Safety BASICs TM ©2004 Cooper Bussmann Bussmann ® Awareness of Safety Issues Campaign Electrical Hazards

Upload: connor-mcgrath

Post on 26-Mar-2015

218 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

Safety BASICsTM

©2004 Cooper Bussmann©2004 Cooper Bussmann

Bussmann® Awareness of Safety Issues Campaign

Electrical Hazards

Page 2: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Electrical Hazards

What are the hazards as you approach

electrical equipment to perform work?

Page 3: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Electrical Hazards

• Shock• Arc flash

– Heat– Fire

• Arc blast– Pressure– Shrapnel– Sound

Example of an arcing fault

Page 4: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

I = V / Z

• What happens with shock?

• What happens when there is a fault?

• What is the difference between a short-circuit and an arcing fault?

Basic Electrical Theory

Page 5: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Electric Shock

• Over 30,000 non-fatal electrical shock accidents occur each year

• Over 600 people die from electrocution each year

• Electrocution remains the fourth (4th) highest cause of industrial fatalities

• Most injuries and deaths could be avoided

Page 6: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Human Resistance Values

Resistance (ohms)

Condition Dry Wet

Finger touch 40,000 to 1,000,000 4,000 to 15,000

Hand holding wire 15,000 to 50,000 3,000 to 6,000

Finger-thumb grasp 10,000 to 30,000 2,000 to 5,000

Hand holding pliers 5,000 to 10,000 1,000 to 3,000

Palm touch 3,000 to 8,000 1,000 to 2,000

Hand around 1-1/2 inch pipe 1,000 to 3,000 500 to 1,500

Two hands around 1-1/2 inch pipe 500 to 1,500 250 to 750

Hand immersed 200 to 500

Foot immersed 100 to 300

Human body, internal, excluding skin

200 to 1,000

This table was compiled from data developed by Kouwenhoven and Milnor.

Page 7: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Electric Shock

Human body resistance (hand to hand) across the body is about 1000

Ohms law: I = V / R amps = 480 volts / 1000

= 0.48 amps (480 mA)

Product safety standards consider 5 mA to be the safe upper limit for children and adults

Page 8: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Electric Shock

mA Affect on person 0.5 - 3 - Tingling sensations 3 - 10 - Muscle contractions and pain 10 - 40 - “Let-go” threshold 30 - 75 - Respiratory paralysis100 - 200 - Ventricular fibrillation200 - 500 - Heart clamps tight 1500 + - Tissue and organs start to

burn

Page 9: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Electric Current Pathways

(A) Touch Potential (B) Step Potential (C and D) Touch / Step Potential

Current passing through the heart and lungs is the most serious

Page 10: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Electric Shock Injury

Page 11: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Arc Flash

As much as 80% of all electrical injuries are burns resulting from an arc-flash and ignition of flammable clothing

Arc temperature can reach 35,000°F - this is four times hotter than the surface of the sun

Fatal burns can occur at distances over 10 ft

Over 2000 people are admitted into burn centers each year with severe electrical burns

Page 12: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Arc Blast

An arc fault develops a “pressure wave”Sources of this blast include:

– Copper expands 67,000 times its original volume when vaporized

– Heat from the arc, causes air to expand, in the same way that thunder is created from a lightning strike

This may result in a violent explosion of circuit components and thrown shrapnel

The blast can destroy structures, knock workers from ladders, or across the room

Page 13: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

BoltedShort Circuit

A B

Arcing Fault

A B

Current Thru Air

Page 14: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Electric Arc

Copper Vapor:Solid to VaporExpands by67,000 times

Intense Light

Hot Air-Rapid Expansion

35,000 °F

Pressure Waves

Sound Waves

Molten Metal

Shrapnel

Page 15: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Personnel Hazards Associated With Arc Flash & Arc Blast

• Heat – burns & ignition of material– Arc temperature of 35,000oF– Molten metal, copper vapor, heated air

