s8610u3009 universal electronic ignition modules training module (plus universal retrofit kits...
DESCRIPTION
S8610U3009 Universal Electronic Ignition Modules Training Module (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006). What you will learn. Ignition Types S8610U3009 Features and Benefits Installation and Set Up Troubleshooting S8610U Advantage Y8610U Retrofit Ignition Kit Overview - PowerPoint PPT PresentationTRANSCRIPT
S8610U3009 Universal Electronic Ignition
Modules Training Module
(plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)
2
What you will learn
• Ignition Types• S8610U3009
- Features and Benefits- Installation and Set Up - Troubleshooting- S8610U Advantage
• Y8610U Retrofit Ignition Kit Overview• Product Cross Reference Information
3
Ignition Sources
• There are 3 different ways a burner can be ignited:
- 1) Standing Pilot Ignition
- 2) Intermittent Pilot Ignition Intermittent Pilot - S8610U
- 3) Direct Burner Ignition Hot Surface Ignition – S8910UDirect Spark Ignition – S87
S8610U3009
5
Universal Intermittent Pilot Module
• What is the S8610U3009?- Provides electronic control of
intermittent pilot ignition systems used on gas fired furnaces, boilers, and other heating appliances
- It’s the brain of the ignition system Receives call for heat signal from the
thermostat Starts the spark ignition Opens the pilot valve Senses to see if the pilot is lit Opens the main burner Shuts things down at the end of the
call for heat Monitors damper as opened or closed,
if damper is attachedOne Part Number:
S8610U3009
6
Normal Operation of an Intermittent Ignition Module
On Off
Valve On
Pilot Lights
Prove
Pilot
Off
Off
Burner Lights
Valve On
End Call
for Heat
MainBurner
Pilot
Ignition
Call for HeatOn a call for heat, both the Pilot valve and the Ignition come on together.
Once the pilot is proved, the Ignition shuts off and the Main burner opens and remains open throughout the call for heat.
When the call for heat ends, both the Main burner and Pilot shut off together.
7
S8610U Features
• Universal Compatibility- Replaces more than 400
Honeywell and competitive models
• Application Flexibility- Works in single-rod and dual-
rod applications- Works with both natural and
LP gas• Quality Honeywell Control
- Provides electronic control for nearly any intermittent pilot ignition systems used on gas-fired furnaces, boilers and more
- Suitable for use with vent dampers
- Provides the ignition sequence, flame monitoring and 100% safety shutoff
• Enhanced Features- Single LED indicates flame
strength and gives diagnostic information
- Direct flame signal readout form the board
- Simplified error codes on label
8
The Benefits
• Feature• Field selectable operating
sequence can be customized
• Control locks to selected sequence on 20th “call for heat”
• LED communicates system status
• Integral damper connector
• Continuous retry ignition sequence
• Benefit• Allows for more options in the field:
- 0 or 30 second prepurge and- 15 or 90 second trial for ignition
• Assures selected sequence is retained permanently
• Green LED indicates status, error codes and pilot flame strength
• If senses use with a vent damper it locks the control, so damper must be used
• Provides 100% shutoff for both Natural and LP applications
9
Additional benefits
• Feature• Single-rod or dual-rod flame
sensor
• Terminal-to-terminal wiring instructions
• Flame sense terminal 3/16” male QC (virtually all 2-rod systems sold have the sense terminal as 3/16” QC)
• Spark cable adapter
• 2.0 A main valve load rating
• Benefit• Works in more applications
• Reduces wiring errors
• Prevents possible mis-wire of spark sense and potential for abnormal appliance light-off
• Includes adapter for rajah and nail type cable on existing systems; Simplified use
• Broader application; Fits more jobs
10
Ignition Sequences when a pilot fails to light
Call for Heat Lockout
ContinuousRetry
Non-Lockout
Valve & Ignition On
Valve & Ignition Off
or...
or...
