scheda per linee collettive di rivelazione a 8 ingressi
TRANSCRIPT
ST7-HV
GENERAL DESCRI PTI ON
Silver-View7 is a supervision program that allows a com puter-based event m anagem ent of fire and cr im e
squad system s through anim at ion and graphic pages. These plants can be com pounded by one or several
panels, ST7 series and ST7 com pat ible. Basically Silver-View7 allows to m anage the act ivit y of the
installat ion without fiscally m oving to it . Silver-View7 program can be installed on one or m ore PCs that
will connect to the fire alarm panel with a LAN Ethernet or serial line.
I nteract ive graphic page with command and display icons
MAI N CARATTERI STI CS OF THE Silver-View7 SOFTW ARE
• PC installed (MS Windows)
• Panel ST7, ST7-HV and AFP21 com pat ible
• Access and configurat ion with USB protect ion device
• Connect ion to the plants though LAN Ethernet or serial line
• Choose of language –English, I talian, French and on request
• Im port zone nam es and ent it ies from panels
• Maps in bitm ap form at (bm p, jpg, etc.)
• Past events with filter to see and export data
• On line m anual
SOFTW ARE PROTECTI ON
The program is installed through a CD and includes a USB protect ion device.
I n order to act ivate it , a regist rat ion on Silver-Tec database is necessary. The
program can st ill run without the USB device – but only in dem o status, and it
allows to see the events on the graphic pages: the lim itat ion of the dem o
status is the im possibilit y to ordain.
Silver-View7 CONFI GURATI ON
Silver-View7 has an easy configurat ion in order to adapt to the fire and gas installat ion requirem ents.
From the m ain panel, the adm inist rator can m odify the graphic pages and the fire plant features on the
m ap. Moreover, the adm inist rator can decide all possible act ions for each level of access and the graphic
pages visible on each PC. I n addit ion to the basic funct ions, the program SILVER-VIEW7 can also have
som e on-dem and opt ions such as SILVER-VI EW7 VI DEO or be custom ized according to the client ’s needs.
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
Silver-View7 Video OPTI ON
Silver-View7 Video allows to com plete the detect ion installat ion with a
video system . The cam eras will be placed in the interested areas and
the im age will be displayed in the graphic m ap. Silver-View7 Video
requires to place cam eras in the areas to protect , a digital recording
system and LAN video t ransm ission. DVR system s by GAMS and
INDIGO can be integrated on Silver-View7 Video
Program Functions
Silver-
View7 Demo
Silver-
View7
Base
Silver-
View7 Video
Co
nn
ecti
on
s USB Dongle: no yes yes
Connect ion through ser ial link
Connect ion through LAN (or WAN) Ethernet
Connect ion to several panels
Connect ion to (some) DVR systems through LAN
Vie
ws
Simulat ion of events to be displayed on graphical maps
Visualizat ion of real events on graphical maps
Summary on the front page of the events and plant status
Event v iew of pre-recorded messages for the operator
On-demand view of analogue values of the field devices
Hierarchical level display of area and zone (opt ional)
Graphical map display of v ideo images of cameras
View events from several panels in the plant
View the status of the connect ion among the panels
Online manual
Event pr int
Acti
on
s
Allows the acknowledgment of alarms and sirens
Allows the display of histor ical events
Allows the inclusion and exclusion of devices
Allows to control actuators ( lights and sirens) also with macro-commands
Co
nfi
gu
rati
on
s
Configure and save user groups and operators
Configure and save messages
Configure and save grouped commands (macro-commands)
I mport , edit ing and saving of graphics pages
Edit and save the t ime slots
Changing the configurat ion of the DVR
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
GENERAL DESCRI PTI ON
The ST7 panel can be program m ed using the software Silver-Pro7.
The program , which is supplied separately from the panel, can be installed on any PC provided with either
a serial port or a link for network connect ion with the panel to be program m ed.
A USB port is also necessary for the protect ion key that is used to prevent tam pering and unauthorised
m odificat ion after test ing.
The Silver-Pro7 program enables to use the panel at the highest possibilit y and hardware m odularit y,
besides being quite sim ple in use, as it ut ilises video windows including tables and select ion m enus
consistent with both panel com posit ion and funct ions to be obtained.
CONFI GURATI ON METHOD
The ST7 panel is m ainly com posed by one basic unit and one or m ore racks, where selected cards
according to the type of system installed are inserted.
Whatever it s special funct ion, each card is pract ically a device connect ing and cont rolling the input
(detect ion) and output (com m and) field devices.
Once they have been inserted into the racks, the cards m ust be configured, through Silver-Pro7 program,
to define:
a) character ist ics and inputs behaviour (sensors)
b) character ist ics and outputs behaviour (actuators)
c) logic and temporal com binat ions ( rules) determ ining which outputs are to be act ivated by status
variat ions of inputs.
During the configurat ion, the assigned zone of each device ( input or output ) is to be defined, as well as
it s behaviour in stand-by, alarm and fault condit ions.
1) Definit ion of inputs
Determ inat ion of behavior and t im e of delay of inputs.
Physical locat ion and addressing of devices.
2) Definit ion of actuators
Determ inat ion of behavior and t im e of delay of outputs.
Physical locat ion and addressing of devices.
3) Definit ion of rules (operat ing logics)
I t defines the status variat ions of inputs to determ ine the act ivat ing condit ions of outputs.
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
POSSI BLE CONFI GURATI ONS
At a general configurat ion level, it is possible to define:
Panel and program language
Panel display param eters
Panel heading and general inform at ion on the type of the panel
Com m unicat ion m ethod for panels, PC’s and printers
Panel and supervision PC’s IP addresses
CPU and cards redundancies
Tim e- related operat ion and periodical test funct ions
Program and configurat ion protect ion param eters.
At panel (and system ) funct ional level, it is possible to configure:
AND, OR, N/ N logic associat ions relevant to inputs and outputs m anaged by panel
Logic associat ions on other network-connected panels
Logic associat ions and events determ ined by t im efram e variat ions.
The logic associat ions can be configured for a m axim um of 300 fire ext inguishing zones and 300 int ruder
alarm s or technologic control zones. Each zone, on the other hand, can have 99 inputs, 99 outputs and
99 logic associat ions.
DATA VALI DI TY CONTROL
I n addit ion to ancillary funct ions, the Silver-Pro7 configurat ion program integrates a configurat ion cont rol
ut ilit y able to detect and report any syntax or consistency errors during the assignm ent of addresses and
logic at t r ibut ions.
Silver-Pro7 is able to produce a pr intable page depict ing the panel com posit ion.
PROGRAM PACK AND PROTECTI ON
The program is supplied on a CD and includes a USB protect ion key which requires, for it s act ivat ion, the
user 's (or installer 's) regist rat ion in Silver-Tec's database.
The protect ion key is necessary as it allows, in combinat ion with the user’s (or installer ’s) password, to
enable or disable panel configurat ion t ransm ission from and to the PC.
PROGRAM MAI N CHARACTERI STI CS
PC installat ion with MS Windows operat ing system
Protect ion of panel configurat ion with password and USB key
Connect ion to panel through ser ial port or network
Standard languages are I talian, English and French; other languages and fonts upon request
Possibility to configure 300 Safety zones, with 99 sensors, 99 actuators and 99 rules per zone
Possibility to configure 300 Secur ity zones, with 99 sensors, 99 actuators and 99 rules per zone
Possibility to configure 999 remote rules for interact ion between panels
Table- type graphic configurat ion method, with guided dropdown menus and on- line help
Organisat ion and storage in working folders with a drop-down st ructure
Ut ility for validity cont rol of configurat ion data
Graphic display and pr int of panel configurat ion
Graphic display and pr int of composit ion of each loop (or bus) , with indicat ion of respect ive consumpt ion
Table- type display and pr int of memory occupat ion by vir tual inputs and outputs used for interact ion between
panels, or setup of logic and part icular associat ions
Display and pr int relat ing to vir tual points dedicated to Modbus communicat ion
Automat ic creat ion of configurat ion file to be exported to SI LVER-VI EW7 supervision program
Automat ic creat ion of executable program to be exported to panel (ST7-HV)
Programming manual (available direct ly from program).
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
DESCRI PTI ON OF THE ST7 -HV PANEL
The ST7-HV panel is a high technological product designed to protect indust r ial plants and equipm ent for
safety applicat ions. I t is characterized by an easy configurabilit y and program m ing, excellent reliabilit y,
and system diagnost ics.
The ST7-HV is sim ilar to a “safety” PLC and it is also configurable and programm able to perform
integrated fire detect ion and fire ext inguishing cont rol, gas detect ion, int ruder alarm and technological
cont rol funct ions, in com pliance with applicat ion and product regulat ions.
I t can interact with other panels of the sam e type, as well as with supervisory and SCADA system s,
through both proprietary and standard protocols, such as Ethernet TCP/ IP, Modbus or OPC server.
MAI N CHARACTERI STI CS
PC configurable with the program
Silver-Pro7
Can be managed through a
supervisory program
Can be networked with other
panels
19“ rack modular const ruct ion
From 2 to 10 racks with 13 card
slots
Front plug- in/ out cards
Two CPU’s, in hot back-up to one
another
Cards interconnected on redundant
bus loop
Cyclical test ing, with automat ic
simulat ion of card inputs and
outputs
Automat ic monitor ing of card and
CPU fault
Automat ic and safe disabling of
malfunct ioning cards
Hot swap of cards and CPU’s
High immunity to elect romagnet ic
disturbances.
REFERENCE STANDARDS AND CERTI FI CATI ONS
SIL2 and SIL3 cert ified to IEC61508 Funct ional Safety (SIL)
MECHANI CAL CONSTRUCTI ON
The panel, which has a m odular st ructure, is m ainly com posed of 19"-3HE anodised alum inium racks
contained in a cabinet with a swivel rack chassis and an acrylic glass door.
The panel can be com posed from a m inim um of 2 racks to a m axim um of 10 racks according to the
needs.
The first rack (base rack) is always necessary and includes one or two CPU’s, the display for the operator
interface and the keyboard. Any further rack is used to install cards, whose type and quant it y depends on
specific applicat ion requirem ents.
Each card is term inated either on a DIN rail-m ounted elect ronic- type term inal block ( for 4m m 2
conductors) , via a flat cable, or on an elect rom echanical- t ype m arshalling term inal block, via a cable with
plug connector.
I n addit ion to versions tailored to m eet specific custom er requirem ents, three standard configurat ions are
available, for the European m arket , in accordance with the CPD cert ificat ions:
ST7 - HV/ 1 R Base rack + 1 card rack, in wall-m ount ing cabinet (L= 600 H= 700 D= 400m m )
ST7 - HV/ 2 R Base rack + 2 card racks, in wall-m ount ing cabinet (L= 600 H= 1100 D= 400m m )
ST7 - HV/ 1 0 R Base rack + up to 10 card racks, in self-standing cabinet (L= 800 H= 2100 D= 800m m ). CONFI GURATI ON
One of the m ost im portant characterist ics of the ST7-HV panel is the user- fr iendly windows-com pat ible
configurat ion program Silver-Pro7, which is quite sim ple to use and m akes it possible to suit the system
to specific applicat ion requirem ents and m odificat ions, if any. With the Silver-Pro7 program , it is possible
to configure logic associat ion and, or, n of n, and t im e based, to use on one panel or m ore connected
panels.
