Page 1: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

EOCR-MS Schneider Electric EOCR Multi-Monitoring and Setting Program

EOCR-MS User Guide

Rev-A.16 Apr 24.2015

Copyright ⓒⓒⓒⓒ Schneider Electric Ltd.

All rights reserved.

Page 2: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Copyright and Disclaimer

이 문서의 저작권은 SCHNEIDER ELECTRIC 에 있습니다.

EOCR, EOCR-MS 는 SCHNEIDER ELECTRIC 의 Trademarks 입니다.

SCHNEIDER ELECTRIC 의 공식적인 허가 없이 이 문서의 일부 또는 전체를 복제, 전송, 배포하거나 변경하

여 사용할 수 없습니다.

이 문서는 정보 전달 및 교육의 목적으로만 만들어졌습니다.

License

EOCR-MS 는 License 가 등록되어야 사용할 수 있습니다.

License 는 1개의 PC에 1개가 필요합니다.

License 관련 정보는 이 문서의 아래를 참고하십시요.

3. EOCR-MS 문제 해결 Guide -> 3.1 EOCR-MS License Error 발생 시

Feedback

SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 향상시키고자 항상 노력하고 있습니다.

EOCR-MS 사용 시 발생하는 문제, 질문 사항 등이 있으면 아래로 알려주시기 바랍니다.

Tel (고객센터) : 1588-2630

http://www.schneider-electric.co.kr

Page 3: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Document Version & History

Version Day of Release History EOCR-MS Version A.0 2013.10.28 A.0 배포

A.12 2013.12.03 A.12 배포 V1.0

1) Contents, Contact 정보 설명 추가

2) License 관련 정보, 문제 해결 설명 추가

A.13 2014.01.09 A.13 배포 V1.4

1) 통신 포트 확장 관련 내용 추가 (Ethernet Gateway 연결 관련)

