sa-000-e-11608_general lighting systems_rev t01.pdf

Upload: prao

Post on 02-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    1/36

    Sultanate of OmanMinistry of Transport and CommunicationsDevelopment of Salalah International Airport

    Main Contract 5Project Specification

    Building, Electrical

    General Lighting Systems

    General Specification

    October 2008

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    2/36

    Sultanate of OmanMinistry of Transport and CommunicationsDevelopment of Salalah International Airport

    Main Contract 5

    Project Specification

    Building, Electrical

    General Lighting Systems

    General Specification

    October 2008

    Report no. SA-000-E-11608

    Issue no. T01

    Date of issue 31.10.2008

    Prepared ALJS/PVN/HO

    Checked TJJ

    Approved HO/THMJ

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    3/36

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    4/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    2

    .

    1 General

    1.1 Introduction

    A. This part specifies the general requirements for the General Lighting. It

    shall be read in conjunction with other parts of the ContractDocumentation.

    B. The work shall include the interim, detailed and final design, manufacture,supply, installation, supervision of own work and test & commissioning of

    the General Lighting including all necessary accessories and coordination

    work as shown on the drawings and specified in relevant specifications and

    as herein specified, and to the satisfaction of the Engineer.

    C. The General Lighting consists of the following, but is not limited to:

    1. Illumination level requirement.2. Emergency lighting.3. Switchboards for emergency lighting.4. Central battery system - mains power supply.5. Self contained emergency battery packs.

    D. The Contractor shall coordinate with all relevant specialist sub-contractorsto ensure that the location of Luminaires shall not interfere with the

    operation and functionality of any other equipment such as, but not

    restricted to, Moving/Intelligent displays and/or illuminated signage of any

    type with particular reference to Reflection and Glare.

    E. The Contractor shall ensure that the general distribution of light shall beuniform avoiding "Hot-Spots" creating a general relaxed atmosphere.

    F. The design shall incorporate necessary allowances for the effect ofcondensation and any subsequential damage to equipment, finishes and

    structure. Claims arising from the effects of either humidity and/or

    condensation will not be entertained.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    5/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    3

    .

    1.2 Related Documents

    A. Employer's Requirements and general provisions of Contract, includingGeneral, Supplementary and Special Conditions of the Contract

    Documents.

    B. Related General Specification Section:

    1. SA-000-E-11603 Low Voltage Protection and Control Devices.

    2. SA-000-E-11604 Low Voltage Cabling.

    3. SA-000-E-11605 Distribution Ways.

    4. SA-000-E-11609 Luminaires and Lamps.

    5. SA-000-E-11611 Earthing and Bonding.

    6. SA-000-E-11612 Electrical Accessories.

    7. SA-000-E-11615 Electromagnetic Compatibility.

    8. SA-000-E-11616 Identification of Components, Cables and

    Equipment.

    9. SA-000-E-11623 Equipment for Controlling of Lighting.

    C. Related Specifications and drawings including, but not limited to:

    1. Architectural Services.2. Structural and Civil works.3. Civil Works.4. Airport SCADA/BMS.5. PMS (Power Management System).6. Airport Fire Protection and Safety systems.7. Mechanical Services.8. IT Systems.9. Lift Installations.10. PA Installations.11. Baggage Handling.12. Travelators and Escalators.

    D. Related Particular Specifications:

    1. SA-000-E-11600 Electrical Installation.

    1.3 Codes and Standards

    A. The design, workmanship, materials and equipment associated with thissection shall comply with the latest issue, including all amendments, of the

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    6/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    4

    .

    appropriate Omani, British and European Standard Specifications.

    Particularly relevant Standard Specifications are as follows:

    Number Title

    OES4 Regulations for Electrical Installations

    CIBSE Commissioning Code L. Lighting

    CIBSE LG7 Office lighting

    ICEL Standards Industry Committee for Emergency Lighting Standards

    BS 67 Specification for ceiling roses

    BS 764 Specification for automatic change-over contactors for emergency

    lighting systems

    BS EN 1838:1999

    BS 5266

    Emergency Lighting

    BS 5225 Method of photometric measurement of battery operated

    emergency lighting Luminaires

    BS 5266-1 Emergency lighting: Part 1 - Code of practice of premises other

    than cinemas and certain other specified used for entertainment

    BS 5266-2 Emergency lighting. Code of practice for electrical low mounted

    way guidance systems for emergency use

    BS 5266-3 Emergency lighting. Specification for small power relays

    (electromagnetic) for emergency lighting applications up to and

    including 32 A

    BS 5266-4 Emergency lighting. Code of practice for design, installation,

    maintenance and use of optical fibre systems

    BS 5266-5 Emergency lighting. Specification for component parts of optical

    fibre systems

    BS 5266-6 Emergency lighting. Code of practice for non-electrical low

    mounted way guidance systems for emergency use.

    Photoluminescent systems

    BS 5499-4 Safety signs, including fire safety signs. Code of practice for

    escape route signing

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    7/36

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    8/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    6

    .

    Detailed and Final Design

    C. Submit Detailed and Final Design in accordance with the Employer'sRequirements divided into a Detailed and Final Design stages including,

    but not limited to:

    1. Design, Construction, Installation, shop and fabrication drawingsincluding, but not limited to:

    a) Detailed drawings including coordination drawings, floor plansand sections drawn to accurate 1:50 scale. Show all luminaries

    locations including emergency lighting and relationships between

    luminaries, switchboards, censors and switches

    b) One line diagrams for emergency lighting and relationshipbetween the normal lighting and the emergency lighting

    c) Strategy for switching on/off emergency lighting in various zones

    d) Detailed drawings for each switchboard for the emergencylighting include dimensioned elevations with layouts of

    component parts

    e) Cable termination facilities and internal wiring arrangements

    f) Show minimum clearances, installed devices, major features

    g) Nameplate legend

    h) Size and number of conductors in each trunking and conduit,including phase, neutral, and earth conductors of main and branch

    buses

    i) Short time and short circuit ratings of switchboard assembly

    j) Single line diagram: Updated version of single line diagramreflecting Switchboards for emergency lighting

    k) Material lists.

