scalable modular data center
TRANSCRIPT
-
8/14/2019 Scalable Modular Data Center
1/39
1Date FieldFooter Field 2009 IBM Corporation
How IBM helps clients, today,
build and deploy data centers
that are flexible and efficient
Joedy Lim
Data Center Solution Architect
Site & Facilities Services
IBM GlobalTechnology Services
-
8/14/2019 Scalable Modular Data Center
2/39
2Date FieldFooter Field 2009 IBM Corporation
Key objectives
Energy efficiency is a global issue with significant impact today and will havean even greater impact in the future
Data center design must change technology and business growth uncertaintyand rising costs drive the need for a new approach
A quick-to-deploy, cost-effective, energy-efficient alternative solution to raised-floor data center space.
-
8/14/2019 Scalable Modular Data Center
3/39
3Date FieldFooter Field 2009 IBM Corporation
Data centers are at a tipping point, driven by energy costsand usage
Increased Compute DemandServer growth 6x, Storage growth 69x this decade 1
By 2011, blades will represent 26% of all servershipments2
Changing cost dynamics
Data centers energy use doubling every 5 years3
New data center construction costs are increasing -$30 to $50M for a 20K square foot data center
Operating costs = 3x capital costs over 20 years
Data center lifecycle mismatch
78% of data centers are > 7 years old4
Technology densities are growing 20x this decade5
33% of managers expect data centers to last 30years6
Meet Business & IT Growth
Reduce capital andoperating costs for data
centers
Reduce risk by providingmore available andpredictable data centeroperations
1. IBM and Consul tant Studies2. IDC Worldwide Blade Server 2008-2011 Forecast, February 2008, IDC #2102293. Koomey, February 2007.
4. Gartner Survey Suggests Extensive Data center Expansion plans on the H orizon, G00154962, mike Chuba, February 200
5. ASHRAE (find source)6. IDC The datacenter evolution: Technologies, D esigns, People and Green, Michel e Bailey, 2008
-
8/14/2019 Scalable Modular Data Center
4/39
4Date FieldFooter Field 2009 IBM Corporation
IBM is investing $1 billion per year for clients and our own usewith five building blocks drive growth and savings
Double your IT capacity
Reduce operational costs
Positive environmental impact
IBM can help you find the value in green
Diagnose
Get the facts tounderstand your energy
use and opportunities
for improvementBuild
Plan, build,and upgrade
to energyefficient
data centers
CoolVirtualizeImplement
virtualization andother innovative
technologies
Measure &
ManageSeize controlwith energymanagementsoftware
Green DataCenter
Use innovativecoolingsolutions
-
8/14/2019 Scalable Modular Data Center
5/39
5Date FieldFooter Field 2009 IBM Corporation
IBMs Data Center FamilyTM
Scalablemodular
data center
Turnkey data center for 500-2,500 square feet
Rapid deployment in 8-12 weeks 20% less cost than traditional data centers
15-30% improved energy efficiency
Enterprisemodular
data center
Standardized design in 5K up to 20K square feet
Designed for high availability
Leadership energy efficiency 66% DCiE
25% faster deployment than custom approach
Open architecture involving leading vendors
Portablemodular
data center
Fully functional data center; multi-vendor support
Portable - temporary and remote data centers
Rapidly deploy in 12-14 weeks
Designed for high availability
Leadership energy efficiency: 77% DCiE
High densityzone
Plug and play infrastructure to support high densityservers in existing data centers
Non-disruptive implementation
35% lower cost than retrofitting existing data center
-
8/14/2019 Scalable Modular Data Center
6/39
6Date FieldFooter Field 2009 IBM Corporation
The IBM scalable modular data center solution provides you a quick-to-deploy, cost-effective, energy-efficient alternative to raised-floor data
center space.
Rapid deployment: A fully functional,data center, from planning to start-up,in 8-12 weeks, at a cost 15 percentlower than traditional data centerdesign and build
Support for low- to high-densitycomputing
Reduced energy costs: energy-efficient design can deliver energycost savings of 20% or more
No need to acquire internalconstruction expertise
Scalable Modular Data Center
-
8/14/2019 Scalable Modular Data Center
7/397Date FieldFooter Field 2009 IBM Corporation
Solution Overview
A scalable modular data center is a turnkey solution. It includes
power and cooling systems for critical IT equipment, racks for
housing equipment, cabling, components that monitor
operations and more.
A space-saving, energy-efficient scalable modular data center solutioncan be configured in a single-row, rack-based architecture.
-
8/14/2019 Scalable Modular Data Center
8/398Date FieldFooter Field 2009 IBM Corporation
Solution Overview, Cont.
Multiple rows of racks can be configured to meet unique spacerequirements.
A scalable modular data center can be implemented in nearly any
configuration in nearly any work environment.
-
8/14/2019 Scalable Modular Data Center
9/399Date FieldFooter Field 2009 IBM Corporation
Solution Overview, Cont.
The IBM and APC solution delivered significant capital and operational
cost savings, providing a compact yet highly scalable infrastructure. We
estimate that the solution is 30 percent more efficient in power and
cooling terms alone, both reducing expenditure and underlining theUniversitys commitment to environmental sustainability.