A.15 2014.02.11 A.15 배포 V1.5

1) 100% 전류 초과 시 아이콘 추가

2) sEOCR Meter Display Option (전압 또는 파워 선택) 설명 추가

A.16 2015.04.24 A.16 배포 V1.7

1) Modbus-TCP 기능 설명 추가

2) Chart Display 기능 설명 추가

3) Event Window 기능 설명 추가

Page 4: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Contents

1 EOCR-MS 소개 ......................................................................................................... 6

1.1 EOCR-MS 기능 및 특징 ........................................................................................ 7

1.2 EOCR-MS Loader 설명 ......................................................................................... 9

1.2.1 Port

1.2.2 Baud Rate

1.2.3 Parity

1.2.4 Stop Bit

1.2.5 Timeout

1.2.6 Interval

1.2.7 Default Setting

1.2.8 Load EOCR-MS

1.3 EOCR-MS 설명 ................................................................................................. 15

1.3.1 매뉴 & Toolbar

1.3.2 Simple Icon display window

1.3.3 순환 모드와 정지 모드

1.3.4 Event log window

1.4 EOCR-MS 매뉴 설명 ........................................................................................... 22

1.4.1 Device Load

1.4.2 Rotate Display Mode

1.4.3 Log Manage

1.4.4 Option – sEOCR Meter Display

1.4.5 Waveform Configure

1.4.6 Waveform Current

1.4.7 Waveform Voltage

1.4.8 Fault History Button

1.4.9 Set Button

1.4.10 Chart Display Option

2 EOCR-MS Easy Use Procedure ................................................................................. 32

2.1 Monitoring Procedure ......................................................................................... 33

2.1.1 Check Device Manager Communication Port : Modbus-RTU 연결 시

2.1.2 Check Device Manager Communication Port : Modbus-TCP 연결 시

Page 5: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

2.1.3 EOCR-MS Loader Configuration and Start EOCR-MS Process

2.1.4 Device Load Configuration and Start Monitoring

2.1.5 Rotate Display Mode & Stop Display Mode (순환 모드와 정지 모드)

2.1.6 Fault History View Example

2.1.7 Waveform View Example

2.2 Setting Procedure .............................................................................................. 41

2.2.1 Click Set Button and Start EOCR Setting Program

2.2.2 Start from 1st Setting : System / Common

2.3 Multi-Process Procedure ...................................................................................... 43

2.3.1 Modbus-RTU 통신 시 물리적인 통신 포트의 확장

2.3.2 Ethernet Gateway 연결

2.3.3 EOCR-MS Loader Configuration and Run another EOCR-MS

3. EOCR-MS 문제 해결 Guide ..................................................................................... 49

3.1 EOCR-MS License Error 발생 시 ............................................................................ 50

3.2 EOCR-MS Fail Log Window 통한 분석 시 ................................................................. 51

3.2.1 EOCR-MS 통신 Error 발생 시

3.2.1.1 Timeout 발생 시

3.2.1.2 CRC Error 발생 시

3.3 EOCR-MS Message Box 발생 시 ............................................................................ 54

3.4 기타 주의 사항 .................................................................................................. 55

3.5.1 통신 케이블의 길이 및 상태

3.5.2 USB 통신 관련 주의 사항

3.5.3 Ethernet Switch 사용 시

Page 6: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1. EOCR-MS 소개소개소개소개

이이이이 장에서는장에서는장에서는장에서는 EOCR-MS 의의의의 기능기능기능기능 및및및및 특징특징특징특징을을을을 설명합니다설명합니다설명합니다설명합니다.

Page 7: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.1 EOCR-MS 기능 및 특징

EOCR-MS 는 SCHNEIDER ELECTRIC 에서 개발한 EOCR Monitoring 기능과 Setting 기능을 수행하는

Powerful 한 Software 입니다.

EOCR-MS 는 아래와 같은 다양한 기능을 제공합니다.

● Multi-Device 지원 :

하나의 SW 는 물리적으로 31 개 까지의 Device 와 동시에 통신할 수 있습니다.

● Multi-Protocol 지원 :

Modbus-TCP, Modbus-RTU 통신프로토콜을 지원하며 Modbus-RTU 모드에서 Node Address 는

1~248 까지 설정할 수 있습니다.

● Multi-Process 지원 :

통신 포트 단위 1개(Modbus-TCP 경우 소켓, Modbus-RTU 경우 COM Port) 에 대해서 하나의 프로

세스를 할당합니다. 따라서 하나의 PC 에서 물리적인 통신포트가 지원하는 한 Device 를 무한확장하

여 통신할 수 있습니다.

● Resizing and Splitter GUI 지원 :

Page 8: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

GUI 는 Resizing and Split 가능합니다.

따라서 일반적인 24인치 이하의 PC 모니터 이외에, 42인치 이상의 대화면 모니터에 연결하여도 모니

터 사이즈에 맞추어져 확장되어 작화 없이 현장에서 모니터링하기에 최적의 방식으로 구현되어있습니

다.

● Icon and Detailed Display 지원 :

Splitter Window 의 좌측에는 아이콘 GUI 를 통해서 모터의 상태를 직관적으로 인식 가능한 GUI

를 보여주고 있으며 Splitter Window 의 우측에는 다양한 정보를 보여주는 GUI 를 보여주게 구성되

어있습니다.

● User Description 지원 :

각 Device 에 대해서 사용자 스스로 Description 을 구분하여 지정하고 확인 할 수 있습니다.

● Fault History and Waveform 지원 :

Fault History 와 Waveform 기능을 통해서 이전 Trip History 를 확인할 수 있습니다.

● Audio 경고 출력 지원 :

경고 상황 시 PC 의 Audio 를 통해서 경고음을 출력하여 GUI 뿐 아니라 소리로도 인지할 수 있도

록 지원하고 있습니다.

Page 9: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.2 EOCR-MS Loader 설명

EOCR-MS Loader 는 EOCR-MS 를 실행시키기 위해서 우선 실행시켜야 하는 SW 입니다.

이렇게 EOCR-MS 를 실행하기위해서 EOCR-MS Loader 를 먼저 실행시키는 이유는 다수의 EOCR-MS 를 실행키쳐 최

적의 모니터링 환경을 지원하기 위함이입니다.

EOCR-MS 의 통신 모드는 EOCR-MS Loader 에서 결정됩니다.

● EOCR-MS Loader 그림

Page 10: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.2.1 Port

TCP/IP 1 ~ TCP/IP 10 까지는까지는 Modbus-TCP 를 위한 Port 입니다.

COM99 까지는 Modbus-RTU 를 위한 Port 입니다.

