Safety Services © 2015 Government of Alberta Alberta Municipal Affairs Clarence C. Cormier, P.Eng. – Chief Electrical Inspector Bob Hall, SCO – Electrical Technical Advisor Codes & Standards Section, M&E (Director – Harry Li) Safety Services Branch (Executive Director – Alex Morrison) Public Safety Division (Assistant Deputy Minister - Bruce McDonald) Alberta Municipal Affairs (Deputy Minister - Brad Pickering) (Elected Minister – Deron Bilous) Government of Alberta (Elected Premier - Rachel Notley) SAFETY CODES COUNCIL CONFERENCE & AGM 2015 The Rimrock Resort Hotel 300 Mountain Avenue, Banff, Alberta, Canada T1L 1J2 1

Upload: dodat

Post on 29-Jun-2018

237 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Alberta Municipal Affairs

Clarence C. Cormier, P.Eng. – Chief Electrical Inspector

Bob Hall, SCO – Electrical Technical Advisor

Codes & Standards Section, M&E (Director – Harry Li)

Safety Services Branch (Executive Director – Alex Morrison)

Public Safety Division (Assistant Deputy Minister - Bruce McDonald)

Alberta Municipal Affairs (Deputy Minister - Brad Pickering)

(Elected Minister – Deron Bilous)

Government of Alberta (Elected Premier - Rachel Notley)

SAFETY CODES COUNCIL CONFERENCE & AGM 2015

The Rimrock Resort Hotel 300 Mountain Avenue, Banff, Alberta, Canada T1L 1J2

1

Page 2: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

2

Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

at Oil & Gas Facilities Alberta Electric Utility Code AMA Update (Sneak in if time

permits!)

Page 3: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 - Highlights Taken from the CE Code 2015 Preface: http://shop.csa.ca/en/canada/c221-canadian-electrical-code/c221-15-package/invt/27013892015pkg;

General - The term “injury” has been replaced with “damage” throughout the Code;

Section 4 now contains requirements for high-voltage cable ampacities and clarified Rules for conductor termination temperature. In addition, a new table (Table 39) simplifies residential service and feeder conductor selection (currently Table 5E!);

Section 8 - More options are provided for load and voltage drop calculations;

Section 10 - Bonding conductor selection has been clarified through the addition of the new Tables 16A and 16B;

Section 12 contains many new and revised requirements for wiring methods, and the conduit fill tables have been expanded;

Section 18 has undergone major revisions. Requirements for Class II and Class III locations have been relocated to Appendix J, and requirements for explosive dust atmospheres based on IEC Zone 20, Zone 21, and Zone 22 have been added;

Section 26 - Requirements for arc-fault protection have been expanded and clarified;

Section 50 has been merged with Section 64; and

Section 62 has been completely rewritten.

Now we will consider the above in a little bit more detail.

3

Page 4: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 4 Section 4 — Conductors

4-004 Ampacity of wires and cables (see Appendix B)

(1) The maximum current that a copper conductor of a given size and insulation is permitted to carry shall be as follows:

(d) single-conductor and 2-, 3-, and 4-conductor cables and single-conductor and 2-, 3-, and 4-conductor metal-armoured and metal-sheathed cables, unshielded and rated not more than 5 kV, in conductor sizes No. 1/0 AWG and larger, installed in accordance with configurations described in Diagrams D8 to D11 in an underground run, directly buried or in a raceway, as specified in Tables D8A to D11B or as calculated by the IEEE 835 calculation method;

(g) shielded cables rated 5 kV to 46 kV in sizes No. 2 AWG to 1000 kcmil, as specified in Tables D17A to D17N for the configurations described therein and the conditions described in Table D17, or as calculated by the IEEE 835 calculation method.

4

Page 5: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 4 4-006 Temperature limitations (see Appendix B)

(1) Where equipment is marked with a maximum conductor termination temperature, the minimum size of conductor used shall be based on the allowable ampacity in the temperature column in Table 1, 2, 3, or 4, with all relevant correction factors being applied as required by Rule 4-004, corresponding to the maximum termination temperature marked on the equipment.

