-mation from your local Hirschmann salespartner or directly from the Hirschmannoffice (address: refer to chapter entitled„Notes on CE identification“).

Safety InstructionsThis manual contains instructions whichmust be observed to ensure your own per-sonal safety and to avoid damage to devices and machinery. Theinstructions are highlighted with a warningtriangle and are shown as follows according to the degree of endan-germent:

zDanger!means that death, serious injury orconsiderable damage to propertywill result if the appropriate safetymeasures are not taken.

zWarning!means that death, serious injury orconsiderable damage to propertycan result if the appropriate safetymeasures are not taken.

zCaution!means that light injury or damage toproperty can result if the appropria-te safety measures are not taken.

Note: is an important piece of informationabout the product, how to use the product,or the relevant section of the documentati-on to which particular attention is to bedrawn.

Certified usagePlease observe the following:

zWarningThe device may only be employedfor the purposes described in thecatalog and technical description,and only in conjunction with externaldevices and components recommen-ded or approved by Hirschmann.The product can only be operatedcorrectly and safely if it is transpor-ted, stored, installed and assembledproperly and correctly. Furthermore,it must be operated and servicedcarefully.

Safety GuidelinesPower Supply

� Switch the basic devices on only whenthe case is closed.

zWarning!The devices may only be connectedto the supply voltage shown on thetype plate.

The devices are designed for opera-tion with a safety extra-low volta-ge.Thus, they may only be connec-ted to the supply voltage connec-tions and to the signal contact withSELV circuits with the voltagerestrictions in accordance withIEC/EN 60950-1.

� For the case where the module is opera-ted with external power supply: Use only asafety extra-low voltage in accordance withIEC/EN 60950-1 to power the system.

� First of all you connect the protectingline, before you establish the furtherconnections. When you remove connec-tions, you disconnect the protecting linelast.

� Relevant for North America:The subject unit is to be suppplied by aClass 2 power source complying with therequirements of the National ElectricalCode, table 11(b). If power is redundantsupplied (two individual power sources) thepower sources together should comply withthe requirements of the National ElectricalCode, table 11 (b).

� Relevant for North America:Power, input and output (I/O) wiring mustbe in accordance with Class I, Division 2wiring methods [Article 501-4(b) of theNational Electrical Code, NFPA 70] and inaccordance with the authority having juris-diction.

Peripheral equipment must be suitable forthe location it is used in.

Use 60/75°C or 75°C copper(CU)wire only.

Safety GuidelinesShielding Ground

Note: The shielding ground of the connec-table twisted pairs lines is connected to thefront panel as a conductor.

� Beware of possible short circuits whenconnecting a cable section with conductiveshielding braiding.

Safety Guidelines Housing

zWarning!Only technicians authorized by Hir-schmann are permitted to open thehousing.

Note: The device is grounded via the sepa-rated ground screw. It is located on the leftunder the front panel.

� Make sure that the electrical installationmeets local or nationally applicable safetyregulations.

zWarning!The ventilation slits must not becovered so as to ensure free air cir-culation.

The distance to the ventilation slotsof the housing has to be a minimumof 10 cm.

Never insert pointed objects (thinscrewdrivers, wires, etc.) into theinside of the subrack! This especial-ly applies to the area behind thesocket connectors. Failure to obser-ve this point may result in injuriescaused by electric shocks.

Note: If installed the device must be opera-ted exclusively in switch cabinets with fireprotection characteristics according toIEC/EN 60950-1.

Note: The housing has to be mounted inupright position.

Safety Guidelines Environment

zWarning!The device may only be operated inthe listed ambient temperaturerange at the listed relative air humi-dity (non-condensing).

� The installation location is to be selec-ted so as to ensure compliance with the cli-matic limits listed in the Technical Data.

� To be used in an up to Pollution Degree2 environment only (IEC 60664-1).