S8 1 - HS PANEL
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
TECHNI CAL SPECI FI CATI ON SUMMARY:
Mechanical Modular ity
St ructure Self-standing cabinet , with swivel 19"-3H rack chassis and door
Front Acrylic glass door, lockable
Expansion By addit ion of racks, each having 13 card slots
Term inal blocks On DI N rail
Card installat ion Font plug- in
Card replacement Hot swap (no need for either panel switching off, or intervent ion on connect ions and
wir ing)
Field connect ion Through term inal block cards and flat cables (monitored connect ion)
Card connect ion Through ser ial line on redundant bus managed by FPGA
Direct Control and I nterfacing
4-20 mA inputs On cards and modules for 4-20 mA inputs
Addressable devices Total 130 loops, 127 addresses per loop
Detect ion cards Specific cards, with self-configurat ion capability (also to exist ing detect ion lines)
Technologic controls Addressable cards and modules on BUS
Commands Addressable cards and modules on BUS
Automat ic f ire ext inguishing
control
Special nat ive cards for this funct ion can control up to 64 ext inguishing zones cert if ied
to EN 12094-1
Ext inguishing controls
(direct ional valves) Special nat ive cards for this funct ion, with no logic and control lim itat ion
Repeaters Repeaters with alphanumeric display on addressable bus
Remote control From PC with SI LVER-VI EW7 software and OPC server
Communicat ion protocol TCP/ I P on Ethernet , with communicat ion control
Mult i-panel architecture Ethernet and Modbus, copper or opt ic f ibre, redundant
External SCADA interfacing Standard MODBUS RTU protocol; propr ietary protocol on Ethernet
Elect ronic Modular ity
Display (LCD) Liquid crystal, ret ro illum inated, graphic type, 320 x 240 pixel
Main CPU
ST7-CP1101-N (One or two CPUs)
Hitachi 32-bit CPU with internal operat ing system and integrated watch dog
4 MByte Data Memory SRAM + 2 MByte Program Memory on Flash Eprom
2 RS232 ports + 1 Ethernet 10/ 100 base TX port per CPU.
Cards on base rack
- I / O base card and interface ST7-FT3001
- Display + keyboard and signalling ST7-DU1001-N
- Base back Plane BP1301-N
Necessary cards on
expansion racks and
connectors
- BP1401-N Back plane rack ( flat cable)
- BP1402-N Back plane rack (cable plug)
- RC1201-N Rack controller and internal bus
- FT3201-N/ FT3202 Term inal block module
- FT3103-N/ T8007/ FT3104 Relay cards
Addit ional cards on
expansion racks
(max 9 racks)
- ST7-I C4001 Eight inputs, convent ional detect ion
- ST7-I C5001 One 4-20 mA analogue input
- ST7-I C5002 Two analogue inputs
- ST7-I C5003 Eight analogue inputs
- ST7-OC6001 Eight 500 mA monitored outputs
- ST7-OC6101 Sixteen open collector outputs
- ST7-OC6201 Eight polar ity reversal-monitored outputs
- ST7-OC6002 Four monitored outputs
- ST7-EX9001 Fire ext inguishing control (EDC), cert if ied to EN12094-1
- ST7-LS9002 Special logic control
- ST7-AL7001-S Addressable analogic loop control DCP (UL)
- ST7-AL7002-S Analogue addressable loop control, ESP protocol
- ST7-AL7003-S Analogue addressable loop control, SSP protocol
- ST7-AL7004-S Analogue addressable loop control, Apollo protocol
- ST7-MD8001-N MODBUS RTU card
- ST7-AL7005-S Addressable bus control, System Sensor protocol
Power supply
Feeder There is the availability of several sizes of feeders 2.5, 4 or 20A and can be
paralleled.
Cert if ied to EN 54-4, with fault indicat ion in case of mains supply failure, bat tery
charger or bat tery fault , overheat ing
Bat tery charger Can be coupled with feeder
Bat tery charge and aging status monitor ing, through m icrocontroller-processed
algor ithm ; thermal compensat ion dur ing bat tery charging; test ing but ton; bat tery capacity ≤ 110 Ah.
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
DI SPLAY OF ST7 PANEL
The display card is the interface between the panel and the operator.
I t is com posed by a liquid crystal, LED back lit , graphic type, with thir t y 52-characters lines, twenty-
three keys and a buzzer.
MAI N CHARACTERI STI CS
Large display easily visible thanks to a wide viewing angle
Displays all panel status condit ions and necessary interact ive inform at ion for the operator
Display and LED indicat ions are in accordance with the fire fight ing standards EN 54-2
Access to operator funct ions is subject to different level passwords
Polycarbonate m em brane, with dust and dir t -proof keys.
PANEL AND LED STATUS
ALA
RM
TE
ST
ZO
NE
CO
MM
ON
F
AU
LT
DE
VIC
ES
F
AU
LT
SO
UN
DE
RS
F
AU
LT
PS
U1
FA
UL
T
PS
U2
FA
UL
T
EA
RT
H F
AU
LT
SY
ST
EM
FA
UL
T
CO
MM
ON
D
ISA
BL
ED
DE
VIC
ES
D
ISA
BL
ED
SO
UN
DE
RS
D
ISA
BL
ED
OU
TP
UT
S
DE
LA
YE
D
PO
WE
R O
N
Normal status - - - - - - - - - - - - - ⊗
Zone Test ing - ∅ - - - - - - - - - - - -
Common fault - - ∅ - - - - - - - - - - -
Card fault - - - ∅ - - - - - - - - - -
Signalling fault - - - - ∅ - - - - - - - - -
Power supply fault - - - - - ∅ ∅ - - - - - - -
Leakage to earth - - - - - - - ∅ - - - - - -
System fault (CPU) - - - - - - - - ∅ - - - - -
Disabling in progress - - - - - - - - - ⊗ - - - -
Devices disabled - - - - - - - - - - ⊗ - - -
Sounder output disabled - - - - - - - - - - - ⊗ - -
Outputs delayed - - - - - - - - - - - - ⊗ -
Alarm not acknowledged ∅ - - - - - - - - - - - - -
Alarm acknowledged ⊗ - - - - - - - - - - - - -
LED status legend ⊗ = on ∅ = blinking - = off
DI SPLAY S8 1 -DU1 0 0 1 - N
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
POSSI BLE ACTI ONS THROUGH KEYS
OPERATOR’S ACTI ONS Level 1
Level 2
Operator
Level 3
Maintenance
Silencing of panel alarms OK OK OK
Cancellat ion of cont rol delay OK OK OK
Displaying of alarm and fault status OK OK OK
Silencing and act ivat ion of evacuat ion sounders - OK OK
I nclude, exclude and reset funct ions - OK OK
Displaying of event history and exclusions - OK OK
Test ing of panel, zones and devices - OK OK
Modificat ion of date and t ime - OK OK
Access to system configurat ion funct ions - - OK
Access to diagnost ics funct ions - - OK
KEYS DESCRI PTI ON
ACCESSIBLE FUNCTIONS THROUGH KEYS
I con Meaning Level Funct ion
Panel alarm silencing 1-2-3 Silences panel buzzer
Sounder alarm silencing 2-3
Silences of general alarm horns in the
system
Panel reset 2-3
Resets all panel and detect ion line alarms,
detectors included
Evacuat ion com m and 2-3
Act ivates system audible alarms for
evacuat ion
Delay t im e set t ing 1-2-3 Annuls delay t ime count on act ive actuators
Select ion cancellat ion 1-2-3 Back to previous page
Scroll 1-2-3
Enables display of complete list within
operator ’s cycle menu
Direct ions within m enus 2-3
Enables navigat ion in panel access and
operat ion menus
Num erical keys 0-9 1-2-3
Enable enter ing passwords and making
select ions in menus
Enter 1-2-3
Confirms select ion dur ing access operat ions
to panel menus
Funct ion F1 1-2-3
Varies depending on access level and panel
status.
FURTHER I NDI CATI ON
Display rear side LED’s Funct ion
LD 15 Current ly not used
LD 16 Current ly not used
Link CPU-A Communicat ion with CPU-A
Link CPU-B Communicat ion with CPU-B
Link FT3001-N Communicat ion with card FT3001-N
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
ST7 - CP1 1 0 1 -N CPU CARD
This card is system 's cent ral unit and contains the m icro-cont roller, which processes all the inform at ion
provided by the other cards of the panel.
I n addit ion to the m icro-cont roller, the card has a flash m em ory, a buffered stat ic RAM, a watchdog
circuit and an Ethernet cont roller with an RJ 45 Ethernet output connector.
MAI N CHARACTERI STI CS
Can be hot swapped
Suitable for applicat ions fault - tolerant up to SIL3 level in accordance with I EC-61508
Designed to operate in parallel ( redundancy)
Autom at ic set once the second CPU has been put in
Micro-cont roller 25 MHz Renesas (HITACHI ) H8-2318
4-Mbit (512K X8) buffered stat ic RAM with lithium bat tery
2-Mbit expandable FLASH m em ory
ETHERNET 10/ 100 link via RJ 45
Watchdog external to CPU, for software funct ional cycle m onitor ing
Fault self-check on the hardware
Built - in clock
I nternal CPLD dedicated to the com m unicat ion m anagem ent
Operat ing system residing in internal flash m em ory
On- line t ransfer of configurat ion program
Front plug- in, with locking screws
OPERATI ON
The CPU card can be used in either single or redundant configurat ion with two CPU’s operat ing in parallel.
Both CPU’s process inform at ion from the cards of the panel, but only one ( the pr im ary) of the two
interacts with them . Once the prim ary CPU stops operat ing, the other im m ediately takes it s place without
disrupt ing on-going operat ions or losing captured events.
COMMUNI CATI ON
Thanks to the RJ 45 port located on the CPU, m ore ST7 m ult ifunct ion panels can be connected each other
or to a supervising PC, via LAN. The panel’s interconnect ion serves to t ransfer events or inform at ion
between them . The Connect ion with the supervisor PC allows you to m anage the panel from a rem ote
locat ion.
Status LED’s
Link Act ivity Run W do
Linked to LAN ⊗ - - - Communicat ing ⊗ ∅ - - CPU act ive in pr imary mode ⊗ CPU act ive in secondary mode ⊗ - ∅ - CPU blocked - - - ⊗ Legend ∅ = blinking ⊗ = on - = off
CARD S8 1 -CP1 1 0 1 - N
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
RACK CONTROL CARD
This card m anages the com m unicat ions am ong the rack’s cards and the CPU’s; it receives data from the
CPU and it sorts them am ong the 13 cards in the rack through 2 different com m unicat ion channels and
vice versa.
Only one card RC1201-N for each rack is necessary and it has to be placed in the 14 th available slot .
MAI N FEATURES
Suitable for applicat ions fault - tolerant up to SIL3 level in accordance with I EC-61508
Allows the interchange of inform at ion between the CPU’s and the cards in the
rack through 13 serial connect ions ( for cards) and 2 BUS in a loop ( for the CPU)
Can be hot swapped
No need of connect ions to the field
Com m unicat ion protocol with MANCHESTER code m anaged by FPGA
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
Absorpt ion 20 m A at 24 Vdc
OPERATI ON
The card is used only to manage the communicat ion between rack and cards and between the racks
and the CPU’s of the panel.
The communicat ion is redundant and it works on two separate channels, Link A and Link B; in case of
interrupt ion on one of the two connect ions, the panel will work regular ly, although signaling a fault in
communicat ion.
CONFI GURATI ON
Rack address is defined according to the posit ion of selector placed on the card
POSI TI ON OF THE CARD ST7 - E2 0 0 2
The Rack Controller card shall be placed only in
the last slot on the r ight of each rack.
The other 13 slots of the rack can be used for all
other type of card.
Status condit ions
Led indicat ion
LI NK A LI NK B RUN I NTERRUPTS CARDS
I N OUT I N OUT FLT 1 FLT 2 FLT 3
Link A act ive in input ⊗ - - - - - - -
Link A act ive in output - ⊗ - - - - - -
Link B act ive in input - - ⊗ - - - - -
Link B act ive in output - - - ⊗ - - - -
Regular working mode ( led blinking) - - - - ⊗ - - -
I nterrupt pending from a card - - - - - ⊗ - -
I nterrupt pending on link A (CPU A) - - - - - ⊗ -
I nterrupt pending on link B (CPU B) - - - - - - - ⊗
Legend ⊗= on - = off; - - - = not provided
DI P-SW Rack 1 Rack 2 Rack 3 Rack 4 Rack 5 Rack 6 Rack 7 Rack 8 Rack 9 Rack 10
SW 1-1 OFF ON OFF ON OFF ON OFF ON OFF ON
SW 1-2 OFF OFF ON ON OFF OFF ON ON OFF OFF
SW 1-3 OFF OFF OFF OFF ON ON ON ON OFF OFF
SW 1-4 OFF OFF OFF OFF OFF OFF OFF OFF ON ON
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
DEFAULT I NPUT AND OUTPUT MANAGEMENT CARD FOR HS VERSI ON OF ST7 PANEL
This card can m anage 10 digital inputs, 16 open collector outputs and one m onitored output for fire alarm
siren cont rol. I n addit ion, the card checks the ground leakage of the supply voltage.
The ST7 FT3001 card can be connected with a flexible cable to a FT3201-N term inat ion card or to a
FT3102-N relay board, to have respect ively, 16 open collector or 16 SPDT contact relay outputs.
