sa-000-e-11608_general lighting systems_rev t01.pdf
TRANSCRIPT
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
1/36
Sultanate of OmanMinistry of Transport and CommunicationsDevelopment of Salalah International Airport
Main Contract 5Project Specification
Building, Electrical
General Lighting Systems
General Specification
October 2008
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
2/36
Sultanate of OmanMinistry of Transport and CommunicationsDevelopment of Salalah International Airport
Main Contract 5
Project Specification
Building, Electrical
General Lighting Systems
General Specification
October 2008
Report no. SA-000-E-11608
Issue no. T01
Date of issue 31.10.2008
Prepared ALJS/PVN/HO
Checked TJJ
Approved HO/THMJ
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
3/36
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
4/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
2
.
1 General
1.1 Introduction
A. This part specifies the general requirements for the General Lighting. It
shall be read in conjunction with other parts of the ContractDocumentation.
B. The work shall include the interim, detailed and final design, manufacture,supply, installation, supervision of own work and test & commissioning of
the General Lighting including all necessary accessories and coordination
work as shown on the drawings and specified in relevant specifications and
as herein specified, and to the satisfaction of the Engineer.
C. The General Lighting consists of the following, but is not limited to:
1. Illumination level requirement.2. Emergency lighting.3. Switchboards for emergency lighting.4. Central battery system - mains power supply.5. Self contained emergency battery packs.
D. The Contractor shall coordinate with all relevant specialist sub-contractorsto ensure that the location of Luminaires shall not interfere with the
operation and functionality of any other equipment such as, but not
restricted to, Moving/Intelligent displays and/or illuminated signage of any
type with particular reference to Reflection and Glare.
E. The Contractor shall ensure that the general distribution of light shall beuniform avoiding "Hot-Spots" creating a general relaxed atmosphere.
F. The design shall incorporate necessary allowances for the effect ofcondensation and any subsequential damage to equipment, finishes and
structure. Claims arising from the effects of either humidity and/or
condensation will not be entertained.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
5/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
3
.
1.2 Related Documents
A. Employer's Requirements and general provisions of Contract, includingGeneral, Supplementary and Special Conditions of the Contract
Documents.
B. Related General Specification Section:
1. SA-000-E-11603 Low Voltage Protection and Control Devices.
2. SA-000-E-11604 Low Voltage Cabling.
3. SA-000-E-11605 Distribution Ways.
4. SA-000-E-11609 Luminaires and Lamps.
5. SA-000-E-11611 Earthing and Bonding.
6. SA-000-E-11612 Electrical Accessories.
7. SA-000-E-11615 Electromagnetic Compatibility.
8. SA-000-E-11616 Identification of Components, Cables and
Equipment.
9. SA-000-E-11623 Equipment for Controlling of Lighting.
C. Related Specifications and drawings including, but not limited to:
1. Architectural Services.2. Structural and Civil works.3. Civil Works.4. Airport SCADA/BMS.5. PMS (Power Management System).6. Airport Fire Protection and Safety systems.7. Mechanical Services.8. IT Systems.9. Lift Installations.10. PA Installations.11. Baggage Handling.12. Travelators and Escalators.
D. Related Particular Specifications:
1. SA-000-E-11600 Electrical Installation.
1.3 Codes and Standards
A. The design, workmanship, materials and equipment associated with thissection shall comply with the latest issue, including all amendments, of the
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
6/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
4
.
appropriate Omani, British and European Standard Specifications.
Particularly relevant Standard Specifications are as follows:
Number Title
OES4 Regulations for Electrical Installations
CIBSE Commissioning Code L. Lighting
CIBSE LG7 Office lighting
ICEL Standards Industry Committee for Emergency Lighting Standards
BS 67 Specification for ceiling roses
BS 764 Specification for automatic change-over contactors for emergency
lighting systems
BS EN 1838:1999
BS 5266
Emergency Lighting
BS 5225 Method of photometric measurement of battery operated
emergency lighting Luminaires
BS 5266-1 Emergency lighting: Part 1 - Code of practice of premises other
than cinemas and certain other specified used for entertainment
BS 5266-2 Emergency lighting. Code of practice for electrical low mounted
way guidance systems for emergency use
BS 5266-3 Emergency lighting. Specification for small power relays
(electromagnetic) for emergency lighting applications up to and
including 32 A
BS 5266-4 Emergency lighting. Code of practice for design, installation,
maintenance and use of optical fibre systems
BS 5266-5 Emergency lighting. Specification for component parts of optical
fibre systems
BS 5266-6 Emergency lighting. Code of practice for non-electrical low
mounted way guidance systems for emergency use.
Photoluminescent systems
BS 5499-4 Safety signs, including fire safety signs. Code of practice for
escape route signing
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
7/36
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
8/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
6
.
Detailed and Final Design
C. Submit Detailed and Final Design in accordance with the Employer'sRequirements divided into a Detailed and Final Design stages including,
but not limited to:
1. Design, Construction, Installation, shop and fabrication drawingsincluding, but not limited to:
a) Detailed drawings including coordination drawings, floor plansand sections drawn to accurate 1:50 scale. Show all luminaries
locations including emergency lighting and relationships between
luminaries, switchboards, censors and switches
b) One line diagrams for emergency lighting and relationshipbetween the normal lighting and the emergency lighting
c) Strategy for switching on/off emergency lighting in various zones
d) Detailed drawings for each switchboard for the emergencylighting include dimensioned elevations with layouts of
component parts
e) Cable termination facilities and internal wiring arrangements
f) Show minimum clearances, installed devices, major features
g) Nameplate legend
h) Size and number of conductors in each trunking and conduit,including phase, neutral, and earth conductors of main and branch
buses
i) Short time and short circuit ratings of switchboard assembly
j) Single line diagram: Updated version of single line diagramreflecting Switchboards for emergency lighting
k) Material lists.