Page 3: RSP Supply Industrial Automation SCADA Hardware - Description … · 2015. 9. 5. · 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up

3

CONTROL DRAWING for Industrial ETHERNETRail Switch 2 and Rail Transceiver 2 FamilyAccording to ANSI / ISA 12.12.01-2012

Rev.: 0 Date: 2012-07-13 Document No.: 000163806DNR Page 1 of 1

NON HAZARDOUS LOCATION

Power Supply: (Redundant: P1, P2) 24 V DC

Relay Contacts:Associated Apparatus:Equipment with nonincendive fi eld wiring 1

HAZARDOUS LOCATION Class I, Division 2 Groups A, B, C, D

The Use in Hazardous Locations is only allowed for Rail Switch 2 and Rail Transceiver 2 Family model No‘s which are individually labelled “FOR USE IN CLASS I, DIVISION 2 HAZARDOUS LOCATIONS”Notes:

The nonincendive fi eld wiring circuit concept allows interconnection of nonincendive fi eld wiring apparatus and associated nonincendive fi eld wiring apparatus using any of the wiring methods permitted for unclassifi ed locations when certain parametric conditions are metCapacity: Ca ≥ Ci + CCable Inductivity: La ≥ Li + LCable The maximum cable length has to be determined as follows:(a) max. Cable Length < (La - Li) / LCable and (b) max. Cable Length < (Ca - Ci) / CCable The lower value of (a) and (b) is to apply.CableL: inductance per unit length of used cable.CableC: capacitance per unit length of used cable.Other C-parameters and L-parameters are according to ANSI / ISA 12.12.01-2012 section 7.Where cable capacitance and inductance values per foot are not known, the following values shall be used:CCable 60 pF/foot, LCable 0.2 µH/footNonincendive fi eld wiring circuits must be wired in accordance with the National Electric Code (NEC), NFPA 70, article 501.

1

Nonincendive Field Wiring Parameters:

The Relay Contacts are dependent upon the following Entity Parameters:

Vmax Imax Ci Li

30 V 90 mA 2.5 nF 1 µH

WARNING – EXPLOSION HAZARD – SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR SUITABILITY FOR HAZAR-DOUS LOCATIONS OR EXPLOSIVE ATMOSPHERES.

WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

DO NOT OPEN WHEN ENERGIZED.

Relay Contacts:Associated Apparatus:Equipment with nonincendive fi eld wiring 1

Power Supply: (Redundant: P1, P2) 24 V DC

Detail: RS2-xxx

Detail: RT2-xxx

The equipment must be installed in a tool-locked enclosure.

Page 4: RSP Supply Industrial Automation SCADA Hardware - Description … · 2015. 9. 5. · 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up

4

– EN 61131-2 – Programmable Controllers.

– CFR-47 Part 15 – Code of Federal Regulati-ons.

– UL 508 – Underwriters Laboratories Inc.Safety for Industrial Control Equipment.

– ISA 12.12.01 – Nonincendive ElectricalEquipment for Use in Class I and II, Divisi-on 2 and Class III, Divisions 1 and 2 Hazar-dous (Classified) Locations.

– UL 60950 – Safety for Information Technology Equipment.

Certified devices are marked with a certification identifier.

7Notes on CE identificationThe devices comply with the regula-tions of the following Europeandirectives:

2004/108/EC (EMV)Directive of the European Parlia-ment and of the Council on theapproximation of the laws of theMember States relating to electro-magnetic compatibility.

2011/65/EU (RoHS) Directive of the European Parlia-ment and of the Council on therestriction of the use of certainhazardous substances in electricaland electronic equipment.

The EU declaration of conformity iskept available for the responsibleauthorities in accordance with theabove-mentioned EU directives at:

Hirschmann Automation and Control GmbH Stuttgarter Straße 45-51D-72654 NeckartenzlingenTelephone: +49 (0)1805 14-1538

Staff qualification requirements

Note: Qualified personnel, as understoodin this manual and in the warning signs, arepersons who are familiar with the setup,assembly, startup, and operation of thisproduct and are appropriately qualified fortheir job. This includes, for example, thosepersons who have been:

– trained or directed or authorized toswitch on and off, to ground and to labelpower circuits and devices or systems inaccordance with current safety enginee-ring standards

– trained or directed in the care and use ofappropriate safety equipment in accor-dance with the current standards of safetyengineering

– trained in providing first aid.

