scada hardware manual

Upload: ramu-gunaseelan

Post on 10-Apr-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Scada Hardware Manual

    1/99

    meritHARDWARE MANUAL

    TABLE OF CONTENTS

    1.0 Introduction

    1.1 Organization of the Manual

    1.2 Who will get the best out of this manual

    2.0 Overview of Traction Power Distribution

    3.0 Overview of the Scada System

    3.1 Remote Control Centre

    3.2 Location of RCC equipment

    3.3 Remote Terminal Unit ( RTU )

    4.0 Functional Description of the SCADA System

    4.1 General

    4.2 Remote Control Centre

    4.3 Remote Terminal Unit

    5.0 Technical description of Remote Terminal Unit

    5.1 General

    5.2 RTU at Traction Sub-station

    5.3 RTU at sectioning and paralleling post

    5.4 RTU at sub-sectioning and paralleling post

    5.5 Functional description of Remote terminal Unit

    5.5.1.0 Logic chassis

    5.5.1.1 CPU module

    5.5.1.1.1 Watch dog Timer

    5.5.1.1.2 Interrupt Logic

    5.5.1.1.3 Address Latch

    5.5.1.1.6 Memory

    5.5.1.2.0 Digital Output Module ( DOM )

    5.5.1.2.1 Functional Description of DOM

    5.5.1.2.2 Select Before Operation and Description

    5.5.1.3.0. Digital Input Module ( DIM )

    5.5.1.3.1 Interface Connection and Functional Description

    Page No : 1

  • 8/8/2019 Scada Hardware Manual

    2/99

    meritHARDWARE MANUAL

    5.5.1.4.0 Analog Input Module ( POWER METER )

    5.5.1.4.1 Functional Description of POWER METER

    5.5.2.0 Interface Card Enclosure

    5.5.2.4 Catanery Interface ( CIC )5.5.3.0 Modem

    5.5.3.1 Overview of Modem

    5.5.4.0 Power Supply Unit

    5.5.4.1 Principle of Operation

    5.5.4.2 Protection Features

    5.5.4.2.1 Mains Supervision

    5.5.4.2.2 Battery Supervision

    5.5.4.3 Functional Description of LDA75F5.5.4.4 Functional Description of LDC30F

    5.5.4.5 Overcurrent Protection

    5.5.4.6 Overvoltage Protection

    5.5.4.7 FoldBack Characteristics

    5.5.6.0 Contactors / Relays

    5.5.7.0 Terminal Block

    5.6.0 Description of Telemetry at TSS

    5.6.1 Under Voltage Tripping of Bridging Interruptors5.6.2 Scheme of Telemetry at SP

    5.6.3 Scheme of Catenary Indication at SP

    5.6.4 Closing of Bridging Interruptors

    5.6.5 Under Voltage Tripping of Interruptors

    5.6.6 Sequence of Operations of Under Voltage Tripping

    5.6.7 Catenary Voltage Sensing at TSS

    5.6.8 Scheme of Telemetry at TSS

    5.6.9 Auto Re-closing Scheme at TSS

    5.6.10 Field Wiring

    Page No : 2

  • 8/8/2019 Scada Hardware Manual

    3/99

    meritHARDWARE MANUAL

    6.0 Maintenance of SCADA System

    6.1 Maintenance philosophy

    6.2 RTU Power Supply Unit

    6.4 Table of Periodic Inspection and Maintenance6.5 Fault Finding and Rectification

    6.6 Testing Equipment Requirement

    6.7 Test Equipment

    7.0 RTU Trouble Shooting Procedure

    7.1 TeleSignal

    7.2 Telemetry

    7.3 Telecommand

    7.4 Power supply Unit7.5 Trouble Shooting Chart for UPS

    7.6 Trouble Shooting Procedure for Modem

    7.7 TeleSignal Fault Finding Chart

    7.8 TeleMetry Fault Finding Chart

    7.9 TeleCommand Fault finding Chart

    8.0 Downloading Program To Rtu Micro controller

    9.0 Download Parameters to RTU

    9.1 Testing the various parameters using MERITDIAG:

    Page No : 3

  • 8/8/2019 Scada Hardware Manual

    4/99

    meritHARDWARE MANUAL

    CHAPTER - 1

    1.0 INTRODUCTION

    1.1 ORGANISATION OF THIS MANUAL

    This document is the hardware manual of Remote Terminal Unit for Supervisory Control

    and Data Acquisition (SCADA) System designed, manufactured and supplied by M/s

    MERIT, Chennai. It contains the technical description, user procedures and maintenance

    aspects of the system.

    This manual helps the user to correctly install the system , use it effectively and maintain

    properly.

    The manual starts with an overview of traction distribution network and briefly introduces the

    user to the SCADA system. Then the manual gives the technical description of the system

    and the associated sub-systems. Finally, it deals with the maintenance aspects.

    1.2 Who will get the best out of this manual ?

    This manual is prepared for the use of the technical persons who are involved in using the

    system and those who have the responsibility for maintaining it. The details contained in

    this manual are highly technical in nature and hence the reader is expected to have a

    basic understanding of electronics circuits and exposure to the latest state of art

    technology.

    The manual only covers basic trouble-shooting procedures and techniques. The reader is

    advised to contact the technically trained engineers of SCADA system, before embarking

    on component changes.

    Page No : 4

  • 8/8/2019 Scada Hardware Manual

    5/99

    meritHARDWARE MANUAL

    CHAPTER - 2

    2.0 OVERVIEW OF TRACTION POWER DISTRIBUTION

    25KV AC, 50 Hz Single phase electric traction system is adopted for the electrified tracks.

    Power is obtained from State Electricity Boards (SEBs) from their network at

    220/132/110/66 KV at traction substations (TSS) and stepped down to 25 KV.

    The high voltage winding of the single phase transformer is connected across two phases

    and one terminal of the 25KV winding is connected to the rail and the other terminal to the

    catenary system (Over Head Equipment (OHE)). The TSSs are spaced at a distance of

    40 to 60 km.

    The supply to the OHE from TSS is fed through interrupters located at feeding post (FP).

    Adjacent TSSs normally supply power to the OHE on different phases to reduce

    unbalance in the supply authorities grid.

    To avoid the pantograph of a locomotive or electric multiple unit from bridging the supply

    from different phases when it passes from one zone to another, a neutral section is

    provided to separate the OHEs fed from different phases. The switching station provided

    at neutral section is called "Sectioning and Paralleling post" (SP). At the SP in multi track

    sections, the OHEs are also paralleled independently on either side of the neutral section

    to reduce voltage drop. In an emergency, when a TSS is out of commission, feed from

    adjacent TSSs on either side is extended up to the failed TSS by closing interrupters at

    SP. The pantograph(s) of locomotive(s) or electric multiple unit is (are) lowered at the

    failed TSS to avoid short circuiting the phases at the insulated overlap.

    Between a TSS and adjacent neutral section, the OHE is divided into sub-sections for

    isolating the faulty section for the purpose of maintenance and repairs.

    The switching stations provided at such points are called "Sub-sectioning and paralleling

    posts (SSP). The OHE of various tracks, in multiple track sections, are also paralleled at

    the SSP to reduce voltage drop in OHE. The sub-sectors are further divided into

    elementary sections by the use of manually operated isolators.

    Page No : 5

  • 8/8/2019 Scada Hardware Manual

    6/99

    meritHARDWARE MANUAL

    At TSS, SP and SSP, equipment like power transformers, circuit breakers, interrupters,

    single and double pole isolators, potential and current transformers, lightning arrestors, LT

    supply transformers etc., are installed in a fenced enclosure which is locked up. A

    masonry building is provided for housing the control panels, SCADA equipment, batteryand battery chargers, telephones and others.

    All traction substations are manned and switching stations are normally unmanned. The

    devices that are controlled from RCC through the SCADA equipment are circuit breakers,

    interrupters and transformer tap changers. The tap changer of the transformer, circuit

    breakers and interrupters can also be operated locally at the TSS, SP and SSP as the

    case may be.

    At the TSS, a local / remote changeover switch is provided on the control panel, as well as

    in the mechanism box of the circuit breaker, interrupter and motor operated isolators. No

    control panel exists for the interrupters at the SP and SSP and therefore the local / remote

    changeover switch is provided on the mechanism box of the interrupter.

    Page No : 6

  • 8/8/2019 Scada Hardware Manual

    7/99

    meritHARDWARE MANUAL

    CHAPTER 3

    3.0 OVERVIEW OF THE SCADA SYSTEM

    The SCADA system is designed to monitor the status and control of the 25KV electrified

    traction system. It is a fully integrated hardware and software system with a central control

    to monitor and control the field devices located at remote sites.

    The SCADA system can be classified into two broad categories:

    1. Remote Control Centre (RCC)

    2. Remote Terminal Unit (RTU)

    3.1 Remote Control Centre

    RCC is designed for monitoring different types of data like catenary indication, device statusand telemetry from various control stations. It also controls the field equipment like circuit

    breakers, bridging interrupters, transformer tap position changing etc., RCC stores the

    data regarding alarms, events, and telemetry to help the user to analyse the status of the

    overhead equipment and switching stations. This data can be used for maintenance

    purposes also. For example, RCC helps the user to easily identify the fault in OHE located

    in various sections, for immediate rectification.

    RCC consists of the following equipment:

    a) Main and standby Computerb) Operator Workstation computer

    c) Communication Processors with Modems

    d) Printer and Print Sharer Switch

    e) Modem

    f)UPS

    g) Battery

    3.2 Location of RCC equipment

    These equipments are located in Traction Power Control (TPC) room. The UPS and

    batteries are located in the UPS room and batteries room respectively. Main and Standby

    Computers, Communication Processors, Modems Workstation Computers and Printers

    are installed in the TPC Room. Supervisory console is installed at CTPC Room.