• Second degree burn threshold:– 80oC / 175oF (0.1 sec), 2nd degree burn

• Third degree burn threshold:– 96oC / 205oF (0.1 sec), 3rd degree burn

• Intense light– Eye damage, cataracts

Page 16: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

• Pressures from expansion of metals & air

• Eardrum rupture threshold: – 720 lbs/ft2

• Lung damage threshold:– 1728 - 2160 lbs/ft2

• Shrapnel • Flung across room or from

ladder/bucket

Personnel Hazards Associated With Arc Flash & Arc Blast

Page 17: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Flash protection boundaries and incident energy exposure calculations both dependent upon:

Duration of arc-fault or time to clear• Speed of the overcurrent protective device

Arc-fault current magnitude• Available fault current

• Current-limitation can reduce

Overcurrent Protection Role

Page 18: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

IEEE / PCIC & NFPA 70E

• Ad Hoc Safety Subcommittee– Users– Consultants– Manufacturers– Medical experts

• Following are some of the tests run– All of the devices used for this testing were

applied according to their listed ratings

Page 19: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

IEEE / PCIC Staged Arc Flash Test Set-up

Page 20: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

22.6 KA SymmetricalAvailable Fault Current

@ 480V, 3 Phase

Fault Initiated on Line Side of 30AFuse

30A RK-1Current Limiting Fuse

Size 1 Starter

Test No. 46 cycle STD

640A OCPDNon Current Limitingwith Short Time Delay

Set @ 6 cycle opening

Page 21: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Page 22: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 4 Still Photo

Page 23: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 4 Still Photo

Page 24: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 4 Still Photo

Page 25: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 4 Still Photo

Page 26: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 4 Still Photo

Page 27: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 4 Still Photo

Page 28: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 4 Still Photo

Page 29: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

>225oC/437oF

>225oC/437oF

Results: Test No.4

T1

T2

P1

T3

Sound

141.5 db @ 2 ft.

50oC/122oF

>2160 lbs/ft2

> Indicates Meter Pegged

Page 30: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

22.6 KA SymmetricalAvailable Fault Current

@ 480V, 3 Phase

Fault Initiated on Line Side of 30AFuse

30A RK-1Current Limiting Fuse

Size 1 Starter

Test No. 3

601A.Class LCurrent Limiting Fuse

Page 31: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Page 32: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 3 Still Photo

Page 33: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 3 Still Photo

Page 34: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 3 Still Photo

Page 35: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 3 Still Photo

Page 36: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

> 175oC/347oF

Results: Test No.3

T1

T2

P1

Sound

133 db @ 2 ft.

62oC/143.6oF

504 lbs/ft2

T3(No Change

From Ambient)

> Indicates Meter Pegged

Page 37: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

22.6 KA SymmetricalAvailable Fault Current

@ 480V, 3 Phase

30A RK-1Current Limiting Fuse

Size 1 Starter

Test No. 1

601A.Class LCurrent LimitingFuse

Fault Initiated on Load Side of 30AFuse

Page 38: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Page 39: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 1 Still Photo

Page 40: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 1 Still Photo

Page 41: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 1 Still Photo

Page 42: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Test 1 Still Photo

Page 43: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Results: Test No.1

T1

T2

P1

T3

Sound(No Change From Ambient)

(No Change From Ambient)

(No Change From Ambient)

(No Change From Ambient)

(No Change From Ambient)

Page 44: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Non-Current Limiting

Reduced Fault Current

via Current-Limitation

Test 1

Test 4

Test 3

Current-Limitation: Arc Energy Reduction

Page 45: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Summary

• Shock, arc flash and arc blast are the three recognized electrical hazards

• Shock injuries result from electrical current flowing through the body

• Arcing faults can generate enormous amounts of energy

• Injuries from arcing faults are a result of the tremendous heat and pressure generated

Page 46: Safety BASICs TM ©2004 Cooper Bussmann B ussmann ® A wareness of S afety I ssues C ampaign Electrical Hazards

©2004 Cooper Bussmann

Summary

• Overcurrent protective devices have an impact on the two most important variables of arc flash hazards:– Time (speed of the OCPD)– Fault current magnitude (current-limitation

may help reduce)• Current-limitation may be able to

significantly reduce the energy released during arcing faults