rtu and chiller maintenance for maximum efficiency · 2015-05-28 · • chiller maintenance o...
TRANSCRIPT
RTU and Chiller Maintenance
for Maximum EfficiencyMay 28, 2015
Meet Your Panelists
Working to deliver the energy you need, whenever you need it.
That’s our Promise to Michigan.
2
• Mike Carter
• Justin Kale
• Subject Matter Experts:
o David MacDonald , Marketing Manager,
Business Energy Efficiency Programs
o Phil Walsh, Corporate Account Manager
3
• HVAC basics
• RTU maintenance
• Chiller basics
• Chiller maintenance
o Compressor
o Evaporator/Condenser
o Economizers
o Air HandlersSource: NREL
Table of Contents
4Poll Questions
• Do you have a formal proactive
chiller/RTU maintenance program
in place?
a) Yes
b) No
c) Not sure
5Maintenance Basics
• Proactive/preventive versus reactive
• Predictive maintenance
o Based on actual performance
o Log books are important
• RTU trends
• Chillers
o Refrigerant temperatures and pressures
o Condenser-water entering and leaving temperatures
o Chilled-water entering and leaving temperatures
o Run times for automatic refrigerant purge units
o Real-time monitoringSource: www.sxc.hu
6Maintenance Basics
• What are signs of maintenance issues?
o Deformation
o Discoloration
o Oxidation
o Corrosion
o Scale
o Leakage of fluid or vapor
o Excessive noise/vibration
o Loose/missing fasteners
o Ice buildup
o Frost or condensate
o Worn or damaged insulating
materials
7Maintenance Basics
• Root Cause Analysis
Man
• The actions of personnel
Method
• A process or procedure
Machine
• Specific piece of equipment or tool
Materials
• Consumables
Measurement
• How data is generated or used
Mother Nature
• Abnormal environmental effectsSource: Mark Orge, Canadian Facility Management & Design
8HVAC Basics
• Power (Capacity)
o Motor power (kW) = Horsepower x 0.746/efficiency X LF
• A 12 hp motor = 12 hp x 0.746/0.9 = 8.85 kW
• 1 kW = 3,412 Btu/hr
9Packaged Rooftop Units (RTU)
Image courtesy of Daikin Applied
Gas heatersEvaporator Condenser
Compressor
Filter rackExhaust fan
ControlsEconomizerDampers
Plenum fan
10Packaged Rooftop Units (RTU)
• RTU maintenance study
o 20-ton RTU for mall in South Carolina
• 7-day per week operation
• Service /repair costs of $14,348
o Undetected failure of one condenser fan
o Compressor replacement
o Thermostatic-expansion-valve (TXV) failure
o Installed in 2003 and serviced in 2013
o Instrumented from 2010-2013
• 45 refrigerant and air sensors
2003 2010 % 2014
IEER Efficiency 11.2 7.8 - 30% 9.5
Power demand 23.7 kW 30.3 kW + 28% 25.3
11Packaged Rooftop Units (RTU)
• RTU maintenance study
o Service energy savings
of $1,870 per year
o Projected preventive maintenance
results (2003 to 2010)
$8,400 added energy cost of deferred maintenance
$5,600 cost of preventive maintenance
$2,800 energy cost savings (50% ROI)
o Would also avoid occupant complaints
12Packaged Rooftop Units (RTU)
• Preventive maintenance priorities
1. Cleaning the condenser coil.
2. Verifying operation of the condenser fan(s).
3. Adjusting refrigerant charge.
4. Verifying proper economizer operation.
5. Checking compressor discharge temperature.
6. Testing compressor oil for the presence of acid.
7. Testing high- and low-pressure cutout switches.
8. Adjusting the thermostatic expansion valve (TXV).
9. Checking and adjusting the blower belt.Source: West & Beaufort, Advan Tek Consulting
13Packaged Rooftop Units (RTU)
• Preventive maintenance – Bi-annual
Source: West & Beaufort, AdvanTek Consulting in HPAC Engineering
14Packaged Rooftop Units (RTU)
• Preventive maintenance - Annual
Source: West & Beaufort, AdvanTek Consulting in HPAC Engineering
15Packaged Rooftop Units (RTU)
Cleaning RTU coils
o If the evaporator airflow is restricted
by 36%, the capacity drop is 20%.