    Page No : 7

  • 8/8/2019 Scada Hardware Manual

    8/99

    meritHARDWARE MANUAL

    System configuration

    Page No : 8

  • 8/8/2019 Scada Hardware Manual

    9/99

    meritHARDWARE MANUAL

    3.3 Remote Terminal Unit (RTU) DESIGN AND MANUFACTURE BY M/S SANMAR

    RTU is designed to control and monitor field equipment. It accepts digital and analog input

    signals from the remote field equipment. It receives the control commands from the RCC.

    RTU can be divided into the following four parts:

    a) Logic Chassis

    b) Interface Unit

    c) Energy Meter

    d) Modem

    RTU accepts digital and analog input signals from the remote locations (TSS/SP/SSP) and

    receives the control command from the RCC to perform the following tasks :

    * Status input monitoring and change of status

    * Control output operation

    * Analog input monitoring

    * Communication with RCC

    RTU is designed to be flexible, modular and reliable making it easy to maintain and expand.

    A highly integrated microprocessor based system, coupled with firmware programming

    allows the RTU to perform sophisticated control and data acquisition functions.

    RTU system can be configured for a wide variety of I/O mix, which can be configured and

    expanded as required in the field. The configuration of an RTU is stored in non-volatile

    memory and may be edited or expanded without hardware changes.

    The RTU provides the following basic data acquisition functions:

    * Data acquisition for status input and analog input

    * Control outputs

    * RTU / Master station communications

    Implementation of the RTU capabilities is a combination of hardware logic and firmware

    logic that is stored in Read Only Memory (ROM). This provides a convenient means to

    alter and / or extend the capabilities of the RTU without significant hardware modification.

    Page No : 9

  • 8/8/2019 Scada Hardware Manual

    10/99

    meritHARDWARE MANUAL

    Each TSS RTU will support,

    * up to ninety six (96 ) Digital Input points

    * up to Fourty Eight (48 ) Digital Output Points

    * up to sixty four (8 ) analog input Points

    Page No : 10

  • 8/8/2019 Scada Hardware Manual

    11/99

    meritHARDWARE MANUAL

    CHAPTER 4

    4.0 FUNCTIONAL DESCRIPTION OF SCADA SYSTEM

    4.1 General

    The SCADA System, from RCC enables the Traction Power Controller (TPC) to control the

    25 KV traction power supply to OHE. It also monitors and operates various equipments at

    traction sub stations located enroute.

    The SCADA System for Traction Power Control consists of two major parts:

    a) Main and Standby Computers, Work station computers, Communication processors

    are connected in the LAN set up and Powered through UPS with battery back up at

    RCC

    b) Remote Terminal Units (RTU) for acquisition of field parameters from the unmanned

    control stations along the traction network.

    The RCC and RTUs are connected in Wide Area Network (WAN).

    The RCC Computers communicate with each RTU in a predefined sequence over the WAN

    to acquire information regarding;

    * Status of CB, interrupter, relays etc.

    * Alarm condition in the controlled station

    Measurand values

    4.2 Remote Control Centre

    The Main and Standby Computers are Server Grade Pentium IV with 15" color monitor.The Main computer interacts between the Communication processor and Workstation

    computers. It collects the formatted RTU information from Communication processor and

    sends the processed information to the Operating Workstation (OWS) computers, which

    enables the user to understand the field conditions.

    The Main computer also responds to the requests of the OWS computer, which receives

    commands from Traction power controller. Then, this information will be formatted and

    sent to the communication processor.

    The Main computer also updates available information with the slave computer, which

    should have the same information. Whenever the Main computer fails, then the Slave will

    become Main with updated information.

    The Communication Processors (CP) are Server Grade Pentium IV Computers.

    The Workstation Computers are Server Grade Pentium IIV with 21" color monitor

    Page No : 11

  • 8/8/2019 Scada Hardware Manual

    12/99

    meritHARDWARE MANUAL

    4.3 Remote Terminal Unit (RTU)

    RTU accepts digital and analog input signals, from the remote locations, TSS, SP and SSP.

    It receives the control signals from the RCC. It performs the following tasks:

    * Input status monitoring and recording the change of status

    * Control output operation

    * Analog input monitoring

    * Communication with RCC

    RTU consists of the following five parts, namely (not shown in the block diagram),

    * Power Supply Unit

    * Logic Chassis

    * Interface Unit

    * Modem

    * Termination Section

    Power Supply unit Consists of two Parts, one for main 24V dc supply and the other is

    (5v, 12v, -12v) for Modem and Interface card reference supply.

    The Logic Chassis is the main part of RTU, and is based on microprocessor. It is used to

    control and process all field signals. Each Logic Chassis supports 96 digital input, 48

    digital output signals, 8 analog input signals.

    The Interface Unit receives and controls the field signal devices. Energy Meter that is part

    of the Interface Unit is used to convert the field analog signals like voltage and current.

    Modem is used to convert the digital information to analog information suitable to for four

    wire based communication cable and vice-versa in the FSK & PSK mode.

    Termination Section is used to interconnect the field cables and RTU internal cables to

    perform the control and supervisory operation at the field.

    CHAPTER - 5

    Page No : 12

  • 8/8/2019 Scada Hardware Manual

    13/99

    meritHARDWARE MANUAL

    5.0 TECHNICAL DESCRIPTION OF REMOTE TERMINAL UNIT

    5.1 GENERAL

    The Remote Terminal Unit (RTU) acts as the common interface between the field devices

    and the Remote Control Centre of the system. The Remote Terminal Unit is designed

    to be flexible, modular and reliable, making it easy to maintain and easy to expand. It is

    highly integrated microprocessor based logic system, coupled with firmware

    programming, which allows the Remote Terminal Unit to perform sophisticated control

    and data acquisition functions.

    RTU accepts digital and analog input signals from the Remote locations (TSS / SP / SSP)

    and receives the Control command from the RCC to perform the following tasks:

    * Status input monitoring and change of status

    * Control Output operation

    * Analog Input monitoring

    * Communication with RCC

    5.2 RTU AT TRACTION SUB-STATION - TSS

    This RTU is designed for the following capacity:

    * 24 Telecommands

    * 48 Telesignals

    * 06 Telemetries

    The term Tele command is used in railways to give output and sense the status feedback

    for the particular device. Generally each Telecommand represents two digital outputs

    and corresponding two digital inputs.

    Page No : 13

  • 8/8/2019 Scada Hardware Manual

    14/99

    meritHARDWARE MANUAL

    RTU Block Diagram

    The following are the Telecommands available in the TSS RTU:

    1. 132 KV Circuit Breakers - 02

    Page No : 14

  • 8/8/2019 Scada Hardware Manual

    15/99

    meritHARDWARE MANUAL

    2. 25 KV Circuit Breakers - 05

    3. 25 KV Interrupters - 05

    4. Auto Re-closure - 02

    5. Tr. Tap Changer - 026. Interlock release - 01

    The scheme of operating the sl.no.1, 2 & 3 is shown in the figure. This requires close and

    open operations from the RTU and monitoring the status.

    Auto reclosure is the facility available in the field. TSS control panel to close the feeder CB

    automatically once whenever the CB trips and the scheme will become locked out

    condition. The RTU is to sense the locked out signal and command is to be given to

    release / reset the lock out.

    Transformer, which is stepping down 132 KV to 30 KV, is having six steps of tapping

    position. This TAP POSITION may be raised or lowered by giving RAISE or LOWER

    commands and status of TAP POSITION (any one out of six) is to be monitored.

    The following are the Telesignals to be sensed at TSS:

    TYPE I Telesignals

    * Transformer alarm - 2 nos

    * Transformer fault - 2 nos

    * Transformer Tap position - 12 nos

    * 110V DC Fail for Tr. Trip - 2 nos

    * 110V DC Fail for Tr. Alarm - 1 no

    * W.P.C / D.P.R / O.C.R relay (FCB I) - 3 nos

    * W.P.C / D.P.R / O.C.R relay (FCB II) - 3 nos

    Using 110V DC from the field senses the above alarms.

    Page No : 15

  • 8/8/2019 Scada Hardware Manual

    16/99

    meritHARDWARE MANUAL

    Block diagram of tss

    Page No : 16

  • 8/8/2019 Scada Hardware Manual

    17/99

    meritHARDWARE MANUAL

    General scheme of TSS wiring

    Page No : 17

  • 8/8/2019 Scada Hardware Manual

    18/99

    meritHARDWARE MANUAL

    Tss wiring 2 of 2

    Page No : 18

  • 8/8/2019 Scada Hardware Manual

    19/99

    meritHARDWARE MANUAL

    G.A DIAGRAM OF TSS

    TYPE II Telesignals

    * 240V AC failure / PSU on DC - 1 no

    * 25 KV feeder PT Fuse fail - 2 no

    * Tr. Line Pt Fuse fail - 1 no

    * 25 KV Shunt Cap. PT fuse fail - 1 no

    In the above alarms are sensed by using availability of 240V AC and 110V AC from the

    field.

    TYPE III Telesignals

    * 110V DC Low - 1 no

    Page No : 19

  • 8/8/2019 Scada Hardware Manual

    20/99

    meritHARDWARE MANUAL

    In the above alarms are sensed by using availability of 110V DC from field batteries.

    TYPE IV Telesignals

    * Catenary indication - 4 nos.

    In the above alarms are sensed by the availability of 120V AC from PTs connected to the

    Overhead equipment.

    The term Telemetry is used in railways to measure the current, voltage and Maximum

    demand from the field. Each Telemetry will have one analog input from the field.

    Voltage

    Current

    Maximum demand

    Voltage is measured from the 25 KV / 110 V Pts and Voltage changeover scheme connects

    the higher side of the PT voltage to the Transducer.

    Current is measured from the CTs whose ratings are given below

    The Accuracy of the Voltage, Current, PF and MD is Class A Type (ie, 0.5%).

    Dead Band : 0 to 255 ( 1 byte)

    Resolution : 10 Bit

    Normal value : 1000 Units.

