INFRARED INSPECTION SURVEY REPORT SAMPLE CUSTOMER MCC SURVEY DATA COLLECTED: 4/9/2018

Upload: others

Post on 22-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

INFRARED INSPECTION SURVEY REPORT

SAMPLE CUSTOMER

MCC SURVEY

DATA COLLECTED: 4/9/2018

Page 2: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

REPORT DATE

EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

PAGE #

03/29/18 107L126 APCU Heater Power Panel

Line #2 connection on this power panel has an elevated thermal pattern that indicates a loose connection in early stages.

During scheduled outage, inspect and tighten connections. MODERATE 3

03/29/18 Bottom FuseMain Cooling Tower Cell 3

Fan

The bottom fuse has a comparatively elevated thermal pattern. This could be due to a worn or incorrect fuse, or may be load related.

Verify correct fuse and verify load is balanced. MODERATE 4

03/29/18Steam Turbine

Generator Enclosure

Steam Turbine This unit has a loose connection During scheduled outage, inspect and tighten connections. MODERATE 5

03/29/18 Enclosure Vent Fan 1 CTG2 This connection has a comparatively elevated thermal

pattern that indicates a loose connection. During scheduled outage, inspect and tighten connections. MINOR 6

03/29/18 EN1700 Industrial Control Panel

Connection #21 has a comparatively elevated thermal pattern that indicates a loose connection.

During scheduled outage, inspect and tighten connections. MINOR 7

1- CRITICAL

2- DEFECTS ARE IN MODERATE STAGES

3 - DEFECTS MAY BE PRESENT

4 - LEVELS ARE ABOVE NORMAL

5 - NORMAL

2 of 7

Page 3: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F137 °F95.7 °F41.3 °F69 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE

OBSERVATIONS: Line #2 connection on this power panel has an elevated thermal pattern that indicates a loose connection in early stages. Temperatures are elevated but not excessive at this time.

Facility location: Equipment Name: 107L126Data Collected: Image Filename: IR000010

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: APCU Heater Power Panel

www.conditionmonitoringservices.com

3 of 7

Page 4: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F162.2 °F97.4 °F64.8 °F94.2 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: Verify correct fuse and verify load is balanced.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE

OBSERVATIONS: The bottom fuse has a comparatively elevated thermal pattern. This could be due to a worn or incorrect fuse, or may be load related.

Facility location: Equipment Name: FusesData Collected: Image Filename: IR000060

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: Main Cooling Tower Cell 3 Fan

www.conditionmonitoringservices.com

4 of 7

Page 5: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F113.2 °F73.8 °F39.4 °F45.2 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE

OBSERVATIONS: This unit has a loose connection at the location marked below.

Facility location: Equipment Name: Steam Turbine Data Collected: Image Filename: IR000061

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: Steam Turbine Generator Enc.

www.conditionmonitoringservices.com

5 of 7

Page 6: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F106.7 °F84.6 °F22.1 °F38.7 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MINOR

OBSERVATIONS: This connection has a comparatively elevated thermal pattern that indicates a loose connection. Temperatures are elevated but not excessive at this time.

Facility location: Equipment Name: Enclosure Vent Fan 1Data Collected: Image Filename: IR000059

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: CTG2

www.conditionmonitoringservices.com

6 of 7

Page 7: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F97 °F87.7 °F9.3 °F29 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MINOR

OBSERVATIONS: Connection #21 has a comparatively elevated thermal pattern that indicates a loose connection. Temperatures are comparatively elevated but minor at this time.

Facility location: Equipment Name: EN1700Data Collected: Image Filename: IR000062

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: Industrial Control Panel

www.conditionmonitoringservices.com

7 of 7