2. Detailed Design drawings for wiring and circuit diagrams with wireterminal numbering: Single line, elementary, and schematic diagramsof equipment to be supplied, differentiating between manufacturers
installed and field installed wiring.
3. Lighting calculations for all individual rooms.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
9/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
7
.
1.4.2 Product data
A. Submit the following according to the Employer's Requirements, but notlimited to:
1. Complete and detailed information of all materials and equipment tobe incorporated in the work.
2. Detailed description and specifications, catalogues cuts, installationdata, diagrams, dimensions, controls and any other data required to
demonstrate compliance with the Employer's Requirements. Each item
submitted shall be referenced to the applicable paragraph in the
Specification.
3. A point by point statement of compliance. The statement ofcompliance shall consist of a list of numbered paragraphs. Each
specification paragraph shall be cross referenced to the page/drawingin the submittal on which the compliance is confirmed; the confirming
data on the page/drawing shall be highlighted for ready identification.
Where the proposed system complies fully, indicate by placing the
word "comply" opposite the paragraph number. Where the proposed
system does not comply, or accomplishes the stated function in a
manner different from that described, provide a full description of the
deviation. Where the full description of a deviation is not provided, it
shall be assumed that the proposed system does not comply with the
paragraph in question. Any submission that does not include a point
by point statement of compliance as specified shall be disqualified.
4. Copy of relevant test certificates from the manufacturer ensuring thatthe lighting system complies with the Specifications.
1.4.3 Samples
A. Submit products samples to establish the suitability of the product andutilised for future product reference. Samples shall not be returned to the
Contractor.
B. Submit the following according to the Employer's Requirements:
1. Central battery samples including, but not limited to:
a) Valve Regulated Lead Acid (VRLA) type maintenance free typeb) Enclosure body, epoxy powder coated with access doors
2. Cable entry; top, bottom3. Wiring.4. Cable identification tags.5. Labelling in English and Arabic.6. Interfaces with Airport SCADA.7. Earthing and bonding arrangements.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
10/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
8
.
C. Submit the following details along with each product item, but not limitedto:
1. Manufacture (Make).2. Type.3. Product/component reference code.4. Technical characteristics.5. Country of origin.6. Test certificates.
1.4.4 Operation and Maintenance Manuals
A. Submit the following according to the Employer's Requirements:
1. List of material installed on site including material reference number
given by the material manufacturer.
2. Data sheets for all material installed on site.
3. Relevant telephone and fax numbers for manufactures including pointof contacts, address and references to homepages.
4. Maintenance data for all kinds of equipment installed includingmaintenance plan.
5. Inspection and test plans.
6. All test certifications from manufacturers.
7. List of spare parts required for a maintenance period for 5 years.
8. Instruction manuals.
9. Operator manuals.
10. Maintenance manuals.
1.4.5 As-built drawings
A. Submit the following according to the Employer's Requirements:
1. Up-dated construction issue drawings modified to accurately reflectthe installations as installed on site.
1.4.6 Spare parts
A. Provide spare parts for 2 years for operation of the plant, but as a minimumthe following:
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
11/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
9
.
No. Description Quantity
Tools
1 Fuse puller (set) One with each Central Battery System
2 Panel standard keys One with each Central Battery System
3 Diagnostic tool with software and
hardware
One with each type of Central Battery
System
4 Central Battery System maintenance
toolkit
One set with each lot of supply
Components
1 Transformer By-pass 1 of each type
2 Capacitors (DC & AC) 1 of each type
3 Rectifier Module 1 of each type
4 Relay solid state 5 %
5 IGBT Module on inverter side 1 of each type
6 IGBT Module on converter Side 1 of each type
7 Power side fuses 5 % of each size and type used
8 Control fuses 5 % of each size and type used
9 Switch 32 A, 4 position rotary switch 5 %
10 Control transformer 1 of each type
11 Converter side transformer 1 of each type
12 DC side choke 1 of each type
13 Inverter choke 1 of each type
14 Display board 5 %
15 LED Front panel display 5 %
16 Auxiliary PSU 5 %
17 Single phase Axial fan 5 %
1.4.7 Warranties and Guarantees
A. The Contractor shall provide all Warranty and Guarantee Certificates inaccordance with the Employer's Requirements.
B. Defects Liability Period:
1. The Contractor shall include for all maintenance procedures inaccordance with the manufacturers requirements during the defects
liability period and shall prepare a comprehensive schedule of
maintenance procedures that shall be carried out.
2. The Contractor shall provide an exhaustive quantified schedule ofmaintenance spares for this period, and these spares shall be in
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
12/36
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
13/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
11
.
