s4d500-am03-01 ac axial fan-hyblade€¦ · ac axial fan-hyblade ® sickled blades (s series) with...
TRANSCRIPT
AC axial fan - HyBlade®
sickled blades (S series)with short square nozzle
S4D500-AM03-01
ebm-papst Mulfingen GmbH & Co. KGBachmühle 2 · D-74673 MulfingenPhone +49 7938 81-0Fax +49 7938 [email protected] partnership · Headquarters MulfingenCounty court Stuttgart · HRA 590344
General partner Elektrobau Mulfingen GmbH · Headquarters MulfingenCounty court Stuttgart · HRB 590142
Nominal data
Type S4D500-AM03-01Motor M4D110-GF
Phase 3~ 3~ 3~ 3~Nominal voltage VAC 400 400 400 460Connection Δ Y Δ ΔFrequency Hz 50 50 60 60
Type of data definition ml ml ml mlValid for approval / standard CE CE CE CESpeed min-1 1390 1180 1590 1640Power input W 720 550 1020 1060Current draw A 1.41 0.95 1.7 1.64Max. back pressure Pa 140 100 130 138Min. ambient temperature °C -40 -40 -40 -40Max. ambient temperature °C 65 65 50 60Starting current A 6.5ml = max. load · me = max. efficiency · fa = running at free air · cs = customer specs · cu = customer unitSubject to alterations
Data according to ErP directive
Installation category AEfficiency category StaticVariable speed drive NoSpecific ratio* 1.00* Specific ratio = 1 + pfs / 100 000 Pa
Actual Request 2013 Request 2015
Overall efficiency ηes 33.4 28.8 32.8Efficiency grade N 40.6 36 40Power input Pe kW 0.73Air flow qv m³/h 5860Pressure increase pfs Pa 151Speed n min-1 1385Data established at point of optimum efficiency
Item no. 10061-5-9980 · Revision 78747 · Release 2012-12-04 · Page 1 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC axial fan - HyBlade®
sickled blades (S series)with short square nozzle
S4D500-AM03-01
Technical features
Mass 13 kgSize 500 mmSurface of rotor Coated in blackMaterial of terminal box PP plasticMaterial of blades Press-fitted sheet steel blank, sprayed with PP plasticMaterial of guard grille Steel, coated in black plastic (RAL9005)Number of blades 5Direction of air flow "V"Direction of rotation Counter-clockwise, seen on rotorType of protection IP 54Insulation class "F"Humidity class F4-1Max. permissible ambient motortemp. (transp./ storage)
+ 80 °C
Min. permissible ambient motortemp. (transp./storage)
- 40 °C
Mounting position Shaft horizontal or rotor on bottom; rotor on top on requestCondensate discharge holes Rotor-sideOperation mode S1Motor bearing Ball bearingTouch current acc. IEC 60990(measuring network Fig. 4, TNsystem)
<= 3.5 mA
Electrical leads Via terminal boxMotor protection Thermal overload protector (TOP) brought outCable exit AxialProtection class I (if protective earth is connected by customer)Product conforming to standard EN 61800-5-1; CEApproval GOST; VDE; CCC
Item no. 10061-5-9980 · Revision 78747 · Release 2012-12-04 · Page 2 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC axial fan - HyBlade®
sickled blades (S series)with short square nozzle
S4D500-AM03-01
Product drawing
1 Direction of air flow "V"2 Tightening torque 1.5±0.2 Nm3 Cable diameter: min. 6 mm, max. 12 mm, tightening torque: 2±0.3 Nm
Item no. 10061-5-9980 · Revision 78747 · Release 2012-12-04 · Page 3 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC axial fan - HyBlade®
sickled blades (S series)with short square nozzle
S4D500-AM03-01
Connection screen
Δ Delta connection Y Star connection L1 = V1 = blueL2 = U1 = black L3 = W1 = brown W2 yellowU2 green V2 white TOP 2 x greyPE green/yellow
Item no. 10061-5-9980 · Revision 78747 · Release 2012-12-04 · Page 4 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC axial fan - HyBlade®
sickled blades (S series)with short square nozzle
S4D500-AM03-01
Charts: Air flow 50 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]9.0008.0007.0006.0005.0004.0003.0002.0001.0000
qv[cfm]5.0004.0003.0002.0001.0000
]aP[sf p
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
pfs
_E[IN
H2O
]
0,85
0,8
0,75
0,7
0,65
0,6
0,55
0,5
0,45
0,4
0,35
0,3
0,25
0,2
0,15
0,1
0,05
0
]aP[s
f p
]aP[s
f p
1
2
3
4
5
6
7
8
Measurement: LU-106631Measurement: LU-106885
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
12345678
Conn.
ΔΔΔΔYYYY
UV400400400400400400400400
fHz5050505050505050
nmin-1
14201410140013901275124512151180
Pe
W540603659720433476515550
IA1.211.281.341.410.710.780.840.95
LpAin
dB(A)68666465
LwAin
dB(A)7572717172706868
LwAout
dB(A)7573717173706868
qvm3/h91958315727062808255732563355410
pfs
Pa05010014003976104
Conn. = Connection · U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet sideLwAout = Sound power level outlet side · qv = Air flow · pfs = Pressure increase
Item no. 10061-5-9980 · Revision 78747 · Release 2012-12-04 · Page 5 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC axial fan - HyBlade®
sickled blades (S series)with short square nozzle
S4D500-AM03-01
Charts: Air flow 60 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]14.00013.00012.00011.00010.0009.0008.0007.0006.0005.0004.0003.0002.0001.0000
qv[cfm]8.0007.0006.0005.0004.0003.0002.0001.0000
]aP[sf p
240
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
pfs
_E[IN
H2O
]
0,95
0,9
0,85
0,8
0,75
0,7
0,65
0,6
0,55
0,5
0,45
0,4
0,35
0,3
0,25
0,2
0,15
0,1
0,05
]aP[s
f p
1
2
3
4
Measurement: LU-110160
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
1234
Conn.
ΔΔΔΔ
UV460460460460
fHz60606060
nmin-1
1680167016551640
Pe
W85492710001060
IA1.411.491.571.64
LpAin
dB(A)71706868
LwAin
dB(A)79777575
LwAout
dB(A)79777675
qvm3/h109201008092458545
pfs
Pa050100138
Conn. = Connection · U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet sideLwAout = Sound power level outlet side · qv = Air flow · pfs = Pressure increase
Item no. 10061-5-9980 · Revision 78747 · Release 2012-12-04 · Page 6 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com