    2. Detailed Design drawings for wiring and circuit diagrams with wireterminal numbering: Single line, elementary, and schematic diagramsof equipment to be supplied, differentiating between manufacturers

    installed and field installed wiring.

    3. Lighting calculations for all individual rooms.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    9/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    7

    .

    1.4.2 Product data

    A. Submit the following according to the Employer's Requirements, but notlimited to:

    1. Complete and detailed information of all materials and equipment tobe incorporated in the work.

    2. Detailed description and specifications, catalogues cuts, installationdata, diagrams, dimensions, controls and any other data required to

    demonstrate compliance with the Employer's Requirements. Each item

    submitted shall be referenced to the applicable paragraph in the

    Specification.

    3. A point by point statement of compliance. The statement ofcompliance shall consist of a list of numbered paragraphs. Each

    specification paragraph shall be cross referenced to the page/drawingin the submittal on which the compliance is confirmed; the confirming

    data on the page/drawing shall be highlighted for ready identification.

    Where the proposed system complies fully, indicate by placing the

    word "comply" opposite the paragraph number. Where the proposed

    system does not comply, or accomplishes the stated function in a

    manner different from that described, provide a full description of the

    deviation. Where the full description of a deviation is not provided, it

    shall be assumed that the proposed system does not comply with the

    paragraph in question. Any submission that does not include a point

    by point statement of compliance as specified shall be disqualified.

    4. Copy of relevant test certificates from the manufacturer ensuring thatthe lighting system complies with the Specifications.

    1.4.3 Samples

    A. Submit products samples to establish the suitability of the product andutilised for future product reference. Samples shall not be returned to the

    Contractor.

    B. Submit the following according to the Employer's Requirements:

    1. Central battery samples including, but not limited to:

    a) Valve Regulated Lead Acid (VRLA) type maintenance free typeb) Enclosure body, epoxy powder coated with access doors

    2. Cable entry; top, bottom3. Wiring.4. Cable identification tags.5. Labelling in English and Arabic.6. Interfaces with Airport SCADA.7. Earthing and bonding arrangements.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    10/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    8

    .

    C. Submit the following details along with each product item, but not limitedto:

    1. Manufacture (Make).2. Type.3. Product/component reference code.4. Technical characteristics.5. Country of origin.6. Test certificates.

    1.4.4 Operation and Maintenance Manuals

    A. Submit the following according to the Employer's Requirements:

    1. List of material installed on site including material reference number

    given by the material manufacturer.

    2. Data sheets for all material installed on site.

    3. Relevant telephone and fax numbers for manufactures including pointof contacts, address and references to homepages.

    4. Maintenance data for all kinds of equipment installed includingmaintenance plan.

    5. Inspection and test plans.

    6. All test certifications from manufacturers.

    7. List of spare parts required for a maintenance period for 5 years.

    8. Instruction manuals.

    9. Operator manuals.

    10. Maintenance manuals.

    1.4.5 As-built drawings

    A. Submit the following according to the Employer's Requirements:

    1. Up-dated construction issue drawings modified to accurately reflectthe installations as installed on site.

    1.4.6 Spare parts

    A. Provide spare parts for 2 years for operation of the plant, but as a minimumthe following:

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    11/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    9

    .

    No. Description Quantity

    Tools

    1 Fuse puller (set) One with each Central Battery System

    2 Panel standard keys One with each Central Battery System

    3 Diagnostic tool with software and

    hardware

    One with each type of Central Battery

    System

    4 Central Battery System maintenance

    toolkit

    One set with each lot of supply

    Components

    1 Transformer By-pass 1 of each type

    2 Capacitors (DC & AC) 1 of each type

    3 Rectifier Module 1 of each type

    4 Relay solid state 5 %

    5 IGBT Module on inverter side 1 of each type

    6 IGBT Module on converter Side 1 of each type

    7 Power side fuses 5 % of each size and type used

    8 Control fuses 5 % of each size and type used

    9 Switch 32 A, 4 position rotary switch 5 %

    10 Control transformer 1 of each type

    11 Converter side transformer 1 of each type

    12 DC side choke 1 of each type

    13 Inverter choke 1 of each type

    14 Display board 5 %

    15 LED Front panel display 5 %

    16 Auxiliary PSU 5 %

    17 Single phase Axial fan 5 %

    1.4.7 Warranties and Guarantees

    A. The Contractor shall provide all Warranty and Guarantee Certificates inaccordance with the Employer's Requirements.

    B. Defects Liability Period:

    1. The Contractor shall include for all maintenance procedures inaccordance with the manufacturers requirements during the defects

    liability period and shall prepare a comprehensive schedule of

    maintenance procedures that shall be carried out.

    2. The Contractor shall provide an exhaustive quantified schedule ofmaintenance spares for this period, and these spares shall be in

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    12/36

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    13/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    11

    .

    2 Product Specification and FunctionalDescription

    2.1 General

    A. The detailed lighting design shall be based on the following luminaire andlamp maintenance properties and illumination requirements:

    1. Lamp lumen maintenance factor: 0.8.2. Luminaire maintenance factor: 0.8.3. Room surface maintenance factor: 0.8.

    B. Room surface reflection factors shall be as specified below in accordanceto CIBSE Code for interior lighting 2006, unless any special materials or

    colours are utilised:

    Surface Light Medium Dark

    Ceiling 70 % 50 % 30 %

    Walls 50 % 30 % 10 %

    Floor 30 % 20 % 10 %

    C. The Average maintained illumination level of various rooms/areas shall becalculated and the uniformity (Ratio of minimum illumination to average

    illumination) in any room shall be as follows:

    Area Uniformity illumination

    (min/average)

    Indoor >0.6

    External

    Yard Area

    Street Lighting

    Car Parking

    >0.4

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    14/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    12

    .