    Value of the LSB bit : 10 mv

    (Resolution )

    For 25 KV side

    Primary side - Secondary side

    1000A or 500A - 5A

    1500A or 750A - 5A

    For 132 KV side

    Primary side - Secondary side

    100A or 200A - 5A

    The secondary side will be connected to the Energy Meter through Shorting terminals.

    Page No : 20

  • 8/8/2019 Scada Hardware Manual

    21/99

    meritHARDWARE MANUAL

    Maximum demand is the parameter calculated from the measured Voltage and Current.

    This will be done in the software at the Remote Control Center.

    5.3 RTU AT SECTIONING AND PARALLELING POST - SP

    The following is the design capacity of SP RTU :

    Telecommands - 8 nos

    Telesignals - 12 nos

    Telemetry - 4 nos

    The following are the Telecommands available in the SP RTU

    25 KV interrupter - 4 nos

    Spare - 4 nos

    In general ,SP will have two nos of parallel interrupters which could be operated by issuing

    open and close commands and another two nos of bridging interrupters which have to

    meet the following Under voltage trip conditions :

    Under-voltage Tripping

    Under voltage tripping is the facility provided for bridging interrupters of SP. The two

    different phases of 25 KV voltage are fed from the adjacent TSS to the Bridginginterrupter and it should not be closed when both sides of the voltages are high.

    Whenever one side TSS fails, then RTU is able to close the Bridging interrupters to

    extend the feed from one side to another side. After extending the feed, if both side

    voltages are going low, then RTU should trip the bridging interrupters.

    The following are the Telesignals to be sensed at SP :

    TYPE I Telesignals

    * Spare - 4 nos

    The above alarms are sensed by the availability of 110V DC from the field.

    TYPE II Telesignals

    * 240V AC failure / PSU on DC - 1 no

    * Spare - 1 no

    Page No : 21

  • 8/8/2019 Scada Hardware Manual

    22/99

    meritHARDWARE MANUAL

    In the above alarms are sensed by the availability of 240V AC.

    TYPE III Telesignals

    * 110V DC Low - 1 no

    * Spare - 1 no

    In the above alarms are sensed by the availability of 110V DC from field batteries.

    TYPE IV Telesignals

    * Catenary Indication - 4 nos

    (Inclusive of Under voltage tripping facility)

    In the above alarms are sensed by the availability of 120V AC from PTs connected to the

    Overhead equipment.

    Block diagram of sp & ssp

    Page No : 22

  • 8/8/2019 Scada Hardware Manual

    23/99

    meritHARDWARE MANUAL

    General scheme of sp/ssp wiring

    Page No : 23

  • 8/8/2019 Scada Hardware Manual

    24/99

    meritHARDWARE MANUAL

    General scheme of sp / ssp wiring 2 of 2

    Page No : 24

  • 8/8/2019 Scada Hardware Manual

    25/99

    meritHARDWARE MANUAL

    G.A DIAGRAM OF SP /SSP

    Page No : 25

  • 8/8/2019 Scada Hardware Manual

    26/99

    meritHARDWARE MANUAL

    TELEMETRY

    In SP, voltage is measured from the up and down line 30 KV / 120V PTs where thesecondary voltage of the PT is connected to the Energy Meter.

    5.4 RTU AT SUB-SECTIONING AND PARALLELING POST - SSP

    The following is the design capacity of SSP RTU :

    Telecommands - 8 nos

    Telesignals - 12 nos

    Telemeter - 4 nos *

    ( * The above 4no Telemeters are spare. Hence Transducers will not be provided in the

    RTU)

    The following are the Telecommands available in the SSP RTU :

    25 KV interrupter - 3 nos

    Spare - 5 nos

    The following are the Telesignals are to be sensed at SSP :

    TYPE I Telesignals

    * Spare - 8 nos

    The above alarms are sensed by using availability of 110V DC from the field.

    TYPE II Telesignals

    * 240V AC failure / PSU on DC - 1 no

    * Spare - 1 no

    The above alarms are sensed by using availability of 240V AC.

    TYPE III Telesignals

    Page No : 26

  • 8/8/2019 Scada Hardware Manual

    27/99

    meritHARDWARE MANUAL

    * 110V DC Low - 1 no

    * Spare - 1 no

    The above alarms are sensed by using availability of 110V DC from the field batteries.

    TYPE IV Telesignals ( Subject to the requirement )

    * Catenary indication - 4 nos.

    The above alarms are sensed by using availability of 120V AC from PTs connected to the

    overhead equipment.

    5.5 Functional Description of Remote Terminal Unit

    Remote Terminal Unit is comprised of the following modular blocks

    a) Logic Chassis

    b) Interface Unit

    c) Modem

    d) Power Supply Unit

    e) Transducer

    f) Contactors / Relays

    g) Terminal Block

    Page No : 27

  • 8/8/2019 Scada Hardware Manual

    28/99

    meritHARDWARE MANUAL

    Signal flow diagram

    5.5.1.0 Logic Chassis

    A highly integrated microprocessor based logic system, coupled with firmware

    programming, allows Logic Chassis to perform sophisticated control and data acquisition

    functions. The Logic Chassis can be configured for a wide variety of I/O mix which can

    be configured and expanded as required in the field. The configuration of an Logic

    Chassis is stored in non-volatile memory and may be edited or expanded without

    hardware changes

    Page No : 28

  • 8/8/2019 Scada Hardware Manual

    29/99

  • 8/8/2019 Scada Hardware Manual

    30/99

    meritHARDWARE MANUAL

    Block diagram of logic chasis

    5.5.1.1 CPU Module

    CPU Module acts as the backbone to Logic Chassis. It is based on the microcontroller

    Technology Philips micro-controller 80C669. The 80C669 is a highly integrated 16 bit

    device with 33MHz speed which implements the following on-chip features

    * Serial communication:

    Page No : 30

  • 8/8/2019 Scada Hardware Manual

    31/99

    meritHARDWARE MANUAL

    In build in CPU and can support up to two serial ports on the

    designed baud rate

    * Number of DI, DO and AI can handle by a single CPU:

    Digital Input and Digital Output: Maximum 1536

    Analog input: Maximum 8

    * Up to 16 Mbytes linear address space

    * Five programmable chip selects

    * Maximum of 56 interrupts

    Block diagram of CPU

    Page No : 31

  • 8/8/2019 Scada Hardware Manual

    32/99

    meritHARDWARE MANUAL

    Functional block diagram of CPU

    These features combined with 33 MHz processor clock to perform many sophisticated

    Page No : 32

  • 8/8/2019 Scada Hardware Manual

    33/99

    meritHARDWARE MANUAL

    data acquisition and control functions as software tasks. It contains the following function

    blocks

    * Watchdog timer

    * Interrupt Logic

    * Address Latch

    * Modules Select Logic

    * Module Address Data Bus

    * Flash EPROM and RAM

    * Dip Switches to set the address of Node

    LED Indications

    To display the operating status, the CPU module have four LED indications

    INDICATION FUNCTION

    PWR Supply Voltage Monitor

    RUN CPU status and error display

    TXI TX Status OF COM1

    RXI RX Status OF COM1

    TX2 TX Status OF COM2

    RX2 RX Status OF COM2

    Red ON Supply Voltage < 17V dc and Low

    Battery

    Details of RUN LED

    LED STATUS MEANING

    OFF Controller stopped / Fault

    Page No : 33

  • 8/8/2019 Scada Hardware Manual

    34/99

    meritHARDWARE MANUAL

    Green blinking Controller Running

    5.5.1.1.1 Watchdog Timer

    The inbuilt function of the Micro controller monitors three vital conditions for the

    Microcontroller, power supply and external reset.

    First, a precision temperature compensated reference and comparator circuit is used to

    monitor the status of +5V (VCC) power supply. When VCC falls below 4.65 V, the Chip

    forces reset to the active state. When VCC returns to normal, i.e. greater than 4.65V,

    then the reset signal is kept active for a minimum of 250ms to allow the power supply

    and processor to stabilize. It has also additional feature of write protection for CMOSRAM or EPROM.

    The watchdog timer continuously monitors the process of Microprocessor. The Watchdog

    accomplishes this by activating the reset line, if the strobe input is not driven low before

    the chips internal 500 ms timer has timed out. The strobe input is derived from the

    microprocessor timer / counter output (TCO) which must be set from the software. If the

    software does not reset the timer counter within the allotted time, a strobe pulse is not

    generated and the reset line is forced to the active state. The reset is held momentarily

    and then released, which causes the RTU to reinitialize and start execution from the

    restart vector.

    5.5.1.1.2 Interrupt Logic

    The Logic Chassis is a real time device and therefore fully utilizes interrupts. There are two

    external hardware sources from which an interrupt can originate. The first is initiated

    when a change occurs at a status input. Status input modules contain the logic which

    generate a signal any time their input values are changed, these signals are then sent toCPU and are input at data latches.

    It should be noted that only odd numbered COS lines are input to data latch this is

    because the even numbered modules pass their interrupts along to the odd numbered

    Page No : 34

  • 8/8/2019 Scada Hardware Manual

    35/99

    meritHARDWARE MANUAL

    modules using the dedicated COS and COMPEN lines on the MOD bus and the odds in

    turn pass the COS to data latch.

    An active COS signal at the inputs to data latch acts to generate an active state at its output

    and in turn at the 80C167C interrupt input. When the processor receives an interrupt, it

    immediately enters service routine, which reads latch to determine which pair of Status

    inputs signals (COS), caused the interrupt. Once the pair has been determined, the

    processor reads the indicated module pair to determine the specific input or inputs, which

    have changed.

    5.5.1.1.3 Address Latch

    The 89C669 utilizes a multiplexed Address data bus; therefore it is necessary to de

    multiplex or latch the address information. The Address latch is comprised of D type

    latches whose outputs are always enabled and clocked by the ALE (Address Latch

    Enable) signal

    5.5.1.1.6 Memory

    The Memory is divided into 3 types

    Processor RAM

    External RAM

    Processor RAM of 2KB is made available to the processor module to store the non-

    alterable storage of program code. The ram may be accessed through 16bit word or Byte

    segments.