5 Min Off
Call for Heat
Valve & Ignition On
90 Sec Trial
90 Sec Trial
Trial Period
5 Min Off
LockoutShuts off and does not retry
Does not shut off, could be a safety issue
S8610U - Continuous retry with 100% safety shutoff between trials
11
SPARK
REMOTE SENSE
SENSE JUMPER WIRE
CUSTOMIZE OPERATING SEQUENCE
STATUS LED
P1 VENT DAMPER CONNECTOR
MV
MV/PV
PV
BRN/GND 24 GND
24V (OPT.)
TH-W (OPT.)
S8610U Control Layout
FLAME CURRENT MEASUREMENT PORTS
Installation
13
Installation of the S8610U
• Mount new ignition module - Do not mount with terminals facing up- protect the module from exposure to water, moisture, corrosive
chemicals and excessive dust and grease.
• Wire the module- Wire the module per the installation instructions- Verify the thermostat anticipator setting
14
Wiring continued
For systems with a vent damper connect the damper to P1
Once the vent damper connection is made, the control must be used with a vent damper.
15
Use With 1-Electrode Pilot
Jumperremains onSENSE
S8610U C
ON
TINU
OU
S RE-TR
Y24V, 60 H
z; PV = 1A M
ax.; MV = 2A
Max.
! WA
RN
ING
MV
MV/PV
PV
GND
24V
24V
TH-W
If module has been used w
ithvent dam
per, it will only w
orkw
ith damper connected.
Honeyw
ell
STATU
S
S1
1 2
ON
SPAR
K
SENSE
DA
MPER
0 Sec. P
repurge90 S
ec. Trial for Ignition
To wire this up, one wire runs from the Igniter to the module SPARK terminal. The black jumper connected to the SENSE terminal remains connected
16
OR Use With 2-Electrode Pilot
S8610U C
ON
TINU
OU
S RE-TR
Y24V, 60 H
z; PV = 1A M
ax.; MV = 2A
Max.
! WA
RN
ING
MV
MV/PV
PV
GND
24V
24V
TH-W
If module has been used w
ithvent dam
per, it will only w
orkw
ith damper connected.
Honeyw
ell
S1
1 2
ON
SPAR
K
SENSE
DA
MPER
0 Sec. P
repurge90 S
ec. Trial for Ignition
Sense WireSpark Wire
Unplug jumperand cut off wire
On a two rod application, there will be two wires running from the pilot to the module. The high voltage wire to SPARK and the flame sensor wire to SENSE
STATU
S
Set Up
18
Set Up the S8610U
• Review the module installation and set up for use- Visually inspect, safety check, and review operating sequence
per installation instructions- Customize the operating sequence based on the specifications
of the originally installed control
19
Customize Operating Sequence
Prepurge Trials for Ignition Sw 1 Sw 2
None90 Seconds OFF OFF30 Seconds 90 Seconds ON OFFNone15 Seconds Off ON30 Seconds 15 Seconds ON ON
Set the dip switches per the application.