General Safety Instructions� This device is electrically operated.Adhere strictly to the safety requirementsrelating to voltages applied to the device asdescribed in the operating instructions!

zWarning!Failure to observe the informationgiven in the warnings could result inserious injury and/or major damage.

Only personnel that have receivedappropriate training should operatethis device or work in its immediatevicinity. The personnel must be fullyfamiliar with all of the warnings andmaintenance measures in theseoperating instructions.

Correct transport, storage, andassembly as well as careful operati-on and maintenance are essential inensuring safe and reliable operationof this device.

Use only undamaged parts!

� These products are only to be used inthe manner indicated in this version of the”Description and Operating Instructions”.

� Particular attention is to be paid to allwarnings and items of information relatingto safety.

zWarning!Any work that may have to be per-formed on the electrical installationshould be performed by fully quali-fied technicians only.

zWarning!LED- or LASER components accor-ding to IEC 60825-1: CLASS 1 LASER PRODUCT. LIGHT EMITTING DIODE - CLASS 1LED PRODUCT.

Based specifications and standards:The devices fulfill the following specificati-ons and standards: – EN 61000-6-2 Generic standards – Immu-nity for industrial environments.

– EN 55022 – Information technology equip-ment – Radio disturbance characteristics.

– EN 60950 – Safety of Information Techno-logy Equipment (ITE).

The product can be used in the indu-strial sphere.– Interference immunity: EN 61000-6-2

– Radio interference level: EN 55022 Class A

zWarning!This is a Class A device. This equip-ment may cause radio interference ifused in a residential area; in thiscase it is the operator�s responsibili-ty to take appropriate measures.

The precondition for compliancewith EMC limit values is strict adhe-rence to the construction guidelinesspecified in this description andoperating instructions.

FCC Note:This equipment has been tested and foundto comply with the limits for a Class A digi-tal device, persuant to part 15 of the FCCRules. These limits are designed to providereasonable protection against harmful inter-ference when the equipment is operated ina commercial environment. This equipmentgenerates, uses, and can radiate radio fre-quency energy and, if not installed andused in accordance with the instructionmanual, may cause harmful interference toradio communications. Operation of thisequipment in a residential area is likely tocause harmful interference in which casethe user will be required to correct the inter-ference at his own expense.

,Recycling Note:After its use, this product has to beprocessed as electronic scrap anddisposed of according to the prevai-ling waste disposal regulations ofyour community / district / country /state.

Fig. 1: Overview display elements and interfaces of the RS2-5TX(/FX)

4 ports 10/100BASE-T(X) (ports 2 to 5), RJ45 connectors autonegotiaton + autopolarity RS2-5TX/FX

1 port 100BASE-FX (port 1), MTRJ connector

1

2 3

4 5

5 Ports nach 10/100BASE-T(X) (Ports 1 bis 5), RJ45-Anschlüsse Autonegotiaton + Autopolarity RS2-5TX

2 3

4 5

1

P2P1

DA/STAT

2

1

3

5

Port

2

4

3

1

5

xRS2-5TX i

4

Page 5: RSP Supply Industrial Automation SCADA Hardware - Description … · 2015. 9. 5. · 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up

5

1. Functional description

The 10/100BASE-T(X) ports of an RS2-5TX(/FX) represent a terminal connectionfor the connected LAN segment. You canconnect single devices or complete networksegments.

1.1 FRAME SWITCHING FUNCTIONSStore and ForwardAll data received by the RS2-5TX(/FX) fromthe system bus or at the ports is stored andchecked for validity. Invalid and defectiveframes (> 1,518 bytes or > 1,522 bytes VLANframes or CRC error) as well as fragments(< 64 bytes) are discarded. The RS2-5TX(/FX) forwards the valid frames.

Multi address capabilityAn RS2-5TX(/FX) learns all source addres-ses per port. Only packets with– unknown addresses– addresses learnt at this port– a multi/broadcast addressin the destination address field are sent tothis port.An RS2-5TX(/FX) learns up to 1,000 addres-ses. This becomes necessary if more thanone terminal device is connected to one ormore ports. In this way several independentsubnetworks can be connected to an RS2-5TX(/FX).