2 Product Specification and FunctionalDescription
2.1 General
A. The detailed lighting design shall be based on the following luminaire andlamp maintenance properties and illumination requirements:
1. Lamp lumen maintenance factor: 0.8.2. Luminaire maintenance factor: 0.8.3. Room surface maintenance factor: 0.8.
B. Room surface reflection factors shall be as specified below in accordanceto CIBSE Code for interior lighting 2006, unless any special materials or
colours are utilised:
Surface Light Medium Dark
Ceiling 70 % 50 % 30 %
Walls 50 % 30 % 10 %
Floor 30 % 20 % 10 %
C. The Average maintained illumination level of various rooms/areas shall becalculated and the uniformity (Ratio of minimum illumination to average
illumination) in any room shall be as follows:
Area Uniformity illumination
(min/average)
Indoor >0.6
External
Yard Area
Street Lighting
Car Parking
>0.4
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
14/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
12
.
D. The Contractor shall utilise an Industry Standard Windows Based
Electrical Calculations software for calculating the Lighting and
Emergency Lighting Levels according to the relevant standards detailed
within this Specification. The Contractor shall determine the reflectancevalues, based on the finishes schedule detailed within the Employer's
Requirements.
1. The following calculated data shall be submitted as a minimum forboth Lighting and Emergency Lighting Calculations:
a) Average Lighting levels on the working Plane, Floor, all walls,ceiling
b) The % reflectance's
c) Compliance with LG7
d) Uniformity and Ratio's of Illuminance
e) Total installed Watts
f) 3d Visualisation
g) Isometric diagram
h) Glare
i) Photometric Data
j) Polar Intensity Curves
k) Illuminance Cone Diagrams
l) Cartesian and Isolux Diagrams
m) Confirmation of all Emergency lighting calculations inaccordance with relevant standards.
2. Based on the initial results issued by the Contractor to the Engineer,additional information may be required; the software used shall be
fully customisable to provide all technical calculation results to verify
the Contractor's proposals can be accurately verified.
3. Lighting calculations shall be carried out utilising proprietary lightingdesign software.
4. The Contractor shall submit the proposed Lighting calculationssoftware for approval by the Engineer prior to lighting design being
performed.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
15/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
13
.
2.2 Lighting General
2.2.1 Illumination level requirement
A. The lighting shall be established according to CIBSE code for interiorlighting. The general lighting of various spaces shall be planned to provide
the following illumination levels:
Space type
Type of lighting(possible lamp
sources)(see note 1)
Avg.Illumination
level (lx)
33kV & 11kV Switch Gear Room LFL 200
Ablution Room LFL/CFL 200
Access from Car Parking LFL/MH 200
Airport Operation Control Centre LFL 500
Animal Holding Room LFL/CFL 250
Animal Quarantine Laboratory LFL 500
Arrival Hall LFL/CFL/MHL 200
Assembly shops LFL/MHL 300
Baggage Handling LFL/CFL/MHL 350
Baggage reclaim carousel LFL/CFL/MHL 350
Balloon filling Room LFL 300
Bar LVL/CFL/Coldcathode/fibre Optic
50-200
Battery Room LFL 150Bridge House CFL/LFL 150
Bulk Store LFL 100
Bus Departure Gate / lounge MHL/LFL 200
Business Class Lounges CFL/MHL/LFL 200
Car Parking:
Parking Area
Ramp
Entrance / Exit
MHL / SON50
100
100
Cargo Area MHL / SON 200
Cargo Deck LFL/MHL 250
Cargo Dock LFL/MHL 250
CCR Room LFL 300
Changing Room LFL 150
Charger Room LFL 200
Check-In-Counters LFL / CFL 500
Check-in-hall CFL/MHL/LFL 350
Chloride Room (Chemical Room) LFL/MHL 150
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
16/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
14
.
Space type
Type of lighting(possible lamp
sources)(see note 1)
Avg.Illumination
level (lx)
CIP Area (Arrival) CFL/MHL/LFL 350
CIP Business Centre LVL/CFL/LFL 350
Cleaning Equipment Rooms LFL 150
Clinic
Consulting Area
Examination Room -General
Examination Room-Local
LFL/CFL300
300
1000
Cloak Rooms LFL/CFL 100-150
Cloth Dressing Room LFL/CFL 150
Cold store freezer Room LFL/MHL 100
Compressor Room (Fire fightingequipment)
LFL/MHL 150
Concourse CFL/MHL/LFL 350
Control Room LFL/CFL 300
Cool Room LFL 100
Corridor - General CFL/LFL 100
Corridor & Circulation Spaces CFL/MHL/LFL 250
Courier Mail Holding Store Room LFL/MHL 150
Customs and Immigration Hall & Desks LFL/CFL 500
Customs Area LFL/CFL 500
Dangerous Good - Radioactive store LFL/MHL 150
Dangerous Goods - Chemical Stores LFL/MHL 100
Departure / Arrival Concourses
MHL / CFL
350
(Care shouldbe takenwith thevertical
illuminationof
Informationboards)
Departure Corridor CFL/MHL 200
Departure Lounge MHL / CFL 350
Dinning Room - Staff LFL/CFL 300 200
Dry Store LFL 100
Duty free shop LVL/ CFL/ LFL 500
Early baggage / store LFL 200
Electrical Equipment Maintenance LFL/MHL 300
Electrical Room LFL 200
Electrical rooms, plant rooms LFL 200
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
17/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
15
.