Art Gloster, CIO of Bryant University
-
8/14/2019 Scalable Modular Data Center
10/3910Date FieldFooter Field 2009 IBM Corporation
Highlights of the Solution Architecture
Sample Solution for a Unique Room Shape
-
8/14/2019 Scalable Modular Data Center
11/3911Date FieldFooter Field 2009 IBM Corporation
Highlights of the Solution Architecture
Sample Solution for A Small Data Center
-
8/14/2019 Scalable Modular Data Center
12/3912Date FieldFooter Field 2009 IBM Corporation
Highlights of the Solution Architecture
Sample Solution for A Medium-Sized Data Center
-
8/14/2019 Scalable Modular Data Center
13/3913Date FieldFooter Field 2009 IBM Corporation
Highlights of the Solution Architecture
Sample Solution for A Large Data Center
-
8/14/2019 Scalable Modular Data Center
14/3914Date FieldFooter Field 2009 IBM Corporation
Pictorial View of Scalable Modular Data Center
-
8/14/2019 Scalable Modular Data Center
15/3915Date FieldFooter Field 2009 IBM Corporation
With the scalable modular data center, most of the infrastructure iswithin the rows of racks, helping to increase efficiency and savefloor space
Cabling
Uninterruptible powersupply (UPS)/batteries
In-row cooling
Equipment racks
UPS power distribution/bypass
Non-raised-floorenvironment
-
8/14/2019 Scalable Modular Data Center
16/3916Date FieldFooter Field 2009 IBM Corporation
The server, storage and other IT equipment is installed inequipment racks
600mm and 750mm / 19 and 23, 42U and 48U racks
-
8/14/2019 Scalable Modular Data Center
17/39
17Date FieldFooter Field 2009 IBM Corporation
SMDC UPS and battery solutions
10kW/40kW
w/batteries
40kW/40kW
w/batteries
10kW/80kW
w/battery rack
80kW/80kW
w/battery cabinet
-
8/14/2019 Scalable Modular Data Center
18/39
18Date FieldFooter Field 2009 IBM Corporation
Cooling Solutions
RC SeriesChilled Water
Up to 30kW
RP Series
To 37kW DX Air Cooled
To 70kW Chilled Water
Chilled Water Cooling
Distribution Unit
For up to 12 racks
Air cooled modular chiller units
50kW 220kW
-
8/14/2019 Scalable Modular Data Center
19/39
19Date FieldFooter Field 2009 IBM Corporation
SMDC offers overhead power distribution
Overhead single or 3 phasepower distribution
eliminates clutter under raised flooroptimizing air flow (if existing raisedfloor environment)
Brings 3 phase power to the rack forsmart load balancing
Reduces electrical contractor labor,easier to install and maintain
Eliminates need for raised floor ifdesired
-
8/14/2019 Scalable Modular Data Center
20/39
20Date FieldFooter Field 2009 IBM Corporation
SMDC allows the cooling configurations required in todays high densitydata center environments to cool up to 70kW per rack
Hot aisle / Cold aisle configurationRack contained cooling
Closed loop
Up to 18kW/rack
-
8/14/2019 Scalable Modular Data Center
21/39
21Date FieldFooter Field 2009 IBM Corporation
Multiple cooling methods can be mixed and utilized in one SMDCsolution
-
8/14/2019 Scalable Modular Data Center
22/39
22Date FieldFooter Field 2009 IBM Corporation
Sample 3D SMDC View
-
8/14/2019 Scalable Modular Data Center
23/39
23Date FieldFooter Field 2009 IBM Corporation
Sample 3D SMDC View
-
8/14/2019 Scalable Modular Data Center
24/39
24Date FieldFooter Field 2009 IBM Corporation
Sample 3D SMDC View
-
8/14/2019 Scalable Modular Data Center
25/39
25Date FieldFooter Field 2009 IBM Corporation
Views of the solution
-
8/14/2019 Scalable Modular Data Center
26/39
26Date FieldFooter Field 2009 IBM Corporation
Views of the solution
-
8/14/2019 Scalable Modular Data Center
27/39
27Date FieldFooter Field 2009 IBM Corporation
Component
Inclusive
Electrical
Uninterruptible Power Supply (UPS)
Precision In-row Cooling
Rack
Monitoring System
Out of Scope
Civil work
Fire system
Security system
Data cabling
-
8/14/2019 Scalable Modular Data Center
28/39
28Date FieldFooter Field 2009 IBM Corporation
SMDC Express (RC and SC)
-
8/14/2019 Scalable Modular Data Center
29/39
29Date FieldFooter Field 2009 IBM Corporation
SMDC 20 kVA
RD
RC
-
8/14/2019 Scalable Modular Data Center
30/39
30Date FieldFooter Field 2009 IBM Corporation
SMDC 40 kVA
RD
RC
-
8/14/2019 Scalable Modular Data Center
31/39
31Date FieldFooter Field 2009 IBM Corporation
SMDC 80 kVA
RD
RC
-
8/14/2019 Scalable Modular Data Center
32/39
32Date FieldFooter Field 2009 IBM Corporation
Contact & Resource Link
Contact
Joedy Lim IBM Indonesia
Nico Steffanus Sutikno IBM Indonesia
Adhy Wijaya APC Indonesia
Resource Link
Sales One Site & Facilities
http://w3-03.ibm.com/services/salesone/Global/html/sfs.html#1
Solution Finder Engagement Portfolio SMDC
http://spimweb1.boulder.ibm.com/services/sosf/dyno.wss?oid=549
http://w3-03.ibm.com/services/salesone/Global/html/sfs.html#How%20IBM%20helps%20clients,%20today,%20build%20and%20deploy%20data%20centers%20that%20are%20flexible%20and%20efficienthttp://spimweb1.boulder.ibm.com/services/sosf/dyno.wss?oid=549http://spimweb1.boulder.ibm.com/services/sosf/dyno.wss?oid=549http://w3-03.ibm.com/services/salesone/Global/html/sfs.html#How%20IBM%20helps%20clients,%20today,%20build%20and%20deploy%20data%20centers%20that%20are%20flexible%20and%20efficient -
8/14/2019 Scalable Modular Data Center
33/39
33Date FieldFooter Field 2009 IBM Corporation
SEE BLUE.THINK GREEN.