Troubleshooting
21
Troubleshooting of the S8610U
Flame signal is not getting back to the module•This is a common problem
•Probable causes•Bad wiring in the flame detection circuit•Pilot not burning properly•Flame sensor damaged/corroded•Cracked/contaminated ceramic
22
LED status and flame strength
Green LED status codes Indicates status, error codes and flame strength
23
Status LED
Green Status LED CodesOFF No “call for heat”Flash fast Power up – internal checkHeartbeat Normal startup – ignition started2 5 min. retry delay3 Recycle4 Flame out of sequence5 Damper error6 Control internal error7 Flame rod shorted to ground8 Low voltage
4-second solid on followed by “x” 1-second flashes indicates flame current
24
Flame current measurement
Pilot flame current can be measured using a standard micro-ammeter
Universal IP Retrofit Ignition System Kits
Y8610U
26
Universal IP Retrofit Ignition System Kit
• What is the Y8610U?- Complete kit converting conventional standing pilot systems to
intermittent pilot systems. - Use with 24 Vac gas-fired atmospheric furnaces, boilers and
heating appliances- Natural or LP gas (includes LP conversion kit)- Reintroduced in 2007 to include the new S8610U3009
27
Y8610U6006 Features
• The Y8610U6006 (replaced Y8610U3003) Ignition System Kit includes:- S8610U3009 Intermittent Pilot Ignition Module- VR8304M3558 Gas Valve - ¾” x ¾” - Harness Assembly, Ignition Cable Assembly, Mounting Kit,
Ignitor, L.P. Conversion Kit, Pipe Bushing or Fitting and ¾” Straight Flange
- Y8610U6006 FEATURES :- Continuous Retry Ignition Sequence - LP or Natural Gas - Valve Capacity – 270K BTUH- ¾” to ½” Bushings- LP Kit
28
Y8610U4001 Features
• Y8610U4001 (replaced Y8610F5003) includes:- S8610U3009 Intermittent Pilot Gas Burner Control- VR8204A2142 Gas Valve – ½” X ½”- Harness Assembly, Ignition Cable Assembly, Mounting Kit, Igniter
Kit, L.P. Conversion Kit, and ¾” Straight Flange
- Y8610U4001 FEATURES :- Continuous Retry Ignition Sequence - LP or Natural Gas - Valve Capacity – 150K BTUH- LP Kit
Product Cross Reference
30
Product Cross Reference
• Where do I find Honeywell electronic ignition cross reference and selection information?
- www.customer.honeywell.com- Honeywell Application Selection and Cross Reference Guide – Form 63-9575- Honeywell Laminated Truck Visor – Form 63-9581G- S8610U Technicians Quick Reference Guide – Form - Honeywell Residential Technical Support: 1-800-468-1502
63-9581G 63-9575
31
Product Cross Reference Guide
Forms 63-9575 and 63-9581G – information also found in product installation sheets.
32
www.customer.honeywell.com
• See Cross Reference Search box in right column.
33
The S8610U Advantage
• When promoting the S8610U keep these advantages in mind:
- The S8610U replaces over 400 Honeywell and competitor’s ignition modules, reducing inventory and callbacks.
- Easy Installation saves the contractor valuable time and resources.
- Field-selectable pre-purge and ignition timings make the S8610U a Universal replacement
- The S8610 is application flexible and can be used with single rod or dual rod systems, and natural or LP gas.
- The diagnostic LED and flame signal indicator make troubleshooting simple, solving the problem quickly and satisfying the customer.
S8610U Universal Electronic Ignition
Knowledge Test
35 HONEYWELL - CONFIDENTIAL File Number
• Now that you completed this training module, take the short quiz to test your knowledge.
Universal Electronic Ignition Knowledge Test
36 HONEYWELL - CONFIDENTIAL File Number
Test
1. The S8610U3009 is an intermittent pilot ignition module? T or F
2. The S8610U is application flexible and work with single or dual rod systems? T or F
3. On the S8610U once the controls senses a vent damper, the control can be used without a vent damper? T or F
4. The operating sequence on the S8610U is customized by setting dip switches on the device? T or F
5. A new feature on the S8610U includes a separate LED flame signal indicator? T or F
37 HONEYWELL - CONFIDENTIAL File Number
Test
6. The S8610U has continuous retry and 100% safety shut off between cycles? T or F
7. The S8610U works with only natural gas? T or F8. Flame strength readings can be taken directly
from the board with a standard micro-ammeter? T or F
9. The Y8610U kits convert applications from standing pilot to hot surface ignition? T or F
10.The Honeywell S8610U replaces over four hundred Honeywell and competitive ignition modules? T or F
38 HONEYWELL - CONFIDENTIAL File Number
Answer Key
1. T2. T3. F4. T5. F6. T7. F8. T9. F10.T