Space type
Type of lighting(possible lamp
sources)(see note 1)
Avg.Illumination
level (lx)
Electronic Equipment Maintenance LFL/MHL 300-500
Emergency & Exit LightsIn accordance with
Employer'sRequirements
As specifiedin sectionregarding
emergencylighting
Emergency Equipment Store LFL/MHL 100
Emigration Counters
LFL / CFL
500horizontal
200 verticalat
immigrants'faces
Engine Hall/ Generator room LFL/MHL 150
Engineering Workshop LFL/MHL 500
Entrance Lobby, Corridor LFL/CFL 200
Entry to Boarding Lounges / Boarding Passcheck points
CFL/LFL 200
Equipment Room LFL 150
Executive facilities CFL/LFL 150
Fine soldering, fine spot welding etc. LFL/MHL 750
Fire Chief Room LFL/CFL 500
Fixed passenger boarding bridges CFL/LFL 200
Foam Tank MHL 150
Fork lift charger room LFL/MHL 200
Fuel tank room LFL/MHL 150
GAS Cylinder Room LFL/MHL 150
Gate lounges LFL/CFL/MHL 200
General Cargo Processing Hall LFL/MHL 100
Goods Scanning Area LFL/MHL 500
Goods Screening Areas CFL/LFL 500
GSM Operator Room LFL/CFL 500
Guard Room LFL 300
Gymnasium LFL/MHL 400
Health Spa CFL/LFL 150
Hotel Lobby & Reception LVL/CFL 300
Hotel Office LVL/CFL/LFL 500
Hotel Restaurant Area LVL/CFL 200
Hotel Service area CFL/LFL 200
Human remains store LFL/CFL 250
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
18/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
16
.
Space type
Type of lighting(possible lamp
sources)(see note 1)
Avg.Illumination
level (lx)
HVAC Plant Room LFL / MHL 150
Inert Gas Room LFL/MHL 200
Information & Inquiry lobby LFL 300
Inspection and shop testing LFL/MHL 500-1000
IT Rooms LFL/CFL 500
IT Store LFL 300
IT Work shop LFL/CFL 300
Kitchen LFL 300
Laboratories LFL/MHL 500
Laundry LFL/CFL 300
Lecture Theatres LVL/LFL/CFL 300-500
Libraries
LFL/CFL
300(Reading
Area)
150 (RackArea)
Loading Areas MHL 150
Loading Dock MHL/LFL 150
Lobby LVL/CFL 300
Locker Room LFL/CFL 150
Low Voltage Room LFL 200
Main Switch Board Room LFL 200
Mechanical Room LFL/MHL 150
Meet & Greet Room CFL/MHL 200
Meeting Room LFL/CFL 500
Mixer Room (Pump House) LFL/MHL/SON 150
Museums & Art gallery LFL/CFL/LFL 300
Offices LFL 500
Packing Despatch LFL/MHL 300
Paint shop LFL/MHL 300-1000
Pantry LFL 300
Perishable Cargo Processing Hall LFL/MHL 100
Personnel processing area LFL/CFL 500
Piers MHL / CFL 350
Plant Isolation room LFL/CFL 250
Plant quarantine Room LFL/CFL 250
Porch MHL/LFL 200
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
19/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
17
.
Space type
Type of lighting(possible lamp
sources)(see note 1)
Avg.Illumination
level (lx)
Porter's Rest Room LFL/CFL 150
Prayer Room LFL/CFL 200
Printing Room LFL/MHL 500
Public circulation area LFL/CFL/MHL 200
Queuing Area LFL / CFL / MHL 200
Reception LVL/CFL 500
Recreation Room LFL/CFL 300
Refuse Store MHL/SON 100
Rentable shops. (Concessionaries shop) LVL/LFL 500
Rest Room LFL/CFL 150
Restaurant, Food Court LVL/ CFL/ LFL 200-300
Retail Concourse MHL / CFL 500
ROP Body checking Room LFL/CFL 500
ROP Control Room LFL 300
ROP facilities LFL/CFL 150
ROP IT Room LFL 500
ROP lounge LFL/CFL/MHL 200
Security Check Area MHL / CFL / LFL 500
Security Equipment Room LFL 150
Seminar Rooms LFL/CFL/LVL 500
Server room, PABX room and UPS rooms LFL 300
Service areas LFL 200
Service Corridor LFL/CFL 100
Service Counter Room LFL/CFL 500
Sewage pumping station LFL 150
Sheet metal work LFL/MHL 500-750
Simulator Room LFL 300
Sniffer Dog Room (Kennels/pen only) LFL/CFL 250
Special delivery store room LFL/MHL 150
Sprinkler room LFL/MHL 150
Staff Rest Room LFL/CFL 150
Staircases - escape only LFL/CFL 100
Staircases, Escalators, Travelators, Lifts CFL 250
Stores LFL 100 / 150
Strong Room (Valuable Goods store) LFL/MHL 150
Structural Steel Fabrication LFL/MHL 300-500
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
20/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
18
.
Space type
Type of lighting(possible lamp
sources)(see note 1)
Avg.Illumination
level (lx)
Switch Gear Room LFL 200
Technical Room LFL 150
Ticket counters, check-in desks,information desks
LFL/CFL/LVL 500
Toilet Corridor LFL/CFL 100
Toilets LFL / CFL/LVL 150
Tool Rooms LFL 500
Training room LFL/CFL 500
Transformer Rooms LFL 150
Unclaimed Goods Store Room LFL/MHL 100
Unpacking, Sorting LFL/MHL 200
Vehicle processing area LFL/MHL 200
Viewing gallery area LFF/CFL 200
VIP Area (Arrival) CFL/MHL/LFL 350
VIP Bedroom suite LVL/LFL 100
Waiting Hall MHL/LFL/CFL 350
Washing bay for trucks MHL/SON 300
Waste processing area MHL/SON 300
Watch Room LFL/CFL 0-500
Welding LFL/MHL 300Worker facility LFL/CFL 150
Note 1:LFL: Linear Fluorescent lamps
CFL: Compact fluorescent lamps
MHL: Metal Halide vapour lamps
SON: High Pressure Sodium Vapour Lamps
LVL: Low voltage tungsten-halogen lamps
2.3 Emergency Lighting
2.3.1 General
A. Emergency lighting shall fulfil the following functions:
1. Illumination of the escape routes and immediate external areas atdischarge points shall be as according to the Fire Safety Strategy
Report and shown on applicable drawings.