Learnt addressesAn RS2-5TX(/FX) monitors the age of thelearned addresses. The RS2-5TX(/FX) dele-tes address entries from the address tablewhich exceed a certain age (300 seconds).Note: Restarting deletes the learnedaddress entries.

Tagging (IEEE 802.1Q)The IEEE 802.1 Q standard designates theVLAN tag to be included in a MAC dataframe for the VLAN and prioritizing func-tions. The VLAN tag consists of 4 bytes (2bytes tag protocol identifier TPID, 2 bytestag control information TCI). It is insertedbetween the source address field and thetype field. Data packets with a VLAN tag aretransmitted unchanged by the RS2-5TX(/FX).

1.2 SPECIFIC FUNCTIONS OF THE TP/TX INTERFACELink controlThe RS2-5TX(/FX) monitors the connectedTP/TX line segments for short-circuits orinterrupts using regular Idle signals inaccordance with IEEE standard 802.310/100BASE-T/TX. The RS2-5TX(/FX) doesnot transmit any data to a TP/TX segmentfrom which it does not receive an Idle sig-nal.

Note: A non-occupied interface is assessedas a line interrupt. The TP/TX line to termi-nal equipment which is switched off is like-wise assessed as a line interrupt as the de-energised bus coupler cannot transmit Idlesignals.

Auto polarity exchangeIf the receive line pair is incorrectly connec-ted (RD+ and RD- switched) polarity is auto-matically reversed.

AutocrossingThe RS2-5TX(/FX) detects the transmit andreceive pairs (MDI, MDI-X). The RS2-5TX(/FX) automatically configures its portfor the correct transmit and receive pins.

Consequently it does not matter whetheryou connect devices using a cross-over orstraight cable.

1.3 SPECIFIC FUNCTIONS OF THEF/O INTERFACELink control (RS2-5TX/FX)The RS2-5TX/FX monitors the connectedF/O line for interrupts using idle signalsduring frame pauses in accordance withIEEE standard 802.3 100BASE-FX. The RS2-5TX/FX transmits no data to an F/O linefrom which it is receiving no idle signal.Low Light Detection: If the optical inputpower decreases below the low light thres-hold the transmit and receive path will bedisabled for data and the idle signal will betransmitted.

1.4 FURTHER FUNCTIONS AND FEATURESResetThe RS2-5TX(/FX) will be reset by the follo-wing action:– input voltages fall below a threshold

After a reset the following action is carriedout:– initialization

1.5 DISPLAY ELEMENTSEquipment statusThese LEDs provide information about sta-tuses which affect the function of the entireRS2-5TX(/FX).P1 – Power 1 (green LED)– lit: – supply voltage 1 present– not lit: – supply voltage 1 less than 9.6 V

P2 – Power 2 (green LED)– lit: – supply voltage 2 present– not lit: – supply voltage 2 less than 9.6 V

Port StatusThese LEDs display port-related informati-on.DA/STAT 1 to 5 – Data, Link status (green LED)– not lit: – no valid link– flashes: – data activity– lit: – valid link

1.6 INTERFACES10/100 MBit/s connection (TP port)Five (RS2-5TX/FX: four) 10/100 Mbit ports(8-pin R45 sockets) allow DTEs or indepen-dent network segments complying with thestandards IEEE 802.3 100BASE-TX /10BASE-T to be connected. These portssupport autonegotiation and the autopolari-ty function.

The socket casings are electrically connec-ted to the front panel of the RS2-5TX(/FX).

– Pin configuration of the RJ45 socket:– 1 line pair: pin 3 and pin 6– 1 line pair: pin 1 and pin 2– remaining pins: not used.

Fig. 2: Pin configuration of an TP/TX interface

n.c. Pin 8n.c. Pin 7TD- Pin 6n.c. Pin 5n.c. Pin 4

Pin 3TD+Pin 2RD-Pin 1RD+

100 Mbit/s connection (FX port)The 100 MBit/s port of the RS2-5TX/FX supports the IEEE 802.3 100BASE-FX FDXstandard (full duplex). It uses an MTRJconnector. The 100 MBit/s port allows onefurther DTE or an optical network component to be connected.