OPERATI ON
The ST7-FT3001 card is to be mounted on a DIN rail and, therefore, it is norm ally installed on panel back
plate.
I t is connected with the panel display (DU1001-N) and with a term inat ion card (ST7 T8007 or FT3201-N)
by m eans of FLAT cables that can be hot swapped.
The two LED’s respect ively indicate the presence of power supply and the operat ion of the serial link with
the panel display.
DEFAULT OUTPUTS THROUGH T8 0 0 7 -1 OR FT3 2 0 1 -N CARD
The ST7 panel norm ally includes an FT3102-N-1 card, which is used to produce the output funct ions
required by the EN 54-2 standard. I f, on the other hand, a FT3201-N term inat ion card is ut ilised, the
outputs have the sam e funct ions but are of an Open Collector t ype.
Specific relay outputs are available for int ruder alarm funct ions, fire fight ing funct ions and funct ions
com m on to both of these applicat ions.
Som e relays are also provided for a norm ally energised stand-by condit ion.
Relay
(T8007)
Normally
energized Default Outputs
Mode
Safety Secur ity
K1 PREALARM
K2 ALARM
K3 FAULT
K4 DEVI CES DI SABLED
K5 LOCAL BUZZER
K6 SPARE
K7 GENERAL ALARM
K8 TAMPER
K9 GENERAL FAULT
K10 BURGLAR ALARM
K11 SPARE
K12 NORMAL OPERATI ON
K13 SYSTEM FAULT
K14 POWER SUPPLY FAULT
K15 CPU OR PROCESS FAULT
K16 pulsing PANEL RESET
CARD S8 1 - FT3 0 0 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
DEFAULT I NPUTS & ALARM OUTPUT
I t is a term inal st r ip, on which panel default inputs and panel output to alarm horn are term inated.
Term inal Funct ion Note
∅ M1 Buzzer silencing remote input N.O. (normally open)
∅ M2 Sounder silencing remote input N.O.
∅ M3 Panel reset remote input N.O.
∅ M4 Evacuat ion command remote input N.O.
∅ M5 Bat tery status (supply/ charge) 0 Vdc (charge)
∅ M6 PSU1 pr imary supply fault N.C. (normally closed)
∅ M7 PSU2 secondary supply fault N.C.
∅ M8 Bat tery charging status (deep and maintenance) 0 Vdc (deep)
∅ M9 Fault external to panel N.C.
∅ M10 Tamper alarm external to panel N.C.
∅ M11 Fire alarm siren posit ive output 250 mA max (monitored line)
∅ M12 Fire alarm siren negat ive output 250 mA max (monitored line)
NOTE:
When asked, the board ST7-FT3001 is coupled to the relay card FT3101-N to m ake available the
repet it ions of the cent ral state with voltage- free changeover contacts.
The connect ion between the two units is carr ied out sim ply by using a flat cable-m ixed.
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
BACKPLANE CARDS FOR ST7 RACK
These cards are used for elect ric supply and interconnect ion between ST7 cards and the field.
BP1 3 0 1 - N BACK- PLANE FOR PANEL BASE RACK
I nterface between CPU’s and the cards of the system
Backplane of basic rack of ST7 panel HS version
Prop up connectors for elect r ic supply
Connector for display
Connectors for pr inter and PC serial link
Com pletely passive
RJ45 type BUS connectors, which connect the CPU’s and the racks.
BP1 4 0 1 - N FLAT CABLE W I RI NG BACKPLANE FOR CARD RACKS
Allows the connect ion between the cont roller card RC1201-Nand the cards of the rack
Allows the connect ion between the cards and the field through flat cable and term inat ion cards
RJ45 BUS connectors.
BP1 4 0 2 - N BACK PLANE FOR PLUG CABLE CONNECTI ON
Allows the connect ion between the cont roller card and the cards in the rack in safety- related
applicat ions and with heavy current loads
The connect ion between the cards and the field is carr ied out via pre-wired cable plugs direct ly on
m arshalling term inal box
RJ45 BUS connectors.
BACK-PLANE CARDS S8 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
TERMI NAL BLOCK MODULES ON DI N RAI L
FT3201-N FT3202-N
These m odules are used in ST7-HV panels, to connect
the field devices, and they are ready to be fixed on
DIN rail to place on the backplane of the panel.
The connect ion between the rack and the term inal
block is m ade through flat cable with connectors.
The term inal blocks FT3201 and FT3202 (size
57(L)x77(H)x60(P)m m ) have exclusively term inal
blocks, the others have also relays.
The card FT3102-N2 can be connected with flat cable
and with connector.
Type Term inal blocks
FT3102-N Term inal block with 16 relays
FT3103-N Term inal block with 8 relays
FT3104-N Term inal block with 4 SPDT relays
FT3201-N 16 term inals for 4 mm2 cable
FT3202-N 8 term inals for 4 mm2 cable
PLUG CABLE CONNECTORS
PC2301-S PC2301-SR
The cables with plug connectors are used for direct
connect ion between the panel cards and the field
m arshalling term inal blocks. Cables with two
connectors are also available (R suffix) , which contain
the term inat ion and connect ions necessary for system s
with redundant inputs and outputs.
TYPE Conductors Connectors
PC2001-S 16 Single
PC2001-R 16 Double
PC2101-S 2 Single
PC2101-R 2 Double
PC2201-S 8 Single
PC2201-R 8 Double PC2201-R1 8 Double PC2301-S 4 Single
PC2301-R 4 Double
PC2401-S 6 Single
PC2501-S 8 Single
PC2501-R 8 Double
PANEL CARD COMPATI BI LI TY W I TH TERMI NAL BLOCK MODULES AN D PLUG CABLE CON NECTORS
Connectors IC4001
IC5001
IC5002
IC5003
OC6001
OC6101
OC6201
OC6002
AL7001-S
AL7002-S
MD8001-N
AL7003-S
AL7004-S
AL7005-S
FT3 2 0 1 - N ◊ ◊ ◊ FT3 2 0 2 - N ◊ ◊ ◊ ◊ ◊ ◊ ◊ ◊ ◊ ◊ FT3 1 0 2 - N ◊ FT3 1 0 3 - N ◊ FT3 1 0 4 - N ◊ PC2 0 0 1 - S ◊ ◊ ◊ PC2 0 0 1 - R PC2 1 0 1 - S ◊ PC2 1 0 1 - R PC2 2 0 1 - S ◊ ◊ PC2 2 0 1 - R PC2 2 0 1 - R1 PC2 3 0 1 - S ◊ ◊ ◊ ◊ ◊ ◊ PC2 3 0 1 - SR PC2 4 0 1 - S ◊ PC2 5 0 1 - S ◊ PC2 5 0 1 - R
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CABLE TERMI NATI ON CARDS W I TH RELAY
These are used in the ST7 panel to m anage actuators and power appliance and are direct ly connected to
the base rack ST7 or to the card ST7 FT3201-N
FT3 1 0 3 - N
TERMINATION BLOCK WITH 8 RELAYS
EXCHANGE CONTACTS C/ NO / NC
Contacts 5 to 30 Vdc
DIN rail m ount ing
Led for each relay
Size L 135 x H 77 x D 40 m m
FT3 1 0 2 - N
TERMINATION BLOCK WITH 16 RELAYS
EXCHANGE CONTACTS C/ NO / NC
Contacts 5 to 30 Vdc
Led for each relay
DIN rail m ount ing
Size L 170 x H 77 x D 65
Enabling relay from flat cable or
term inal block
FT3102-N BR1 BR2
Term inal blocks:
NC = Normally closed
NO = Normally open
COM = Common
K1 K2 K3 K4 K5 K6 K7 K8
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
BR3 BR4
K9 K10 K11 K12 K13 K14 K15 K16
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
Act ivat ion input BR5
Relay K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16 C
Term inal blocks 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
OPERATI ON
Both cards can be used together with the command card ST7 OC6101 to convert the open collector outputs in free of
tension contacts with 8 or 16 relays.
Through the programming of the FT3201-N, the working status of relays can be set in f ix or lashing, energised or non-
energised way.
Note:
One FT3102-N card is already supplied with the ST7 panel (complete version) and it is used to reproduce the status
signalling and the repet it ions required by the standard.
I n the ST7 HV version, this card is connected to the control card ST7 FT3001.
T 8006-1 Relay
NC = Normally closed
NO = Normally open
COM = Common
K1 K2 K3 K4 K5 K6 K7 K8
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
NC
NO
CO
M
Term inal blocks 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
RELAY CARDS S8 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ONS W I TH CABLE TERMI NATI ON CARDS ( UL VERSI ON)
FT3301-N
The cable term inat ion cards are used to connect the
field devices in the ST7-HV panel (UL version) .
The cable term inat ion cards are arranged for the DIN
rail fixing to place on the backside plate of the panel.
TYPE Term inat ion blocks
FT3301-N Term inat ion block with 16 contacts
FT3302-N Term inat ion block with 8 contacts
FT3303-N Term inat ion block with 6 contacts
FT3304-N Term inat ion block with 24 contacts
FT3305-N Term inat ion block with 12 contacts
FT3302-N
FT3303-N
The cards FT330X-N type are used to increase the
resistance of the system to overvoltage that m ight be
caused during the connect ion of devices in som e
cr it ical applicat ions.
FT3304-N
FT3305-N
ST7 - HV PANEL CARD COMPATI BI LI TY W I TH TERMI NATI ON CARDS ( UL VERSI ON)
Connectors IC4001
IC5001
IC5002
IC5003
OC6001
OC6101
OC6201
OC6002
AL7001-S
AL7002-S
MD8001-N
AL7003-S
AL7004-S
FT3 3 0 1 - N ◊ ◊ ◊ FT3 3 0 2 - N ◊ FT3 3 0 3 - N- 2 ◊ ◊ ◊ ◊ FT3 3 0 4 - N ◊ ◊ FT3 3 0 5 - N ◊ ◊ ◊
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
8 - I NPUT CARD FOR CONVENTI ONAL DETECTI ON
The ST7- IC4001 card can m anage convent ional (non-addressable) detect ion lines. I t is part icular ly
suitable for system s where detect ion lines are already in place, for cross- line logic cont rol of autom at ic
fire ext inguishing system s ( for NFPA) , or in int r insic safety system s.
MAI N CHARACTERI STI CS
Redundable (note 1)
Can be hot swapped (note 2)
Suitable for applicat ions fault - tolerant up to SIL3 level according to the standards IEC61508
Double program m able alarm threshold for each line
Autom at ic verificat ion and confirm at ion of the alarm status
Suitable to various detectors ( types and brands)
Program m able for SAFETY or SECURITY operat ing m ode
Can m anage and cont rol eight lines
Line inclusion/ exclusion through panel keyboard
Autom at ic test ing of each line every thir t y seconds
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
OPERATI ON
The I C4001-S card can m onitor eight input lines, checking their current variat ions to get status
inform at ion. Line status is individually signalled and signalling can be different , depending on selected
SAFETY or SECURI TY operat ing m ode. I t can be configured to indicate two different alarm thresholds for each line and to apply or not a
verificat ion algorithm for alarm s. With the configurat ion, it is possible to define each alarm threshold to
adapt them to the actuat ion threshold (current ) of the detectors installed.
Through the detect ion lines, alarm but tons or voltage- free contacts belonging to the devices that need
to m onitor the status can be m onitored.
PROGRAMMABLE PARAMETERS VI A SOFTW ARE
Status SAFETY SECURI TY Normal operat ing mode NO/ NC NC
Logic status of the latching/ non latching line
(note 2)
Latching/ Non- latching Latching
Alarm ver if icat ion (note 3) Enabled/ Disabled Disabled
Alarm threshold programmable on 256 levels Pre-alarm / Alarm Fixed thresholds
I ndicat ion of line short -circuit Fault / Alarm Tampering
Audible alarm modalit ies Normal/ Silent / Buzzer Normal/ Silent
Status SAFETY Mode SECURI TY Mode
Yellow LED Red LED Yellow LED Red LED
Normal - - - -
Excluded ⊗ - ⊗ -
Fault ∅ - ∅ -
Tampering - - - - - - - ∅
Pre-alarm - ∅ - - - - - -
Alarm - ⊗ - ⊗
LED status legend ⊗ = on - = off ∅ = blinking - - - = not available
CARD S8 1 - I C4 0 0 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
Connect ion via Term inat ion Module FT3 2 0 1 -N
Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors. The electronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2.