2. Indicate the escape route direction clearly as required.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
21/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
19
.
3. Provide the exit signs on all the exits.
4. Ensure fire alarm call points, fire fighting equipment and other life
saving equipments on the premises are illuminated as required.
5. Interface and intercommunication with SCADA/BMS system.
B. The system shall have the approval of the Local Civil Defence Authority.
C. Equipment shall be certified EMC compliant.
D. Emergency lighting installation shall be complete with emergencybatteries, chargers, Luminaires and wiring, all as described in
Specification.
E. Non-maintained Luminaires as indicated on the relevant drawings shall besupplied directly from the battery system. Maintained exit Luminaires shall
be supplied from a separate supply via an independent transformer and
shall only operate from batteries during periods of electrical mains failure.
F. The operation of the emergency lighting system shall be such that on theloss of any individual feeder the system shall switch to either a central
battery supply system or individual battery packs, which shall provide
power for 3 hours to illuminate emergency Luminaires throughout the
building. On restoration of the mains supply the batteries shall be charged
by an integral charger such that the system supplies not less than 85 % of
its rated voltage after a period of 12 hours.
G. Suitable Luminaires selected from the general lighting scheme shall bepowered from the inverters and wired independently of other systems,
using fire-resistant cabling.
H. Central controlled system with central battery system shall be used exceptwhere specified elsewhere. The centralized system shall fulfil the
requirements in accordance with BS EN 50171 and shall as a minimum
perform to the following requirements:
1. Individual light monitoring.
2. Light output - 100 %.
3. Automatic function test.
4. Automatic duration test.
5. Data access/control at central location.
6. Interface to Airport SCADA.
7. 10 years battery life time by 20 C.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
22/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
20
.
8. 2 years electronic log book facility.
9. Maintenance free sealed lead acid batteries.
10. The design shall allow 20 % spare capacity for future expansion. Inaddition, a derating factor of 0.8 shall be applied to negate the effect
of battery ageing so that batteries will supply the load for the full
discharge duration throughout their useful life.
11. Batteries to be sized with a minimum of 20 % spare battery capacity.
12. AC/AC static inverters, which convert DC power from a built-instandby battery to 240V AC 50Hz single-phase power shall be
provided.
13. Luminaires designated for emergency operation, shall operate to theprinciples shown on drawings.
14. The proposed emergency lighting levels shall be in accordance withBS EN 1838, local Regulations, NFPA 101 and the Fire Safety
Strategy Report. The lighting level shall be archived at any time
during the system life including de-rating due to dirt, components
ageing and the reduction in battery voltage as the battery discharges,
however the below table shall be followed as a minimum:
Area Required Lux level Comment
Escape route 1 Lux - along centre line andwith 50 % for at least half thewidth
By Mandatory exit 10.8 Lux
By exit doors 10.8 lx
Stairs 10.8 lx
By change ofdirection
10.8 lx
Fire fighting, safeequipment, first aidpost and fire callpoints
10.8 lx
By change of level 10.8 lx
Intersections ofcorridors
10.8 lx
Outside near final exit 10.8 lx
Open area anti-panicopen area lighting
0.5 Lux - minimum measuredacross whole area
High-risk task arealighting
15 Lux or 10 % of normallighting level (whichever isthe greater value) -uniformity better than 1:10
The ratio of maximumto minimum illuminationshall not be greaterthan 40:1 along thecentre line of theescape route.
The ratio of maximumto minimum illuminationshall not be greaterthan 40:1 in Anti-panicopen areas
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
23/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
21
.
Area Required Lux level Comment
Toilets with no naturallight
Emergency lighting requiredabove exit door - no specificlevel stated
I. The reflection factor for all surfaces shall be set to 0 % when calculatingemergency light levels.
2.3.2 Switchboards for emergency lighting
A. The design, material, construction and performance of switchboards foremergency lighting shall comply with the latest international standards.
B. Switchboards shall be shipped to and stored securely taking into accountconditions found at site. When the switchboard final location is ready to
receive the said switchboard, they shall be installed into position. Once inposition the switchboards shall be finally assembled, including all
components and connections being torque tested in accordance with the
manufacturer's recommendations to ensure there are no loose connections.
C. All indoor switchboards shall be IP 43 ingress protection according to BSEN 60529.
D. Switchboards shall be designed for the following ambient conditions:
1. Outdoor maximum ambient temperature 50 C.
2. Indoor maximum ambient temperature 41 C.
E. Access to the switchboard interior and the protective devices shall be bymeans of a hinged door fixed shut by means of a moulded lever type latch
which shall be able to be locked with the means of a proprietary locking
system.
F. With the door in the open position, it shall not be possible to touch or gainaccess to live parts without the use of a tool. The hinged door shall be
easily removable when in the open position to aid installation and
maintenance.
