Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) www.metalcraftroofing.co.nz Architectural / Specification Enquiries Ph: 09 274 0408 Mobile: 027 603 1096 Email: [email protected] RHCG 00 / 23 COVER SHEET 01 / 23 PARAPET AND BALUSTRADE CAPPING 02 / 23 SOFFIT 03 / 23 FLUSH WINDOW HEAD 04 / 23 FLUSH WINDOW SILL 05 / 23 FLUSH WINDOW JAMB 06 / 23 RECESSED WINDOW HEAD 07 / 23 RECESSED WINDOW SILL 08 / 23 RECESSED WINDOW JAMB 09 / 23 BUTT WINDOW HEAD 10 / 23 BUTT WINDOW SILL 11 / 23 BUTT WINDOW JAMB 12 / 23 METERBOX HEAD 13 / 23 METERBOX SILL 14 / 23 METERBOX JAMB 15 / 23 INTERNAL CORNER 16 / 23 EXTERNAL CORNER 17 / 23 INTERNAL CORNER BOX TYPE 18 / 23 EXTERNAL CORNER BOX TYPE 19 / 23 SOAKER FLASHING 20 / 23 VERTICAL BUTT JOINT 21 / 23 BOTTOM OF CLADDING (FLUSH) 22 / 23 BOTTOM OF CLADDING (RECESSED) 23 / 23 3D WINDOW FLASHINGS DETAIL LIST

Upload: others

Post on 25-Sep-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

CorrugateRESIDENTIAL HORIZONTAL CLADDING

0800 ROOFNZ (0800 766 369)www.metalcraftroofing.co.nz

Architectural / Specification EnquiriesPh: 09 274 0408

Mobile: 027 603 1096Email: [email protected]

00 / 23 COVER SHEET01 / 23 PARAPET AND BALUSTRADE CAPPING02 / 23 SOFFIT03 / 23 FLUSH WINDOW HEAD04 / 23 FLUSH WINDOW SILL05 / 23 FLUSH WINDOW JAMB06 / 23 RECESSED WINDOW HEAD07 / 23 RECESSED WINDOW SILL08 / 23 RECESSED WINDOW JAMB09 / 23 BUTT WINDOW HEAD10 / 23 BUTT WINDOW SILL11 / 23 BUTT WINDOW JAMB12 / 23 METERBOX HEAD13 / 23 METERBOX SILL14 / 23 METERBOX JAMB15 / 23 INTERNAL CORNER16 / 23 EXTERNAL CORNER17 / 23 INTERNAL CORNER BOX TYPE18 / 23 EXTERNAL CORNER BOX TYPE19 / 23 SOAKER FLASHING20 / 23 VERTICAL BUTT JOINT21 / 23 BOTTOM OF CLADDING (FLUSH)22 / 23 BOTTOM OF CLADDING (RECESSED)23 / 23 3D WINDOW FLASHINGS

DETAIL LIST

Page 2: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

PRE-FINISHED PARAPET CAP FLASHINGNO FIXINGS ON TOP OF FLASHING

BUILDING PAPER SHOWN DASHED

CONTINUOUS H3.1 TIMBER PACKING

METALCRAFT CORRUGATEHORIZONTAL CLADDING

WALL FRAMING

PRE-FINISHED SELF DRILLING / TAPPINGSCREW WITH RUBBER WASHER

MIN

. 5.00 °

BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPING ANDCLADDING WITH TIMBER SHOWN DASHED

CLE

ARAN

CE

25m

m

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

20mm CAVITY

METALCRAFT CORRUGATEHORIZONTAL CLADDING

BIRDS BEAK EDGE FORDECK SIDE OF CAPPING

5 GAP

20

15

MIN

. 2 C

OR

RU

GAT

ION

S

MIN

. 2 C

OR

RU

GAT

ION

S

CLE

ARAN

CE

25m

m

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 01 / 23

PARAPET AND BALUSTRADE CAPPING

2014

Page 3: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

BUILDING PAPER SHOWN DASHED

20mm CAVITY

WALL FRAMING

METALCRAFT CORRUGATEHORIZONTAL CLADDING

PRE-FINISHED SOFFIT FLASHING

FLY RAFTER

BARGE BOARD

SOFFIT LINING

PURLIN

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

INTERNAL CEILING LINING

CO

VER

CLA

DD

ING

50m

m(M

IN. 3

5mm

)