Connect ion via Cable Plug PC2 0 0 1 -S or PC2 0 0 1 - R
Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends.
Cable conductors are wired direct ly onto a marshalling terminal block, while the connector is plugged into the backside
of the rack.
Connect ion exam ple of detectors to the card
Redundancy ( note 1 )
I n fault - tolerant systems, this card has to be duplicated, i.e. two cards are to be used, which must be installed in two
cont iguous racks. Each input line from the field has to be connected to both cards and its exclusion is only possible
from both of them.
Latching Mode ( Note 2 )
An alarm status persists unt il reset .
Alarm Verificat ion ( Note 3 )
Pre-alarm and alarm statuses are taken into considerat ion only if they validated by a verif icat ion procedure consist ing
in act ivated detector voltage drop-down and new checking after 7 seconds.
Funct ion Connect ion with FLAT CABLE
Connect ion with PLUG CABLE
Detect ion line 1 + ∅ 1
Scre
w t
erm
ina
l
FT
32
01
FT3201-N
1 White
PC2001-R
- ∅ 2 2 Brown
Detect ion line 2
+ ∅ 3 3 Green
- ∅ 4 4 Yellow
Detect ion line 3 + ∅ 5
5 Grey
- ∅ 6 6 Pink
Detect ion line 4 + ∅ 7 7 Blue
- ∅ 8 8 Red
Detect ion line 5 + ∅ 9 9 Black
- ∅ 10 10 Purple
Detect ion line 6 + ∅ 11 11 Grey/ pink
PC2001-S
- ∅ 12 12 Red/ blue
Detect ion line 7 + ∅ 13
Ba
ck
sid
e o
f
the
ra
ck
13 White/ green
- ∅ 14 14 Brown/ green
Detect ion line 8 + ∅ 15 15 White/ yellow
- ∅ 16 16 Yellow/ brown
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
ANALOGUE DEVI CES CONTROL CARD
One 4-21 m A analogue input card, with two thresholds that can be set through panel keyboard.
I t can m anage gas detect ion system s, as well as level and tem perature signal system s.
I t can cont rol all the 4-20 m A output t ransducers norm ally used for EXPLOSIVE and TOXIC GAS,
OXYGEN, TEMPERATURE and LEVEL sensors.
MAI N CHARACTERI STI CS
Redundable (Note 1)
Can Be Hot Swapped (Note 2)
Suitable for applicat ions fault - tolerant SI L2 or SI L3 according to the norm I EC61508
0-999 display reads engineered values
Values can be expressed in ppm , LEL% , O2% , m A, ° C
LED bar shows signal t rend
Plast ic pocket contains label indicat ing selected m easuring scale
4-24 m A input ( for fault indicat ion of the sensor)
I nput repet it ion on 4-20 m A output in term inal block and serial MODBUS RTU
Two separately set table alarm thresholds
Autom at ic self- test ing every 10 seconds
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
Front plug- in on 19’’ rack, with locking screws
LED I NDI CATI ONS
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Param eter Mode Normal operat ing mode I ncreasing or decreasing value (up/ down)
Logic status of the channel Latching/ Non- latching (Note 3)
Alarm signalling Normal/ Silent / Buzzer only
Analogue value repet it ion on Modbus Yes/ No
Measurement expressed in: Range:
ppm 0~ 5; 0~ 10; 0~ 15; 0~ 20; 0~ 50; 0~ 100; 0~ 200; 0~ 500; 0~ 999
LEL % 0~ 100
O2 % 0~ 25; 15~ 25
mA 4~ 20
°C 0~ 100; 0~ 150; 0~ 220; 0~ 300
CALI BRATI ON
Card calibrat ion can be m ade direct ly from panel keyboard, at access level 3. At this level, it is possible to
set pre-alarm and alarm thresholds, as well as zero and full scale values, applying a known value sam ple
to sensor input .
Status 2 nd Level 1 st Level Fault They indicate status
Red LED Red LED Yellow LED Display
Normal - - - 000 ÷ 999
Line excluded - - ⊗ 000 ÷ 999
Calibrat ion (span) ⊕ ⊕ ∅ 000 ÷ 3FFF
Fault - - ∅ fault code
Pre-alarm ⊗ ⊗ - read value
Alarm ⊗ - - read value
LED status legend ⊕ = based on calibrat ion; ⊗ = act ive; ∅ = blinking; - = off;
CARD S8 1 - I C5 0 0 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A CABLE PLUG Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack.
Connect ion exam ple of a sensor and a repeater
Redundancy ( Note 1 )
I n fault - tolerant systems, this card has to be duplicated, i.e. two cards are to be used, which must be installed in two
cont iguous racks. Each input line from the field has to be connected to both cards and its exclusion is only possible
from both of them.
I n redundancy configurat ion, in order to isolate a device, it will be necessary to isolate both connected channels:
moreover, if a supervision software is used (SI LVER-VI EW7), each device will be displayed with 2 different icons.
Hot Sw ap ( Note 2 )
The card can be removed and replaced without switching off the panel, which would imply system inoperability.
Latching Mode ( Note 3 )
An alarm status persists unt il reset .
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE I nput Signal + ∅ 1
FT3202
1 White
PC2501-
S
- - - ∅ 2 2 - - -
- - - ∅ 3 3 - - -
- - - ∅ 4 4 - - -
Output Signal + ∅ 5 5 Brown
- - - ∅ 6 6 - - -
- - - ∅ 7 7 - - -
- - - ∅ 8 8 - - -
CONNECTI ON VI A TERMI NATI ON MODULE
Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors.
The elect ronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2 and pre- insulated t ips
should be used.
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
MAI N CHARACTERI STI CS
Redundable (note 1)
Can be hot swapped (note 2)
Suitable for applicat ions fault - tollerant SIL2 and SIL3 in accordance with IEC 61508
Two separate and independent channels
Two separately set table alarm thresholds per channel
Two 0-999 displays read engineered values
Values can be expressed in ppm , LEL% , O2% , m A, ° C
Transparent plast ic pockets to contain labels indicat ing selected m easuring scale
Two 4-21 m A inputs
I nput repet it ion on 4-20 m A outputs in term inal block and serial MODBUS RTU
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
2 - ANALOGUE DEVI CES CONTROL CARD
Two 4-21 m A analogue input card, with two thresholds that can be set through panel keyboard.
I t can cont rol all the 4-20 m A output t ransducers norm ally used for EXPLOSIVE and TOXIC GAS,
OXYGEN, TEMPERATURE and LEVEL sensors.
LED indicat ions
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Param eter Mode Normal operat ing mode I ncreasing or decreasing value (up/ down)
Logic status of the latching/ non latching channel Latching/ Non- latching (Note 3)
Alarm modality Normal/ Silent / Buzzer only
Analogue value repet it ion on Modbus Yes/ No
Measurement expressed in: Range:
ppm 0~ 5; 0~ 10; 0~ 15; 0~ 20; 0~ 50; 0~ 100; 0~ 200; 0~ 500; 0~ 999
LEL % 0~ 100
O2 % 0~ 25; 15~ 25
mA 4~ 20
°C 0~ 100; 0~ 150; 0~ 220; 0~ 300
CALI BRATI ON
Card calibrat ion can be m ade direct ly from panel keyboard, at access level 3. At this level, it is possible to
set pre-alarm and alarm thresholds, as well as zero and full scale values, applying a known value sam ple
to sensor input .
Status 2 nd Level 1 st Level Fault I ndicat ion
Red LED Red LED Yellow LED Display
Normal - - - 000 ÷ 999
Pre-alarm - ∅ - Read value
Alarm ⊗ ⊗ - Read value
Channel disabled - - ⊗ - - -
Card not configured - - ∅ F00
Fault for line opening - - ∅ F01
Fault for exceeded range - - ∅ F02
Trouble for internal test failure - - ∅ F03
Atypical or out -of- range current - - ∅ FXX (mA)
Data error in EEPROM - - ∅ E00
Threshold value not valid - - ∅ E01
Range not supported by card - - ∅ E02
Detector being calibrated - - - CAL
LED status legend ⊗ = on - = off ∅ = blinking
CARD S8 1 - I C5 0 0 2
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A CABLE PLUG
Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack.
Connect ion exam ple of a couple of sensors and repeaters
Redundancy ( Note 1 )
I n fault - tolerant systems, this card has to be duplicated, i.e. two cards are to be used, which must be installed in two
cont iguous racks. Each input line from the field has to be connected to both cards and its exclusion is only possible
from both of them.
I n redundancy configurat ion, in order to isolate a device, it will be necessary to isolate both connected channels:
moreover, if a supervision software is used (SI LVER-VI EW7), each device will be displayed with 2 different icons.
Hot Sw ap ( Note 2 )
The card can be removed and replaced without switching off the panel, which would imply system inoperability.
Latching Mode ( Note 3 )
An alarm status persists unt il reset .
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE I nput signal 1 + ∅ 1
FT3202
1 White
CPC2501
-S
- - - ∅ 2 2 - - -
I nput signal 2 + ∅ 3 3 Brown
- - - ∅ 4 4 - - -
Output signal 1 + ∅ 5 5 Green
- - - ∅ 6 6 - - -
Output signal 2 + ∅ 7 7 Yellow
- - - ∅ 8 8 - - -
CONNECTI ON VI A TERMI NATI ON MODULE
Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors.
The elect ronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2 and pre- insulated t ips should be used.
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
MAI N CHARACTERI STI CS
REDUNDABLE (Note 1)
CAN BE HOT SWAPPED (Note 2)
Suitable for applicat ions fault - tolerant SIL2 and SIL3 in accordance with I EC 61508
Eight separate and independent detect ion channels
Values can be expressed in ppm , LEL% , O2% , m A, ° C
Eight 4-21 m A inputs
Repet it ion of 4-20 m A inputs on MODBUS RTU
Two separately set table alarm thresholds per channel
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
8 - ANALOGUE DEVI CES CONTROL CARD
Eight 4-21 m A analogue input card, with two thresholds that can be set through panel keyboard.
I t can cont rol all the 4-20 m A output t ransducers norm ally used for EXPLOSIVE and TOXIC GAS,
OXYGEN, TEMPERATURE and LEVEL sensors.
LED I NDI CATI ONS
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Param eter Mode
Normal operat ing mode I ncreasing or decreasing value (up/ down)
Channel logic status Latching/ Non- latching (note 3)
Alarm modality Normal/ Silent / Buzzer only
Analogue value repet it ion on Modbus Yes/ No
Measurement expressed in: Range:
ppm 0~ 5; 0~ 10; 0~ 15; 0~ 20; 0~ 50; 0~ 100; 0~ 200; 0~ 500; 0~ 999
LEL % 0~ 100
O2 % 0~ 25; 15~ 25
mA 4~ 20
°C 0~ 100; 0~ 150; 0~ 220; 0~ 300
CALI BRATI ON
Card calibrat ion can be m ade direct ly from panel keyboard, at access level 3. At this level, it is possible to
set pre-alarm and alarm thresholds, as well as zero and full scale values, applying a known value sam ple
to sensor input .
Status Alarm Fault
Red LED Yellow LED
Normal - - Pre-alarm ∅ - Alarm ⊗ - Channel disabled - ⊗ Card not configured - ∅ Fault for line opening - ∅ Fault for exceeded range - ∅ Trouble for internal test failure - ∅ Atypical or out -of- range current - ∅ Data error in EEPROM - ∅ Threshold value not valid - ∅ Range not supported by card - ∅ Detector being calibrated - -
LED status legend ⊗ = on - = off ∅ = blinking
CARD S8 1 - I C5 0 0 3 0 0 3
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A TERMI NATI ON MODULE
Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors.
The elect ronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2 and pre- insulated t ips
should be used.
CONNECTI ON VI A CABLE PLUG
Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends.
Cable conductors are wired direct ly onto a marshalling terminal block, while the connector is plugged into the backside of the rack.
Connect ion exam ple of various sensor types
Redundancy ( Note 1 )
I n fault - tolerant systems, this card has to be duplicated, i.e. two cards are to be used, which must be installed in two
cont iguous racks. Each input line from the field has to be connected to both cards and its exclusion is only possible
from both of them.
I n redundancy configurat ion, in order to isolate a device, it will be necessary to isolate both connected channels:
moreover, if a supervision software is used (SI LVER-VI EW7), each device will be displayed with 2 different icons.