Overall: www.ibm.com/greenFor CIOs: www.ibm.com/cio
For facilities managers: www.ibm.com/services/siteandfacilities
http://www.ibm.com/greenhttp://www.ibm.com/greenhttp://www.ibm.com/ciohttp://www.ibm.com/services/siteandfacilitieshttp://www.ibm.com/services/siteandfacilitieshttp://www.ibm.com/services/siteandfacilitieshttp://www.ibm.com/services/siteandfacilitieshttp://www.ibm.com/ciohttp://www.ibm.com/greenhttp://www.ibm.com/green -
8/14/2019 Scalable Modular Data Center
34/39
34Date FieldFooter Field 2009 IBM Corporation
CIOs are not accountable for the energy costs
to run a data center
A recent survey showed 77% of ITdepartments are not responsible forthe data center energy bills1
CIOs do not have the facts to make informeddecisions on how to better manage data centerenergy usage
Less than 20% of businesses haveconducted an energy audit.2
CIOs are surprised with the short payback to
go green
EPA estimates 25-55% annual energysavings are possible3
1. Inf ormationWeek The Cold, Green Facts September 2007. 3. EPA Response to Congress f or Public Law 109-431, A ugust 2007
2. CNet.com, Green IT: do it for the money if nothing else, November 2007 4. Bernstein report, CFO-CIO survey, November 2007
Think Green : What is the role of the CIO?
What isyour
choice?
50% of CFOs havereducing data centepower as a priority4
-
8/14/2019 Scalable Modular Data Center
35/39
35Date FieldFooter Field 2009 IBM Corporation
With SMDC, the UPS can be sized for todays loads and scaledto meet the needs of tomorrow
Symmetra PX
Scale power in 10KW, 16 KW and 25kW Scaleruntime
Benefit
Pay as you grow
Reduce upfront CAPEX
Reduce backend OPEX
Availability
N+1 with no additional chassis required
Efficiency
Newer UPSs run at >90% efficiency, olderUPSs can run at
-
8/14/2019 Scalable Modular Data Center
36/39
36Date FieldFooter Field 2009 IBM Corporation
The In-row cooling method used with SMDC is efficientand effective
In Row Cooling (Close Coupled
Cooling) Deliver cooling directly to the loads
targeted cooling
Shorten air path which requires less fan
power increasing efficiency
Reduces humidification requirements
reducing water and electricity waste
All rated capacity of CRAC can be utilized
Higher rack densities can be achieved (up to
50KW)
N+1 or 2N cooling can be targeted to rows
vs. rooms for targeted availability
Match cooling capacity to load through
intelligent cooling
Contain hot air within a single or multiple
racks to prevent mixing with conditioned air
Chiller Units
Can work with existing customer chiller plant
or design/procure/install new chiller plant
-
8/14/2019 Scalable Modular Data Center
37/39
37Date FieldFooter Field 2009 IBM Corporation
SMDC also utilizes Intelligent Rack Mount PDUs
0U and 1U rack mount PDUs Metered rack PDUs with
alarm thresholds
Many input/outputconfigurations
Remotely switchable on/off
Load balance via built inmetering allows you tobalance phases easily
Remotely manage power to
the rack 1.4KW to 14.4KW power
distribution capacity per unit
-
8/14/2019 Scalable Modular Data Center
38/39
38Date FieldFooter Field 2009 IBM Corporation
Power & Cooling Remote Management and Monitoring withISX Central w/ Capacity & Change Management
Performance Analysis
Know where the power & cooling isgoing to optimize data center efficiency
Predictive failure Analysis
Batteries, fans, etc.
Identify hot spots
Within the room or rack
Track chronic power lineproblems such as brownouts
Intelligently manage capacityand change within the data
center
-
8/14/2019 Scalable Modular Data Center
39/39
Racks can utilize an air containment option to force hot exhaust airthrough the cooling unit to prevent it from mixing with the cooled supplyair
Rack containment options