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

EXTRA NOG FOR TOP FIXING OFWALL CLADDING

BUILDING PAPER TO PROVIDE SEPARATIONOF METAL CAPPING AND CLADDING WITHTIMBER SHOWN DASHED

STST OR GALV. FLAT HEAD NAIL FORFLASHING

INTERNAL WALL LINING

MIN. 50mm

SQUARE STOP CORNICE

5mm GAP

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 02 / 23

SOFFIT

2014

Page 4: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT HEAD

TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING

EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED

INTERNAL WALL LINING

WINDOW LINTEL FRAMING

METALCRAFT CORRUGATEHORIZONTAL CLADDING

PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

DOUBLE GLAZING WINDOW JOINERY

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB

WINDOW HEAD LINER

LINE OF WINDOW JAMB LINER BEHIND

STOPENDS TO HEAD FLASHING

LINE OF JAMB FLASHING BEHIND

5mm

GAP MIN

. 75m

m W

ITH

OU

T H

E M E

DG

E

MIN

.50m

m C

OVE

R

STST OR GALV. FLAT HEAD NAIL FORFLASHING

PVC CAVITY CLOSER

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

DR

IP E

DG

E TO

CLA

DD

I NG

MIN

.15m

m G

AP

MIN

.10m

m C

OVE

R

SU

GG

EST

MIN

.50m

m

DIM

ENS

ION

TO

SU

IT

COMPRESSIBLE FOAM SEALBEHIND TO FILL OVERLAP OF FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 03 / 23

FLUSH WINDOW HEAD

2014

Page 5: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

METALCRAFT CORRUGATE HORIZONTALCLADDING

INTERNAL WALL LINING

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW JAMB LINER BEHIND

WINDOW SILL LINER

MIN. 8mm PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB

FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL

PRE-FINISHED WINDOW SILL FLASHING

WALL FRAMING

BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT SILL

STOPENDS TO SILL FLASHING

LINE OF JAMB FLASHING BEHIND

STST OR GALV. FLAT HEAD NAIL FOR FLASHING

20mm CAVITY

5mm GAP MIN

. 8m

m C

OV

ER

WINDOW SUPPORT BAR

CO

VER

CLA

DD

ING

50m

m(M

IN. 3

5mm

)

PRE-FINISHED SECONDARY FLASHING

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 04 / 23

FLUSH WINDOW SILL

2014

Page 6: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

METALCRAFT CORRUGATEHORIZONTAL CLADDING

BUILDING PAPER SHOWN DASHED

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW SILL LINER BELOW

WINDOW JAMB LINER

TIMBER PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

20mm JAMB BATTEN

INTERNAL WALL LINING

LINE OF SILL FLASHING BELOW

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

20mm CAVITY

LINE OF SILL FLASHING BELOW

PRE-FINISHED WINDOW JAMB FLASHING

COMPRESSIBLE FOAM SEAL TO FILLOVERLAP OF FLASHING

MIN. 10mm COVER

5mm

GAP

PRE-FINISHED SECONDARY FLASHING

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

STST OR GALV. FLAT HEADNAIL FOR FLASHING

SUGGEST MIN. 50mm

DIMENSION TO SUIT

LINE OF HEAD FLASHING ABOVE

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRM CODEOF PRACTICE VERSION 2.2 /2012FOR REQUIRMENT.

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER. SHOWN DASHED

LINE OF HEAD FLASHING ABOVE

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 05 / 23

FLUSH WINDOW JAMB

2014

Page 7: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT HEAD

TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING

EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED

INTERNAL WALL LINING

WINDOW LINTEL FRAMING

METALCRAFT CORRUGATEHORIZONTAL CLADDING

PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

DOUBLE GLAZING WINDOW JOINERY

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB

WINDOW HEAD LINER

LINE OF WINDOW JAMB LINER BEHIND

STOPENDS TO HEAD FLASHING

LINE OF JAMB FLASHING BEHIND

DR

IP E

DG

E TO

CLA

DD

I NG

MIN

. 15m

m G

APM

IN. 1

0mm

CO

VER

5mm

GAP MIN

. 75m

m W

ITH

OU

T H

EM

ED

GE

MIN

. 50m

m C

OVE

R

SU

GG

EST

MIN

.50m

m

DIM

ENS

ION

TO

SU

IT

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PVC CAVITY CLOSER

STST OR GALV. FLAT HEAD NAIL FORFLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 06 / 23

RECESSED WINDOW HEAD

2014

Page 8: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

5mm

GAP

MIN

. 8m

m C

OV

ER

5mm GAP

METALCRAFT CORRUGATE HORIZONTALCLADDING

INTERNAL WALL LINING

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW JAMB LINER BEHIND

WINDOW SILL LINER

MIN. 8mm PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB

PRE-FINISHED WINDOW SILL FLASHING

WALL FRAMING

BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT SILL

STOPENDS TO SILL FLASHING

LINE OF JAMB FLASHING BEHIND

STST OR GALV. FLAT HEAD NAIL FOR FLASHING

20mm CAVITY

WINDOW SUPPORT BAR

PRE-FINISHED SECONDARY FLASHING

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

CO

VER

CLA

DD

ING

50m

m(M

IN. 3

5mm

)

FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 07 / 23

RECESSED WINDOW SILL

2014

Page 9: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

PRE-FINISHED WINDOW JAMBFLASHING

BUILDING PAPER SHOWN DASHED

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW SILL LINER BELOW

WINDOW JAMB LINER

TIMBER PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

20mm JAMB BATTEN

INTERNAL WALL LINING

LINE OF SILL FLASHING BELOW

PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRMCODE OF PRACTICE VERSION 2.2/2012 FOR REQUIRMENT.

METALCRAFT CORRUGATEHORIZONTAL CLADDING

5mm

GAP

MIN. 10mm COVER

PRE-FINISHED SECONDARY FLASHING

5mm GAP

PRE-FINISHED POP RIVETBEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER. SHOWNDASHED

STST OR GALV. FLAT HEAD NAILFOR FLASHING

SEPARATE BATTEN AND FLASHINGAS REQUIRED

SUGGEST MIN. 50mm

DIMENSION TO SUIT

LINE OF HEAD FLASHING ABOVE

LINE OF HEAD FLASHING ABOVE

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 08 / 23

RECESSED WINDOW JAMB

2014

Page 10: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT HEAD

TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING

EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED

INTERNAL WALL LINING

WINDOW LINTEL FRAMING

PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL

STST OR GALV. FLAT HEAD NAIL FOR FLASHING

DOUBLE GLAZING WINDOW JOINERY

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB

WINDOW HEAD LINER

LINE OF WINDOW JAMB LINER BEHIND

STOPENDS TO HEAD FLASHING

LINE OF JAMB FLASHING BEHIND

MIN

.75m

m W

ITH

OU

T H

EM

ED

GE

MIN

. 50m

m C

OVE

R

DR

IP E

DG

E TO

CLA

DD

ING

MIN

. 15m

m G

APM

IN.1

0mm

CO

VER

5mm

GAP

SU

GG

EST

MIN

. 50m

m

DIM

ENS

ION

TO

SU

IT

PVC CAVITY CLOSER

METALCRAFT CORRUGATE HORIZONTALCLADDING

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHEDPRE-FINISHED SELF DRILLING/TAPPING SCREW

WITH RUBBER WASHER

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 09 / 23

BUTT WINDOW HEAD

2014

Page 11: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

5mm

GAP

MIN

. 8m

m C

OV

ER

CO

VER

FLA

SHIN

G

50m

m(M

IN. 3

5mm

)

METALCRAFT CORRUGATE HORIZONTALCLADDING

INTERNAL WALL LINING

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW JAMB LINER BEHIND

WINDOW SILL LINER

MIN. 8mm PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB

FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL

PRE-FINISHED WINDOW SILL FLASHING

WALL FRAMING

BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT SILL

STOPENDS TO SILL FLASHING

LINE OF JAMB FLASHING BEHIND

STST OR GALV. FLAT HEAD NAIL FOR FLASHING

20mm CAVITY

WINDOW SUPPORT BAR

PRE-FINISHED SECONDARY FLASHING

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 10 / 23

BUTT WINDOW SILL

2014

Page 12: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

METALCRAFT CORRUGATEHORIZONTAL CLADDING

BUILDING PAPER SHOWN DASHED

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW SILL LINER BELOW

WINDOW JAMB LINER

TIMBER PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

20mm JAMB BATTEN

INTERNAL WALL LINING

LINE OF SILL FLASHING BELOW

PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRM CODEOF PRACTICE VERSION 2.2 /2012FOR REQUIRMENT.

PRE-FINISHED WINDOW JAMBFLASHING

5mm GAP 5mm GAP

MIN. 50mm

MIN. 10mm COVER

5mm

GAP

STST OR GALV. FLAT HEAD NAILFOR FLASHING

BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBERSHOWN DASHED

SUGGEST MIN.50mm

DIMENSION TO SUIT

LINE OF HEAD FLASHING ABOVE

LINE OF HEAD FLASHING ABOVE

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 11 / 23

BUTT WINDOW JAMB

2014

Page 13: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT HEAD

TEMPORARY PACKER IF REQUIRED, REMOVEDAFTER FIXING

PRE-FINISHED HEAD FLASHING WITH 15° FALL

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB

METER BOX

STOPENDS TO HEAD FLASHING

LINE OF JAMB FLASHING BEHIND

METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.