G. All fixing accessories shall have anti-corrosion finish. All ferrous materialsshall either be corrosion inhibited and painted or hot-dip galvanised to BSEN ISO 1461. Non-ferrous metallic components shall be electroplated to
protect against corrosion.
H. All low voltage exposed terminals of switchboards that may be exposed totouch (with a door open or cover removed) shall be shrouded to IP 20 to
BS EN 60529. Note this requirement does not include terminals within
separate enclosure outgoing cable boxes. These shrouds shall be fitted with
warning labels. Information labels shall also be fixed adjacent to the
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
24/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
22
.
shrouds (on a fixed part of the cubicle) to show where the terminations
connect to e.g. bus bars, cables, etc.
I. The earth bar shall be sized in accordance with BS EN 60439-1 Annex B.
J. Minimum of 20 % spare outgoing space shall be installed in switchboardsfor emergency lighting.
K. The Contractor shall submit to the Engineer for approval, features,characteristics, and ratings of circuit breakers and each switchboard
component specified.
L. The Contractor shall submit to the Engineer for approval, time currentcharacteristic curves for overcurrent protective devices, including circuit
breaker trip devices and fusible devices.
M. The Contractor shall submit to the Engineer for approval, operating andmaintenance data for components.
N. Calibration certificates shall be submitted for all instruments.
O. Operation and maintenance manual shall be submitted as per BS EN60439-1:1999 clause 5.3 and as per Employer's Requirements.
2.3.3 Central battery system - mains power supply
A. Central battery stations shall have dual power supplies, each power source
shall be from a different transformer substation, via an automatic transferswitch (ATS). The ATS shall be monitored to provide secondary mains
supply to the central battery station charger unit, should the primary supply
perform below permitted requirements or fail.
B. Each "Change-over' module (ATS) shall have its own short-circuitprotection.
C. All outgoing distribution cables from the central battery unit shall be of afire resistant type.
D. The above mentioned requirement is for central battery systems supplying
public areas.
E. The control module shall be composed of a microprocessor control modulewith plain text 4- line LCD displays with a minimum of 20 characters per
line, to provide operative status and luminaire failures.
F. Display shall indicate:
1. Circuit earth leakage failure.2. Battery current drawn in emergency mode.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
25/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
23
.
3. Battery current drawn in test mode.4. Battery voltage.5. Battery test.
6. Battery charge failure.7. Luminaire failures, with text address location.8. Sub-circuit board supply failure with text address location.
G. Functions to include Earth leakage test on each circuit, display andprogramming status of each circuit, Monitor and control of all
weekly/daily cycle tests and functions, monitoring of battery at five minute
intervals, communication and programming with each addressable ballast
at the luminaires, automatic logging of all test results and incidents.
Manual test feature in addition to automatic.
H. Touch-pad keys shall be provided for programming and monitoring of thepanels.
I. Memory facility to be provided for two-year logbook:
1. LED's shall indicate:
a) Main operationb) Mains failurec) Battery operationd) Summation fault.
J. Potential free indicator contacts shall be provided for:
1. Operation.2. Battery operation.3. Summary fault.
2.3.4 Central battery units
A. Battery chargers:
1. Battery chargers shall be installed in purpose-made metallicenclosures with an index of protection IP 31 in accordance with BS
EN 60529 suitable for wall or floor mounting, depending on
dimensions.
2. Battery charger enclosures may house the system batteries providingthe design of the enclosure ensures safe operation with the batteries
specified. This arrangement should normally be restricted to smaller
systems e.g. for circuit breaker tripping supplies for power supply to
emergency lighting system, central battery units shall be wall or floor
mounted as required, conforming to BS 4533 Section 102.22, and be
of robust, high quality construction. Enclosures shall be metal, with
hinged lockable doors and with suitable ventilation provided.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
26/36
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
27/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
25
.
Employer's Requirements. The Contractor shall submit calculations to
justify the Ampere-Hour capacity of the batteries for approval to the
Engineer.
3. Battery system shall be provided with a suitably rated switchdisconnector.
4. Batteries shall be mounted on suitable tiered galvanized steel shelvingwith moulded plastic trays to contain any leakage from the battery
cells, and to allow safe easy access for maintenance.
5. Battery terminals shall be coated with the battery manufacturersapproved grease, and shrouded if not enclosed.
6. Date of manufacture shall be stamped on each battery.
7. Guaranteed life is not to be less than 10 years, with a capacity dropdown to not less than 80 percent under normal expected service.
2.3.5 Self contained emergency battery packs
A. Where a central emergency battery unit is not installed, individualemergency luminaries shall consist of individual power packs installed
within or remote to the luminaries.
B. Battery pack units shall consist of converter/inverter devices, with nickel-cadmium batteries to provide 3 hours operation under mains failure, unless
the main supply is restored prior to this.
C. Luminaries with self contained battery packs shall be connected to the liveside of the local lighting circuit and lamps shall operate automatically
under mains failure conditions.
D. Units shall have the capability of sustaining high temperature so that theycan be accommodated in fittings with high internal temperatures. However,
if the internal temperature of the fittings exceeds 50 C, the battery unit
shall be mounted remote to the luminaries. In the case of remote mounting,
a purpose made remote mounting box shall be provided.
E. Key operated switches shall be provided, at locations for all self containedemergency pack unit luminaries, to control the operation of the luminariesmanually for testing purposes and to the satisfaction of the Engineer. Test
key switches shall be clearly labelled Emergency Lighting.