Hot Sw ap ( Note 2 )
The card can be removed and replaced without switching off the panel, which would imply system inoperability.
Latching Mode ( Note 3 )
An alarm status persists unt il reset .
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE I nput signal 1 + ∅ 1
FT3202
1 White
CPC2201
-S
I nput signal 2 + ∅ 2 2 Brown
I nput signal 3 + ∅ 3 3 Green
I nput signal 4 + ∅ 4 4 Yellow
I nput signal 5 + ∅ 5 5 Grey
I nput signal 6 + ∅ 6 6 Pink
I nput signal 7 + ∅ 7 7 Blue
I nput signal 8 + ∅ 8 8 Red
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
8 - MONI TORED LI NE CONTROL CARD
This card has eight 500 m A outputs.
I t is part icular ly suitable for handling autom at ic fire ext inguishing system s, where it can be ut ilised to
cont rol ext inguishing agent release and direct ional valves, or to act ivate visual-audible alarm devices.
MAI N CHARACTERI STI CS
Redundable (note 1)
Can be hot swapped (note 2)
Suitable for applicat ions fault - tolerant SIL2 and SIL3 in accordance with I EC 61508
Tem perature test ing of DMOS and elect ronic com ponents
Funct ional cont rol of comm and lines each 2 seconds
500 m A per output
The card is protected against short circuit , so it is suitable to protect capacit ive loads
with peak current higher than the nom inal value
Software-configurable output behaviour
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
LED I NDI CATI ON ON CARDS
OPERATI ON The card perform s the tests on individual channels cyclically invert ing the signal on the output for a t im e
of about 200. m icroseconds. I n case of discrepancy between the set signal and the input signal, the
system indicates a fault condit ion. For each output are checked, the following situat ions: Open Line,
Short to posit ive, negat ive to Short , Failure of DMOS device driver, Tem perature of the DMOS
device drive, power supply outside the allowed lim its. All channels are tested during operat ion every 2
seconds.
PARAMETER CONFI GURATI ON VI A SOFTW ARE
(x) : These statuses persist unt il logic or operator ’s reset .
(z) : These statuses persist unt il reset by operator.
Status LED’s
Yellow Red
Normal - -
Output disabled ∅ -
Card fault ⊗ -
Line fault ⊗ -
Voltage out of range ⊗ -
Output act ivated - ⊗
LED status legend: ⊗ = act ive; ∅ = blinking; - = off;
Status Output Non-energised Energised Period
Norm al Stable a) ⊗ Fixed
Stable b) ⊗ Fixed
Act ivated
Stable a) ⊗ (x)
Stable b) ⊗ (x)
Delayed ⊗ 0-255 s
Per iodical ⊗ 0-255 s
I SA logics ( repeaters, lamps) ⊗ (z)
Sounder logics ⊗ (z)
CARD S8 1 - OC6 0 0 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A RELAY CARD FT3 1 0 3 - N
This card can be connected to a 8- relay board model FT3103-N simply
by using a flat cable and t ray connectors. The card allows the FT3103-
N line monitor ing of solenoid relays.
CONNECTI ON VI A TERMI NATI ON MODULE
I t is possible to use a term inat ion card and the rack BP1401-N, which
will be connected between them via flat cable.
CONNECTI ON VI A CABLE PLUG PC2 2 0 1 - S or PC2 2 0 1 -R Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack.
CONNECTI ON EXAMPLE OF SOME ACTUATORS
Maxim um current
The card is capable to dr ive resist ive or induct ive loads with a maximum current of500mA at 24 VDC.
I n the case where the card is used to dr ive filament lamps the maximum power of the load should not exceed 4W.
Redundancy ( Note 1 )
I n fault - tolerant systems, this card has to be duplicated, i.e. two cards are to be used, which must be installed in two
cont iguous racks. Each input line from the field has to be connected to both cards and its exclusion is only possible
from both of them.
Hot Sw ap ( Note 2 )
The card can be removed and replaced without switching off the panel, which would imply system inoperability.
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE Output 1 + ∅ 1
FT3202
1 White
CPC2201
-S
Output 2 + ∅ 2 2 Brown
Output 3 + ∅ 3 3 Green
Output 4 + ∅ 4 4 Yellow
Output 5 + ∅ 5 5 Grey
Output 6 + ∅ 6 6 Pink
Output 7 + ∅ 7 7 Blue
Output 8 + ∅ 8 8 Red
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
1 6 - CONTROL CHANNEL CARD W I TH OPEN COLLECTOR OUTPUTS
The card has 16 non-m onitored 250-m A outputs.
I t is widely used for cont rols and direct hardwir ing or in conjunct ion with a 16- relay card (FT3102-N) .
MAI N CHARACTERI STI CS
Can be paired with FT3101-N relay card, with contacts free of tension
Can be paired with ST7 FT3201-N term inat ion m odule or to the PC2001-S plug cable, to
supply 16 open collector outputs allowed to m anage LEDs and non-m onitored loads
Non- redundable
Hot swap (note 1)
250 m A per output
Software-configurable operat ing m ode
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
LED I NDI CATI ON ON CARDS
OPERATI ON
This card effects status and funct ionalit y checks, but does not m onitor the cont rol channels.
I n case of m alfunct ioning, a fault condit ion is shown on panel display.
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Param eter
Act ivat ion m ode
• Steady, normally energised
• Steady, normally de-energised
• Per iodical
• Pulsing mode 1
• Pulsing mode 2
• Delayed after act ivat ion
• Delayed after de-act ivat ion
• Delayed after enabling
• I SA Logic 1A
Period 1 to 255 seconds, in pulsing and per iodical mode only
Type of output normal or sounder
Status OUTPUTS 1 to 1 6
RED LED’s
Channel in normal condit ion - Channel act ivated ⊗ Led status legend ⊗ = on - = off
CARD S8 1 - OC6 1 0 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A RELAY CARD
The card ST7-OC6101 can be connected to a 16 relay card
FT3102-N through the PC2001-S connector wired to term inals
BR5 or direct ly with flat cable connected on J1.
CONNECTI ON VI A TERMI NATI ON MODULE This is possible with a backplane of the rack type BP1401-N and
flat cable with term inat ion card FT3201-N.
CONNECTI ON VI A CABLE PLUG PC2 0 0 1 - S
Connect ion between the card and the field is carr ied out by means of a wired cable, provided with a plug- in connector
connected at the end of the backplane BP1402-N.
Cable conductors are wired direct ly onto a marshalling terminal block, while the connector is plugged into the backside
of the rack.
CONNECTI ON EXAMPLE OF ACTUATORS THAT DO NOT REQUI RE MONI TORI NG
Funct ion Connect ion with FLAT CABLE
Connect ion with PLUG CABLE
Com m and line 1 - ∅ 1
Scre
w
term
ina
l
FT
32
01
FT3201-N
1 White
PC2001-S
Com m and line 2 - ∅ 2 2 Brown
Com m and line 3 - ∅ 3 3 Green
Com m and line 4 - ∅ 4 4 Yellow
Com m and line 5 - ∅ 5
5 Grey
Com m and line 6 - ∅ 6 6 Pink
Com m and line 7 - ∅ 7 7 Blue
Com m and line 8 - ∅ 8 8 Red
Com m and line 9 - ∅ 9 9 Black
Com m and line 10 - ∅ 10 10 Purple
Com m and line 11 - ∅ 11 11 Grey/ pink
Com m and line 12 - ∅ 12 12 Red/ blue
Com m and line 13 - ∅ 13
Re
ar
of
the
rack
13 White/ green
Com m and line 14 - ∅ 14 14 Brown/ green
Com m and line 15 - ∅ 15 15 White/ yellow
Com m and line 16 - ∅ 16 16 Yellow/ brown
Com m and line
+ 17 White/ grey
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
ALARM CONTROL CARD W I TH 8 OUTPUT LI NES MONI TORED THROUGH POLARI TY REVERSAL
The eight 500 m A output lines, which the card m onitors through reversal of their polarit y, are m ainly
ut ilised to cont rol actuators. The card is suitable for use in system s that include devices conform ing to the
NFPA standards, where it can act ivate the alarm sounders.
MAI N CHARACTERI STI CS
Line m onitor ing through polar it y reversal
Outputs act ivated in both steady and pulsing m ode
Can be hot swapped
250 m A available per each com m and output
Non redundable (Note 1)
Tem perature test ing of DMOS and elect ronic com ponents
Software-configurable operat ing m ode
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws.
The card can be connected to FT3104-N which provides four polar it y reversal
2A/ 24Vdc outputs.
OPERATI ON
The card periodically perform s the test on the single channels by invert ing the output signal for durat ion
of about 200 m icroseconds. I n case of discrepancy between configured signal and read signal, the stat ion
signals prom pt ly a fault situat ion. For each single output , the following situat ions are checked: Line
opening, Short -circuit towards posit ive, Short -circuit towards negat ive, pilot DMOS device fault , pilot
DMOS device overheat ing, Supply voltage out of adm it ted lim its. All the channels are tested during
operat ion every 2 seconds.
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Param eter
Act ivat ion m ode
• Steady, normally energised
• Steady, normally de-energised
• Per iodical
• Pulsing mode 1
• Pulsing mode 2
• I SA 1A logics
• Delayed after act ivat ion
• Delayed after de-act ivat ion
• Delayed after enabling
Period 1 to 255 seconds, in pulsing and per iodical mode only
Type of output normal or sounder
Status OUTPUTS 1 to 8
YELLOW LED RED LED
Line in normal condit ion - - Line excluded or disabled ⊗ - Line in t rouble condit ion ∅ - Line act ivated - ⊗
LED status legend ⊗ = on ∅ = blinking - = off
CARD S8 1 - OC6 2 0 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
Connect ions
The card OC6201 can be connected direct ly or through the card FT3104-N
Funct ion Connect ion with FLAT CABLE
Connect ion with PLUG CABLE
Com m and line 1 + ∅ 1
Scre
w t
erm
ina
l
FT
32
01
FT3201-N
1 White
PC2001-S
- ∅ 2 2 Brown
Com m and line 1 + ∅ 3 3 Green
- ∅ 4 4 Yellow
Com m and line 1 + ∅ 5
5 Grey
- ∅ 6 6 Pink
Com m and line 1 + ∅ 7 7 Blue
- ∅ 8 8 Red
Com m and line 1 + ∅ 9 9 Black
- ∅ 10 10 Purple
Com m and line 1 + ∅ 11 11 Grey/ Pink
- ∅ 12 12 Red/ Blue
Com m and line 1 + ∅ 13
Ba
ck
sid
e o
f
the
ra
ck
13 White/ Green
- ∅ 14 14 Brown/ Green
Com m and line 1 + ∅ 15 15 White/ Yellow
- ∅ 16 16 Yellow/ Brown
OPTI ONAL CARD FT3 1 0 4 - N
I f the available 500mA per
channel are not sufficient ,
the card can be connected to
this module, which provides
four polar ity reversal
2A/ 24Vdc outputs.
Connect ion between the card
and the module is effected by
interposit ion of an
ST7/ FT3201 module or an
ST7/ PC2001-S cable plug.
BR1 Term inal Block
∅ 1 Posit ive of 25Vdc elect r ic supply
∅ 2 Negat ive of 25Vdc elect r ic supply
BR2 Term . Block BR3 Term . Block
from card to field
∅ 1 Output 1
OC6201
∅ 1 Output 1
Sounders (2A ∅ 2 ∅ 2
∅ 3 Output 2
OC6201
∅ 3 Output 2
Sounders (2A) ∅ 4 ∅ 4
∅ 5 Output 3
OC6201
∅ 5 Output 3
Sounders (2A) ∅ 6 ∅ 6
∅ 7 Output 4
OC6201
∅ 7 Output 4
Sounders (2A) ∅ 8 ∅ 8
Connect ion exam ple of actuators m anaged w ith polarity reversal
Redundancy ( note 1 )
The card cannot be redundant due to the polar it y reversal for line m onit or ing.
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
4 - MONI TORED LI NE CONTROL CARD
The four 2A output lines of the card are m ainly ut ilised to cont rol solenoids and heavy loads. The card is
part icular ly suitable to m anage autom at ic fire fight ing system s, where it can be used to operate
ext inguishing agent release solenoid valves, or visual-audible evacuat ion and alarm devices.
