sample cable calculation
TRANSCRIPT
-
7/25/2019 Sample Cable Calculation
1/1
www.castlinesystems.com
4mm - 3c - 31mCopper:Cable:90C:XLPE:SWA:BS5467:600/1000v
C Clipped direct
CPC(1) = 6.43mm
CPC(2) = 4mm
RCBO 30mA
32ARCBO 30mA 32A
Max Zs = 1,666.000
= 1.78kA
400.00V - 50Hz
0.1300 0.95pfTN-STPN
26.00A ()Radial circuit
Fixed equipment
393.2 / 227.0V
Cable DataCopper:Cable:90C:XLPE:SWA:BS5467:600/1000v:Table 4E4
Cable Rating (tabulated) Table 4E4A Col-3 42A
Cable Rating (effective) 42A PASS
mV/A/mtr (tabulated) Table 4E4B Col-4 10mV/A/m (r)
mV/A/mtr (temperature corrected) operating 52.99C 8.844mV/A/m (r)
Voltage drop permitted (per phase) 4.00% (9.24V)
Voltage drop Calculated (per phase) 1.69% PASSCircuit voltage drop = 3.91V
Correction FactorsAmbient temperature () 30C = 1.000 Table 4B1
Grouping () 1 ccts = 1.000 Table 4C1
Thermal Insulation () 0mm = 1 Table 52.2
Circuit Protective conductors (cpc)Minimum CPC size ( S = It/k ) 1.30mm k = 143 0.100 sec I = 589.21 A
Cable sheath (copper equivalent) 6.43mm 6.43mm
Internal core 4mm 4mm PASSCPC It/k)
Protective Device DetailsRCBO 30mA 32A
Selected for Short-circuit protection only
Rating () 32 PASS32 26
Breaking capacity () 6kA 6 1.78 PASS
Operating current () 0.03A
Calculated disconnection time 0.100 sec PASS
Maximum permitted disconnection time 0.2 sec Table 41.1
Impedance of device (Z) 1,666.000 PASS1,666.000 0.3920 Z Zs
Earth Fault DataEarth fault loop impedance (Ze) 0.1300
Circuit R1 value 0.1618
Circuit R2 value 0.1002
Circuit R1+R2 value 0.2620
Earth loop impedance (Zs=Ze+R1+R2) 0.3920 PASS1,666.00 0.3920 Z Zs
Earth fault current (=/Zs) 589.21A = 230.95V Zs = 0.3920
Short Circuit DataProspective short curcuit current 1.78 kA
Short circuit withstand time (t = kS/I) 0.942 sec k = 143 S = 4mm I = 589.21 A
Castline Systems - CableCalc BS7671 (17th Edition) Version 5.0.1.26