    Flash RAM (128 KB) is used by the RTU to store configuration variables and system

    data, which require memory to be non-volatile, yet alterable without hardware changes or

    replacement.

    RAM (256KB) is used as a general-purpose area for the microcontroller to store data,

    variables and operating information that are temporary in nature. Information stored in

    this section area is volatile and will be lost in the event that power is removed from the

    Logic Chassis. These devices also word are byte accessed using the select logic

    provided by the processor control lines.

    5.5.1.2.0 Digital output Module (DOM)

    The Control output system for the RTU comprised of two basic types of components,

    Page No : 35

  • 8/8/2019 Scada Hardware Manual

    36/99

    meritHARDWARE MANUAL

    control function modules (DOM) that are added in the Din rail and attached with the CPU

    module to interface with the field equipments through potential free contactors. The

    Digital output module (DOM) contains the logic and CPU interfaces hardware.

    Each Digital output Module (DOT) has sixteen outputs and is designed to drive the

    Contactors of 10A rate, which in turn activate the field equipments. These modules could

    be plugged into the Din rail as and when required.

    5.5.1.2.1 Functional Description of DOM

    The Digital output function module (DOM) is comprised of group of data latches, which

    act together write-read-execute sequence logic to provide secure control operations. All

    control output operations are initiated and monitored by CPU module. A control operation

    begins when CPU places a bit pattern and simultaneously strobe the new value into the

    data latch of the Digital output module. Next the CPU reads back the data, verifies it by

    strobing the data and reads back to latch. If the read data and already sent data are

    same then the CPU issues an execute pulse to drive the Each module provides 8 digital

    outputs at the rate of 24Vdc / 0.1 A and the Module requires the power supply is from

    +18V to +30V dc with the power consumption of 200mW. Respective LEDs of Orange

    color indicates present state of output signal. The Output from the Opto - isolator

    operate the contactors.

    Page No : 36

  • 8/8/2019 Scada Hardware Manual

    37/99

    meritHARDWARE MANUAL

    Connection details of dot

    Page No : 37

  • 8/8/2019 Scada Hardware Manual

    38/99

    meritHARDWARE MANUAL

    Block Diagram of DOT

    5.5.1.2.2 SBO ( Select Before Operation) Operation and Description :

    1. Request: Selection Command

    Whenever activation is enabled in Select Command packet, the selected digital

    output point read by the CPU and simultaneously strobe the new data output point

    into the data latch of the Digital output module.

    2. Response: Select Confirmation

    Once receiving the Select Command from RCC, the CPU module reads back the

    data from data latch of DOT and compare the bit pattern of the digital output value. If

    Page No : 38

  • 8/8/2019 Scada Hardware Manual

    39/99

    meritHARDWARE MANUAL

    bit pattern are matching and CPU sends the Selection Confirmation to RCC and If

    RCC decides to cancel the selection, then the Select command is sent with a

    deactivation and the CPU will disable the data latch value.

    3. Request: Execute Command

    Once RCC gets the Selection confirmation then it transmits the command message

    with Execution packet. After getting the execution command, the CPU enables the

    output channel in DOT that was already selected by the selection command. The

    digital output channel enable time duration depend upon qualifier bit (10 ms to 2.55

    Seconds (in single command record. The default enable time is one second.

    4. Request: Execute Confirmation

    Once the CPU executes the command and enable the selected digital output

    channel, then the RTU responds with an activation termination to RCC to indicate

    that the command has been successfully issued.

    Page No : 39

  • 8/8/2019 Scada Hardware Manual

    40/99

    meritHARDWARE MANUAL

    Connection details of DIT

    BLOCK DIAGRAM OF DIT

    Page No : 40

  • 8/8/2019 Scada Hardware Manual

    41/99

    meritHARDWARE MANUAL

    5.5.1.3.0 Digital Input Module (DIM)

    Each Digital input module has eight inputs and is designed to provide input points of

    status information to the CPU module from the Input interface cards.

    5.5.1.3.1 Interface Connection and Function Description

    The Digital input Module (DIM) accepts the inputs from the field (110v DC) , the 16

    Inputs and the which are multiplexed and Transferred to CPU. All the four inputs areelectrically isolated from the logic circuitry of the module and connected through terminal

    block for input with reference to common 0V connection.

    Basic circuit of Digital input module is shown. It describes the process of the input signal

    with isolation and the LEDs connected to show the status of each signal. The modules

    are designed for signal voltages up to 110V dc and used to collect the binary control

    signals from the system and transmit them to the CPU. It may be easily exchanged in the

    working condition without disconnecting the individual wire. Individual Green LEDs are

    used to show the status of the system and the maximum power consumption is 100mW.

    5.5.1.4.0 Analog Input module (AIT) POWER METER

    The system comprises of a single 8 channel Analog input module with necessary Inbuilt

    Page No : 41

  • 8/8/2019 Scada Hardware Manual

    42/99

    meritHARDWARE MANUAL

    Transducers. The Analog input module fixed in the Din rail and the system uses

    multiplexing method which selects a specific termination channel read by the A to D

    converter. The channels are read sequentially starting with channel 1 and proceeding to

    the last channel configured in the system.

    CONNECTION DETAILS OF AIT

    Page No : 42

  • 8/8/2019 Scada Hardware Manual

    43/99

    meritHARDWARE MANUAL

    BLOCK DIAGRAM OF AIT

    Page No : 43

  • 8/8/2019 Scada Hardware Manual

    44/99

    meritHARDWARE MANUAL

    The Analog input module accepts PT Voltage and Feeder Current and converts them to

    proportional digital values. The module contains A to D converter, reference sources,

    signal conditioning and multiplexing hardware required to select the correct signals from

    the field. In this module we have the features to select the type of input is voltage orcurrent is based on the DIPswitch present at the backside of the module.

    5.5.1.4.1 Functional Description of Power Meter

    The Analog input values are received from the field in the form of PT voltage and Feeder

    current. All the input channels are led to a common multiplexer and are galvanically

    isolated. The time-multiplexed voltage is fed to the instrumentation amplifier where the

    signal is converted from a differential mode to single ended signal. Analog source selectswitch is used to select between the +reference, - reference, ground or multiplexed field

    inputs. The output of the power meter is been transmitted to the CPU module through

    serial data bus.

    .5.2.0 INTERFACE CARD ENCLOSURE

    Interface card enclosure consists CIC INTERFACE to Monitor the Status Of

    Catenary Input Signals

    5.5.2.4 Catnery Interface Module ( CIC )

    Page No : 44

  • 8/8/2019 Scada Hardware Manual

    45/99

    meritHARDWARE MANUAL

    The catenary indication, which is available in the range of 0-120V AC, from the field (25KV /

    100V AC PT) is sensed using this circuit. This catenary indication is sensed with various

    ranges to eliminate the effect of induced voltage from the adjacent OHE when the

    sensing OHE is dead. The comparator circuits have been provided with potentiometerto adjust the drop-off and pickup of the relay as described below:

    The 0-100V AC from PT is fed as an input to the Transformer. An MOV is provided across

    this input to act as a surge arrestor. The stepped down output from the Transformer is

    rectified through bridge rectifier and filtered of transients with capacitance filter C. The

    interface supply (12V DC) is connected to this circuit for functioning of ICs and Relays

    and same voltage is adjusted for comparator input reference voltage.

    Two numbers of 8 way dip switches SW1 and SW2 are provided for pick up (high level) and

    drop off (low level) voltage for catenary indication. The respective

    setting range will be as follows :

    Drop off : 48% to 70% (12 kV to 17.5 kV = 48V to 70V)

    Pickup : 60% to 80% (15 kV to 20 kV = 60V to 80V)

    The Dip switch settings will be in steps of 1 kV.

    TYPE -IV

    Page No : 45

  • 8/8/2019 Scada Hardware Manual

    46/99

    meritHARDWARE MANUAL

    COMPONENT LAYOUT

    Page No : 46

  • 8/8/2019 Scada Hardware Manual

    47/99

    meritHARDWARE MANUAL

    The DC signal corresponding to AC ON input voltage would be stepped down using

    suitable resistor path selected by DIP switch. This will be fed to input of the pick up

    comparator and the trimpot is to be adjusted to make output high. Then the AC OFF

    input voltage is to be set using suitable resistor path selected by DIP switch. This will be

    fed to the input of Drop Off comparator and the respective trimpot is to be adjusted to

    make output high.

    Then the AC OFF input voltage is to be set using suitable resistor path selected by DIP

    switch. This will be fed to the input of Drop Off comparator and the respective trim pot is

    to be adjusted to make the output high.

    Both of these comparator outputs ( U1-U3 ) are to be connected to input of the AND gate.

    This energizes the output relay through driver transistor. The field signal input is

    connected through 32 pin Half Euro connector. The output from this card goes to Digital

    Input Function Module of Logic Chassis through Euro connector.

    5.5.3.0 Modem

    The word MODEM is an acronym for MOdulator and DEModulator. Modem is used to

    transfer data between two computers located at a distant place by using a normal

    telephone line.

    Page No : 47

  • 8/8/2019 Scada Hardware Manual

    48/99

    meritHARDWARE MANUAL

    5.5.3.1 Overview of SCADA Modem

    The basic configuration consists of one master modem and one or slave modems

    connected. The transmit output of master modem is connected to transmit output of all

    slave modems. The receive input of master modem is connected to transmit output of all

    slave modems. Multi-drop Modem configuration can be either 2 wire or 4 wire

    configuration. Our Railway SCADA Multi-drop modem configuration is 4-wire

    configuration The mode of communication between master and slave modem is always

    half duplex mode. At any given time either master modem will be transmitting data to

    slave modem will be transmitting data to the master modem.