• This changes the 3-ton unit to a 2.5-ton unit.
o On the other hand, when the condenser
coils are 50% restricted, the capacity
drops only 11%.
• Blocked condenser coils can increase condensing
temperature by 8ºF to 10ºF resulting in a 6% to 8%
increase in power consumption.
Source: Coil-Tech used with permission
16Packaged Rooftop Units (RTU)
Cleaning RTU coils
o Cleaning methods
• Spraying high-pressure (<600 psi)
cold water
• Surface dirt and debris can be
removed using a stiff bristle brush
or wire brush.
o DO NOT use any detergents with
microchannel condenser coils.
Source: SpeedClean, Inc.
17Packaged Rooftop Units (RTU)
• Fan and belts
18Packaged Rooftop Units (RTU)
• Fan and belts
o Manually rotate the fan(s) to ensure free movement.
o Check motor bearings for wear.
o Do not stretch new belts over the pulley sheaves
• Loosen belt tensioner
o Use a Browning or Gates tension gauge
(or equivalent) to adjust the belt tension.
• Recheck the belt tension at least twice
during the first 2 to 3 days of operation.
• Belt tension may decrease until the new
belts are “run in”.Source: Gates Corporation
19Packaged Rooftop Units (RTU)
• Refrigerant sight glass
o Moisture content of the refrigerant
o Liquid refrigerant is present
• Frothing means shortage
o Green = good (dry)
o Yellow = caution
Source: J&E Hall International
20Poll Questions
• Which of the following is the leading
source of fan drive problems?
a) Improper installation
b) Environmental factors (heat, dirt)
c) Improper drive maintenance
d) Poor drive design
21Chiller Basics
• Chiller components
Source: EERE
22
• Efficiency ratingso One ton (12,000 Btu/hr) equals 3.516 kW at 100% efficiency
o Coefficient of Performance (COP)
COP = Rated Cooling Output, kBtuh / Rated electrical input, kBtuh
o Full Load Value (FLV)
FLV = kW/ton efficiency rating
COP = 3.516 (kW/ton) / FLV (kW/ton)
o Energy Efficiency Ratio (EER)
EER = Cooling output (Btuh) / Electricity consumed (watt)
EER = 12,000 Btuh per ton / FLV (watt per ton)
EER = COP x 3.413
o Application Part Load Value (APLV)
• Other than full load
o Integrated Part Load Value (IPLV)
• Weighted average of full load and part load
FLV
(kW/ton)
COP EER
0.6 5.9 20
0.75 4.7 16
1.0 3.5 12
1.5 2.3 8
Chiller Basics
23Chiller Maintenance
1. Maintain a daily log
2. Perform an oil and refrigerant analysis
3. Keep evaporator and condenser tubes clean
4. Ensure a leak-free unit
5. Maintain proper water treatment
Source: Darin Fackler, Hill York Service
Source: ORNL
24Chiller Compressor Maintenance
• Visual check of compressor oil
o Oil level
o Color (darker is worse)
o Change oil on large systems once
a year and clean particles from case
• Have the condition of your system fluid checked by a
qualified lab, a minimum of four times per year
• Monitor for refrigerant leaks
• Inspect journal and thrust bearings and drive gears
25
• Check the motor terminals for pitting,
corrosion, or loose connections
• Check electrical contactors for
corrosion or pitting
• Check amp draws on all motor loads
• Check the crankcase heaters for
proper operation
• Periodically analyze refrigerant for
moisture, acid, and rust
• Ensure that the pipe insulation is dry
and not broken off.
Source: New York Power Authority
Chiller Compressor Maintenance
26Chiller Compressor Maintenance
• Centrifugal chillers
o Guide vane linkage assembly
and drive mechanism
o Guide vane control shaft seal
• Reciprocating machines
o Compressor suction and
discharge valves.
• Check for high vibration on a
capillary line (causes leaks)
and secure all vibrating lines.
Source: John Tomczyk,
Ferris State University
Source: Atlas Copco Airpower
27
• Take superheat and subcooling temperature
readings to obtain the chiller's maximum efficiency.
• Check for tube corrosion
o Eddy current testing can
identify internal pitting,
freeze damage, cracks,
and wear
o Remove the sludge with
bristle brushes on the end
of long metal rods.
o If badly fouled, use chemicals
Source: Maverick Inspection Ltd.