2.3.6 Central Battery System, automatic self testing
A. The Central Battery System shall be complete with automatic self testing,which shall comprise the following tests as a minimum requirement:
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
28/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
26
.
1. 10 minute monthly tests
2. 180 minute annual test
B. The system shall be fully automated microprocessor based systemproviding detailed testing of the emergency lighting installation from a
central position. Tests can be programmed at dates and times to suit the
user and application and require no human intervention.
C. The central battery system shall allow interrogation of the system as theyoccur and for retrospective analysis of the tests and shall be interfaced with
Airport SCADA
D. Where luminaires are utilised for emergency lighting and supplied via the
central battery system the contractor shall install switching relays whichutilise accurate electronic timers, the relay's shall test the un-switched
supply to the appropriate emergency lighting circuits enabling them to be
interrupted for a selectable test duration. These shall be key switch
operated and shall be utilised in non public areas only.
2.3.7 Self Contained Emergency converted luminaires
A. Where luminaires are the self contained type the contractor shall allow forself testing self contained emergency luminaires and these shall
automatically self test the emergency circuit and provide a fault indication
whenever a failure is identified, these tests shall be carried out on a
monthly and annual basis.
B. Functional tests of the self contained Emergency conversion pack shall nottake place unless the batteries have been fully charged for at least 24 hours
C. If the loss of supply is greater than 8 days, the self test module shallautomatically perform a commissioning test
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
29/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
27
.
3 Execution
3.1 General
A. The emergency lighting system shall operate to functional demands as
required by the Standards, Regulations and fire strategy.
B. Deliver storage and handling of Central battery unit equipment:
1. Deliver equipment fully enclosed only after manufacturer's specifiedenvironmental conditions have been permanently established in spaces
where equipment shall to be placed.
2. Store equipment in spaces with environments controlled withinmanufacturers ambient temperature and humidity tolerances for non-
operating equipment.
3. Ensure clearances around equipment in accordance to manufacturer'swritten instructions, but not less than 900 mm in front of unit.
4. Install system components on at least 100 mm high steel frame bases.Install systems according to manufacturer's printed instructions, and
arrange for manufacturer/supplier to inspect and certify the
installation.
3.2 Emergency Lighting
3.2.1 Wiring
A. Where the emergency lighting system installation is via a central batteryunit, the wiring to emergency luminaries shall be carried out in fire
resistant low smoke sheathed cables, unless specified otherwise.
B. Fire resistant cables for the emergency lighting system via the centralbattery unit shall have White coloured sheath.
C. Where the emergency lighting scheme is self-contained emergency packs,the wiring system shall be either as above, or in PVC insulated single core
wires in conduits.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
30/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
28
.
D. Generally, cables shall be 2.5 mm2cross-sectional area unless specifiedotherwise.
E. The Contractor shall pay careful attention to cable routings so as to keepcable runs to the shortest possible length and ensure the overall volt dropon any circuit is within the tolerances of the luminaries connected and
within the limits specified in the MEDCO regulations.
3.2.2 Installations of batteries
A. The manufacturers recommendation/instructions shall always be followed.
B. Insulated tools shall be used.
C. Personnel erecting battery banks shall remove metallic objects form their
person i.e. watches, rings etc.
D. Eye and hand protection shall be provided.
E. Batteries shall not be left on site for prolonged periods without beingtrickle charged to maintain their condition i.e. if delivery is some weeks
before commissioning of the charger.
F. Due care shall be observed when handling acidic substances.
3.2.3 Installation of Light Fittings
A. Lighting fixtures shall be installed as indicated in the manufactures writteninstructions.
3.2.4 Identification
A. Identify equipment and components according to Employer'sRequirements.
B. All emergency luminaries shall be labelled with 100 mm width yellowcolour labels containing black lettering clearly identifying the circuit
number and the Central battery unit.
3.2.5 Cleaning
A. On completion of installation, inspect unit components. Remove paintsplatters and other spots, dirt, and debris. Touch up scratches and abrasions
in finish to match original finish. Clean unit internally using methods and
materials recommended by manufacturer.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
31/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
29
.
4 Quality Control
A. Implement a quality assurance plan in accordance with the Employer'sRequirements together with testing and commissioning plans, including
but not limited to:
1. Factory Acceptance Test.2. Site and Systems Acceptance Test.3. Site Integration Tests.4. Training of staff.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
32/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
30
.
5 Testing and Commissioning
A. Perform all test and commissioning in accordance to the Employer'sRequirements, with special attention on, but not limited to:
1. Factory Acceptance Test.
2. Site and Systems Acceptance Test.3. Site Integration Test.4. Training of staff.
5.1 Factory Acceptance Test
A. The Contractor shall inform the Engineer of routine factory acceptancetests that shall be performed on any component of the General lighting
system prior to shipping from the manufactures factory.
B. The Contractor shall inform of any test date, time and location to theEngineer at least 4 weeks in advance to witness the test. The cost for
travel, boarding, incidental expenses etc shall be included for the
Employer's and the Engineers representatives (2 each).
C. The Contractor shall submit to the Engineer, prior to shipping, copies of allrelevant certification or approvals for the General lighting system and their
components.
D. Inspection and testing shall be carried out in accordance with BS 7671, theassociated IEE Guidance Notes, OES4, CIBSEcodes L and Mand the
requirements of this specification.