    5.5.4.0 POWER SUPPLY UNIT

    5.5.4.1 Principle of Operation

    The RTU Power supply consists of two parts , one for main 24 v dc Supply and the other

    is (5v, 12v,-12v) for Modem and interface card reference supply.

    Supervisory Module

    The function of this card is to monitor the presence of the input AC voltage and change

    over to battery whenever the input AC voltage crosses beyond the specified limits which

    is less than 155 V or greater than 290 V.

    The Supervisory module monitors the input voltage to check the High/Low value.

    The relay circuitry is used to control the AC/DC Supply switch over.

    The DC LOW, and AC Fail Status also be provided by this module to Digital

    Input Module

    5.5.4.2 PROTECTION FEATURES

    5.5.4.2.1 Mains supervision : When AC Mains voltage is between 155V AC to 290V AC as

    specified in the RDSO document then AC Mains will be connected to the DC-DC

    Page No : 48

  • 8/8/2019 Scada Hardware Manual

    49/99

    meritHARDWARE MANUAL

    converter, otherwise 110V DC battery voltage will be connected.

    5.5.4.2.2 Battery supervision : When battery voltage is between 99V DC to 140V DC as

    specified in the RDSO document then Battery voltage will be connected to the DC-DC

    converter. Protection of electronics from surges and noises are taken care by using

    transient voltage suppressors and line filters. Transient voltage suppressor will prevent

    the abnormal rise of AC input voltage. Line filters will provide filtering of electrical noises

    of DC supply given to the SMPS.

    Page No : 49

  • 8/8/2019 Scada Hardware Manual

    50/99

    meritHARDWARE MANUAL

    Block diagram of Power supply

    PWER SUPPLY WIRING DIAGRAM

    Page No : 50

  • 8/8/2019 Scada Hardware Manual

    51/99

    meritHARDWARE MANUAL

    Block diagram of psu of LDA75f

    Page No : 51

  • 8/8/2019 Scada Hardware Manual

    52/99

    meritHARDWARE MANUAL

    component layout of LDA

    Page No : 52

  • 8/8/2019 Scada Hardware Manual

    53/99

    meritHARDWARE MANUAL

    Ckt of psu LDC 30F

    Page No : 53

  • 8/8/2019 Scada Hardware Manual

    54/99

    meritHARDWARE MANUAL

    component layout of lLDC 30f

    This power supply unit is to work with 240V AC from MAINS. If this voltage goes below

    155V AC, then the input will be cut off and it has to reach 175V AC to become normal. If

    the AC input goes above 290V AC, then it will be cut off. Whenever AC is cut off due to

    high or low level, then the 110V DC input voltage from Battery is to be connected. If this

    Page No : 54

  • 8/8/2019 Scada Hardware Manual

    55/99

    meritHARDWARE MANUAL

    voltage goes below 80V DC, then it has to reach 95V DC to become normal. If it goes to

    140V DC and above it will be cut off.

    5.5.4.3 Functional Description of LDA75FThe DC input voltage is provided through Molex connector at the line and neutral points.

    A 3Amps fuse isolates the power, which is filtered by spike noise suppression capacitor

    C11. A damper discharge resistance bleeder for this capacitor is formed by resistor

    network. The leakage and mutually inductive coupled input is fed to the rectifier bridge.

    The Negative output is AC Grounded to flame grounded before feeding through inrush

    limiting thermistor to tank capacitors. A LC filter combination will filter the rectified output

    to feed a steady current into primary of transformer.

    The primary winding of transformer are current switched by MOSFET TR31 at 140 KHz

    to generate an average input current of 3.3 Amps at 200v AC. Auxiliary winding pin

    provide for soft start control with capacitor. The PWM (Pulse Width Modulation) control

    has pulse modulated between primary winding of the transformer. The output terminals

    of the transformer operate a common cathode dual diode in the feed forward mode

    through inductances. The output is RC damped and LC filtered. Any over/under shoots

    are damped by bleeder resistor network. The output voltage is crowbar clamped with

    zener diode and optically coupled.

    The voltage control is affected by programmable IC, which has comparator resistors

    network for output setting. The Positive/Negative terminals of output are floating with

    respect to ground. The Output Voltage of LDA75F is +24 V DC (3.2 Amps).

    5.5.4.4 Functional Description of LDC30F

    The DC input voltage is provided through Molex connector at the line and neutral points.

    A 3Amps fuse isolates the power, which is filtered by spike noise suppression capacitorC11. A damper discharge resistance bleeder for this capacitor is formed by resistor

    network. The leakage and mutually inductive coupled input is fed to the rectifier bridge.

    The Negative output is AC Grounded to flame grounded before feeding through inrush

    limiting thermistor to tank capacitors. A LC filter combination will filter the rectified output

    to feed a steady current into primary of transformer.

    Page No : 55

  • 8/8/2019 Scada Hardware Manual

    56/99

    meritHARDWARE MANUAL

    The primary winding of transformer are current switched by MOSFET TR31 at 140 KHz

    to generate an average input current of 1.3 Amps at 200v AC. Auxiliary winding pin

    provide for soft start control with capacitor. The PWM (Pulse Width Modulation) controlhas pulse modulated between primary winding of the transformer. The output terminals

    of the transformer operate a common cathode dual diode in the feed forward mode

    through inductances. The output is RC damped and LC filtered. Any over/under shoots

    are damped by bleeder resistor network. The output voltage is crowbar clamped with

    zener diode and optically coupled.

    The voltage control is affected by programmable IC, which has comparator resistors

    network for output setting. The Positive/Negative terminals of output are floating withrespect to ground. The output Voltage of LDC30F is +5V (3.0 Amps), +12V(1.2Amps)

    and 12V(0.3 Amps).

    5.5.4.5 Over current Protection

    Over current protection circuit is built-in to be operated over 120% of the rated current.

    This function works to protect against short circuit and over current condition, which is less

    than 20 seconds, when cause of activation of over current protection is removed, theoutput will be automatically recovered.

    Page No : 56

  • 8/8/2019 Scada Hardware Manual

    57/99

    meritHARDWARE MANUAL

    Supervisory 1 OF 2

    Supervisory 2 OF 2

    Page No : 57

  • 8/8/2019 Scada Hardware Manual

    58/99

    meritHARDWARE MANUAL

    PCB LAYOUT OF SUPERVISORY

    5.5.4.6 Over Voltage Protection

    Over Voltage Protection is builtin and will be operated at 290 of the rated input Voltage.

    When this function operates, input should be shut off. Output Voltage will be recovered

    Page No : 58

  • 8/8/2019 Scada Hardware Manual

    59/99

    meritHARDWARE MANUAL

    whenever the input supply becomes Normal.

    5.5.4.7 Fold Back Characteristics

    INPUT Pick up Drop off

    A.C Input Voltage

    (High Range)

    270V AC 290V AC

    A.C Input Voltage

    (Lower range)

    155V AC 135V AC

    Hysterisis: 20 V AC for both Higher and Lower range.The output voltages are as follows:

    1. Logic Chassis

    +24 v DC with respect to GND

    2. Modem

    +12V DC

    -12V DC

    +5V DC with respect to GND

    3. Contactors

    24V DC with respect to GND

    4. Interface Cards

    +12V DC with respect to GND

    5.5.6.0 Contactors / Relays

    The Contactors are used to activate the field devices such as Circuit breakers, Interruptors,

    Transformer TAP positions and Autoreclosure lockouts. The rating of these contactors is

    as follows

    Make - C & S

    Page No : 59

  • 8/8/2019 Scada Hardware Manual

    60/99

    meritHARDWARE MANUAL

    Coil voltage - 24V DC

    Contactor rating - 10A

    No. Of contacts for CB / BM - 3 NO + I NC

    No. Of contacts for Auto reclosure - 2 NO + 2 NC

    These contactors are suitable for DIN rail mounting as well as screw mounting. DIN rail

    mounting offers ease of assembly in the panels.

    These are made of flame retardant thermoplastic material. These are very strong, compact

    and light in weight. Mounting space is saved due to its compact design.

    Enclosed contacts and shrouded terminals ensure protection against accidental touch. Due

    to modular design, replacement of coil is very easy without disturbing the power

    connections. Accessibility for change of coil is from the front. The terminals have self

    propelling washers for easy connections, bounce free contact system and high contact

    pressure makes the contactor suitable for high making and breaking currents.

    The Relays are used in the Interlocking circuit and under voltage circuit.

    Make : OEN / 4R Series

    Type : 4R Series

    No. of contacts : 3 Changeover

    Coil voltage : 24V DC

    Contact rating : 2A

    Page No : 60

  • 8/8/2019 Scada Hardware Manual

    61/99

    meritHARDWARE MANUAL

    Schematic for tele command

    Page No : 61

  • 8/8/2019 Scada Hardware Manual

    62/99

    meritHARDWARE MANUAL

    Schematic for hv cb tele command

    TAP POSITION

    Page No : 62

  • 8/8/2019 Scada Hardware Manual

    63/99

    meritHARDWARE MANUAL

    5.5.7.0 Terminal Block

    Terminal Block is used to interconnect the field cables and RTU internal cables to

    perform the control and supervisory operation at the field. Interconnection between RTU

    and field terminal block is done in the switching stations to collect the Status / Alarms and

    control the Field equipment. The RTU terminal block section is designed in such a way

    that separate terminal sections are arranged for Tele commands, Tele signals and

    Telemetry.

    Note : Please Refer Annexure I & II for Terminal Block Connection Details.

    5.6.0 DESCRIPTION OF TELEMETRY SYSTEM AT TSS

    5.6.1 Under-voltage Tripping of Bridging Interrupters

    Page No : 63

  • 8/8/2019 Scada Hardware Manual

    64/99

    meritHARDWARE MANUAL

    This scheme is applicable only under extended feed condition. The arrangement is such

    that the bridging interrupters at SP can be closed only when OHE is dead on one side of

    neutral section. The under voltage scheme becomes operative only after the bridging

    interrupter is closed. When the undervoltage scheme is in active condition and if OHEvoltage goes below the set level, then the bridging interrupter will be tripped by the under

    voltage circuit. The logic program is designed such that if both the catenaries are low as

    per the set value then the respective Bridging BM open command will be executed at

    RTU level.

