Michael Sonntag

Institute of Networks and Security

SCADA and security

What is “SCADA”?

SCADA = “Supervisory Control And Data Acquisition”

Control and monitoring systems for industrial machines

Typically very robust: physical & electrical

Often very local: Factory floor

Sometimes widely distributed: Industry plant with several

kilometres length

Sometimes very remote: Management of remote substations Power grid, pipelines, water/gas/sewage distribution, …

SCADA was previously completely different and often “electric”, not

“electronic”, i.e. relays

Today all of them are computerized, but they are still often treated

as of old: Completely separate and as long as you don’t get

physical access, nothing can happen!

More general: “ICS” = Industrial Control System

2

SCADA system diagram

▪ RTU: Remote

Terminal Unit

▪ PLC: Programmable

Logic Controller

▪ Both are “local”

devices for remote

sites. Today typically

small computer

systems

Source: Gerhard Eschelbeck 3

SCADA human-machine-interface example

http://2.bp.blogspot.com/-WvErSWD4bEI/Ti3gy3FFerI/AAAAAAAAAYU/lLk4SO0bjG4/s1600/DCS_PLC_Scada_Systems.jpg

4

SCADA installation example

http://www.miramarautomation.com/controlsystemsusa/PICTURES/RTU-CTRL_ST1.jpg

5

Large control/monitoring panel

http://electrical-engineering-portal.com/wp-content/uploads/scada-dms.jpg

6

Remote SCADA stations - example

http://www.scadalink.com/solutions/img/sagd-scada-solution-02.jpg

7

Remote SCADA stations - example

http://www.scadalink.com/services/img/man-on-tower.jpg

8

Where is SCADA used?

Manufacturing: Controlling production lines

Individual machines, robots, transport devices; quality control

Essential services & commodities: Electricity, gas, water, oil, waste

treatment

Both for production and transmission/distribution

Critical infrastructure!

Large buildings/facilities and environmental control

Heating/ventilation/air conditioning systems (HVAC), lighting, entry

control, energy consumption …

Not typical SCADA, but home automation is quite similar!

Transportation and mass transit

Traffic signals, security checks (signals working, presence

detection etc.), tracking of “cars”, timetable information

9

SCADA operation

Typically programmed once, with “simple” software

Updates are very rare

They continuously send reports on some measured data

Mostly they autonomously control the local system, but “big”

parameter changes come from remote central control stations and

are received “rarely”

Communication bandwidth is low

Focus on: Performance, reliability, flexibility safety

Security is often non-existent

Low computing resources & bandwidth

No priority: Local communication only/own radio frequency,

physically secure, works without, proprietary protocol… Many assumptions are today/in general NOT valid any more!

10

Threats

Deliberate attacks

Insider (disgruntled employees)

Industrial espionage

Organized crime: Extortion

Unfriendly states: Electronic warfare (or harassing)

Accidental threats

Equipment failure

User error

Misdirected attacks/collateral damage

Natural phenomena

Weather, earthquakes, floods, solar activity: Communication

disruption, device damage

11

Potential security problems

Disruption of service

Locally: Just “disturb” (DoS, erroneous commands, …) it

Globally: Use a local system to bring down the network All are interconnected; issuing commands to other local systems might

not be designed, but still possible!

Process redirection: Receiving more/free resources

Process manipulation: Redirect sewage flow into freshwater pipes,

overload electricity transformers/power lines, turn off traffic control

complete collapse etc.

Manipulation of sensor data: “Save” costs, wear out systems, hide

beginning malfunctions, …

Overloading: Little reserves (CPU, memory, …) available

12

Why is security becoming a problem?

Increased interconnection: More remote sites without personnel, but

with data communication

Also increased number of entry points and paths Supervisory authorities, billing, subcontractors etc.

Connected to more systems (e.g. statistics, invoicing, …)

Off-the-shelf hardware and software instead of everything proprietary

(ICT moved into SCADA)

Own custom DB MS SQL Server

Assembler-coded system Linux base + scripts

Proprietory protocol + bus system IP + Ethernet

Compatibility: Old protocols were conceived as serial protocols

without authentication, encryption, or integrity mechanisms but are

still used/supported today

13

Why is security becoming a problem?

“Security is a cost, not an investment”

Devices cost more, additional devices, more complexity, …

Different security models (=primary goals):

ICT: CIA (Confidentiality, Integrity, Availability)

SCADA: SRA (Safety, Reliability, Availability)

Legal problems:

License and support contracts may forbid adding any code or

additional components Adding security is impossible

NDAs may prevent enforcing producers to close vulnerabilities

ICT security SW/devices are ill suited for SCADA

Different content protocols and communication mechanisms

Real time requirements of SCADA: Delay/jitter unacceptable

14

Why is security becoming a problem?

Patching is very rare/potentially complex: See later!