    D. The Contractor shall utilise an Industry Standard Windows Based

    Electrical Calculations software for calculating the Lighting and

    Emergency Lighting Levels according to the relevant standards detailed

    within this Specification. The Contractor shall determine the reflectancevalues, based on the finishes schedule detailed within the Employer's

    Requirements.

    1. The following calculated data shall be submitted as a minimum forboth Lighting and Emergency Lighting Calculations:

    a) Average Lighting levels on the working Plane, Floor, all walls,ceiling

    b) The % reflectance's

    c) Compliance with LG7

    d) Uniformity and Ratio's of Illuminance

    e) Total installed Watts

    f) 3d Visualisation

    g) Isometric diagram

    h) Glare

    i) Photometric Data

    j) Polar Intensity Curves

    k) Illuminance Cone Diagrams

    l) Cartesian and Isolux Diagrams

    m) Confirmation of all Emergency lighting calculations inaccordance with relevant standards.

    2. Based on the initial results issued by the Contractor to the Engineer,additional information may be required; the software used shall be

    fully customisable to provide all technical calculation results to verify

    the Contractor's proposals can be accurately verified.

    3. Lighting calculations shall be carried out utilising proprietary lightingdesign software.

    4. The Contractor shall submit the proposed Lighting calculationssoftware for approval by the Engineer prior to lighting design being

    performed.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    15/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    13

    .

    2.2 Lighting General

    2.2.1 Illumination level requirement

    A. The lighting shall be established according to CIBSE code for interiorlighting. The general lighting of various spaces shall be planned to provide

    the following illumination levels:

    Space type

    Type of lighting(possible lamp

    sources)(see note 1)

    Avg.Illumination

    level (lx)

    33kV & 11kV Switch Gear Room LFL 200

    Ablution Room LFL/CFL 200

    Access from Car Parking LFL/MH 200

    Airport Operation Control Centre LFL 500

    Animal Holding Room LFL/CFL 250

    Animal Quarantine Laboratory LFL 500

    Arrival Hall LFL/CFL/MHL 200

    Assembly shops LFL/MHL 300

    Baggage Handling LFL/CFL/MHL 350

    Baggage reclaim carousel LFL/CFL/MHL 350

    Balloon filling Room LFL 300

    Bar LVL/CFL/Coldcathode/fibre Optic

    50-200

    Battery Room LFL 150Bridge House CFL/LFL 150

    Bulk Store LFL 100

    Bus Departure Gate / lounge MHL/LFL 200

    Business Class Lounges CFL/MHL/LFL 200

    Car Parking:

    Parking Area

    Ramp

    Entrance / Exit

    MHL / SON50

    100

    100

    Cargo Area MHL / SON 200

    Cargo Deck LFL/MHL 250

    Cargo Dock LFL/MHL 250

    CCR Room LFL 300

    Changing Room LFL 150

    Charger Room LFL 200

    Check-In-Counters LFL / CFL 500

    Check-in-hall CFL/MHL/LFL 350

    Chloride Room (Chemical Room) LFL/MHL 150

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    16/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    14

    .

    Space type

    Type of lighting(possible lamp

    sources)(see note 1)

    Avg.Illumination

    level (lx)

    CIP Area (Arrival) CFL/MHL/LFL 350

    CIP Business Centre LVL/CFL/LFL 350

    Cleaning Equipment Rooms LFL 150

    Clinic

    Consulting Area

    Examination Room -General

    Examination Room-Local

    LFL/CFL300

    300

    1000

    Cloak Rooms LFL/CFL 100-150

    Cloth Dressing Room LFL/CFL 150

    Cold store freezer Room LFL/MHL 100

    Compressor Room (Fire fightingequipment)

    LFL/MHL 150

    Concourse CFL/MHL/LFL 350

    Control Room LFL/CFL 300

    Cool Room LFL 100

    Corridor - General CFL/LFL 100

    Corridor & Circulation Spaces CFL/MHL/LFL 250

    Courier Mail Holding Store Room LFL/MHL 150

    Customs and Immigration Hall & Desks LFL/CFL 500

    Customs Area LFL/CFL 500

    Dangerous Good - Radioactive store LFL/MHL 150

    Dangerous Goods - Chemical Stores LFL/MHL 100

    Departure / Arrival Concourses

    MHL / CFL

    350

    (Care shouldbe takenwith thevertical

    illuminationof

    Informationboards)

    Departure Corridor CFL/MHL 200

    Departure Lounge MHL / CFL 350

    Dinning Room - Staff LFL/CFL 300 200

    Dry Store LFL 100

    Duty free shop LVL/ CFL/ LFL 500

    Early baggage / store LFL 200

    Electrical Equipment Maintenance LFL/MHL 300

    Electrical Room LFL 200

    Electrical rooms, plant rooms LFL 200

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    17/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    15

    .