    5.6.2 Scheme of Telemetry at SP

    The arrangement is such that a Power Meter is used to measure the voltage of either up

    line or down line. In case of failure of any one line, the Power Meter will be connected to

    the other line through the PT changeover circuitry. The changeover will be effective

    based on the settings on catenary indication circuit.

    5.6.3 Scheme of Catenary Indication at SP

    The arrangement is such that the catenary indication is available at the pick up voltage and

    will go off at the drop off voltage selected and set by the user.

    The pick up voltage selection range is available from 60% to 80% of PT voltage and drop off

    voltage is available from 50% to 70% of PT voltage. The pick up and drop off settings

    have been provided to take effect of induced voltage in adjacent OHE which otherwise

    may give false indication of OHE live, even after section has actually been de-energised.

    The arrangement of these settings programmed in the CPU card.

    Page No : 64

  • 8/8/2019 Scada Hardware Manual

    65/99

    meritHARDWARE MANUAL

    SCHEME OF TELEMETRY AT TSS

    5.6.4 Closing of Bridging Interrupter

    When OHE is dead on one side of SP, then the bridging interrupter can be closed. This is

    Page No : 65

  • 8/8/2019 Scada Hardware Manual

    66/99

    meritHARDWARE MANUAL

    achieved for BM1 as given below. One end to close command contactor (NT) coil is

    permanently connected with +24V and the other end is controlled by a command driven

    by a Digital output module. The respective output of the Digital output module is

    programmed to give command when any one of the catenary values becomes low whichis sensed from the respective Transducer connected to the Analog input module.

    5.6.5 Under voltage Tripping of Interrupter

    When under voltage circuit is in active condition, if OHE voltage becomes low below the set

    level due to any fault, then the bridging interrupter is to be tripped.

    To achieve this function, one end of the trip command contactor (FT) coil is connected +24V

    DC, and the other end is connected to the Digital output module. Whenever both theadjacent catenaries are going low then the respective Digital output channel will enable

    the FT coil to trip the Bridging BM.

    Note : The Software is designed such a way that the bridging interruptors can be

    closed only when the section on one side of neutral section is dead and the under

    voltage circuit become operative only after the bridging interrupter is closed.

    5.6.6 Sequence of operations of under voltage Tripping

    1. When OHE voltage is available on both sides of SP, then the close command should

    not be executed.

    2. When OHE is dead in any one side of the SP (i.e. PT1 or PT2), the operator will be able

    to close the bridging interrupter by energizing NT coil.

    3. When both the PT fails under the feed extended condition, then the respective Digital

    output module will initiate the command to trip the Bridging BM without Operators action.

    Page No : 66

  • 8/8/2019 Scada Hardware Manual

    67/99

    meritHARDWARE MANUAL

    Hardware Schematic

    Page No : 67

  • 8/8/2019 Scada Hardware Manual

    68/99

    meritHARDWARE MANUAL

    Hardware schematic

    5.6.7 Catenary Voltage Sensing at TSS

    The secondary of 25 KV / 100V PT is fed to the catenary indicator, under voltage

    tripping and telemetry circuit. This voltage is stepped down by the Transformer,

    rectified through a bridge rectifier and filtered of transients with capacitance

    filter C. An MOV (Metal Oxide varistor) is provided across the input to act as

    surge arrestor.

    For catenary indication, 2 nos of 8 way dip switches SW1 and SW2 are provided for

    Page No : 68

  • 8/8/2019 Scada Hardware Manual

    69/99

    meritHARDWARE MANUAL

    selecting pick-up (high level) and drop off (low level) voltage. The respective setting

    range will be as follows :

    Drop off : 48% to 70% (12 KV to 17.5 KV = 48V to 70V)

    Pick up : 60% to 80% (15 KV to 20 KV = 60V to 80V)

    The Dip switch settings will be in steps of 1 KV.

    WARNING

    IT IS TO BE ENSURED THAT THE DROP OFF VOLTAGE SETTING IS ALWAYS

    LESSER THAN PICK-UP VOLTAGE SETTING FOR PROPER OPERATION OF

    SCHEME

    5.6.8 Scheme of Telemetry at TSS

    The arrangement is such that a POWER METER is used to measure the voltage of either

    up line or down line. In case of failure of any one line, the Transducer will be connected

    to the other line through the PT changeover circuitry. The changeover will be effective

    based on the settings on catenary indication circuit.

    5.6.9 Auto Re-Closing scheme at TSS

    In case of tripping of the feeder circuit breaker on fault at TSS, a single shot auto-reclosing

    scheme re-closes that breaker automatically only once after a pre-set time delay. In the

    event of any fault on OHE presisting the feeder circiut breaker trips again and and

    autoreclosing scheme gets automatically locked out to prevent reclosing of the breaker a

    second time. The locked out condition is telesignalled to RCC. The operator releases the

    locked-out condition when a telecommand is initiated through the keyboard console.

    5.6.10 Field Wiring

    Page No : 69

  • 8/8/2019 Scada Hardware Manual

    70/99

    meritHARDWARE MANUAL

    Interconnection between RTU and field terminal block is done in the switching stations to

    collect the Status / Alarms and control the Field equipment. The RTU terminal block

    section is designed in such a way that separates terminal sections are arranged for Tele

    commands, Tele signals and Telemetry.

    Field termination cables are used with different thickness to meet the current carrying

    capacity of the field equipment. Different color cables are used for easy identification of

    the signals in the field. Cable terminations are numbered using the ferrules for the

    traceability of the signals. Signal cables, Power cables and Communication cables are

    routed in different PVC pipes from RTU to field terminal block.

    Auto reclosing

    CHAPTER 6

    Page No : 70

  • 8/8/2019 Scada Hardware Manual

    71/99

    meritHARDWARE MANUAL

    6.0 MAINTENANCE OF SCADA SYSTEM

    6.1 Maintenance philosophy

    In the event of failure of the system, it is recommended to identify the faulty printed circuit

    card and replace the card with a working card. The recommendation is based on the

    complexity of trouble shooting and technology used for mounting of component as

    explained below:

    1. The system is based on the microcontroller technology where almost every

    component has a very high level of integration. The components perform multiple

    functions, as the level of integration is high.

    Therefore, the component has to be tested for all its intended functions to

    conclude whether it is faulty. The testing engineer should know each and every

    function of the component under test and the testing methods. Hence, component

    level troubleshooting needs a specialist with special tools.

    2. The components are soldered to the Printed circuit card with surface

    mounting technology. Removal of faulty components from the card and soldering of

    a new component on to it also needs a skilled person with special and expensive

    tools. These tools are generally used only in a production centre.

    Maintenance of SCADA system may be classified into two as preventive and corrective

    maintenance. Preventive maintenance is to reduce the number of failures and corrective

    maintenance to put back the failed system into operation.

    6.2 RTU Power Supply Unit

    1. Switch off the RTU and check the Power Supply Gently for any loose contact if so tight the same.

    2. Switch On Both AC & DC Supply. Check AC to DC Changeover during the violation of set limit for

    input voltage. Also Check DC to AC Changeover and observe the AC Fail & DC low indication onRTU.

    3. During Changeover observe any disturbance in CPU Module.

    4. To Measure the Ripple Voltage in D.C

    Page No : 71

  • 8/8/2019 Scada Hardware Manual

    72/99

    meritHARDWARE MANUAL

    5. Measure the Output Voltage of RTU power Supply of MCB and ensure that the deviation is with in

    the limit as indicated in the below. If any voltage falls beyond its limit then replace the related

    Module.

    Input Limit

    240V AC ( 155 to 290 V)

    110 V DC ( 100 to 130 V)

    +24V DC (+/- 2 VDC)

    +5 V DC (+ 1 V / - 0.1VDC)

    +12 V DC (+/- 1 VDC)

    -12 V DC (+/ - 1 VDC)

    6.3 UPS SYSTEM

    The UPS System is conservatively designed. It is completely static with all advanced

    digital circuits. This system will provide many years of trouble-free service with minimum

    maintenance. However a regular periodic maintenance program should be followed.

    Table given below provides the schedule maintenance procedure in detail.

    WARNING

    HIGH VOLTAGE IS USED IN THE OPERATION OF THE SYSTEM. HENCE EXTREME CARE

    SHOULD BE TAKEN WHEN PERFORMING MAINTENANCE TASK OF TROUBLE SHOOTING

    THIS SYSTEM, TO PREVENT ACCIDENTAL ELECTRIC SHOCK

    Page No : 72

  • 8/8/2019 Scada Hardware Manual

    73/99

    meritHARDWARE MANUAL

    TABLE - 1

    6.4 TABLE OF PERIODIC INSPECTION AND MAINTENANCE

    Sl No ITEMS INSPECTION PERIOD PROCEDURE

    1 Ventilation

    & opening

    Daily Daily Check that intake and exhaust air

    openings are not obstructed.

    2 Chassis

    Assemblies

    Weekly Weekly Remove dust & foreign particles within

    & Battery the chassis & battery bank

    using compressed air or blower. Check

    mounting bolts and terminals for

    looseness, tighten them, keep the

    battery terminals clean.

    3 Cabinet 3 Months 3 Months Inspect the transformers, chokes for

    evidence of heating, damaged

    insulation, loose mounting of screws.

    Correct any malfunctioning before

    operating the unit. Tighten any loose

    screws or nuts, clean electrical

    contacts with a cloth dampened with

    carbon tetrachloride. Do not use

    cleaning solvent on electrical contacts.

    Replace if found defective.

    4 Controls 3 Months 3 Months Controls 3 Months Check all indicator

    lamps

    5 Controls 6 Months 6 Months Check all the controls for operability.

    Check the operation of meters.

    Replace if any damage or mal-

    functioning is observed.