이때는 PC 장치관리자에 있는 통신 COM Port 심볼릭링크의 Number 를 세팅합니다.

COM1 ~ COM99 까지 세팅할 수 있습니다.

________________________________________________________________________________________________

[주의]

@ Modbus-RTU 통신 포트는 꼭 물리적으로 지원되는 COM Port 임을 확인하십시요.

@ PC 에서 통신포트는 아래와 같은 방법으로 확인할 수 있습니다.

바탕화면 -> 컴퓨터 아이콘 마우스 우측버튼 클릭 -> 속성 -> 하드웨어 -> 장치관리자 -> 포트

Page 11: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

위와 같은 경우 EOCR-MS Loader 의 Port 는 COM3 이 됩니다.

________________________________________________________________________________________________

1.2.2 Baud Rate

Modbus-RTU 를 위한 설정입니다.

38400bps ~ 1200bps 까지 세팅할 수 있습니다.

EOCR 본체의 Baud Rate 값과 일치하여야 합니다.

(EOCR 본체의 Baud Rate 기본값은 19200bps 입니다.)

1.2.3 Parity

Modbus-RTU 를 위한 설정입니다.

Page 12: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

NONE, ODD, EVEN Parity 로 세팅할 수 있습니다.

EOCR 본체의 Parity 값과 일치하여야 합니다.

(EOCR 본체의 Parity 기본값은 EVEN 입니다.)

1.2.4 Stop Bit

Modbus-RTU 를 위한 설정입니다.

ONE 또는 TWO 로 세팅할 수 있습니다.

EOCR 본체의 Parity 값과 일치하여야 합니다.

________________________________________________________________________________________________

[주의]

@ 현재 EOCR 본체에서 Parity 와 Stop Bit 를 구분하여 세팅할 수는 없습니다.

EOCR 본체에서 세팅하는 Parity 값에 Stop Bit 가 포함되어있습니다.

현재 EOCR 본체에서 세팅하는 Parity 값에 포함된 Stop Bit 값을 아래와 같습니다.

EOCR 본체 세팅

Parity Stop Bit

ODD ODD ONE

EVEN EVEN ONE

NONE NONE TWO

NONE1 NONE ONE

________________________________________________________________________________________________

1.2.5 Timeout

Modbus-RTU 를 위한 설정입니다.

통신의 Master (PC, EOCR-MS) 에서 전달하는 Request Packet 에 대해서 통신의 Slave (EOCR 본체) 가 응답

(Response Packet) 하기까지 기다리는 최대 시간을 의미합니다. 이 시간이 지난 후에도 EOCR 본체로부터 Response

Packet 이 없을 시에는 EOCR-MS 는 경고 메시지와 경고 소리를 출력합니다.

Page 13: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.2.6 Interval

Modbus-RTU 를 위한 설정입니다.

1.2.6.1 38400bps Interval

38400bps 기준, 첫 Response 가 있은 후 이후 최종 Data 까지 모두 가져오는데 필요한 시간을 의미합니다.

이 시간이 짮을 경우 CRC Error 가 발생할 수 있으며 이때 EOCR-MS 는 경고 메시지와 경고 소리를 출력합니다.

단 이 시간이 길어질 수록 통신 속도가 느려지므로 최적화된 세팅이 필요합니다.

1.2.6.2 19200bps Interval

19200bps 기준, 첫 Response 가 있은 후 이후 최종 Data 까지 모두 가져오는데 필요한 시간을 의미합니다.

이 시간이 짮을 경우 CRC Error 가 발생할 수 있으며 이때 EOCR-MS 는 경고 메시지와 경고 소리를 출력합니다.

단 이 시간이 길어질 수록 통신 속도가 느려지므로 최적화된 세팅이 필요합니다.

1.2.6.3 9600bps Interval

9600bps 기준, 첫 Response 가 있은 후 이후 최종 Data 까지 모두 가져오는데 필요한 시간을 의미합니다.

이 시간이 짮을 경우 CRC Error 가 발생할 수 있으며 이때 EOCR-MS 는 경고 메시지와 경고 소리를 출력합니다.

단 이 시간이 길어질 수록 통신 속도가 느려지므로 최적화된 세팅이 필요합니다.

1.2.7 Default Setting

이 버튼을 클릭하면 Timeout 과 Interval 값이 EOCR-MS 기준값으로 설정됩니다.