    Space type

    Type of lighting(possible lamp

    sources)(see note 1)

    Avg.Illumination

    level (lx)

    Electronic Equipment Maintenance LFL/MHL 300-500

    Emergency & Exit LightsIn accordance with

    Employer'sRequirements

    As specifiedin sectionregarding

    emergencylighting

    Emergency Equipment Store LFL/MHL 100

    Emigration Counters

    LFL / CFL

    500horizontal

    200 verticalat

    immigrants'faces

    Engine Hall/ Generator room LFL/MHL 150

    Engineering Workshop LFL/MHL 500

    Entrance Lobby, Corridor LFL/CFL 200

    Entry to Boarding Lounges / Boarding Passcheck points

    CFL/LFL 200

    Equipment Room LFL 150

    Executive facilities CFL/LFL 150

    Fine soldering, fine spot welding etc. LFL/MHL 750

    Fire Chief Room LFL/CFL 500

    Fixed passenger boarding bridges CFL/LFL 200

    Foam Tank MHL 150

    Fork lift charger room LFL/MHL 200

    Fuel tank room LFL/MHL 150

    GAS Cylinder Room LFL/MHL 150

    Gate lounges LFL/CFL/MHL 200

    General Cargo Processing Hall LFL/MHL 100

    Goods Scanning Area LFL/MHL 500

    Goods Screening Areas CFL/LFL 500

    GSM Operator Room LFL/CFL 500

    Guard Room LFL 300

    Gymnasium LFL/MHL 400

    Health Spa CFL/LFL 150

    Hotel Lobby & Reception LVL/CFL 300

    Hotel Office LVL/CFL/LFL 500

    Hotel Restaurant Area LVL/CFL 200

    Hotel Service area CFL/LFL 200

    Human remains store LFL/CFL 250

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    18/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    16

    .

    Space type

    Type of lighting(possible lamp

    sources)(see note 1)

    Avg.Illumination

    level (lx)

    HVAC Plant Room LFL / MHL 150

    Inert Gas Room LFL/MHL 200

    Information & Inquiry lobby LFL 300

    Inspection and shop testing LFL/MHL 500-1000

    IT Rooms LFL/CFL 500

    IT Store LFL 300

    IT Work shop LFL/CFL 300

    Kitchen LFL 300

    Laboratories LFL/MHL 500

    Laundry LFL/CFL 300

    Lecture Theatres LVL/LFL/CFL 300-500

    Libraries

    LFL/CFL

    300(Reading

    Area)

    150 (RackArea)

    Loading Areas MHL 150

    Loading Dock MHL/LFL 150

    Lobby LVL/CFL 300

    Locker Room LFL/CFL 150

    Low Voltage Room LFL 200

    Main Switch Board Room LFL 200

    Mechanical Room LFL/MHL 150

    Meet & Greet Room CFL/MHL 200

    Meeting Room LFL/CFL 500

    Mixer Room (Pump House) LFL/MHL/SON 150

    Museums & Art gallery LFL/CFL/LFL 300

    Offices LFL 500

    Packing Despatch LFL/MHL 300

    Paint shop LFL/MHL 300-1000

    Pantry LFL 300

    Perishable Cargo Processing Hall LFL/MHL 100

    Personnel processing area LFL/CFL 500

    Piers MHL / CFL 350

    Plant Isolation room LFL/CFL 250

    Plant quarantine Room LFL/CFL 250

    Porch MHL/LFL 200

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    19/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    17

    .

    Space type

    Type of lighting(possible lamp

    sources)(see note 1)

    Avg.Illumination

    level (lx)

    Porter's Rest Room LFL/CFL 150

    Prayer Room LFL/CFL 200

    Printing Room LFL/MHL 500

    Public circulation area LFL/CFL/MHL 200

    Queuing Area LFL / CFL / MHL 200

    Reception LVL/CFL 500

    Recreation Room LFL/CFL 300

    Refuse Store MHL/SON 100

    Rentable shops. (Concessionaries shop) LVL/LFL 500

    Rest Room LFL/CFL 150

    Restaurant, Food Court LVL/ CFL/ LFL 200-300

    Retail Concourse MHL / CFL 500

    ROP Body checking Room LFL/CFL 500

    ROP Control Room LFL 300

    ROP facilities LFL/CFL 150

    ROP IT Room LFL 500

    ROP lounge LFL/CFL/MHL 200

    Security Check Area MHL / CFL / LFL 500

    Security Equipment Room LFL 150

    Seminar Rooms LFL/CFL/LVL 500

    Server room, PABX room and UPS rooms LFL 300

    Service areas LFL 200

    Service Corridor LFL/CFL 100

    Service Counter Room LFL/CFL 500

    Sewage pumping station LFL 150

    Sheet metal work LFL/MHL 500-750

    Simulator Room LFL 300

    Sniffer Dog Room (Kennels/pen only) LFL/CFL 250

    Special delivery store room LFL/MHL 150

    Sprinkler room LFL/MHL 150

    Staff Rest Room LFL/CFL 150

    Staircases - escape only LFL/CFL 100

    Staircases, Escalators, Travelators, Lifts CFL 250

    Stores LFL 100 / 150

    Strong Room (Valuable Goods store) LFL/MHL 150

    Structural Steel Fabrication LFL/MHL 300-500

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    20/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    18

    .

    Space type

    Type of lighting(possible lamp

    sources)(see note 1)

    Avg.Illumination

    level (lx)

    Switch Gear Room LFL 200

    Technical Room LFL 150

    Ticket counters, check-in desks,information desks

    LFL/CFL/LVL 500

    Toilet Corridor LFL/CFL 100

    Toilets LFL / CFL/LVL 150

    Tool Rooms LFL 500

    Training room LFL/CFL 500

    Transformer Rooms LFL 150

    Unclaimed Goods Store Room LFL/MHL 100

    Unpacking, Sorting LFL/MHL 200

    Vehicle processing area LFL/MHL 200

    Viewing gallery area LFF/CFL 200

    VIP Area (Arrival) CFL/MHL/LFL 350

    VIP Bedroom suite LVL/LFL 100

    Waiting Hall MHL/LFL/CFL 350

    Washing bay for trucks MHL/SON 300

    Waste processing area MHL/SON 300

    Watch Room LFL/CFL 0-500

    Welding LFL/MHL 300Worker facility LFL/CFL 150

    Note 1:LFL: Linear Fluorescent lamps

    CFL: Compact fluorescent lamps

    MHL: Metal Halide vapour lamps

    SON: High Pressure Sodium Vapour Lamps

    LVL: Low voltage tungsten-halogen lamps

    2.3 Emergency Lighting

    2.3.1 General

    A. Emergency lighting shall fulfil the following functions:

    1. Illumination of the escape routes and immediate external areas atdischarge points shall be as according to the Fire Safety Strategy

    Report and shown on applicable drawings.