    6 Controls 12 Months 12 Months Check the cable for input and output

    power and internal wiring to

    components. Check for cracks or

    broken insulation. Replace as

    indicated.

    7 12 Months 12 Months Inspect the general conditions of

    PCBs. Check the components for

    Page No : 73

  • 8/8/2019 Scada Hardware Manual

    74/99

    meritHARDWARE MANUAL

    evidence of over heating, cracks

    orpeeling. Repair or replace board, if

    necessary.

    8 12 Months 12 Months Inspect diodes and silicon Controlled

    rectifiers and their heat dissipators for

    loose mounting or defective electrical

    connections. Tighten screws and nuts.

    9 12 Months 12 Months Inspect PCB, sockets for loose

    components electrical connections.

    Tighten the mounting screws & replace

    defective sockets, if any.

    10 12 Months 12 Months Inspect terminal boards for breakage or

    dry joints. Replace if necessary thedefective TB. Tighten mounting screws

    if necessary.

    11 Inspect the electric wiring for broken

    solder connections or peeled insulation

    and general deterioration. Repair or

    replace wiring. Use carbon

    tetrachloride in well ventilated areas.

    Do not breathe fumes.

    6.5 FAULT FINDING AND RECTIFICATION

    When replacing the components, observe the following :

    Page No : 74

    CAUTION

    FUSE REPLACEMENT MUST BE MADE ONLY WITH TYPES SPECIFIED IN THE

    PARTS LIST

  • 8/8/2019 Scada Hardware Manual

    75/99

    meritHARDWARE MANUAL

    1. When soldering avoid excessive heat which may damage associated

    components.

    2. Be careful while making all soldering joints, as a poorly soldered joint can

    cause further trouble and is one of the most difficult faults to locate.3. Do not drop drips of solder or hardware into the chassis.

    4. Do not damage leads of other components by pushing or them aside.

    5. Maintain a log of all repairs and adjustments. Comprehensive notes and an

    accurate log, make it possible to reverse the procedure or to facilitate the

    communications regarding repair procedure.

    6. When detaching wires from components, mark the wire with tape to ensure

    correct re-wiring.

    7. Always place the component in the exact position occupied original.8. Whenever one or more components have been replaced, testing and

    readjustment of appropriate circuit is necessary.

    6.6 TESTING EQUIPMENT REQUIREMENT

    Whenever it becomes necessary to replace any of the components in the UPS, re-

    adjustment of the appropriate circuits may be necessary. Familiarity with the Systems

    and judgement must be exercised when determining, which component effect re-

    adjustment. Following Table lists the test equipment required for reforming adjustment

    servicing :

    6.7 TEST EQUIPMENT

    EQUIPMENT WITH MODEL / TYPE QTY Mfr

    Oscilloscope with Dual Channel 1 no. APLAB

    Page No : 75

  • 8/8/2019 Scada Hardware Manual

    76/99

    meritHARDWARE MANUAL

    Voltage Probes into 10 Model 2 nos APLAB

    Digital Multimeter Type 1 no. NIL

    Distortion Meter 1 no. APLAB

    Decade Resistance 1 no. APLAB

    Card Servicing Unit 1 no. Numeric

    CHAPTER 7

    7.0 RTU TROUBLE SHOOTING PROCEDURE

    7.1 TELESIGNAL

    The problems in the field equipment can be classified into three types

    a). Telecommand (BM/CB) not operating

    Page No : 76

  • 8/8/2019 Scada Hardware Manual

    77/99

    meritHARDWARE MANUAL

    b). Telesignal (BM/CB status and Alarms) not coming

    c). Telemetry (Voltage/Current) not received from the post

    1. Check the 110 V DC at respective RTU terminal block as per the Field

    Termination Chart or the Wiring Diagram where this voltage comes from the field

    devices. If there is no voltage at RTU terminal block then the problem is not with

    RTU. Check the field equipment side and the cable continuity. If the voltage is

    available then follow the next step.

    2. Replace the respective DIM d as per the wiring diagram or Field termination

    Chart and check respective LED indication at DIM card.

    .

    7.2 TELEMETRY

    1. Check the respective PT/CT secondary at RTU terminal block as per the wiring diagram

    or the Field Termination Chart.

    2. If there is no required minimum Voltage or Current then the problem is not in the RTU

    side. Check the field devices and the interconnecting cables.

    Page No : 77

  • 8/8/2019 Scada Hardware Manual

    78/99

    meritHARDWARE MANUAL

    3. Check the POWER METER input Voltage or Current. If there is no Voltage or Current

    then check the cable between the RTU terminal block and Power Meter input.

    4. Check the power Meyer output, if there is no serial output with respect to input voltage

    or current then replace the Power meter check the value at RCC.

    5. Replace the flat cable and check the value at RCC.

    7.3 TELE COMMAND

    Page No : 78

  • 8/8/2019 Scada Hardware Manual

    79/99

    meritHARDWARE MANUAL

    1. Check the Selected channel enable and indication is proper. If channel does not

    glow, the problem may be resolved by changing the following items one after

    another.

    Change the DOM card.

    a. If the problem is not resolved, then change the cable termination.

    b. If the channel glows, then check the contactor operates. Otherwise check for 24

    V DC across coil; if voltage is available, then replace the contactor.

    c. If the coil voltage is not available, then check the 24 V DC Supply at terminal

    block TB1.

    d. If the contactor operates, then check the NO contact for input and output

    voltages; if available, then problem is in the Field devices side.

    e. If the 110 V DC is not available on the input side then the problem is again on

    the railway terminal board. If voltage is available on the input side but not

    available on the output side then change the contactor.

    7.4 Power Supply Unit :

    ( If output voltages are not coming)

    Page No : 79

  • 8/8/2019 Scada Hardware Manual

    80/99

    meritHARDWARE MANUAL

    1. Check the input voltage of the LDA (OR) LDC Module at Molex connector CN1. (if the

    Voltage is available go to step-7

    2. If the Input Voltage is not present ,Check the output voltage Supervisory Module

    at Molex Connector JP4.

    3. If the supervisory card input voltage is not present , then check the A/C input voltage at

    connector JP1.

    4. If the A/c Input voltage is not present then check the MCB-1 input & Output. ( The

    Voltage Must be less than 290v and greater than 155v )

    5. If the D/C Input voltage is not present then check the fuse (F3) and MCB-2 Input and

    Output.( The Voltage must be less than 140v and greater than 90v DC)

    6. If the Fuse (F3) blown up, then replace the 2A fuse (20mm)

    7. If the the LDA /LDC input voltage is present at connector CN1 ,

    Then check the module fuse (F1).

    8. Check the Output voltage at connector (JP3) for +5v/+12v/-12v.

    ( Check the Molex pin connection and crimping )

    9. Check the Output voltage at Connector (JP5) for 24v/DC.

    ( Check the Molex pin connection and crimping )

    7.5 TROUBLESHOOTING CHART FOR UPS

    NO FAULT SYSTEM REASON REMARKS1 System working on mains but

    not working on batteryBattery fuse blown Check the battery polarity and

    replace the fuse.

    Page No : 80

  • 8/8/2019 Scada Hardware Manual

    81/99

    meritHARDWARE MANUAL

    2 Charger not coming ON whenswitched ON

    Mains input fuse failed ormains MCB tripped

    Check the rating of the fuse.If itis of lower rating, replace withproper fuse.

    Input fuse of the chargerblown

    Check the battery polarity and

    connection. Correct if it iswrong. Replace the fuse

    Contactor not coming ON Check the input supply. If

    present, check the wiring of

    Contactor & rectify it. Check the

    coil. Replace if faulty.3 Mains Input Fuse Failure Very low input

    voltageProvide rated input voltage.

    Input cable capacityis less

    Replace the wiring with correctly

    rated cable.

    Loose contact in theinput wiring

    Tighten the connections.

    4 DC Under Voltage indica tioncomes on even when DCvoltage is nominal and theInverter Trips.

    Inverter Fuse blown Replace the fuse

    5 DC under Voltage comesimmediately after the Inverter isswitched on (NO LOAD) andInverter Trips

    Mains input cable is lessthan rated capacity

    Replace the cable from D.B.

    with correctly rated capacity.

    6 DC under voltage indicationcomes on while working onBattery (in the absence ofmains) and Inverter trips.

    Battery is dischargedBattery cable of lessercapacity less than ratedLoad surge.

    Keep the battery in charged

    condition Replace the cable with

    a correctly rated cable.7 Overload Indication comes on

    while the load is switched ONVoltage reaches 230V Switch on the loads one by

    one .

    7.6 Trouble Shooting Procedure for Modem :

    Page No : 81

  • 8/8/2019 Scada Hardware Manual

    82/99

    meritHARDWARE MANUAL

    Team link SCADA modem is designed in such a way that it requires just plug in the modem

    for normal operation. In case the polling operation does not take place the following points

    will facilitate the first line maintenance of the card.

    Check for correct ness of the jumper setting.

    A) Ensure all the modems involved are powered on.

    1. Make sure that the power card is kept correctly, 230v, AC in case of master modem,

    DC voltage in case of Slave modem.

    2. Verify that the modem is powered on by observing the MR led glowing on the front

    panel.

    B) Ensure that the modem to RTU /MTU connections are proper.

    1. Verify that the RTU/ MTU signals are coming properly at the RS-232C cable coming

    from RTU/ MTU. Verify the following signals are in the range of 3v to 15v at the RS-

    232 C Cable coming from RTU/ MTU.

    -Transmit Data (TXD) at Pin No. 2 of RS-232C cable coming from RTU/

    MTU .

    - Request to send (RTS) at Pin No. 4 of RS-232C cable coming from RTU/

    MTU

    - If the voltages are not present then check for the continuity of the cable.

    - If the signals are present ensure that the RS-232 Cable is mating properly

    with corresponding Connector of the modem end.

    C) Ensure that the Modem to Modem connection are proper.