Wider use and in more important systems

Similar to Linux: Few end-users Few attacks

Increased capabilities of field equipment

You can reuse it for other things, reprogramming is actually

possible (no more EPROMs!), sending data is SW (=changeable,

e.g. to DoS) instead of HW

▪ Public (=shared) networks used for data transfer

▪ Standard systems can be used for contacting

▪ Attacking the system (flooding) may influence the SCADA

15

Potential security issues

Classification of problems (Target: SCADA):

Modify/disrupt sensor data flow (=outgoing) Show false values, cut off central control system

Modify/disrupt command flow (=incoming) Issue commands or prevent changes to configuration

Modify/disrupt system (=other program/“switch off”)

Snooping: Unauthorized gathering of sensor data

Delays: Communication is delayed (in-/outgoing) Itself dangerous, or to hide attacks for some time

Similar/classical problems exist regarding the central control station,

which is typically a “normal” computer system (but additional

communication channel)

16

Examples of (lacking) SCADA security

Default vendor password

For maintenance and testing

Typically identical in (at least) each device of a product line

Sometimes impossible to disable

May even allow remote connection

Additional functionality

Daemons not turned off (remains of default configuration)

Keys for signing updates are included in the update

Extract key from device/update Create your own update!

Proprietary protocol

Often same/similar as very old ones Many people now know it,

reverse engineering simple (buy two devices!)

Security disabled by default to ease installation

17

Examples of (lacking) SCADA security

Old devices: Replacing everything is expensive

Devices may be very old (but see also: Windows XP!)

Amortization over 15-20 years or longer

Other systems in the SCADA network

Example: Safety systems on SCADA network and the safety

engineers programmed the safety system from their normal

desktop computer: Get into LAN (get in safety desktop ) get

in safety system access to SCADA network!

18

Security “advantages” of SCADA systems

Often rather obscure programming language

Similarly often uncommon assembler code ( processors)

Knowledge on multiple systems required

Get into UI system (Windows), reach control server (Linux), attack

SCADA stations (Proprietary)

Network separation: While it IS possible, it might not be easy to

reach the control system

Obscurity: Few data about SCADA systems is public

Handbooks/brochures reserved for paying customers only

Specialized hardware needed for physical interfaces

Each installation is comparatively unique

If it crashes, it will reboot automatically (“watchdog timers”)

Physical security / tamper proof

19

“But the network is completely separate!”

Even if it is: Can someone add own devices into it?

Attaching cables to a bus system?

Plugging in at spare ports?

GSM: Calling the correct number + password?

Wireless communication/network?

Is it really separate?

Management and maintenance? Updates? Development?

Note: “Separate” means also: No data medium may cross the border,

i.e. installing patches through SD-Cards not separate any more,

as a virus could spread through this!

Result: No SCADA network is ever completely separate!

Minimization is still very useful and necessary!

20

Separating networks

Never allow direct connection to public networks/Internet

Introduce strong protection devices between networks

Ideally (very complex and expensive!): “Public” network, e.g. company LAN

Firewall

Intermediate system for data exchange (DMZ, data warehouse)

Firewall

Control system and local SCADA network

Firewall

Remote SCADA network:

Firewall

SCADA device(s)

Plus IDS at several locations

At each remote location

21

Patching SCADA systems

Risk of vulnerability to be patched vs risk of patch disturbing the

production?

Higher priority for perimeter defences (firewalls etc.), as these are

cheaper and less riskier to implement/update?

Does the vendor still exist/support the system?

Can the system run the patched system at all?

How to (reliably!) update 1000 remote systems while they are

actively in use to control a process?

How to test patches?

A complete duplicate system or a model of it ( communication

link simulation!) might not be available

Who may authorize/perform installation of patches?

Operator of the system, maintenance contractor, vendor?

22

Patching SCADA systems

Can the patch be installed during normal operation?

Sufficient memory, CPU, bandwidth, … for this?

How long will the “reboot” take?

Critical systems are redundant – during patching they are not First patch redundant system, then test & switch over, then install on

“main” system and go back to fully redundant

Patch management:

Which system is at which patch level?

Which patches have been tested?

Compatibility: Configuration, resources, …

De-installation of patches in case of problems

Do we have backups?

Will the system still run or is physical intervention necessary?

23

Malware example: Stuxnet

Stuxnet is one of the extremely rare malware examples for SCADA

systems

Attacks are more common, but these occur “manually”

Stuxnet is a platform-independent worm containing multiple rootkits

Original target system: Windows (hidden by rootkit)

Infects SCADA control software on them (if present)

From there moves to SCADA systems itself (rootkit) if they match

certain properties, where it activates its payload

Timeline: 6/09 (First infection), &/10 (First malware report)

Very precisely targeted at specific systems

Large Windows infection rate (6 millions? China, 30.000 Iran)

Siemens: Only 24 SCADA systems were infected

24

Stuxnet properties

Extremely complex software requiring detailed knowledge on

Windows + Siemens SCADA systems

Contained 4 zero-day exploits for Windows

Rootkit for SCADA system

Two valid certificates for driver signing (Realtek, JMicron)

Probably physically stolen; both are in one industrial complex

Specific knowledge on SCADA system at target facility needed: What

system, which configuration, program code

Including the devices controlled by it

For testing a similarly equipped facility would be needed

Estimated effort:

6 month of 5-10 core developers + management, quality control,

reconnaissance, procurement…

25

Stuxnet properties

Unusually large: Approx. 500 kB in size

Written in several programming languages: C, C++, Step7 (several

possibilities)

Works without any Internet connection: Infection, spreading and

“jump to Step7”

Last one is via a special data cable: Communication library (DLL)

is modified to enable this

Several variants (at least 3) exist, which add/remove/change some

functionality

26

Stuxnet spreading

Initial infection takes place via a USB device (memory stick, external

harddisk, …)

Opening the directory in icon view is sufficient, no further

interaction is necessary Vulnerability in processing .LNK files (Win XP – Win 7)

Previous version used a different method (Autorun.inf vuln.)