    2. Indicate the escape route direction clearly as required.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    21/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    19

    .

    3. Provide the exit signs on all the exits.

    4. Ensure fire alarm call points, fire fighting equipment and other life

    saving equipments on the premises are illuminated as required.

    5. Interface and intercommunication with SCADA/BMS system.

    B. The system shall have the approval of the Local Civil Defence Authority.

    C. Equipment shall be certified EMC compliant.

    D. Emergency lighting installation shall be complete with emergencybatteries, chargers, Luminaires and wiring, all as described in

    Specification.

    E. Non-maintained Luminaires as indicated on the relevant drawings shall besupplied directly from the battery system. Maintained exit Luminaires shall

    be supplied from a separate supply via an independent transformer and

    shall only operate from batteries during periods of electrical mains failure.

    F. The operation of the emergency lighting system shall be such that on theloss of any individual feeder the system shall switch to either a central

    battery supply system or individual battery packs, which shall provide

    power for 3 hours to illuminate emergency Luminaires throughout the

    building. On restoration of the mains supply the batteries shall be charged

    by an integral charger such that the system supplies not less than 85 % of

    its rated voltage after a period of 12 hours.

    G. Suitable Luminaires selected from the general lighting scheme shall bepowered from the inverters and wired independently of other systems,

    using fire-resistant cabling.

    H. Central controlled system with central battery system shall be used exceptwhere specified elsewhere. The centralized system shall fulfil the

    requirements in accordance with BS EN 50171 and shall as a minimum

    perform to the following requirements:

    1. Individual light monitoring.

    2. Light output - 100 %.

    3. Automatic function test.

    4. Automatic duration test.

    5. Data access/control at central location.

    6. Interface to Airport SCADA.

    7. 10 years battery life time by 20 C.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    22/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    20

    .

    8. 2 years electronic log book facility.

    9. Maintenance free sealed lead acid batteries.

    10. The design shall allow 20 % spare capacity for future expansion. Inaddition, a derating factor of 0.8 shall be applied to negate the effect

    of battery ageing so that batteries will supply the load for the full

    discharge duration throughout their useful life.

    11. Batteries to be sized with a minimum of 20 % spare battery capacity.

    12. AC/AC static inverters, which convert DC power from a built-instandby battery to 240V AC 50Hz single-phase power shall be

    provided.

    13. Luminaires designated for emergency operation, shall operate to theprinciples shown on drawings.

    14. The proposed emergency lighting levels shall be in accordance withBS EN 1838, local Regulations, NFPA 101 and the Fire Safety

    Strategy Report. The lighting level shall be archived at any time

    during the system life including de-rating due to dirt, components

    ageing and the reduction in battery voltage as the battery discharges,

    however the below table shall be followed as a minimum:

    Area Required Lux level Comment

    Escape route 1 Lux - along centre line andwith 50 % for at least half thewidth

    By Mandatory exit 10.8 Lux

    By exit doors 10.8 lx

    Stairs 10.8 lx

    By change ofdirection

    10.8 lx

    Fire fighting, safeequipment, first aidpost and fire callpoints

    10.8 lx

    By change of level 10.8 lx

    Intersections ofcorridors

    10.8 lx

    Outside near final exit 10.8 lx

    Open area anti-panicopen area lighting

    0.5 Lux - minimum measuredacross whole area

    High-risk task arealighting

    15 Lux or 10 % of normallighting level (whichever isthe greater value) -uniformity better than 1:10

    The ratio of maximumto minimum illuminationshall not be greaterthan 40:1 along thecentre line of theescape route.

    The ratio of maximumto minimum illuminationshall not be greaterthan 40:1 in Anti-panicopen areas

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    23/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    21

    .

    Area Required Lux level Comment

    Toilets with no naturallight

    Emergency lighting requiredabove exit door - no specificlevel stated

    I. The reflection factor for all surfaces shall be set to 0 % when calculatingemergency light levels.

    2.3.2 Switchboards for emergency lighting

    A. The design, material, construction and performance of switchboards foremergency lighting shall comply with the latest international standards.

    B. Switchboards shall be shipped to and stored securely taking into accountconditions found at site. When the switchboard final location is ready to

    receive the said switchboard, they shall be installed into position. Once inposition the switchboards shall be finally assembled, including all

    components and connections being torque tested in accordance with the

    manufacturer's recommendations to ensure there are no loose connections.

    C. All indoor switchboards shall be IP 43 ingress protection according to BSEN 60529.

    D. Switchboards shall be designed for the following ambient conditions:

    1. Outdoor maximum ambient temperature 50 C.

    2. Indoor maximum ambient temperature 41 C.

    E. Access to the switchboard interior and the protective devices shall be bymeans of a hinged door fixed shut by means of a moulded lever type latch

    which shall be able to be locked with the means of a proprietary locking

    system.

    F. With the door in the open position, it shall not be possible to touch or gainaccess to live parts without the use of a tool. The hinged door shall be

    easily removable when in the open position to aid installation and

    maintenance.