1.2.8 Load EOCR-MS

이 버튼을 클릭하면 EOCR-MS 를 실행하게 됩니다.

이때 EOCR-MS Loader 에서 설정한 통신 Configuration 값이 EOCR-MS 에 적용되어 실행됩니다.

Page 14: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Modbus-TCP 모드 실행 시 아래와 같이 실행됩니다.

Modbus-RTU 모드 실행 시 아래와 같이 실행됩니다.

Page 15: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.3 EOCR-MS 설명

● EOCR-MS 그림 및 설명

EOCR-MS 는 아래와 같은 형태입니다.

1.3.1 매뉴 & Toolbar

EOCR-MS 의 다양한 기능은 위 매뉴 & Toolbar 를 통해서 지원합니다.

Page 16: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

________________________________________________________________________________________________

[참고]

[그림 : Modbus-RTU 연결] [그림 : Modbus-TCP 연결]

위의 Main Bar Text Description 에서 EOCR-MS : COM9 Connection, EOCR-MS : COM7 Connection, EOCR-MS :

COM3 Connection 에서 COMx 는 현재 연결된 통신포트의 심볼릭링크 Number 를 가르쳐줍니다. Modbus-RTU 사

용시 다수의 물리적인 COM 통신포트에 각각의 EOCR-MS 를 실행 시 EOCR-MS 는 위 Main Bar Text Description

으로 구분할 수 있습니다.

(동일한 심볼릭링크에 동일한 EOCR-MS 는 다수개 실행할 수 없습니다.)

Modbus-RTU 경우 위와 같이 PC 장치관리자의 COM 포트 심볼릭링크 Number 와 EOCR-MS Port Number 를 맞추

어야 하지만 Modbus-TCP 경우 소켓 연결을 통한 Ethernet 프로토콜을 사용하므로 위와 같이 EOCR 장비 갯수에 맞

추어 단순희 EOCR-MS 를 순차적으로 확장하여 사용하시면 됩니다.

________________________________________________________________________________________________

Page 17: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.3.2 Simple Icon display window

다양한 Icon 과 Short Description Display 를 통해서 직관적인 Monitoring 기능을 지원합니다.

Page 18: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.3.2.1 Display icon

모터 상태에 맞추어 직관적인 Icon Display 를 지원합니다.

@ Device Load 전 기본 상태 :

@ Motor Stop 시 :

@ Motor 기동 시 :

@ Motor Trip 시 :

@ 재통신 Fail 시 [통신 이상없이 진행되다가이후 Fail 발생 시] :

@ Motor Run 시 [Max Current / OC 가 90 % 미만 시의 예] :

@ Motor Run 시 [Max Current / OC 가 95% (90 % ~ 100 % 는 동일 아이콘형식) 시의 예] :

@ Motor Run 시 [Max Current / OC 가 100 % 초과 시의 예] :

Page 19: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

________________________________________________________________________________________________

[참고]

@ Motor Run 시 Display 되는 Icon 의 우측 Bar 는 10 개로 구성되어있으며 1개의 Bar 는 미세하게 10등분되어

1% 변화에 대해서도 반영되어 Display 됩니다.

@ Motor Trip 시와 재통신 Fail 시는 아래와 같은 경고 Dialog 팝업 창과 경고음을 출력시켜줍니다.

모터 재통신 Fail 시는 정상적인 Monitoring 기능을 수행할 수 없으므로 이때에도 비상상황으로 간주하여 경고기능을

수행하게 됩니다.

________________________________________________________________________________________________

1.3.3 Rotate Display Mode & Stop Display Mode (순환 모드와 정지모드)

1.3.3.1 Rotate Display Mode (순환 모드)

Page 20: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

EOCR-MS 를 최초 실행하면 아래와 같은 모습니다.

이때 Device Load 버튼을 누르면 EOCR 통신을 연결하면 아래와 같이 5초마다 아래 빨강 테두리 영역에 Load

된 EOCR 모니터링 정보를 Update 하며 순환하게 됩니다.

Page 21: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.3.3.2 Stop Display Mode (정지 모드)

아래와 같이 Load 된 Device 의 좌측 원형 Icon 을 클릭하면 순환 모드가 정지되고 선택 한 EOCR 의 정보만 계속 보

여주게 됩니다.