(2) For the purpose of Subrule (1), and except as provided for by other Rules of this Code, where the maximum conductor termination temperature for equipment is not marked, the maximum conductor termination temperature shall be considered to be

(a) 60 °C for equipment

(i) rated not more than 100 A; or

(ii) marked for use with No. 1 AWG or smaller conductors; and

(b) 75 °C for equipment

(i) rated more than 100 A; or

(ii) marked for use with conductors larger than No. 1 AWG.

(3) Notwithstanding Subrule (2), for high-voltage equipment where conductor termination temperatures are not marked, it shall be permitted to consult the manufacturer to establish the permitted termination temperature.

(4) Subrules (1) and (2) shall apply only to the first 1.2 m of conductor length measured from the point of termination on the equipment.

(5) Where a cable transition is made to meet the requirements of Subrule (1) or (2), the length of a conductor terminating on equipment shall be not less than 1.2 m.

(6) Where the conductor ampacity is selected from Tables D8A to D11B or from Table 12E, Subrules (1) and (2) shall apply.

5

Page 6: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 4

6

Page 7: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 8

Section 8 — Circuit loading and demand factors

8-002 Special terminology (see Appendix B)

Basic load — the load of lighting and receptacle circuits, based on the outside dimensions of a specific area of building occupancy, as listed in Table 14.

Calculated load — the load calculated in accordance with the applicable requirements of this Section.

Demonstrated load — historical maximum demand watt information recorded over at least a 24-month period for the same type of facility as the one in question, equated to watts per m2.

7

Page 8: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 8

8

Page 9: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 10

9

Section 10 — Grounding and bonding

Table 16

(Note: This Table has been deleted.)

Table 17

(Note: This Table has been deleted.)

Table 18

(Note: This Table has been deleted.)

Page 10: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 10

10

Page 11: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 10

11

Page 12: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 12

Section 12 — Wiring methods

Non-metallic-sheathed cable

12-510 Running of cable between boxes and fittings

12-516 Protection for cable in concealed installations

Armoured cable

12-610 Terminating armoured cable

Mineral-insulated cable, aluminum-sheathed cable, and copper-sheathed cable

12-706 Method of supporting

Raceways

General

12-904 Conductors in raceways

12-910 Conductors in conduit and tubing

Rigid and flexible metal conduit

12-1010 Maximum spacing of conduit supports

12-1014 Conductors in conduit

Rigid PVC conduit

12-1124 Split straight conduit

Rigid Types EB1 and DB2/ES2 PVC conduit

12-1160 Maximum number of conductors

12

Page 13: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 12 Rigid RTRC conduit

12-1200 Scope

12-1202 Use

12-1216 Conduit supports

12-1218 Maximum number of conductors

Liquid-tight flexible conduit

12-1302 Use of liquid-tight flexible metal and non-metallic conduit

12-1304 Maximum number of conductors

12-1308 Supports

Electrical metallic tubing

12-1402 Use

12-1404 Restrictions on use

12-1410 Maximum number of conductors

12-1412 Connections and couplings

12-1414 Provision for bonding continuity

13

Page 14: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 12 Electrical non-metallic tubing

12-1504 Supports

12-1506 Maximum number of conductors

Cellular floors

12-1814 Provision for bonding

Cable trays

12-2200 Method of installation

12-2208 Provisions for bonding

Cablebus

12-2252 Use of cablebus

Installations of boxes, cabinets, outlets, and terminal fittings

12-3000 Outlet boxes

12-3002 Outlet box covers

12-3016 Outlet boxes, cabinets, and fittings

14

Page 15: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 12 CE Code

2012

15

Page 16: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 12 Table 6

(Note: This Table has been deleted.)