MAI N CHARACTERI STI CS
Redundable (note 1)
Can be hot swapped (note 2)
Suitable for applicat ion fault - tolerant up to level SIL3 of the standard I EC61508
Outputs can be paralleled (note 3)
Line self- test ing every 2 seconds
Cont inuous m onitor ing of short / opening/ fault condit ion of pilot circuit
I nternal tem perature m onitor ing of the com m and device and of the elect ronic supply
2m A per output available for resist ive loads
Can pilot elect r ically explosive cart r idge actuators
Software-configurable operat ing m ode
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
OPERATI ON
The card cyclically tests each line, by reversing the output signal for about 200 m icroseconds. I n case of
discrepancy between set t ing and reading, the panel provides a fault signal. For each output , the following
condit ions are m onitored: Line opening, Short -circuit towards posit ive, Short -circuit towards negat ive,
DMOS fault , DMOS overheat ing, Supply voltage out of range. All lines are autom at ically tested every 2
seconds.
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Param eter
Act ivat ion m ode
• Steady, normally energised
• Steady, normally de-energised
• Per iodical
• Pulsing mode 1
• Pulsing mode 2
• I SA 1A logics
• Delayed after act ivat ion
• Delayed after de-act ivat ion
• Delayed after enabling Period 1 to 255 seconds, in pulsing and per iodical mode only
Type of output normal or sounder
Status OUTPUTS 1 to 4
YELLOW LED RED LED
Line in normal condit ion - - Line excluded or disabled ⊗ - Line in t rouble condit ion ∅ - Line act ivated - ⊗
LED status legend ⊗ = on ∅ = blinking - = off
CARD S8 1 - OC6 0 0 2
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
Connect ion exam ple of actuators w ith heavy loads
Redundancy ( Note 1 )
I n fault - tolerant systems, this card has to be duplicated, i.e. two cards are to be used, which must be installed in two
cont iguous racks. Each input line from the field has to be connected to both cards and its exclusion is only possible
from both of them.
Hot Sw ap ( Note 2 )
The card can be removed and replaced without switching off the panel, which would imply system inoperability.
W arning
I n case of normally energised outputs, configure the system to enable hot swap without undesired consequences.
Current per line ( Note 3 )
Lim ited to 10 W, in case of connect ion with filament bulbs.
Funct ion
Connect ion with PLUG CABLE
Output 1 +
1 White
CPC2201
-S
Output 2
+
2 Brown
Output 3 +
3 Green
Output 4 +
4 Yellow
CONNECTI ON
Warning : Due to required current ,
only cable plug connect ion is
possible.
Connect ion between the card and
the field is carr ied out by means of a
cable, provided with a plug- in
connector at one of its ends.
The other end can be connected to a
term inal block to be placed on the
backside of the rack.
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONTROL CARD ( ECD) FOR FI RE EXTI NGUI SHI NG SYSTEMS
This card gathers and elaborates the signals and logics relat ing to fire ext inguishing cont rol. Using the
inputs and outputs m anaged by the other cards of the ST7 panel, it enables system com pliance with the
EN 12094-1 standard. I t does not have physical I / O, but uses inputs and com m ands m anaged by other
cards of the ST7 system .
MAI N CHARACTERI STI CS
I T PERFORMS THE FUNCTI ONS OF AN ECD (elect r ic cont rol and delay device)
I T IS CERTIFIED, BY AN ACCREDITED BODY, TO THE EUROPEAN C.P.D. -
CONSTRUCTION PRODUCT DIRECTI VE (Cert . n° 0 5 1 - CPD- 0 1 3 9 / 0 1 3 8 / 0 1 3 7 )
I T MAKES THE ST7 SYSTEM COMPLIANT TO EN 12094-1
I t allows to build fire ext inguishing system s cert ified SIL2 and SIL3 ( IEC 61508)
LED indicat ion of ext inguishing zone status
I t m anages 4 vir tual input s (V- I N) and 10 vir tual outputs (V-OUT)
0-60 second ext inguishing cont rol delay is configurable at operator level 3
Can be hot swapped (Note 1)
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
OPERATI ON
I t elaborates the inputs and outputs physically located on other cards of the ST7 panel using vir tual
inputs and outputs that are processed, according to preconfigured logics, for ext inguishing system cont rol
in com pliance with regulat ions.
ZONE STATUS I NDI CATI ON
POSSI BI LE CONFI GURATI ON
Each ext inguishing zone needs anEX9001 card, whatever the num ber of it s sect ions, while the physical
outputs to operate the ext inguishing system (actuators, valves, visual/ audible alarm s, etc.) can be,
indifferent ly, on ST7-OC6001 (eight 0.5A channels) , ST7-OC6201 (eight polar ity reversal channels) or
ST7-OC6002 ( four 2A channels) cards, or addressable m odules on BUS.
The inputs from the field (pushbut tons, lim it switches, sequence stop, detect ion) are connected to such
cards as the ST7- IC4001 (eight detect ion lines) or/ and the ST7-AL7002-S loop cont rol cards.
Each ext inguishing zone, even in the case of very com plex system s, can be configured, through the
Silver-Pro7 program , to create logic associat ions between vir tual inputs and outputs (V- IN 1-4; V-OUT 1-
10) and physical inputs and outputs.
LED Funct ion
ACTI VATED Act ivated condit ion
RELEASED Ext inguishing system operated
FAULT General fault
DI SABLED General disabling
I NHI BI T Emergency stop
HOLD Emergency hold
AUTOMATI C OFF Automat ic mode excluded
RESERVE Reserve cylinder bank
CARD S8 1 - EX9 0 0 1
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
VI RTUAL CONNECTI ONS The card elaborates the virtual inputs const ituted by the output variables from the other panel cards ( IN,
END) to produce vir tual outputs (OUT) , which are obtained through software elaborat ion by internal logic
devices.
The vir tual outputs thus generated are input variables to other cards and are used to create special
funct ional logics for fire ext inguishing system cont rol.
Hot Sw ap ( Note 1 )
The card can be removed and replaced without switching off the panel, which would imply system inoperability.
I nput variables Funct ions
V1 Manual act ivat ion
V2 Automat ic actuat ion
(AND)
V3 Automat ic actuat ion
excluded
V4 Discharge t ime extended
(Hold)
V5 Ext inguishing st r ing
inhibit ion (Abort )
V6 Reserve bat tery select ion
V7 Secondary discharge
V8 Act ive system input
(Flow/ Pls)
V9 General anomaly
V10 General disabling
Output variables Funct ion
V1 Act ive condit ion
V2 Main bat tery start
(pr imary)
V3 Reserve bat tery start
(pr imary)
V4 Secondary discharge
main bat tery
V5 Secondary discharge
reserve bat tery
V6 Flashing warning alarms
V7 Fix warning alarms
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
SPECI AL LOGI C CONTROL CARD
This card is designed to produce and m anage funct ional logics through flip/ flop, toggle and t im er devices.
Tim ers can be configured to operate in two m odes (A and B) .
MAI N CHARACTERI STI CS
Operat ing m ode configurable through Silver-Pro7 software program
Up to 100 software logic devices for flip/ flop funct ions of a set / reset t ype
Up to 100 software logic devices for “ toggle” funct ions
Up to 100 software t im ers individually program m able from 0 to 255 seconds
Hot swap
Com m unicat ion m anagem ent by FPGA
I nternal logic m anagem ent by m icro-cont roller
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
OPERATI ON
The card elaborates the virtual inputs const ituted by the output variables from the other panel cards to
produce vir tual outputs, which are obtained through software elaborat ion by internal logic devices.
The vir tual outputs thus generated are input variables to other cards and are used to create part icular
funct ional logics.
STATUS I NDI CATI ON
CONFI GURATI ON
Both the logic devices and the input / output variables are defined during configurat ion, which is carr ied
out through the Silver-Pro7 program .
The logic devices that can be produced by m eans of this card are the following:
Software Device Configurat ion
Type Variables Mode Alarm Delay Alarm Signalling
Flip Flop I nput / Output Set / Reset 0-255 seconds Normal/ Silent / Buzzer only
Toggle I nput / Output I n-Out Not applicable Normal/ Silent / Buzzer only
Timer I nput / Output Timer A or Timer B 0-255 seconds Normal/ Silent / Buzzer only
TERMI NAL BLOCK CONNECTI ON
This card has no connect ion with the field and, therefore, needs no wir ing to a term inal block.
LED Funct ion
F1 Lights up when an input var iable to the card is act ivated
F2 Lights up when an output var iable from the card is act ivated
F3 Blinks when t imers are act ivated
DI SABLED Lights up when an input or an output var iable to/ from the card is disabled
CARD S8 1 -LS9 0 0 2
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
Logic Device w ith Flip-Flop Funct ion - Set / Reset Type
A Set input provides a high output
(Q) , after a delay t ime (T) .
The output is zeroed by the front
end of the Reset input .
I f Reset occurs within the delay
t ime (T) , the output (Q) remains
low.
Logic Device w ith Tim er Funct ion - Mode A
The input ( I n) must remain high,
dur ing the set delay t ime (T) ,
otherwise the output (Out)
remains low.
After the delay t ime (T) , the
output (Out) remains high as long
as the input ( I n) is also high.
Logic Device w ith Tim er Funct ion - Mode B
The act ivat ion of the input ( I n)
increases the output (Out) , which
remains high for the durat ion of
the set delay t ime (T) , or as long
as the input ( I n) remains act ive.
Logic Device w ith Toggle Funct ion
The act ivat ion (on front end) of
the input ( I n) raises the output
(Out) .
The next act ivat ion of the input
( I n) zeroes the output (Out) .
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CARD FOR CONTROL OF ADDRESSABLE AND ANALOG DEVI CES W I TH DCP PROTOCOL
This card m anages the addressable devices that adopt the DCP (Digital Communicat ion Protocol) protocol of
HOCHIKI Am erica.
A wide range of fire detectors, push but tons, opt ical-acoust ic indicators and input / com m and m odules UL
Listed and FM APPROVED are available.
MAI N CHARACTERI STI CS
Non redundant (note 1)
Hot swap
127 addresses with 3 I / O channels each
Loop connect ion ( farthest point at 1500 m )
Selectable sensibilit y of detectors
Able to cont rol UL Listed and FM Approved devices:
Sm oke detectors
Com bined detectors (sm oke/ tem perature)
Tem perature detectors
Short circuit isolators
Addressable signalling units
Mini-zone addressable m odules
Addressable push but tons
Periodic auto- test of the card operat ion and of all connected devices
Com m unicat ion m anagem ent by FPGA
Front plug- in on 19’’ rack, with locking screws
LED I NDI CATI ONS
OPERATI ONS
The card com m unicates, t hrough the DCP protocol, with all the devices on a loop, periodically polling
them or receiving calls ( interrupts) from the devices that have detected a status variat ion. Alarm ing
occurs after the inform at ion has been processed, through specific algorithm s for the devices; e.g. sm oke
detectors can provide dynam ic alarm thresholds that adjust them selves to compensate for opt ic sensing
elem ent contaminat ion.
PROGRAMMABLE FEATURES
Status condit ions Operat ions Normal operat ing mode Normally open or normally closed in the normal status
Channel logic status (note 2) Latching/ non latching
Smoke detectors sensibility predeterm ined
Alarm thresholds I nput pre alarm / alarm
Signalling on outputs for alarm Programmable depending on the type of actuator
Output act ivat ion way Programmable depending on the type of actuator
Time ( impulsive and per iodic way only) Programmable depending on the type of actuator
Opt ical acoust ic signals As for UL864 standard, with synchronizat ion
LED Status I ndicat ion
ACTI VE ⊗ One or more inputs in alarm or act ive condit ion
DI SABLED ⊗ One input or output disabled
FAULT ∅ Fault condit ion
LOOP FAULT ∅ Loop short -circuit or opening
LOG ON FAULT ∅ Discrepancy between read and expected devices
SERVI CE ∅ Opt ical smoke detector(s) dir ty
TX POL. ∅ Data t ransm ission to devices on loop
RX POL. ∅ Data receipt from devices on loop
Legend: ⊗= led on ; ∅= led blinking
CARD S8 1 -AL7 0 0 1 - S
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A TERMI NATI ON MODULE FT3 2 0 1 - N Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors. The electronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2.
CONNECTI ON VI A CABLE PLUG PC2 3 0 1 - S
Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack.