DR

IP E

DG

E TO

CLA

DD

ING

MIN

. 15m

m G

AP

MIN

. 5m

m G

AP

MIN

. 75m

m W

ITH

OU

T H

E M E

DG

E

MIN

. 50m

m C

OVE

R

PRE-FINISHED 'U' BRACKET FIXED TOMETERBOX BEFORE INSTALLATION

EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED

INTERNAL WALL LINING

PVC CAVITY CLOSER

STST OR GALV. FLAT HEAD NAIL FOR FLASHING

METALCRAFT CORRUGATE HORIZONTALCLADDING

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 12 / 23

METERBOX HEAD

2014

Page 14: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

METALCRAFT CORRUGATE HORIZONTALCLADDING

BUILDING PAPER SHOWN DASHED

METER BOX

WINDOW SILL LINER

MIN. 8mm PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB

WALL FRAMING

INTERNAL WALL LINING

LINE OF JAMB FLASHING BEHIND

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

20mm CAVITY

FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL

METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.

PRE-FINISHED FLASHING

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPING ANDCLADDING WITH TIMBER SHOWN DASHED

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

STOPENDS TO SILL FLASHING

CO

VER

CLA

DD

ING

50m

m(M

IN. 3

5mm

)

PRE-FINISHED SECONDARY FLASHING

STST OR GALV. FLAT HEAD NAIL FOR FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 13 / 23

METERBOX SILL

2014

Page 15: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

METALCRAFT CORRUGATEHORIZONTAL CLADDING

BUILDING PAPER SHOWN DASHEDMETER BOX

TIMBER PACKER

20mm JAMB BATTENINTERNAL WALL LINING

LINE OF SILL FLASHING BELOW

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER FLEXIBLE FLASHING TAPE OVER

BUILDING PAPER FOR FULLWIDTH/DEPTH SILL

LINE OF HEAD FLASHING ABOVEPRE-FINISHED WINDOW JAMBFLASHING FIXED TO METERBOXBEFORE INSTALLATION

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILLAND JAMB

METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.

CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.

BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBERSHOWN DASHED

STST OR GALV. FLAT HEAD NAILFOR FLASHING

PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER

PRE-FINISHED POP RIVET BEDDEDIN SILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

SUGGEST MIN. 50mm

DIMENSION TO SUIT

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

LINE OF HEAD FLASHING ABOVE

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 14 / 23

METERBOX JAMB

2014

Page 16: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

METALCRAFT CORRUGATEHORIZONTAL CLADDING

WALL FRAMING

20mm CAVITY

PRE-FINISHED INTERNALCORNER FLASHING

INTERNAL WALL LINING

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

BUILDING PAPER SHOWN DASHED

SU

GG

EST

MIN

. 75m

m

DIM

ENS

ION

TO

SU

IT

SUGGEST MIN. 75mm

DIMENSION TO SUIT

CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.

STST OR GALV. FLAT HEAD NAIL FORFLASHING

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PRE-FINISHED SECONDARY FLASHING

PRE-FINISHED POP RIVETBEDDED IN SILICONE ORPRE-FINISHED 8g WAFER-TEK SCREW

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 15 / 23

INTERNAL CORNER

2014

Page 17: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

20mm CAVITY

METALCRAFT CORRUGATE HORIZONTALCLADDING

INTERNAL WALL LINING

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

WALL FRAMING

PRE-FINISHED EXTERNALCORNER FLASHING

BUILDING PAPER SHOWN DASHED

SUGGEST MIN. 75mm

DIMENSION TO SUIT

SU

GG

EST

MIN

. 75m

m

DIM

ENS

ION

TO

SU

IT

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRM CODEOF PRACTICE VERSION 2.2 /2012FOR REQUIRMENT.

BUILDING PAPER TO PROVIDESEPARATION OF METALCAPPING AND CLADDING WITHTIMBER SHOWN DASHED

PRE-FINISHED POP RIVETBEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

STST OR GALV. FLAT HEAD NAIL FORFLASHING

PRE-FINISHED SECONDARYFLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 16 / 23

EXTERNAL CORNER

2014

Page 18: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

METALCRAFT CORRUGATEHORIZONTAL CLADDING

WALL FRAMING

20mm CAVITY

PRE-FINISHED INTERNAL CORNERFLASHING

INTERNAL WALL LINING

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

BUILDING PAPER SHOWNDASHED

MIN. 50mm COVER

MN

. 50m

m C

OVE

R

5mm

GAP

5mm GAP

CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

STST OR GALV. FLAT HEAD NAIL FORFLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 17 / 23

INTERNAL CORNER BOX TYPE

2014

Page 19: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

20mm CAVITY

METALCRAFT CORRUGATEHORIZONTAL CLADDING

INTERNAL WALL LINING

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

WALL FRAMING

BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBERSHOWN DASHED

MIN. 50mm COVER

MIN

. 50m

m C

OVE

R5mm

GAP

5mm GAP

BUILDING PAPER SHOWN DASHED

PRE-FINISHED EXTERNAL CORNERFLASHING

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRMCODE OF PRACTICE VERSION2.2 /2012 FOR REQUIRMENT.