Two hidden files are copied to the system and one is installed as

driver-filter for the file system

Ensures survivability of reboots and acts as rootkit So these files will not be visible on disk/USB devices

These files are digitally signed, or this would not work

If no admin rights are present, it uses exploits to elevate itself to

admin before continuing

Also stops, if later than 24.6.2012 Self-termination!

27

Stuxnet spreading

Installs itself in running processes (no reboot needed)

Which one it is depends on running the antivirus program It might install even in the AV process itself!

If some AV programs are present and later than a specific date,

infection is stopped (to risky/detectable)

It uses special techniques when loading itself as a DLL to

circumvent behavioural blocking

Contacts all other Windows servers in the LAN to infect them (if they

not already are) via RPC/Print spooler

Also used to update existing infections to latest version

Infects all removable drives to spread out further

Propagates through network shares as well

Uses the current user and WMI to copy & execute itself

28

Stuxnet spreading

If a server with the WinCC (Siemens development environment for

Step7 system) database is found, the default hardcoded vendor

password is used to inject itself into the remote database

When WinCC is run, the database is cleaned and the payload

written to a DLL (via in intermediate CAB file)

The DLL is converted into a stored procedure and run whenever

the DB is started Infection of local system

29

Stuxnet reporting back

After it has installed itself, it will check whether internet access is

possible, by trying Windows Update or MSN

If not Continue with other tasks

Contacts Command&Control servers

www.mypremierfutbol.com, www.todaysfutbol.com

It uploads configuration information and checks for updates

Encryption: XOR with a static 31 byte long key

Whatever code is sent, is injected into a process and run Backdoor or update functionality!

30

Stuxnet infecting

It infects all (with restrictions) Step7 projects

To ensure the DLL is loaded whenever the project is loaded in the

development/management environment

DLL is used for communication between WinCC and SCADA system

Allows injecting code into the SCADA system and hiding it when

retrieving/inspecting code there

Delegates to the original DLL after inspection/modification

Three different infection sequences exist, two very similar, the

third seems to be incomplete and for a different CPU

Infection takes place only if it is a specific model with a specific CPU

and certain static parameters (configuration of connected devices)

31

Stuxnet on SCADA

Also it must contain the subroutine “FC1869” (communication with

Profibus devices) and contains at least one communication module

CP-342-5

Then copies code to SCADA system and ensures it is run

A CP-342-5 device is used to create variable frequencies for

controlling the rotation speed of electric motors

Malware activity only, if the drives are from two specific vendors!

The frequency must be between 807 and 1210 Hz Which is VERY high for such devices (capable of >600 Hz USA

export regulated as usable for Uranium enrichment!)

No hiding on the device itself – connection through uninfected

management system will show it (cryptically!)

32

Stuxnet: System configuration required

http://www.symantec.com/connect/blogs/stuxnet-breakthrough

Must be from

Vacon or Fararo

Paya

33

Stuxnet payload

With random delays (13 days to 3 month) it begins activity

It modifies the actual frequency for short intervals

(1410 2 Hz 1064 Hz 1410), but reports correct frequency Each step works only briefly: 15/50 minutes

This is done with 27 days between the individual steps

(Probable) aim: Destroying centrifuges for uranium enrichment

Fragile: 10% loss/year during normal operation seems common

1064 Hz = Nominal speed ( 334 m/sec wall speed of centrifuge)

Through directly sending control commands to the interface

Stuxnet sends/listens on global comm. bus First SCADA device to

elapse long wait time activates all simultaneously

34

Summary

SCADA systems are not a primary attack target today:

Too few systems

Each of them is different

Making money from them is complex and dangerous

But:

Terrorism (from state to disgruntled ex-employees)

Targeted attacks for information stealing

Getting in through SCADA as “backdoor” into normal LAN Connect at some remote station, get through the command center,

reach the internal network, and install malware there

SCADA security will become more important

Especially during development: From no/little security to full

security similar to “normal” computers today

35

Potential future research directions

IDS/IPS might be useful: SCADA systems possess very regular

communication patterns – everything out of the ordinary is alarming

anyway

So anomaly detection might finally work!

Patching and update management

Both in designing systems as well as tools E.g. Dual-core CPUs might help in testing/deployment; can be

switched off to conserver energy; useful for “peak” needs too

Separating networks (“data diodes”)

Enabling forensics: Ensuring data is available to trace problems back