Table 6A

Maximum number of 600 V thermoset conductors without a jacket, Types R90XLPE, RW75XLPE, RW90XLPE, and RPV90, of one size in trade sizes of conduit or tubing

Table 6B

Maximum number of 1000 V thermoset conductors without a jacket, Types R90XPLE, RW75XLPE, RW90XLPE, and RPV90, of one size in trade sizes of conduit or

tubing

Table 6C

Maximum number of 600 V thermoset conductors with a jacket, Types R90XPLE, RW75XLPE, RW90XLPE, R90EP, RW9075EP, RW90EP, and RPV90, of one size in

trade sizes of conduit or tubing

Table 6D

Maximum number of underground conductors, Types RWU90XLPE, TWU, and TWU75, of one size in trade sizes of conduit or tubing

Table 6E

Maximum number of 1000 V and 2000 V thermoset conductors without a jacket, Type RPVU90, of one size in trade sizes of conduit or tubing

16

Page 17: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 12 Table 6F

Maximum number of 1000 V and 2000 V thermoset conductors with a jacket, Type RPVU90, of one size in trade sizes of conduit or tubing

Table 6G

Maximum number of 2000 V thermoset conductors without a jacket, Type RPV90, of one size in trade sizes of conduit or tubing

Table 6H

Maximum number of 1000 V thermoset conductors with a jacket, Type RPV90, of one size in trade sizes of conduit or tubing

Table 6I

Maximum number of 2000 V thermoset conductors with a jacket, Type RPV90, of one size in trade sizes of conduit or tubing

Table 6J

Maximum number of thermoplastic conductors, Types TW and TW75, of one size in trade sizes of conduit or tubing

Table 6K

Maximum number of thermoplastic conductors, Types TWN75 and T90 NYLON, of one size in trade sizes of conduit or tubing

17

Page 18: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 18 Section 18 — Hazardous locations

Scope and introduction

18-000 Scope (see Appendices B, F, and J)

(1) This Section applies to locations in which electrical equipment and wiring are subject to the conditions

indicated by the following classifications.

(2) This Section supplements or amends the general requirements of this Code.

(3) For additions, modifications, renovations to, or operation and maintenance of existing facilities employing the Division system of classification, the continued use of the Division system of classification shall be permitted.

(4) Where the Division system of classification is used as permitted by Subrule (3), the Rules for Class I, II, and III locations found in Annex J18 of Appendix J shall apply.

18-004 Classification of hazardous locations (see Appendices B, J, and L)

Hazardous locations shall be classified according to the nature of the hazard, as follows:

(a) explosive gas atmospheres; or

(b) explosive dust atmospheres.

18-006 Locations containing an explosive gas atmosphere (see Appendix B)

Explosive gas atmospheres shall be divided into Zones 0, 1, and 2 based upon frequency of occurrence and

duration of an explosive gas atmosphere.

18-008 Locations containing an explosive dust atmosphere (see Appendix B)

Explosive dust atmospheres shall be divided into Zones 20, 21, and 22 based upon frequency of occurrence and duration of an explosive dust atmosphere.

18

Page 19: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 18 Section 18 — Hazardous locations

Zone 0 — a location in which explosive gas atmospheres are present continuously or are present for long periods.

Zone 1 — a location in which

(a) explosive gas atmospheres are likely to occur in normal operation; or

(b) the location is adjacent to a Zone 0 location, from which explosive gas atmospheres could be communicated.

Zone 2 — a location in which

(a) explosive gas atmospheres are not likely to occur in normal operation and, if they do occur, they will exist for a short time only; or

(b) the location is adjacent to a Zone 1 location, from which explosive gas atmospheres could be communicated, unless such communication is prevented by adequate positive-pressure ventilation from a source of clean air, and effective safeguards against ventilation failure are provided.

Zone 20 — a location in which an explosive dust atmosphere, in the form of a cloud of dust in air, is present continuously, or for long periods, or frequently.

Zone 21 — a location in which an explosive dust atmosphere, in the form of a cloud of dust in air, is likely to occur in normal operation occasionally.

Zone 22 — location in which an explosive dust atmosphere, in the form of a cloud of dust in air, is not likely to occur in normal operation but, if it does occur, will persist for a short period only.

