sans healthcare watch
TRANSCRIPT
SANS Committees: Healthcare Watch -Report Back Toby v Reenen CSIR
SANS 204: ENERGY EFFICIENCY IN BUILDINGS
Services Working Group
• Work being concluded on interpretation and application of XA2 50% hot water rule. • XA2 demands that 50% of annual hot water consumed be
generated by means other than direct electric heating. • The intention of the rule is to save a minimum of 50% of the
water heating energy. • Unfortunately the wording “by volume” in the ruling allows
for significantly lower savings to be accepted by solar water heating and heat pump installations.
SANS 204: ENERGY EFFICIENCY IN BUILDINGS
Services Working Group
• Work being concluded on interpretation and application of XA2 50% HOT WATER RULE. • It is proposed that the voluntary SANS 204 standard pilot a
more stringent requirement of demanding that 50% of the ENERGY REQUIRED in GENERATING the consumed hot water volume be from means other than direct electric heating.
• The issue of the viability of induction geysers has also been raised for review.
SANS 204: ENERGY EFFICIENCY IN BUILDINGS - Climate Map
• The Existing Climate Map is being
reviewed: • Simple to interpret • Coarse resolution of “binning”
doesn’t reflect local nuances in climate
• Very difficult to measure and quantify
• Doesn’t offer detailed insight to design information
SANS 204: ENERGY EFFICIENCY IN BUILDINGS - Climate Map
• A Revised Map needs the following: • Map data needs to be relevant to
building energy calculations, tools, regulations and standards
• Needs to allow for clear interpretation by stakeholders
• Needs to reflect the human perception of climate
• Needs to reflect building response to climate (Passive design)
• RH% • Convection?
SANS 204: ENERGY EFFICIENCY IN BUILDINGS - Climate Map
• Proposed model • Calculate SET using current best
climate data. • Develop index representing
Summer-High & Winter-Low SET per cell. (A:B)
• Single index could then be used in consideration of seasonal peak heating and cooling requirements
SANS 1544: ENERGY PERFORMANCE CERTIFICATES • This committee has established to
finalise the drafting of the standard for energy performance certificates.
• The measurement defined by this standard includes energy consumption data collected from one year of operation of a building but excluding its first year of operation.
• The energy consumption data includes building as well as operational energy • This annual value will then be
benchmarked against the guidance values from SANS 10400-XA.
SANS 1544: ENERGY PERFORMANCE CERTIFICATES
• It is noted that the SANS 10400-XA
does not define energy consumption guidelines data for healthcare buildings and the committee would welcome the submission of healthcare based energy consumption data for evaluation and inclusion.
SANS 10400-O: VENTILATION & LIGHTING
• This committee was established to address a number of
concerns regarding the lighting and ventilation requirements contained therein. • Of particular concern to healthcare buildings is the
methodology adopted by and contents of Table 2. • Application of ASHRAE 62.1
• Additive Method • Nuanced Approach • Can result in more energy efficient systems
• Requirements for Respiratory Isolation Rooms (WHO Guide) • Lighting: Task Lighting & Colour Rendering Index
Occupants/Equipment NOT ADAPTABLE or
Tolerant of Indoor Conditions
Occupants/Equipment ADAPTABLE or
Tolerant of Indoor Conditions
• Hierarchy of Design Solutions
Fully Mechanical Ventilation
Hybrid systems with Climatic adaptability
Fully Passive Ventilation
Are
a O
ccu
pie
d
IUSS: Ventilation Design Philosophy
SANS 10400: Future work
• Other work that will be addressed as the committees are
established: • Fire protection requirements in healthcare buildings • (Your comments here)
• (and here) • (and here)