    Page No : 82

  • 8/8/2019 Scada Hardware Manual

    83/99

    meritHARDWARE MANUAL

    1. Ensure that the connection from the Master modem are properly connected

    to Slave modems.

    2. Check the continuity of the Communication Line.

    D). Ensure that the Modems are operating properly

    Check for MR led on the modem, if MR is glowing put the Analog loop back switch in to

    On position and send data and check, if data is not correct modem could be faulty. If

    data is correct then connect the modem with any one of the Remote modems and ask

    them to put in to Digital Loop back switch in to ON position, send data and receive,

    check for correctness. If the data is not correct check for communication cable. If thedata is correct then,

    Start the polling cycle and observe the following

    1. Master Modem:

    - CTS led should always be glowing.

    - TD and RD led should blink

    2) Slave Modem:- DCD led should glow, if not check for the communication cable.

    - RD led should blink, if not check the following

    - Check the RS-232 cable from RTU.

    - Check whether RTU is responding for the polling.

    If still the problem persists then replace the modem .

    7.7 TELESIGNAL FAULT FINDING CHART

    Page No : 83

  • 8/8/2019 Scada Hardware Manual

    84/99

    meritHARDWARE MANUAL

    Page No : 84

    CHECK THE RTU TERMINAL BLOCK FOR110V FOR FIELD INPUT

    110V AT

    TB

    NOT A RC PROBLEM

    REPLACE DIM

    DIM LED

    IS

    GLOWING

    REPLACE DIM

    MODULE

    NO

    YES

    YES

    YES

    NO

    NO

    PROBLEM SOLVED

  • 8/8/2019 Scada Hardware Manual

    85/99

    meritHARDWARE MANUAL

    7.8 TELEMETRY FAULT FINDIING CHART

    Page No : 85

    CHECK THE RTU TERMINAL BLOCK FOR

    FIELD INPUT

    FIELD

    INPUT NOT A RCPROBLEM

    CHECK FUSE &CABLE FOUND

    FAULTYREPLACE IT.

    REPLACE THE

    Power Meter

    NO

    YES

    YES

    YES

    NO

    NO

    CHECKPOWER Meter

    INPUT &

    Supply

    CHECK

    POWER

    METER

    OUTPUT

    PROBLEM SOLVED

  • 8/8/2019 Scada Hardware Manual

    86/99

    meritHARDWARE MANUAL

    7.9 TELECOMMAND FAULT FINDING CHART

    8.0 DOWNLOADING PROGRAM TO RTU MICROCONTROLLER:

    Procedure:

    Page No : 86

    CHECK THE RESPECTIVE CHANNEL LED IS

    ENABLED

    LED

    ENABLE

    D

    REPLACE DOTMODULE

    CHECK THEO/P

    VOLTAGE

    AT TB

    PROBLEM SOLVED

    NO

    YES

    YES

    YES NOCONTACTOR IS

    OPERATING

    CHECKVOLTAGE

    ACROSS COIL

    REPLACE THE CABLE

    YES

    REPLACE THECONTACTOR

    CHECK THE WIRING FOR LOSSE

    CONNECTION. ANY DAMAGE REPLACE IT

    NO

    NO

  • 8/8/2019 Scada Hardware Manual

    87/99

    meritHARDWARE MANUAL

    1. Set the jumper J2 of CPU to download mode. Connect the serial-port-1 of CPU tosystem serial port.

    2. Software used for Download Program: C:\SCSI\BIN\SPJTERM.EXE

    The preloaded SPJTERM.EXE is the programming tool of the micro controller used in theRTU.

    3. After opening the program click Settings to set the communication Settings.

    4. Set the parameters as shown below.

    5. After setting the port parameters click port open to initialize the serial port.

    Page No : 87

  • 8/8/2019 Scada Hardware Manual

    88/99

    meritHARDWARE MANUAL

    The window will appear as shown below.

    6. Click the In System Programming in File menu.

    RTU is now ready for download and the communication is now initialized with theController.

    7. Set all the parameters as shown below.

    Page No : 88

  • 8/8/2019 Scada Hardware Manual

    89/99

    meritHARDWARE MANUAL

    8.Click Full Chip Erase to clear the buffers of Micro controller.

    9. Click Browse and select the .HEX file of RTU download file. The path and name of the filewill be appearing on the band HEX file to download.

    10. Click Program to start the downloading.

    Page No : 89

  • 8/8/2019 Scada Hardware Manual

    90/99

    meritHARDWARE MANUAL

    The above shown window will disappear after download is completed. Switch off the RTUand set the jumper J2 of CPU to normal position and Switch ON. RTU is now ready fornormal working.

    9.0 Download Parameters to RTU

    Procedure :

    1. Software used for Download Program: C:\ADRA\MERITDIAG.EXE

    The preloaded MERITDIAG.EXE is the downloading tool of the Merit RTU.

    2. Click Baud Rate and set the speed of serial communication. Default-600.

    Page No : 90

  • 8/8/2019 Scada Hardware Manual

    91/99

    meritHARDWARE MANUAL

    3. Click Comm Port and set the serial port to witch the RTU is connected. Default-Comm 1.

    Page No : 91

  • 8/8/2019 Scada Hardware Manual

    92/99

    meritHARDWARE MANUAL

    4.Click Setup and set the parameters to download to the RTU.

    5. After setting the parameters click Download & Update button to set the RTU parameters.

    Note: Before Clicking Download & Update make sure that the Digital Input Modules and the

    Digital Output Modules selected must match the actual modules inserted in the RTU. While

    setting the slot for Digital Output modules the RTU will start from the number of digital input

    modules and the slots will be allocated automatically after the Digital Input modules. If amismatch occurs while download, the modules will gets damaged and may cause serious

    damages to the whole unit.

    Setting of Analog Input Channels:

    SSP - 0

    SP - 2

    Page No : 92

  • 8/8/2019 Scada Hardware Manual

    93/99

    meritHARDWARE MANUAL

    TSS/FP - 8

    Now the RTU is ready for communication and operation. All the DI, DO and AI channels can

    be checked through MERITDIAG.

    6. The RTU running memory buffers can be cleared by clicking Reset RTU Database.

    7. The RTU real time clock can be set by clicking Set RTU Time.

    9.1 Testing the various parameters using MERITDIAG:

    1. Click Scan Digital Inputs. The window will appear as shown below. All the DI channels

    can be tested and viewed.

    Page No : 93

  • 8/8/2019 Scada Hardware Manual

    94/99

    meritHARDWARE MANUAL

    2. Click Scan Output Status. The window will appear as shown below. All the DO

    channels can be tested and viewed

    Testing Procedure: Click on the channel to be tested.

    Press space bar once. On will appear.

    Page No : 94

  • 8/8/2019 Scada Hardware Manual

    95/99

    meritHARDWARE MANUAL

    Click on Set Outputs. The particular channel will be made On by RTU.

    Press space bar again. On will get disappeared.

    Click on Set Outputs. The particular channel will be made off by RTU.

    Press space bar twice. Timd will appear.

    Click on Set Outputs. The particular channel will be made On and Off by RTU.

    3. Click Scan Analog Inputs. The window will appear as shown below. Analog count ,

    percentage and unit against all the AI channels can be viewed here.

    Page No : 95

  • 8/8/2019 Scada Hardware Manual

    96/99

    meritHARDWARE MANUAL

    LIST OF ABBREVIATIONS

    Page No : 96

  • 8/8/2019 Scada Hardware Manual

    97/99

    meritHARDWARE MANUAL

    A Amperes

    AC Alternating Current

    AIT Analog Input Termination

    BM Bridging interrupter

    CAN Controller Area Network

    CB Circuit Breaker

    CD Carrier Detect

    CP Communication Processor

    CPU Central Processor Unit

    CT Current Transformer

    CTA Cable Termination Module

    DDC Bus Coupler Module

    DC Direct Current

    DIFM Digital Input Functional Module

    DIT Digital Input Termination

    DIP Dual-In-line Package

    DMA Direct Memory Access

    DOT Digital Output Termination

    DRAM Dynamic Random Access Memory

    EMF Electro Motive Force

    EPROM Electrically Programmable Read Only Memory

    FP Feeding Post

    FSK Frequency Shift Keying

    Hz Hertz

    IBM PC International Business Machines Personal Computer

    IC Integrated CircuitIDE Integrated Drive Electronics

    IRQ Interrupt Request

    LAN Local Area Network

    LC Logic Chassis

    Page No : 97

  • 8/8/2019 Scada Hardware Manual

    98/99

    meritHARDWARE MANUAL

    LED Light Emitting Diode

    MB Mega Byte

    MOBI Mod Bus Interface

    MODEM Modulator Demodulator

    MOSFET Metal Oxide Semiconductor Field Effect Transistor

    MOV Metal Oxide Varistor

    NC Normally Closed

    NO Normally Open

    NVRAM Non-volatile Read Only Memory

    OHE Overhead Equipment

    PC Personal Computer

    PCB Printed Circuit Board

    PCS Peripheral Chip Select

    POST Power ON Self Test

    PWM Pulse Width Modulation

    RCC Remote Control Centre

    RD Receive Data

    RF Radio Frequency

    RLA Relay

    ROM Read Only Memory

    RTS Request to Send

    RTU Remote Terminal Unit

    SCADA Supervisory Control and Data Acquisition

    SCR Silicon Controlled Rectifier

    SEB State Electricity Board

    SH ShuntSIMM Single-in-line Memory Module

    SP Sectioning and Paralleling Post

    SSP Sub-sectioning and Paralleling Post

    SVGA Super Video Graphic Accelerator

    SW Switch

    Page No : 98

  • 8/8/2019 Scada Hardware Manual

    99/99

    meritHARDWARE MANUAL

    TB Terminal Block

    TCO Timer Counter Output

    TD Transmit Data

    TPC Traction Power ControlTSS Traction Sub-station

    UPS Uninterrupted Power Supply

    V Volts

    VGA Video Graphic Accelerator

    WAN Wide Area Network