5pin terminal blockThe supply voltage and the indicatorcontact are connected via a 5pin terminalblock with screw locking. If the terminalblock is fitted the wrong way round, thedevice will still work correctly.

zWarning!The RS2-5TX(/FX) equipment isdesigned for operation with a safetyextra-low voltage. Thus, they mayonly be connected to the supply voltage connections with SELV cir-cuits with the voltage restrictions inaccordance with IEC/EN 60950-1.

– Voltage supply: Redundant voltage sup-plies are supported. Both inputs aredecoupled. There is no load distribution.With redundant supply, the power packsupplies the RS2-5TX(/FX) only with thehigher output voltage. The supply voltageis electrically isolated from the housing.

Fig. 3: Pin configuration of 5 pin terminalblock

Ground connectionThe RS2-5TX(/FX) is grounded via a separa-te screw connection.

2. Configuration

2.1 CONNECTING DTE AND OTHERNETWORK SEGMENTSIt is possible to connect up to five DTEs orother network segments to the 10/100Mbit/s ports of the RS2-5TX using twistedpair cabling It is possible to connect up to four DTEs orother TP/TX network segments to the10/100 Mbit/s ports of the RS2-TX/FX usingtwisted pair cabling. One optical networkcomponent can be connected at 100 Mbit/sto the optical port using fiber optic cable(ref. Fig. 4).

+24 V

0 V

0 V

0 V

+24 V *

L1+

L2+

M

M

M

Page 6: RSP Supply Industrial Automation SCADA Hardware - Description … · 2015. 9. 5. · 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up

6

Notes:– The front panel of the RS2-5TX(/FX) is grounded via a separate ground connec-tion.

– Do not open the housing.

– The shielding ground of the twisted paircables is electrically connected to the frontpanel.

3.3 STARTUP PROCEDURE� You start up the RS2-5TX(/FX) byconnecting the supply voltage via the 5-pinterminal block.

3.4 DISMANTLING� To take the RS2-5TX(/FX) off the ISO/DINrail, insert a screwdriver horizontally underthe housing into the locking slide, pull it(without tipping the screwdriver) down-wards and lift the RS2-5TX(/FX) upwards.

3. Assembly, startup procedureand dismantling

3.1 UNPACKING, CHECKING� Check whether the package was deliver-ed complete (see scope of delivery).� Check the individual parts for transportdamage.

zWarning!Use only undamaged parts!

3.2 ASSEMBLYThe equipment is delivered in a ready-to-operate condition. The following procedureis appropriate for assembly:

� Pull the terminal block off the RS2-5TX(/FX) and wire up the supply voltage.� Fit the RS2-5TX(/FX) on a 35 mm stan-dard DIN rail to DIN EN 50 022.� Attach the upper snap-on slide bar ofthe RS2-5TX(/FX) to the standard DIN railand press it down until it locks into position.� Fit the signal lines.

4. Further support

In the event of technical queries, please talkto the Hirschmann contract partner respon-sible for looking after your account or direc-tly to the Hirschmann office. You can findthe addresses of our contract partners onthe Internethttp://www.hirschmann.com

You can contact us

in the EMEA region atTel.: +49 (0)1805 14-1538 E-mail: [email protected]

in the America region atTel.: +1 (717) 217-2270E-mail: [email protected]

in the Asia-Pacific region atTel.: + 65 6854 9860E-mail: [email protected]

www.hicomcenter.com gives you an up-to-date overview of training courses abouttechnology and products.

Fig. 4: Configuration with RS2-5TX (RS2-5TX/FX): Connection of up to 5 (4) data termi-nal equipments or further segments via TP/TX as well as connection via fiberoptic cable with one optical port on the RS2-5TX/FX

Roboter

Bediener- station

SPS

I/O - Block

100 Mbit/s HIPER-Ring 100 Mbit/s 10 Mbit/s

RS2-FX/FX RS2-FX/FX

RS2-5TXRS2-�5TX/FX

RS2-TX

x RS2-5TXi

X

x RS2-5TXi

X

12 34 5

12 34 5

Fig. 6: Assembling the RS2-5TX(/FX)

5. Technical data

General data

Operating voltage NEC Class 2 power source 24 VDC -25% +33%) safety extra-low voltage (SELV) (redundant inputs decoupled), 5 A maximum