19

Page 20: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 26 Section 26 — Installation of electrical equipment

Receptacles

26-700 General (see Appendix B)

(12) All receptacles of CSA configuration 5-15R and 5-20R installed in a child care facility shall be tamperresistant receptacles and shall be so marked.

(13) Notwithstanding Subrule (12), receptacles dedicated for stationary appliances such that the receptacle is rendered inaccessible or those located 2 m from the floor or finished grade shall not be required to be tamper resistant.

26-702 Receptacles exposed to the weather (see Appendix B)

(1) Receptacles exposed to the weather shall be provided with wet location cover plates.

(2) Receptacles of CSA configurations 5-15R, 5-20R, 5-20RA, 6-15R, 6-20R, and 6-20RA shall be provided with cover plates suitable for wet locations, whether or not a plug is inserted into the receptacle, and marked “Extra Duty”.

(3) Notwithstanding Subrules (1) and (2), cover plates marked “Wet Location Only When Cover Closed”, or the equivalent, shall be permitted for receptacles

(a) installed facing downward at an angle of 45° or less from the horizontal; or

(b) located at least 1 m above finished grade and not in a wet location.

26-712 Receptacles for dwelling units (see Appendices B and G)

(a) except as otherwise provided for in this Code, in dwelling units duplex receptacles shall be installed in the finished walls of every room or area, other than bathrooms, hallways, laundry rooms, water closet rooms, utility rooms, or closets, so that no point along the floor line of any usable wall space is more than 1.8 m horizontally from a receptacle in that or an adjoining space, such distance being measured along the floor line of the wall spaces involved;

(d) in dwelling units there shall be installed in each kitchen

(vi) a sufficient number of duplex receptacles installed on the remaining finished walls in accordance with Item (a);

20

Page 21: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 26 Section 26 — Installation of electrical equipment

Branch circuits for residential occupancies

26-720 Special terminology

In this Subsection, the following definitions apply:

Arc-fault protection — a means of recognizing characteristics unique to both series and parallel arc-faults and de-energizing the circuit when an arc-fault is detected.

Combination-type arc-fault circuit interrupter — a device that provides both series and parallel arc-fault protection to the entire branch circuit wiring, including cord sets and power supply cords connected to the outlets, against the unwanted effects of arcing.

Outlet branch-circuit-type arc-fault circuit interrupter — a device that provides both series and parallel arc-fault protection to downstream branch circuit wiring, cord sets, and power supply cords against the unwanted effects of arcing and also provides series arc-fault protection to upstream branch circuit wiring. 21

Page 22: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 26 Section 26 — Installation of electrical equipment

Branch circuits for residential occupancies

(f) each branch circuit supplying 125 V receptacles rated 20 A or less shall be protected by a combination-type arc-fault circuit interrupter, except for branch circuits supplying

(i) receptacles installed in accordance with

(A) Rule 26-710(f); or

(B) Rule 26-712(d)((i), (iii), (iv), and (v); and

(ii) a single receptacle for a sump pump where

(A) the receptacle is labelled in a conspicuous, legible, and permanent manner identifying it as a sump pump receptacle; and

(B) the branch circuit does not supply any other receptacles; and

(g) notwithstanding Item (f), the entire branch circuit need not be provided with arc-fault protection where

(i) an outlet branch-circuit-type arc-fault circuit interrupter is installed at the first outlet on the branch circuit; and

(ii) the wiring method for the portion of the branch circuit between the branch circuit overcurrent device and the first outlet consists of metal raceway, armoured cable, or non-metallic conduit or tubing.