Connect ion exam ple The connect ion between the card and the devices takes place through two wires (posit ive and negat ive line) which
return to the tab form ing a r ing. This connect ion is allowed if the devices do not exceed the maximum current
allowed for the loop. I n case the devices require a separate power supply, this will consist of a fur ther connect ion of
two conductors to carry the posit ive and negat ive of the 24 Vdc.
NOTES
Redundancy ( note 1 )
The card cannot be redundant because of the int r insic operat ion of the ser ial communicat ion protocol.
Latching m ode ( note 2 )
The alarm threshold is memorised unt il the reset , otherwise all t ransact ions will take place following the line.
DCP com pat ibility
This card is compat ible with the DCP protocol HOCHI KI AMERI CA.
For fur ther informat ion, please visit the internet site of the manufacturer: ht tp: / / www.hochikiamerica.com
As example, below there are some devices of the protocol:
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE Posit ive loop out + ∅ 1
FT3202
1 White
CPC2301-S Negat ive loop out - ∅ 2 2 Brown
Posit ive loop in + ∅ 3 3 Green
Negat ive loop in - ∅ 4 4 Yellow
- - - ∅ 5 5
- - - ∅ 6 6
- - - ∅ 7 7
- - - ∅ 8 8
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
ANALOGUE ADDRESSABLE DEVI CE CONTROL CARD - ESP PROTOCOL
Cont rol card for devices that are addressable through the HOCHIKI ESP protocol. SMOKE, TEMPERATURE
and COMBI NED fire detectors, as well as PUSHBUTTONS and CONTROL MODULES, with m onitored and
non-m onitored lines, are available with the ESP protocol
This type of card is used only for fire fight ing system cont rol.
MAI N CHARACTERI STI CS
NON-REDUNDANT (Note 1)
CAN BE HOT SWAPPED (Note 2)
Up to 127 addresses, 3 channels each
Loop connect ion ( farthest point at 1500 m )
Detector sensit ivit y can be set as HI GH/ MEDIUM/ LOW
Can cont rol detectors of the ASX series, cert ified to EN 54-7 and EN 54-9
Sm oke detector ALG (photoelect r ic) and AIE ( ionisat ion)
Com bined detectors (sm oke/ tem perature) ACA-E
Tem perature detectors ATG-E
Short -circuit isolators YBO and YBO-R/ SCI (with socket )
Addressable sounders CHQ-WS and CHQ-BS (with socket )
CHQ-MZ m ini-zone, CHQ-R double relay, CHQ-S double input addressable m odules
MCP-E addressable call points (pushbut tons)
Periodical funct ionalit y self- test ing of card and all connected devices
Com m unicat ion m anagem ent by FPGA
Front plug- in on 19’’ rack, with locking screws.
OPERATI ON
The card com m unicates, t hrough the ESP protocol, with all the devices on a loop, periodically polling
them or receiving calls ( interrupts) from the devices that have detected a status variat ion. Alarm ing
occurs after the inform at ion has been processed, through specific algorithm s for the devices; e.g. sm oke
detectors can provide dynam ic alarm thresholds that adjust them selves to compensate for opt ic sensing
elem ent contaminat ion.
PARAMETER CONFI GURATI ON VI A SOFTW ARE
I nput operat ing mode NO/ NC
Channel logic status (Note 3) Latching/ Non- latching
Smoke detector sensit iv ity High/ Medium/ Low
Alarm thresholds Pre-alarm / Alarm
Alarm output Normal/ Silent / Buzzer only
Output act ivat ion mode Steady energised, steady de-energised, per iodical, pulsing
Per iod (pulsing and per iodic mode only) Output set table between 1 and 15 seconds
Tone of sounders on loop 7 different tones set table
Volume of sounders on loop 55 to 98 dBA, set table on 13 steps
LED Status I ndicat ion
ACTI VE ⊗ One or more inputs in alarm or act ive condit ion
DI SABLED ⊗ One input or output disabled
FAULT ∅ Fault condit ion
LOOP FAULT ∅ Loop short -circuit or opening
LOG ON FAULT ∅ Discrepancy between read and expected devices
SERVI CE ∅ Opt ical smoke detector(s) dir ty
TX POL ∅ Data t ransm ission to devices on loop
RX POL ∅ Data receipt from devices on loop
LED status legend ⊗ = on ∅ = blinking
CARD S8 1 -AL7 0 0 2 - S
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A TERMI NATI ON MODULE FT3 2 0 1 - N Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors. The electronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2.
CONNECTI ON VI A CABLE PLUG PC2 3 0 1 - S
Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack.
Connect ion Exam ples The connect ion between the card and the devices takes place through two wires (posit ive and negat ive line) which
return to the tab form ing a r ing. This connect ion is allowed if the devices do not exceed the maximum current
allowed for the loop. I n case the devices require a separate power supply, this will consist of a fur ther connect ion of
two conductors to carry the posit ive and negat ive of the 24 Vdc.
NOTES
Redundancy ( Note 1 )
Card redundancy is not possible, due to ser ial com municat ion protocol.
Latching Mode ( Note 3 )
An alarm status persists unt il reset .
ESP com pat ibility
This card is com pat ible with HOCHIKI ’s ESP protocol.
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE Posit ive loop out + ∅ 1
FT3202
1 White
CPC2301-S Negat ive loop out - ∅ 2 2 Brown
Posit ive loop in + ∅ 3 3 Green
Negat ive loop in - ∅ 4 4 Yellow
- - - ∅ 5 5
- - - ∅ 6 6
- - - ∅ 7 7
- - - ∅ 8 8
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
MODBUS PROTOCOL SERI AL COMMUNI CATI ON CARD
This Modbus RTU Master/ Slave protocol comm unicat ion card provides two independent output ports: one
RS485 (Half Duplex) and one RS232.
MAI N CHARACTERI STI CS
Non- redundable but with double connect ion (note 1)
Can be hot swapped (note 2)
Modbus RTU protocol
Master or Slave configurat ion
Manages the following variables:
512 Boolean input variables (32x16-bit words)
512 output Boolean variables (32x16-bit words)
130x16-bit analogue variables
Analogue variables are related to 4-20 m A input card values
One RS 232 serial + 1 RS 485 serial line usable sim ultaneously
MODBUS address and param eter configurat ion through two 8-selector dip switches
Periodical funct ionalit y self- test ing of card and all connected devices
Com m unicat ion m anagem ent by FPGA
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
OPERATI ON
I n MASTER m ode, the card is only used for connect ing, through the RS 485 port , two peer- to-peer or
Master/ Slave ST7 panels.
I n SLAVE m ode, the card is used to respond to the requests from an external supervisory system - which
m ay be a PC, a PLC, another panel, a PES, or a SCADA – cyclically interrogat ing the ST7 panel to update
it s data base.
Further inform at ion on card operat ing m ode can be provided, upon request , in a specific docum ent
describing the param eters used by the protocol.
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Param eter MODBUS address 1 to 255, through 8-selector dip switch SW1
SLAVE mode address refers to MD8001-N card
MASTER mode address refers to SLAVE per ipheral to be sent controls
Baud rate set table through SW2 (1-2-3) 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Par ity set table through SW2 (4-5) none, even, odd
RS 485 line term inable with jumper 120 Ohm
LED Status I ndicat ion
ACTI VE ⊗ One input var iable is act ive
DI SABLED ⊗ One input or output var iable is disabled
FAULT ∅ Communicat ion fault ( in Master mode only)
MASTER ∅ Master mode operat ion
TX RS232 ∅ Any transm ission from RS232 port
RX RS232 ∅ Any receipt on RS232 port
TX RS485 ∅ Any transm ission from RS485 port
RX RS485 ∅ Any receipt on RS485 port
LED status legend ⊗ = on ∅ = blinking
CARD S8 1 -MD8 0 0 1 - N
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A TERMI NATI ON MODULE Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors. The electronics- type term inals are suitable.
CONNECTI ON VI A CABLE PLUG
Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack or into a DB9 type connector.
Exam ples
A FT3202-N term inal block m odule is used for serial RS232 connect ion between card and PC or PLC, if
any, via a DB9 connector and term inal blocks 1, 2, and 3.
Term inals 4, 5 and 6 are t o be used, taking into considerat ion m anufacturer 's inst ruct ions on cable type
and wir ing.
Redundancy ( Note 1 )
I n fault - tolerant systems, this card has to be duplicated, i.e. two cards are to be used, which must be installed in two
cont iguous racks.
Hot Sw ap ( Note 2 )
The card can be removed and replaced without switching off the panel, which would imply system inoperability.
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE TX DATA RS232 T ∅ 1
FT3202-N
1 White
PC2401-S
RX DATA RS232 R ∅ 2 2 Brown
GND G ∅ 3 3 Green
Posit ive RS485 + ∅ 4 4 Yellow
Negat ive RS485 - ∅ 5 5 Grey
GND G ∅ 6 6 Pink
- - - ∅ 7 7
- - - ∅ 8 8
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
ANALOGUE ADDRESSABLE DEVI CE CONTROL CARD - SSP PROTOCOL
Cont rol card for SSP (Silver-Tec Protocol) protocol addressable devices. I t can m anage up to 127
analogue/ digital input addressable modules and cont rol m odules. This card must not be used with fire
detect ion system s.
MAI N CHARACTERI STI CS
NON REDUNDANT (Note 1)
CAN BE HOT SWAPPED (Note 2)
127 addresses on SSP protocol
Serial connect ion on 1200 m bus
Serial line can be looped (3000 m m ax)
Can cont rol following addressable m odules
ST7-Mod-DI : eight non-m onitored inputs
ST7-Mod-DO : eight non- m onitored open collector outputs
ST7-Mod-AIT : four double balanced inputs, for int ruder alarm
ST7-Mod-AI020 : one 4-20 m A analogue input
ST7-Mod-AI010 : 1 0-10 V analogue input
ST7-Mod-DISP : status repeater display (Note 3)
Periodical funct ionalit y self- test ing of card and all connected devices
Com m unicat ion m anagem ent by FPGA
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws.
OPERATI ON
The card com m unicates, through the SSP protocol, with all the devices on a loop, periodically polling
them or receiving calls ( interrupts) from the devices that have detected a status variat ion. The analogue
input m odules can be polled, to show device value reading, either by the operator ( from the panel) or by
a supervisory program .
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Status
I nput operat ing mode NO/ NC
Channel logic status (Note 4) Latching/ Non- latching
Analogue module measur ing range See data sheets relevant to addressable devices
Thresholds Pre-alarm / Alarm
Alarm output Normal/ Silent / Buzzer only
Output act ivat ion mode Steady energised, steady de-energised, per iodical, pulsing
Per iod (pulsing and per iodic mode only) Output set table between 1 and 15 seconds
LED Status I ndicat ion
ACTI VE ⊗ One or more inputs in alarm or act ive condit ion
DI SABLED ⊗ One input or output disabled
FAULT ∅ Fault condit ion
LOOP FAULT ∅ Loop short -circuit or opening
LOG ON FAULT ∅ Discrepancy between read and expected devices
SERVI CE ∅ Opt ical smoke detector(s) dir ty
TX POL ∅ Data t ransm ission to devices on loop
RX POL ∅ Receipt of data from devices on loop
LED status legend ⊗ = on ∅ = blinking
CARD S8 1 -AL7 0 0 3 - S
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
CONNECTI ON VI A TERMI NATI ON MODULE Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors. The electronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2.
CONNECTI ON VI A CABLE PLUG
Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack.
Connect ion Exam ples
The connect ion between the card and devices takes place through two wires (posit ive and negat ive line) which
return to the tab form ing a r ing. This connect ion is allowed if the devices do not exceed the maximum current
allowed for the loop. I n case the device requires a separate power supply, this will consist of a fur ther connect ion of
two conductors to carry the posit ive and negat ive of the 24 Vdc. The bus can also operate without r ing closure, in
which case a jumper on the term inal board inputs and outputs of the loop.
NOTES
Redundancy ( Note 1 )
Card redundancy is not possible, due to ser ial communicat ion protocol.
Hot Sw ap ( Note 2 )
The card can be removed and replaced without switching off the panel, which would imply system inoperability.
ST7 -Mod-DI SP Status Repeater ( Note 3 )
The alarm condit ion remains displayed unt il reset .
Latching Mode ( Note 4 )
An alarm status persists unt il reset .
SSP Com pat ibility
This card is compat ible with SSP protocol and with the addressable modules of the ser ies ST7 Mod-XXX.