STST OR GALV. FLAT HEAD NAIL FORFLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 18 / 23

EXTERNAL CORNER BOX TYPE

2014

Page 20: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

BUILDING PAPERSHOWN DASHED

METALCRAFT CORRUGATEHORIZONTAL CLADDING

PRE-FINISHED FLAT HEADWAFER-TEK SCREW FORFLASHING

INTERNAL WALL LINING

20mm CAVITY

WALL FRAMING

PRE-FINISHED SOAKERFLASHING BELOW WINDOWJAMBS

BUILDING PAPER TOPROVIDE SEPARATION OFMETAL CAPPING ANDCLADDING WITH TIMBERSHOWN DASHED

SOAKER FLASHING ONLY REQUIRED TOLINE UP WITH WINDOW JAMB ABOVE.REFER TO MRM CODE OF PRACTICEVERSION 2.2 /2012 FOR REQUIRMENT.

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 19 / 23

SOAKER FLASHING

2014

Page 21: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

BUILDING PAPERSHOWN DASHED

METALCRAFT CORRUGATEHORIZONTAL CLADDING

PRE-FINISHED SELFDRILLING / TAPPING SCREWWITH RUBBER WASHER

INTERNAL WALL LINING

WALL FRAMING

PRE-FINISHED JOINTERFLASHING

5mm GAP

MIN. 50mm COVER

BUILDING PAPER TO PROVIDESEPARATION OF METALCAPPING AND CLADDING WITHTIMBER SHOWN DASHED

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 20 / 23

VERTICAL BUTT JOINT

2014

Page 22: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

20mm CAVITY

INTERNAL WALL LINING

WALL FRAMING

METALCRAFT CORRUGATEHORIZONTAL CLADDING

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

PRE-PRIMED SKIRTING

CONCRETE SLAB

MIN

. 15m

m D

RIP

ED

GE

MIN

. 50m

m L

AP

BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBER OVERFLASHING. SHOWN DASHED

PRE-FINISHED NON-PERFORATEDCLOSURE FLASHING WITH 10° FALL

VEN

TILA

TIO

N G

AP

3- 5m

m

STST OR GALV. FLAT HEAD NAIL FORFLASHING

BUILDING PAPER SHOWN DASHED

PVC CAVITY CLOSER

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 21 / 23

BOTTOM OF CLADDING (FLUSH)

2014

Page 23: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

INTERNAL WALL LINING

WALL FRAMING

PVC CAVITY CLOSER

MIN

. 75m

m C

OV

ER

VEN

TILA

TIO

N G

AP

3 - 5

mm

PRE-PRIMED SKIRTING

CONCRETE SLAB

MIN

. 50m

m L

AP

20mm CAVITY

METALCRAFT CORRUGATEHORIZONTAL CLADDING

BUILDING PAPER OVER FLASHINGSHOWN DASHED

STST OR GALV. FLAT HEAD NAIL FORFLASHING

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBER SHOWNDASHED

ALTERNATIVE OPTIONBIRDS BEAK EDGE

5 GAP

20

15

PRE-FINISHED NON-PERFORATEDCLOSURE FLASHING WITH 10° FALL

HEMMED EDGE

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 22 / 23

BOTTOM OF CLADDING (RECESSED)

2014

Page 24: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateRHCG ......Corrugate RESIDENTIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL HORIZONTAL CLADDING

RHCG 23 / 23

3D WINDOW FLASHINGS

2014

HEAD FLASHING

JAMB FLASHING

SILL FLASHING

METALCRAFTCORRUGATEHORIZONTALCLADDING

ALUMINIUMWINDOWJOINERY

COMPRESSIBLEFOAM SEALBEHIND TO FILLOVERLAP OFFLASHING

FLUSH WINDOW FLASHINGS RECESSED WINDOW FLASHINGS

HEAD FLASHING

JAMB FLASHING

ALUMINIUMWINDOWJOINERY

SILL FLASHING

METALCRAFTCORRUGATEHORIZONTALCLADDING