Chiller Evaporator/Condenser Maintenance
28
• Clean debris and dirt from water tower condenser
and unclog spray nozzles, especially in the spring.
o Clean pre-strainers
o Spray should be uniform
• Clean condenser coils
o A 1/32” scale buildup results in a
7% reduction in energy efficiency
Chiller Water-side Maintenance
Source: Baltimore Aircoil Company
29
Source: M360 Energy
• Apply proper water filtering
Chiller Water-side Maintenance
• How familiar are you with our energy efficiency programs?
• How familiar are you with our specialized Business Customer Care team and dedicated Business Center?
a) Very familiar
b) Somewhat familiar
c) Not very familiar
d) Not at all familiar
Poll Question 30
31
• Check cold water basin
o Pump leaks or obstructions
o Clean sump strainer
• If atmosphere is extremely dirty,
it may be necessary to clean strainer weekly
o Check and adjust bleed rate
o Make-up water valve is working
o Heater controls are working
• Clean debris and dirt from water tower
condenser and unclog spray nozzles,
especially in the spring.
o Clean pre-strainers
o Spray should be uniform
Chiller Water-side Maintenance
Source: Baltimore Aircoil Company
32
• Install water gauges so you can see
pressure drops; particularly through
the evaporator.o Water supplied to the unit should have a minimum
differential pressure of 15 psi at the chiller
• Check for proper water flowo Overflow can cause vibration, damaging
the copper tubes.
o Put a bypass valve on the end of the
pipe run going to the chillers.
o Keep chilled water flow rate between
3 to 12 feet per second.
Source: Denver Water
Chiller Water-side Maintenance
33
• Check fan belt for proper
tension and any belt wear or
improper alignment.
• Check fan bearings and
lubricate, if necessary.
• Check belt tension and adjust.
• For gear drives, check oil level.
• Clean strainer
o If atmosphere is extremely
dirty, it may be necessary to
clean strainer weekly. Source: Virginia Department of Mines, Minerals, and Energy
Chiller Water-side Maintenance
34
• Re-enabling economizers
o Address any outstanding
performance issues
• Maintain the calibration of
enthalpy sensors
• Measure the difference between
the indoor and outdoor pressure
during economizer operation
o Avoid building over-pressurization
o Relief air system must have an
adequate airflow path
Chiller Economizer Maintenance
35
• Verify that the outside air sensor is
in a good, representative location
o Never in direct sun; not too close
to air outlets
• Make sure the mixed air
sensors are located
correctly as well
o In a place with good mixing
Source: energycodes.gov
Chiller Economizer Maintenance
36Chiller Air Handler Maintenance
• Cycle your dampers open and
closed periodically
o Avoid stuck dampers
• Adjust actuators to achieve full
damper closure
o Close gaps
• Worn for blade and jamb seals.
• Grease serviceable (not sealed)
blower shaft bearings
Source: Dave Moser, CLEAResult
37Wide Variety of Incentives From Consumers Energy
• VFD on HVAC Fans and CW Pumps: $40-60/hp
• High Efficiency air conditioners and chillers: $30-40/Ton
• Air-Side Economizer: $15/Ton
• Chilled Water Reset Retrofit : $1 - $1.50/Ton
• Demand Control Ventilation : $.02-.04/sq.ft.
• Ductwork Insulation: $3-$6/ft.
To find a business energy efficiency incentive that works for
you, contact Consumers Energy at 877-607-0737.
38Tune-Up/Maintenance Incentives
• Boilers
o Up to $500 per boiler
• Furnaces/RTU’s
o Up to $125 per unit
• Chillers
o $350 per chiller
• Steam traps
o $140 per trap
39Poll Question
• How valuable has this Webinar been to you?
a) Not valuable at all.
b) Slightly valuable
c) Moderately valuable.
d) Very valuable.
e) Extremely valuable.
40Resources
• Standard Practice for Inspection
and Maintenance of Commercial
Building HVAC Systems
(ANSI/ASHRAE/ACCA Standard
180-2012).
Questions?
Working to deliver the energy you need, whenever you need it. That’s our Promise to Michigan.
41
• Resources For You Sign up for our FREE Solution Center eNewsletter
• Ask an Expert
• Tools, calculators and energy-saving tips
• All available online
• Contact Us Website: www.ConsumersEnergy.com/business
Phone: 800-805-0490
Email: [email protected]