    G. All fixing accessories shall have anti-corrosion finish. All ferrous materialsshall either be corrosion inhibited and painted or hot-dip galvanised to BSEN ISO 1461. Non-ferrous metallic components shall be electroplated to

    protect against corrosion.

    H. All low voltage exposed terminals of switchboards that may be exposed totouch (with a door open or cover removed) shall be shrouded to IP 20 to

    BS EN 60529. Note this requirement does not include terminals within

    separate enclosure outgoing cable boxes. These shrouds shall be fitted with

    warning labels. Information labels shall also be fixed adjacent to the

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    24/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    22

    .

    shrouds (on a fixed part of the cubicle) to show where the terminations

    connect to e.g. bus bars, cables, etc.

    I. The earth bar shall be sized in accordance with BS EN 60439-1 Annex B.

    J. Minimum of 20 % spare outgoing space shall be installed in switchboardsfor emergency lighting.

    K. The Contractor shall submit to the Engineer for approval, features,characteristics, and ratings of circuit breakers and each switchboard

    component specified.

    L. The Contractor shall submit to the Engineer for approval, time currentcharacteristic curves for overcurrent protective devices, including circuit

    breaker trip devices and fusible devices.

    M. The Contractor shall submit to the Engineer for approval, operating andmaintenance data for components.

    N. Calibration certificates shall be submitted for all instruments.

    O. Operation and maintenance manual shall be submitted as per BS EN60439-1:1999 clause 5.3 and as per Employer's Requirements.

    2.3.3 Central battery system - mains power supply

    A. Central battery stations shall have dual power supplies, each power source

    shall be from a different transformer substation, via an automatic transferswitch (ATS). The ATS shall be monitored to provide secondary mains

    supply to the central battery station charger unit, should the primary supply

    perform below permitted requirements or fail.

    B. Each "Change-over' module (ATS) shall have its own short-circuitprotection.

    C. All outgoing distribution cables from the central battery unit shall be of afire resistant type.

    D. The above mentioned requirement is for central battery systems supplying

    public areas.

    E. The control module shall be composed of a microprocessor control modulewith plain text 4- line LCD displays with a minimum of 20 characters per

    line, to provide operative status and luminaire failures.

    F. Display shall indicate:

    1. Circuit earth leakage failure.2. Battery current drawn in emergency mode.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    25/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    23

    .

    3. Battery current drawn in test mode.4. Battery voltage.5. Battery test.

    6. Battery charge failure.7. Luminaire failures, with text address location.8. Sub-circuit board supply failure with text address location.

    G. Functions to include Earth leakage test on each circuit, display andprogramming status of each circuit, Monitor and control of all

    weekly/daily cycle tests and functions, monitoring of battery at five minute

    intervals, communication and programming with each addressable ballast

    at the luminaires, automatic logging of all test results and incidents.

    Manual test feature in addition to automatic.

    H. Touch-pad keys shall be provided for programming and monitoring of thepanels.

    I. Memory facility to be provided for two-year logbook:

    1. LED's shall indicate:

    a) Main operationb) Mains failurec) Battery operationd) Summation fault.

    J. Potential free indicator contacts shall be provided for:

    1. Operation.2. Battery operation.3. Summary fault.

    2.3.4 Central battery units

    A. Battery chargers:

    1. Battery chargers shall be installed in purpose-made metallicenclosures with an index of protection IP 31 in accordance with BS

    EN 60529 suitable for wall or floor mounting, depending on

    dimensions.

    2. Battery charger enclosures may house the system batteries providingthe design of the enclosure ensures safe operation with the batteries

    specified. This arrangement should normally be restricted to smaller

    systems e.g. for circuit breaker tripping supplies for power supply to

    emergency lighting system, central battery units shall be wall or floor

    mounted as required, conforming to BS 4533 Section 102.22, and be

    of robust, high quality construction. Enclosures shall be metal, with

    hinged lockable doors and with suitable ventilation provided.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    26/36

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    27/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    25

    .

    Employer's Requirements. The Contractor shall submit calculations to

    justify the Ampere-Hour capacity of the batteries for approval to the

    Engineer.

    3. Battery system shall be provided with a suitably rated switchdisconnector.

    4. Batteries shall be mounted on suitable tiered galvanized steel shelvingwith moulded plastic trays to contain any leakage from the battery

    cells, and to allow safe easy access for maintenance.

    5. Battery terminals shall be coated with the battery manufacturersapproved grease, and shrouded if not enclosed.

    6. Date of manufacture shall be stamped on each battery.

    7. Guaranteed life is not to be less than 10 years, with a capacity dropdown to not less than 80 percent under normal expected service.

    2.3.5 Self contained emergency battery packs

    A. Where a central emergency battery unit is not installed, individualemergency luminaries shall consist of individual power packs installed

    within or remote to the luminaries.

    B. Battery pack units shall consist of converter/inverter devices, with nickel-cadmium batteries to provide 3 hours operation under mains failure, unless

    the main supply is restored prior to this.

    C. Luminaries with self contained battery packs shall be connected to the liveside of the local lighting circuit and lamps shall operate automatically

    under mains failure conditions.

    D. Units shall have the capability of sustaining high temperature so that theycan be accommodated in fittings with high internal temperatures. However,

    if the internal temperature of the fittings exceeds 50 C, the battery unit

    shall be mounted remote to the luminaries. In the case of remote mounting,

    a purpose made remote mounting box shall be provided.

    E. Key operated switches shall be provided, at locations for all self containedemergency pack unit luminaries, to control the operation of the luminariesmanually for testing purposes and to the satisfaction of the Engineer. Test

    key switches shall be clearly labelled Emergency Lighting.

    2.3.6 Central Battery System, automatic self testing

    A. The Central Battery System shall be complete with automatic self testing,which shall comprise the following tests as a minimum requirement:

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    28/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    26

    .