E. The Contractor shall furnish the Engineer with co-ordinated drawings "ForApproval" highlighting predicted Lux levels for all areas. The minimum
acceptable Lux levels shall be in accordance with the Employer's
Requirements measured one hour after Sun-Set.
F. Emergency lighting system: Emergency lighting systems shall be inspectedand tested in accordance with the inspection and test procedures detailed
within BS 5266.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
33/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
31
.
5.2 Site and Systems Acceptance Test
A. The pre testing and Commissioning of all equipment shall be carried outby the equipment Manufacturer and shall be witnessed by the Engineer,
prior to putting into service the equipment shall be demonstrated to theEngineer and Employer's representative, carrying out all necessary
functional tests.
B. Testing methods: The Engineer shall be notified of the method to be usedfor each type of test and notification shall be given in accordance with the
Employer's Requirements.
C. Inspection and testing shall be carried out in accordance with BS 7671, theassociated IEE Guidance Notes, OES4 and the requirements of this
specification, this include but not limited to:
1. Testing Agency: Arrange and pay for the services of an electricaltesting agency to perform inspection and tests on switchboard,
components, and accessories.
2. Test Procedure: Conform to the following:
a) Manufacturer's required field service tests: Supervision of unitinstallation, connections, and adjustments by a factory-authorised
service representative. All report results shall be issued in writing
b) Perform tests on completion of unit installation and after buildingcircuits have been energized. Provide instruments to permit
accurate observation of tests
c) Test unit functions, operations, and protective features. Adjust toensure operation complies with Specifications. Include the
following tests:
i Simulate Malfunctions: Verify protective device operation
ii Demonstrate low battery voltage shutdowns, and transfers of
supply due to normal source failure and restoration
iii Verify emergency supply duration
iv Operate each type of load served by the unit without
symptoms of abnormal supply such as noise, vibration, or
pulsation of the load or its output. All light fixtures, ceiling
roses, modules, wires, etc shall be identified
v Manually equalise charging of battery cells according to
manufacturer's written instructions. Record individual cell
voltages.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
34/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
32
.
3. Ensure that required lux levels for all rooms and locations have beenachieved at completion of all finishes, record tests and submit to the
Engineer for verification.
D. Ensure sufficient task lighting is available during all stages of site testing.
E. Visual and Mechanical Inspections. Perform as a minimum the following:
1. Compare nameplates of equipment and detailed components withsingle line diagram and specified requirements, and report
discrepancies.
2. Check for proper anchorage, required clearances, physical damage,and proper alignment of switchboards and components.
3. Inspect all doors, panels, and sections for paint, dents, scratches, fitand missing hardware.
4. Verify that fuse and circuit breaker sizes, types, and ratings conformto requirements. Include control power and potential, control power
transformer fuses, and fuses for fused circuit breakers.
5. Inspect bus connections for high resistance. Use low resistanceohmmeter or check tightness of bolted bus joints by using a calibrated
torque wrench. Refer to manufacturers instructions for proper torque
values.
6. Test electrical and mechanical interlock systems for proper operationand sequencing. Make closure attempts on locked open devices. Make
opening attempts on locked closed devices. Attempt key exchanges
with devices in exchange preventing positions.
7. Clean Central battery unit's interior and exterior using manufacturersapproved methods and materials.
8. Inspect mechanical indicating devices for proper operation.
F. Retest: Correct deficiencies identified by tests and observations andcompletely retest switchgear. Verify by the system tests that the total
assembly meets specified requirements.
G. Upon completion of installation, inspect interior and exterior ofswitchboards. Remove paint splatters and other spots, dirt, and debris.
Touch up surface scratches and marks to match original finish.
5.3 Site Integration Test
A. The Contractor shall undertake system-wide integrated testing inaccordance with the General Requirements.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
35/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC
33
.
5.4 Training of Staff
A. The Contractor shall implement a comprehensive system-wide trainingprogramme for selected/appointed Employer's personnel for all aspects of
General Lighting Systems.
B. The Contractor shall provide for all aspects and requirements for trainingsessions. A written outline and agenda of the training material and full
contents shall be submitted for Employer's approval.
C. The training shall include, but not limited to:
1. Classroom based written and visual media instruction and site basedoperation of the said plant.
2. Cover all operating features of the plant and interconnected system.
D. Training shall be performed by experienced and competent trainingpersonnel, familiar with the system and training techniques. The
Contractor shall submit for approval the CV/Resume of all training
personnel.
E. Training and all training materials shall be offered in bilingual languages;Arabic and English.
F. Training literature shall be presented in bound printed documents, allgraphs, pictures and diagrams shall be in colour. Each participant attending
training sessions shall have literature presented according to training
presentation (see item 5.4.K).
G. The number of training sessions and number of Employer'sattendees/participants shall be as indicated in the Electrical Particular
Specifications. Document No. SA-000-E-11600 Particular Electrical
Specification.
H. The Contractor shall provide a suitable classroom environment; based for aclass size of 20 people at any one training session.
I. Plant and equipment utilised in the classroom environment shall be thesame; manufacture, model and type as installed at site.
J. Training sessions shall be scheduled at the convenience of the Employer.
K. Training presentation sessions shall be scheduled for, but not limited to:
1. Operations Management.2. Operations personnel.3. Technical Supervisors.4. Technicians.
-
8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf
36/36
Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification
34
6 Revision Log
Date Issue Description
31.10.2008 T01 Issued for Tender