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE Posit ive loop in + ∅ 1
FT3202
1 White
CPC2301-S Negat ive loop in - ∅ 2 2 Brown
Posit ive loop out + ∅ 3 3 Green
Negat ive loop out - ∅ 4 4 Yellow
- - - ∅ 5 5
- - - ∅ 6 6
- - - ∅ 7 7
- - - ∅ 8 8
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
ANALOGUE ADDRESSABLE DEVI CE CONTROL CARD – APOLLO PROTOCOL
Cont rol card for addressable devices that require APOLLO DISCOVERY and XP95 protocols.
With these protocols a wide range of fire detectors, push but tons, opt ic-acoust ic signalling and
input / com m and m odules are available.
MAI N CHARACTERI STI CS
Non redundant (note 1)
Can be hot swapped
127 m ult ichannel addresses
Loop connect ion ( farthest point at 1500 m eters)
Detector sensit ivit y selectable during the configurat ion of the panel
Sensors cert ified to EN54 and for m arine applicat ions
Sm oke detectors (photoelect r ic and ionisat ion)
Com bine detectors (sm oke/ tem perature)
Tem perature detectors
Short -circuit isolators
Addressable sounders
Addressable push but tons
Wide range of addressable m odules with several inputs/ outputs
Sensors and wireless interface units XPander
Periodical funct ionalit y self- test ing of card and all connected devices
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
LED indicat ion on card
OPERATI ON
Through two connect ion and feeder cables, the card com m unicates with all devices connected on the
loop, periodically polling them or receiving calls ( interrupt ) from the devices that have detected a status
variat ion.
Alarm ing occurs after the inform at ion has been processed, through specific algorithm s for the devices;
e.g. sm oke detectors can provide dynam ic alarm thresholds that adjust them selves to com pensate for
opt ic sensing elem ent contam inat ion.
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Status Operat ions Operat ing mode: NA or NC
Channel logic status (note 2) Latching/ Non- latching
Smoke detectors sensibility Set table depending on the type of sensor
Thresholds Set table depending on the type of sensor
Signalling mode on alarm outputs Normal / Silent / buzzer only
Output act ivat ion mode Steady energised, steady de-energised, per iodical, pulsing
Per iod (pulsing and per iodic mode only) Output set table between 1 to 15 seconds
Horn tone on the loop Set table depending on the type of signalling
Horn volume on the loop Set table depending on the type of horn
LED Status I ndicat ion
ACTI VE ⊗ One or more inputs in alarm or act ive condit ion
DI SABLED ⊗ One input or output disabled
FAULT ∅ Fault condit ion
LOOP FAULT ∅ Loop short circuit or opening
LOG ON FAULT ∅ Discrepancy between read and expected devices
SERVI CE ∅ Opt ical smoke detector(s) dir ty
TX POL. ∅ Data t ransm ission to devices on loop
RX POL. ∅ Data receipt from devices on loop
LED status legend: ⊗= on ; ∅= blinking
CARD S8 1 - F7 0 0 8 CARD S8 1 -AL7 0 0 4 - S
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
Connect ion via term inat ion m odule Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors. The electronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2.
Connect ion via plug cable Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack.
Connect ion Exam ple The connect ion between the card and devices takes place through two wires (posit ive and negat ive line) which return
to the tab form ing a r ing. This connect ion is allowed if the devices do not exceed the maximum current allowed for the
loop. I n case the device requires a separate power supply, this will consist of a fur ther connect ion of two conductors to
carry the posit ive and negat ive of the 24 Vdc.
NOTES
Redundancy ( note 1 )
Card redundancy is not possible, due to ser ial communicat ion protocol.
Latching m ode ( note 2 )
The alarm condit ion remains displayed unt il reset otherwise all t ransact ions will carry on according to the loop.
Com pat ibility of loop com m unicat ion protocol.
This card is compat ible with protocols APOLLO DI SCOVERY and XP95.
For fur ther informat ion please visit the site of device’s manufacturer: ht tp: / / www.apollo- fire.co.uk
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE Loop out + + ∅ 1
FT3202
1 White
CPC2301-S Loop out - - ∅ 2 2 Brown
Loop in + + ∅ 3 3 Green
Loop in - - ∅ 4 4 Yellow
- - - ∅ 5 5
- - - ∅ 6 6
- - - ∅ 7 7
- - - ∅ 8 8
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
ADDRESSABLE DEVI CE CONTROL CARD – SYSTEM SENSOR PROTOCOL
Sm oke, tem perature, combined detectors, push but t ons, com m and m odules, m anaging m odules and
radio m odules for wireless detectors are available with this protocol.
MAI N CHARACTERI STI CS
Non redundant (note 1)
Can be hot swapped
99 addresses for sensors and 99 addresses for m odules
Loop connect ion ( farthest point at 1500 m eters)
Detector sensit ivit y selectable on 5 or 9 levels
Able to cont rol devices cert ified according to EN 54-7 e EN 54-9 (CPD) .
Sm oke, flam e, tem perature sensors.
Com bined detectors (sm oke/ tem perature)
Mult i element com bined detectors (sm oke/ tem perature/ CO/ flam e)
Short -circuit isolators
Addressable horns
Addressable push but tons
Analogue interface m odules 4-20 m A
Sensors and wireless interface units
Periodical funct ionalit y self- test ing of card and all connected devices
SMD technology m ult ilayer circuit
Front plug- in on 19’’ rack, with locking screws
LED indicat ion on card
OPERATI ON
Through two connect ion and feeder cables, the card com m unicates with all devices connected on the
loop, periodically polling them or receiving calls ( interrupt ) from the devices that have detected a status
variat ion.
Alarm ing occurs after the inform at ion has been processed, through specific algorithm s for the devices;
e.g. sm oke detectors can provide dynam ic alarm thresholds that adjust them selves to com pensate for
opt ic sensing elem ent contam inat ion.
PARAMETER CONFI GURATI ON VI A SOFTW ARE
Status Operat ions Operat ing mode: NA or NC
Channel logic status (note 2) Latching/ Non- latching
Smoke detectors sensibility 5 or 9 set table sensit iv ity levels
Thresholds I nput in pre-alarm / alarm
Signalling mode Fire, Supervisory, Gas, Anomaly, Hide, buzzer only
Output act ivat ion mode Steady energised, steady de-energised, per iodical, pulsing
Per iod (pulsing and per iodic mode only) Output set table between 1 to 15 seconds
LED Status I ndicat ion
ACTI VE ⊗ One or more inputs in alarm or act ive condit ion
DI SABLED ⊗ One input or output disabled
FAULT ∅ Fault condit ion
LOOP FAULT ∅ Loop short circuit or opening
LOG ON FAULT ∅ Discrepancy between read and expected devices
SERVI CE ∅ Opt ical smoke detector(s) dir ty
TX POL. ∅ Data t ransm ission to devices on loop
RX POL. ∅ Data receipt from devices on loop
LED status legend: ⊗= on ; ∅= blinking
CARD S8 1 -AL7 0 0 5 - S
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
Connect ion via term inat ion m odule Connect ion between the card and the field is basically obtained by interposit ion of a term inal block module, which is
mounted on a DI N rail inside the panel and is connected to the card rack by means of a flat cable with two quick
connectors. The electronics- type term inals are suitable for cables having a sect ion area of up to 4 mm2.
Connect ion via plug cable Connect ion between the card and the field is carr ied out by means of a special cable, provided with a plug- in connector
at one of its ends. Cable conductors are wired direct ly onto a marshalling term inal block, while the connector is
plugged into the backside of the rack.
Connect ion Exam ple The connect ion between the card and devices takes place through two wires (posit ive and negat ive line) which return
to the tab form ing a r ing. This connect ion is allowed if the devices do not exceed the maximum current allowed for the
loop. I n case the device requires a separate power supply, this will consist of a fur ther connect ion of two conductors to
carry the posit ive and negat ive of the 24 Vdc.
NOTES
Redundancy ( note 1 )
Card redundancy is not possible, due to ser ial communicat ion protocol.
Latching m ode ( note 2 )
The alarm condit ion remains displayed unt il reset otherwise all t ransact ions will carry on according to the loop.
Com pat ibility w ith protocol SYSTEM SENSOR
This card is compat ible with the protocol SYSTEM SENSOR.
For fur ther informat ion please visit the site of addressable device’s manufacturer.
This image cannot currently be displayed. This image cannot currently be displayed. This image cannot currently be displayed.
This image cannot currently be displayed.
This image cannot currently be displayed.This image cannot currently be displayed.
This image cannot currently be displayed.
Funct ion
Connect ion with FLAT CABLE
Connect ion with PLUG CABLE Loop out + + ∅ 1
FT3202
1 White
CPC2301-S Loop out - - ∅ 2 2 Brown
Loop in + + ∅ 3 3 Green
Loop in - - ∅ 4 4 Yellow
- - - ∅ 5 5
- - - ∅ 6 6
- - - ∅ 7 7
- - - ∅ 8 8
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk
ST7-HV
SUMMARY TABLE OF CARDS FOR SERI ES ST7-HV
DATA ABOUT THE BASE CARDS FOR SERI ES ST7 - HV
CARACTERISTICS CP1101-N DU1001-N BP1301-N FT3001
Dimensions 25 mm x 150
275 mm x 150
75 mm x 150
138 mm x 78
I ndicat ive weight in grams 90 150 75 180
Stocking tem perature -30 + 80 °C -30 + 80 °C -30 + 80 °C -30 + 80 °C
Operat ing tem perature -5 + 50 °C -5 + 50 °C -5 + 50 °C -5 + 50 °C
Relat ive hum idit y 95% NC 95% NC 95% NC 95% NC
Power supply From 22 to 29 Vdc From 22 to 29 Vdc From 22 to 29Vdc From 22 to 29 Vdc
Card absorpt ion ( rest ) 70 mA 70 mA 0 mA 100 mA
Absorpt ion for each channel used NA 10 mA / LED NA 250 mA (max)
Maximum current for output channel NA NA NA 250 mA
Maximum total absorpt ion 80 mA 180 mA NA 600 mA
For a com plete base, consider: One CPU = 280 mA Two CPUs = 380 mA
DATA COMMON TO ALL RACK CARDS OF SERI ES ST7 -HV
CARACTERISTICS
Dimensions (standard 19” height 3 unit s) 25 mm width x 150 mm depth
I ndicat ive weight 90 grams
Stocking tem perature -30 + 80 °C
Operat ing tem perature -5 + 50 °C
Relat ive hum idit y 95% non-condensing
Power supply from 22 to 29 Vdc
( I NDI CATI VE) ABSORPTI ON AT 2 4 VDC OF EACH RACK CARD FOR THE SERI ES ST7 - HV
INPUT , COMMUNICATION AND SERVICE CARDS IC4001 IC5001 IC5002 IC5003 MD8001-N
RC1201-N
Card absorpt ion ( rest ) (mA) 18 35 45 70 14 50
Absorpt ion for each channel used (mA) 5 4-16 4-16 4-16 - -
Maximum current for each output channel (mA) - 4-21 4-21 - - -
Card maximum total absorpt ion (mA) 58 72 120 198 14 20
I ndicat ive absorpt ion ( * ) to calculate at rest (mA) 58 40 55 110 16 50
COMAND CARDS AND SPECIAL LOGICS OC6001 OC6101 OC6201 OC6002 EX9001 LS9002
Card absorpt ion ( rest ) (mA) 35 12 25 35 12 16
Absorpt ion for each channel used (mA) 4 - 4 8 - -
Maximum current for each output channel (mA) 500 250 250 2000 - -
Card maximum total absorpt ion (mA) - - - - - - - - 12 16
I ndicat ive absorpt ion ( * ) to calculate at rest (mA) 67 12 67 67 12 16
LOOP AND COMMUNICATION CARDS AL7001-S AL7002-S AL7003-S AL7004-S AL7005-S
Card absorpt ion ( rest ) (mA) 90 90 70 90 39
Absorpt ion for each channel used (mA) - - - - - - - - - -
Maximum supplied current for loop (mA) 400 400 250 400 500
Card maximum total absorpt ion (mA) 490 490 320 490 539
I ndicat ive absorpt ion ( * ) to calculate at rest (mA) 300 300 200 300 400
Note: ( * ) to determ ine the power absorpt ion at rest sum the power absorpt ion at rest of all connected devices
Silver-Tec Ltd Tel: +44 (0)1384 671611 Email: [email protected] www.silver-tec.co.uk