    1. 10 minute monthly tests

    2. 180 minute annual test

    B. The system shall be fully automated microprocessor based systemproviding detailed testing of the emergency lighting installation from a

    central position. Tests can be programmed at dates and times to suit the

    user and application and require no human intervention.

    C. The central battery system shall allow interrogation of the system as theyoccur and for retrospective analysis of the tests and shall be interfaced with

    Airport SCADA

    D. Where luminaires are utilised for emergency lighting and supplied via the

    central battery system the contractor shall install switching relays whichutilise accurate electronic timers, the relay's shall test the un-switched

    supply to the appropriate emergency lighting circuits enabling them to be

    interrupted for a selectable test duration. These shall be key switch

    operated and shall be utilised in non public areas only.

    2.3.7 Self Contained Emergency converted luminaires

    A. Where luminaires are the self contained type the contractor shall allow forself testing self contained emergency luminaires and these shall

    automatically self test the emergency circuit and provide a fault indication

    whenever a failure is identified, these tests shall be carried out on a

    monthly and annual basis.

    B. Functional tests of the self contained Emergency conversion pack shall nottake place unless the batteries have been fully charged for at least 24 hours

    C. If the loss of supply is greater than 8 days, the self test module shallautomatically perform a commissioning test

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    29/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    27

    .

    3 Execution

    3.1 General

    A. The emergency lighting system shall operate to functional demands as

    required by the Standards, Regulations and fire strategy.

    B. Deliver storage and handling of Central battery unit equipment:

    1. Deliver equipment fully enclosed only after manufacturer's specifiedenvironmental conditions have been permanently established in spaces

    where equipment shall to be placed.

    2. Store equipment in spaces with environments controlled withinmanufacturers ambient temperature and humidity tolerances for non-

    operating equipment.

    3. Ensure clearances around equipment in accordance to manufacturer'swritten instructions, but not less than 900 mm in front of unit.

    4. Install system components on at least 100 mm high steel frame bases.Install systems according to manufacturer's printed instructions, and

    arrange for manufacturer/supplier to inspect and certify the

    installation.

    3.2 Emergency Lighting

    3.2.1 Wiring

    A. Where the emergency lighting system installation is via a central batteryunit, the wiring to emergency luminaries shall be carried out in fire

    resistant low smoke sheathed cables, unless specified otherwise.

    B. Fire resistant cables for the emergency lighting system via the centralbattery unit shall have White coloured sheath.

    C. Where the emergency lighting scheme is self-contained emergency packs,the wiring system shall be either as above, or in PVC insulated single core

    wires in conduits.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    30/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    28

    .

    D. Generally, cables shall be 2.5 mm2cross-sectional area unless specifiedotherwise.

    E. The Contractor shall pay careful attention to cable routings so as to keepcable runs to the shortest possible length and ensure the overall volt dropon any circuit is within the tolerances of the luminaries connected and

    within the limits specified in the MEDCO regulations.

    3.2.2 Installations of batteries

    A. The manufacturers recommendation/instructions shall always be followed.

    B. Insulated tools shall be used.

    C. Personnel erecting battery banks shall remove metallic objects form their

    person i.e. watches, rings etc.

    D. Eye and hand protection shall be provided.

    E. Batteries shall not be left on site for prolonged periods without beingtrickle charged to maintain their condition i.e. if delivery is some weeks

    before commissioning of the charger.

    F. Due care shall be observed when handling acidic substances.

    3.2.3 Installation of Light Fittings

    A. Lighting fixtures shall be installed as indicated in the manufactures writteninstructions.

    3.2.4 Identification

    A. Identify equipment and components according to Employer'sRequirements.

    B. All emergency luminaries shall be labelled with 100 mm width yellowcolour labels containing black lettering clearly identifying the circuit

    number and the Central battery unit.

    3.2.5 Cleaning

    A. On completion of installation, inspect unit components. Remove paintsplatters and other spots, dirt, and debris. Touch up scratches and abrasions

    in finish to match original finish. Clean unit internally using methods and

    materials recommended by manufacturer.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    31/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    29

    .

    4 Quality Control

    A. Implement a quality assurance plan in accordance with the Employer'sRequirements together with testing and commissioning plans, including

    but not limited to:

    1. Factory Acceptance Test.2. Site and Systems Acceptance Test.3. Site Integration Tests.4. Training of staff.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    32/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    30

    .

    5 Testing and Commissioning

    A. Perform all test and commissioning in accordance to the Employer'sRequirements, with special attention on, but not limited to:

    1. Factory Acceptance Test.

    2. Site and Systems Acceptance Test.3. Site Integration Test.4. Training of staff.

    5.1 Factory Acceptance Test

    A. The Contractor shall inform the Engineer of routine factory acceptancetests that shall be performed on any component of the General lighting

    system prior to shipping from the manufactures factory.

    B. The Contractor shall inform of any test date, time and location to theEngineer at least 4 weeks in advance to witness the test. The cost for

    travel, boarding, incidental expenses etc shall be included for the

    Employer's and the Engineers representatives (2 each).

    C. The Contractor shall submit to the Engineer, prior to shipping, copies of allrelevant certification or approvals for the General lighting system and their

    components.

    D. Inspection and testing shall be carried out in accordance with BS 7671, theassociated IEE Guidance Notes, OES4, CIBSEcodes L and Mand the

    requirements of this specification.

    E. The Contractor shall furnish the Engineer with co-ordinated drawings "ForApproval" highlighting predicted Lux levels for all areas. The minimum

    acceptable Lux levels shall be in accordance with the Employer's

    Requirements measured one hour after Sun-Set.

    F. Emergency lighting system: Emergency lighting systems shall be inspectedand tested in accordance with the inspection and test procedures detailed

    within BS 5266.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    33/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    31

    .