22

Page 23: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 26 26-956 Submersible pumps installed in bodies of water

(1) Submersible pumps installed in bodies of water shall comply with the following:

(a) the voltage supplying the submersible pump shall not exceed 150 volts-to-ground;

(b) the pump motor shall be bonded to ground by a conductor that

(i) is sized in accordance with Rule 10-814;

(ii) is integral with the supply cable, or within the same protective enclosure as the power supply conductors if single conductors are used;

(iii) has the same type of insulation as the supply conductors; and

(iv) terminates adjacent to the location where the branch circuit conductors receive their supply;

(c) the wiring method to the pump shall be

(i) Type RWU75, RWU90, TWU, or TWU75 or equivalent single conductor or twisted assemblies of these types, suitable for handling at –40 °C, enclosed in a plastic water pipe or in rigid PVC conduit; or

(ii) Type SOW, G, G-GC, W, or the equivalent portable power cable;

(d) ground fault protection shall be provided to de-energize all normally ungrounded conductors supplying the submersible pump with a ground fault current trip setting adjusted to function as low as practicable to permit normal operations of the pump, but in no case shall the ground fault current setting be greater than 10 mA for an operating time period not exceeding 2.7 s; and

(e) the supply conductors or cables shall be run from an outdoor connection facility, above or below ground, to the main distribution panelboard in accordance with the requirements of Section 12.

(2) Notwithstanding Item (1)(a), submersible pumps installed in bodies of water shall be permitted to operate at voltages exceeding 150 volts-to-ground where

(a) a deviation has been allowed in accordance with Rule 2-030;

(b) the operating voltage does not exceed 5.5 kV;

(c) the electrical installation is maintained by qualified electrical maintenance staff; and

(d) the area around the submersible pump is protected from access by the public by fencing, cribbing, or isolation and so marked.

23

Page 24: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Sections 50 & 64

2012Section 50 — Solar photovoltaic systems

2015Section 50

Note: This Section has been deleted.

Section 64 — Renewable energy systems

Inverters

Solar photovoltaic systems

Small wind systems

Large wind systems

Micro-hydropower systems

Hydrokinetic power systems

Stationary fuel cell systems

Storage batteries 24

Page 25: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

CE Code 2015 – Section 62 Section 62 — Fixed electric heating systems

Scope

62-000 Scope (see Appendix B)

(1) This Section applies to

(a) fixed electric space-heating systems for heating rooms and similar areas;

(b) fixed surface heating systems; and

(c) fixed electric heating systems not covered by Item (a) or (b).

E.g. Bare element water heater — a self-contained, factory-assembled water heater that heats water by direct contact with the uninsulated heating element wire.

(2) The requirements of this Section supplement or amend the general requirements of this Code.

25

Page 26: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

2015 Oil & Gas Code

“Code for Electrical Installations at Oil & Gas Facilities 2015”.

Planned Adoption September 1, 2015.

Will be available at the Queen’s Printer.

Rene Leduc is Chair of O&G Code WG.

Reports to the ETC.

Last meeting was 2014/04/11.

4 column change document available upon request.

26

Page 27: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Alberta Electric Utility Code 2013 Adopted October 1, 2013.

Available at the Queen’s Printer.

Only one STANDATA – VAR-EUC-Scope [rev-1].

Jim Porth is Chair of the AEUC WG.

Reports to ETC.

Last meeting was 2015/3/18.

Unlike the O&G code, the AEUC working group has decided not to follow the Canadian Electrical code cycle. Instead, they will be following the CSA O/H and U/G standards cycle (CE Code, Part III). Next publication planned for 2016.

27

Page 28: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

28

AMA Electrical Update

What’s new in 2015?

Page 29: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Agenda

1. Electrical Staff

2. Committee Participation

3. Codes & Standards

4. STANDATA

5. Advisories

6. Forms & Reports

Page 30: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Electrical Staff 1. Chief Electrical Inspector– Clarence Cormier, Codes &

Standards (Edmonton) 2. Electrical Technical Advisor – Bob Hall, Codes &

Standards (Edmonton) 3. Senior Electrical Inspector – Brian McIntosh, Field

Services (Grand Prairie) 4. Electrical Inspector – Kevin Glubrecht, Field Services

(Red Deer) 5. Electrical Inspector – David Phillips, Field Services

(Edmonton) 6. Electrical Inspector – Ben Chan, Field Services

(Calgary) 7. Electrical Inspector – Steve Eagles, Partnership

Support (Red Deer)