Buffer time min. 10 ms at 24 VDC

Potential difference between input Potential difference to input voltage, +24 VDC: 32 VDCvoltage and housing Potential difference to input voltage, ground: -32 VDC

Power consumption at 24VDC, maximum 2.6 W; 8.9 Btu (IT)/h RS2-5TX4.0 W; 13.6 Btu (IT)/h RS2-5TX/FX

Overload current protection at input non-changeable fuseDimensions W x H x D 40 mm x 145 mm x 80 mm 1.6 in x 5.7 in x 3.15 inWeight 520 g 1.15 lb Ambient temperature Surrounding air 0 ºC to + 60 ºC 32 ºF to 140 ºFStorage temperature Surrounding air - 20 ºC to + 80 ºC -4 ºF to 176 ºFHumidity up to 95% (non condensing)Atmospheric pressure suitable for use in up to 2000 m (795 hPa, higher altitudes on demand)Laser protection Class 1 conforming to EN 60825-1Protection type IP 20

Page 7: RSP Supply Industrial Automation SCADA Hardware - Description … · 2015. 9. 5. · 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up

7

Radiated emission CFR-47 Part 15 Class A,Warning!This is a Class A device. This equipment may cause radio interference if used in a residential area. In this case the operator may be required to take appropriate measures.

Interference proofDischarge of static electricity

Contact discharge EN 61000-4-2 Test level 3Air discharge EN 61000-4-2 Test level 3

Electromagnetic fields EN 61000-4-3 Test level 3Fast transients EN 61000-4-4 Test level 3Surge voltage symmetrical EN 61000-4-5 Test level 2Surge voltage asymmetrical EN 61000-4-5 Test level 3Cable-based RF faults EN 61000-4-6 Test level 3

StabilityVibration IEC 60068-2-6 Test FC, testing level in line with IEC 61131-2 Shock IEC 60068-2-27 Test Ea, testing level in line with IEC 61131-2

Network size

TP/TX port 10BASE-T/100BASE-TXLength of a twisted pair segment 100 m (328 ft) maximumF/O port 100BASE-FXAccording to IEEE 802.3 100BASE-FX System attenuation

50/125 µm fiber (multimode, MM) 0 to 8 dB RS2-5TX/FX62,5/125 µm fiber (multimode, MM) 0 to 11 dB RS2-5TX/FX

F/O line length (example)50/125 µm fiber (multimode, MM) 5 km approx. (data of fiber: 1.0 dB/km, 800 MHz*km)62,5/125 µm fiber (multimode, MM) 4 km approx. (data of fiber: 1.0 dB/km, 500 MHz*km)

Interfaces

RS2-5TX 5 TP/TX ports RJ45 sockets, 10/100 MBit/sRS2-5TX/FX 4 TP/TX ports RJ45 sockets, 10/100 MBit/s

+ 1 FX port MTRJ connection, multimode, 100 MBit/s

Displays

Equipment status 1 x green LED P1 – power 1, supply voltage 1 present1 x green LED P2 – power 2, supply voltage 2 present

Port status 5 x green LED DAT/STAT 1 to 5 – data, link status

Scope of delivery

Rail Switch RS2-5TX or RS2-5TX/FX incl. terminal block for supply voltage, description and operating instructionsOrder number

Rail Switch RS2-5TX 943 732-003Rail Switch RS2-5TX/FX 943 732-103

Accessories

Manual “Basics Industrial ETHERNET and TCP/IP” 280 720-834

Rail Power Supply RPS 30 943 662-003Rail Power Supply RPS 80 EEC 943 662-080Rail Power Supply RPS 120 EEC 943 662-120

Page 8: RSP Supply Industrial Automation SCADA Hardware - Description … · 2015. 9. 5. · 10/100 MBit/s twisted pair ports (10/100BASE-TX, RJ45 connectors). It is possible to connect up

Hirschmann Automation and Control GmbHStuttgarter Straße 45-51D-72654 NeckartenzlingenGermanyTel.: +49 (0)1805 14-1538E-mail: [email protected]: http://www.hirschmann.com

Printed in GermanySubject to alterations