    5.2 Site and Systems Acceptance Test

    A. The pre testing and Commissioning of all equipment shall be carried outby the equipment Manufacturer and shall be witnessed by the Engineer,

    prior to putting into service the equipment shall be demonstrated to theEngineer and Employer's representative, carrying out all necessary

    functional tests.

    B. Testing methods: The Engineer shall be notified of the method to be usedfor each type of test and notification shall be given in accordance with the

    Employer's Requirements.

    C. Inspection and testing shall be carried out in accordance with BS 7671, theassociated IEE Guidance Notes, OES4 and the requirements of this

    specification, this include but not limited to:

    1. Testing Agency: Arrange and pay for the services of an electricaltesting agency to perform inspection and tests on switchboard,

    components, and accessories.

    2. Test Procedure: Conform to the following:

    a) Manufacturer's required field service tests: Supervision of unitinstallation, connections, and adjustments by a factory-authorised

    service representative. All report results shall be issued in writing

    b) Perform tests on completion of unit installation and after buildingcircuits have been energized. Provide instruments to permit

    accurate observation of tests

    c) Test unit functions, operations, and protective features. Adjust toensure operation complies with Specifications. Include the

    following tests:

    i Simulate Malfunctions: Verify protective device operation

    ii Demonstrate low battery voltage shutdowns, and transfers of

    supply due to normal source failure and restoration

    iii Verify emergency supply duration

    iv Operate each type of load served by the unit without

    symptoms of abnormal supply such as noise, vibration, or

    pulsation of the load or its output. All light fixtures, ceiling

    roses, modules, wires, etc shall be identified

    v Manually equalise charging of battery cells according to

    manufacturer's written instructions. Record individual cell

    voltages.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    34/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    32

    .

    3. Ensure that required lux levels for all rooms and locations have beenachieved at completion of all finishes, record tests and submit to the

    Engineer for verification.

    D. Ensure sufficient task lighting is available during all stages of site testing.

    E. Visual and Mechanical Inspections. Perform as a minimum the following:

    1. Compare nameplates of equipment and detailed components withsingle line diagram and specified requirements, and report

    discrepancies.

    2. Check for proper anchorage, required clearances, physical damage,and proper alignment of switchboards and components.

    3. Inspect all doors, panels, and sections for paint, dents, scratches, fitand missing hardware.

    4. Verify that fuse and circuit breaker sizes, types, and ratings conformto requirements. Include control power and potential, control power

    transformer fuses, and fuses for fused circuit breakers.

    5. Inspect bus connections for high resistance. Use low resistanceohmmeter or check tightness of bolted bus joints by using a calibrated

    torque wrench. Refer to manufacturers instructions for proper torque

    values.

    6. Test electrical and mechanical interlock systems for proper operationand sequencing. Make closure attempts on locked open devices. Make

    opening attempts on locked closed devices. Attempt key exchanges

    with devices in exchange preventing positions.

    7. Clean Central battery unit's interior and exterior using manufacturersapproved methods and materials.

    8. Inspect mechanical indicating devices for proper operation.

    F. Retest: Correct deficiencies identified by tests and observations andcompletely retest switchgear. Verify by the system tests that the total

    assembly meets specified requirements.

    G. Upon completion of installation, inspect interior and exterior ofswitchboards. Remove paint splatters and other spots, dirt, and debris.

    Touch up surface scratches and marks to match original finish.

    5.3 Site Integration Test

    A. The Contractor shall undertake system-wide integrated testing inaccordance with the General Requirements.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    35/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    P:\61400\3_DOC\10_Tender_Doc\02_SA\CRN_55_MC 5_Civil & Building WorksSalalah\Final\31.10.2008\03_Specifications\E_Building_Electrical\Electrical\SA-000-E-11608_General lighting systems_Rev T01.DOC

    33

    .

    5.4 Training of Staff

    A. The Contractor shall implement a comprehensive system-wide trainingprogramme for selected/appointed Employer's personnel for all aspects of

    General Lighting Systems.

    B. The Contractor shall provide for all aspects and requirements for trainingsessions. A written outline and agenda of the training material and full

    contents shall be submitted for Employer's approval.

    C. The training shall include, but not limited to:

    1. Classroom based written and visual media instruction and site basedoperation of the said plant.

    2. Cover all operating features of the plant and interconnected system.

    D. Training shall be performed by experienced and competent trainingpersonnel, familiar with the system and training techniques. The

    Contractor shall submit for approval the CV/Resume of all training

    personnel.

    E. Training and all training materials shall be offered in bilingual languages;Arabic and English.

    F. Training literature shall be presented in bound printed documents, allgraphs, pictures and diagrams shall be in colour. Each participant attending

    training sessions shall have literature presented according to training

    presentation (see item 5.4.K).

    G. The number of training sessions and number of Employer'sattendees/participants shall be as indicated in the Electrical Particular

    Specifications. Document No. SA-000-E-11600 Particular Electrical

    Specification.

    H. The Contractor shall provide a suitable classroom environment; based for aclass size of 20 people at any one training session.

    I. Plant and equipment utilised in the classroom environment shall be thesame; manufacture, model and type as installed at site.

    J. Training sessions shall be scheduled at the convenience of the Employer.

    K. Training presentation sessions shall be scheduled for, but not limited to:

    1. Operations Management.2. Operations personnel.3. Technical Supervisors.4. Technicians.

  • 8/10/2019 SA-000-E-11608_General lighting systems_Rev T01.pdf

    36/36

    Main Contract 5 - Project SpecificationBuilding, Electrical - General Lighting SystemsGeneral Specification

    34

    6 Revision Log

    Date Issue Description

    31.10.2008 T01 Issued for Tender