Page 31: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Committee Participation ALBERTA ELECTRICAL TECHNICAL COUNCIL AND 3 OF ITS 4 WORKING GROUPS:

CANADIAN ELECTRICAL CODE WORKING GROUP

ELECTRICAL UTILITY CODE WORKING GROUP

OIL & GAS CODE WORKING GROUP

CSA

TC CANADIAN ELECTRICAL CODE (CE CODE), PART 1

TC WIND TURBINES

TC INDUSTRIAL PRODUCTS (TCIP)

TSC INTEGRATED COMMITTEE ON HAZARDOUS LOCATIONS (ICHL)

OBJECTIVE BASED INDUSTRIAL ELECTRICAL CODE (OBIEC) – CE CODE, PART 4

ELECTRICAL PRODUCT SAFETY - HEALTH CANADA

UL

UL ELECTRICAL COUNCIL

UL STP 111 - COMMITTEE FOR MULTIOUTLET AND PREFABRICATED WIRING ASSEMBLIES

UL STP 9540 - ENERGY STORAGE SYSTEMS AND EQUIPMENT

ULC ADVISORY COUNCIL

ULC STANDARDS COMMITTEE ON LIVE WORKING (S400A)

UL-ULC 1088 TC Standard for Temporary Lighting Strings

Page 32: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Codes & Standards

http://www.municipalaffairs.alberta.ca/cp_electrical_codes_standards.cfm

Presently the Canadian Electrical Code, Part 1 (twenty-second edition), Canadian Standards Association standard C22.1-12, 2015 adoption-enforcement planned for September 1;

Presently the Code for Electrical Installations at Oil and Gas Facilities, 4th Edition, 2013, published by the Safety Codes Council, 2015 adoption-enforcement planned for September 1;

Presently the Alberta Electrical Utility Code, 4th Edition, 2013, published by the Safety Codes Council, adoption-enforcement planned for 2016/2017 to more closely follow the CSA O/H & U/G standards.

Page 33: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

STANDATA http://www.municipalaffairs.alberta.ca/cp_electrical_standata.cfm

STANDATA reissued in 2014:

INTRODUCTION – MARCH 2014

Safety Codes Act (Interpretations)

Reporting of Electrical Incidents/Accidents

Electrical Code Regulation (Interpretations)

Section 2 - Electrical Systems Equipment

Canadian Electrical Code STANDATA (Interpretations)

Errata

Section 2 – General Rules

Section 4 – Conductors

Section 10 – Grounding and Bonding

Section 12 – Wiring Methods

Section 18 – Hazardous Locations

Section 22-Locations in Which Corrosive Liquids or Vapours or Excessive Moisture are Likely to be Present

Section 26 - Installation of Electrical Equipment

Section 30 - Installation of Lighting Equipment

Section 32 - Fire Alarm Systems, Fire Pumps and Carbon Monoxide Alarms

Variances STANDATA

Canadian Electrical Code

Rule 2-024 – RE: Oil and Gas Industry Electrical Submersible Pumps

Rule 2-024 – RE: Liquid-filled Transformers

Page 34: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Advisories

http://www.municipalaffairs.alberta.ca/cp_electrical_advisories.cfm

New link: ULC Advisory - Fire Resistive, Fire Resistant and Circuit Integrity Cables

http://ul.com/code-authorities/fire-code/fire-resistive-and-circuit-integrity-cables/

Otherwise – No Change.

Page 35: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Forms & Reports

http://www.municipalaffairs.alberta.ca/cp_electrical_forms_and_reports.cfm

2014 Electrical Incident Statistics Report forthcoming March, 2015.

Page 36: Safety Services Alberta Municipal Affairs Tech... · Alberta Municipal Affairs ... Alberta Electrical Code Highlights Canadian Electrical Code 2015 Code for Electrical Installations

Safety Services

© 2015 Government of Alberta

Questions?