다시 순환모드로 변경하려면 Rotate Display Mode 아이콘을 클릭하면 됩니다.

1.3.4 Event Log Window

EOCR-MS 의 Event Log Window 에서 어떤 Device (EOCR) 에서 Trip 이 일어난 시간, 통신 Fail 이 일어난 시간 등

을 확인할 수 있습니다. 또한 아래와 같이 F-H 버튼을 클릭하여 Fault History 정보를 확인할 수 있습니다.

좌측의 EOCR-MS Toolbar 의 Log Manage 아이콘 클릭 시에 아래와 같이 Log Dialog 가 실행되며 이 Dialog

를 통해서 위 Event Log Window 창의 Log 를 Clear 할 수 도, RTF(Word), XLS, TXT 파일 형식으로도 저장할 수 있

습니다.

Page 22: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.4 EOCR-MS 매뉴 설명

1.4.1 Device Load

EOCR-MS 실행 후 최초에 클릭하여야 하는 버튼입니다. 또한 통신 재설정, User Description 재설정 등을 위해서도 사

용됩니다.

1개의 EOCR-MS 는 Device Load Dialog 를 통해서 물리적으로 최대 31개의 Device 를 연결할 수 있습니다.

1.4.1.1 Device Load – Communication Port Information Read

Device Load Dialog 의 COMMUNICATION PORT INFORMATION READ 영역은 현재 EOCR-MS Loader 를 통해서

설정한 통신 파라미터 정보를 보여줍니다.

아래는 EOCR-MS Loader 의 COM3 포트를 선택 후 EOCR-MS 실행 시 Device Load 창의 Communication Port

Information Read 상황입니다.

Page 23: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

아래는 EOCR-MS Loader 의 TCP/IP 1 포트를 선택 후 EOCR-MS 실행 시 Device Load 창의 Communication Port

Information Read 상황입니다.

Page 24: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.4.1.2 Device Load – Motor Name (User Description Edit Box)

Device Load Dialog 의 Motor Name Edit Box 를 통해서 User 가 Display 하고자 원하는 Device 정보를 입력할 수

있습니다.

1.4.1.3 Device Load – Product Name

Device Load Dialog 의 Product Name Combo Box 를 통해서 nEOCR 또는 sEOCR 을 선택할 수 있습니다.

(현재 버전은 nEOCR, sEOCR 만을 지원합니다.)

1.4.1.4 Device Load – Slave ID

Modbus RTU 통신 연결에서만 설정하는 파라미터입니다.

Device Load Dialog 의 Slave ID Combo Box 를 통해서 EOCR 본체의 Modbus RTU ID (1~248) 를 할당할 수 있습니

다.

1.4.1.5 Device Load – IP

Modbus TCP 통신 연결에서만 설정하는 파라미터입니다.

EOCR 본체에 설절된 IP 를 입력합니다.

1.4.1.5 Device Load – Load Button

Motor Name, Product Name, Slave ID, IP 가 설정되었으면 이후 아래 Load 버튼을 클릭하여 EOCR 본체와 통신을 연

결합니다.

통신이 연결되지 않은 경우 아래와 같이 Disconnected 로 표시됩니다.

통신이 연결된 경우 아래와 같이 Connected 로 표시됩니다.

Page 25: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Connected 된 이후 Device Load Dialog 창을 닫으면 아래와 같이 Device Load Dialog 에서 설정한 Description 이

Icon Display Window 영역에 출력됩니다.

________________________________________________________________________________________________

[참고]

@ Load 버튼을 통해서 통신 연결 시 Pass, Fail 상태와 Fail 원인등은 Pass Log, Fail Log Window 를 통해서 더 자세히

관찰할 수 있습니다.

________________________________________________________________________________________________

1.4.2 Rotate Display Mode (순환 모드)

Stop Display Mode (정지 모드) 에서 Rotate Display Mode (순환 모드) 로 전환하고자 할 때 사용합니다.

1.4.3 Log Manage

Log Manage 버튼 클릭 시에 아래와 같이 Log Dialog 가 실행되며 이 Dialog 를 통해서

Pass, Fail, Fault History Log 를 Clear 할 수 도, RTF(Word), XLS, TXT 파일 형식으로 저장할 수도 있습니다.

Page 26: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.4.4 Option - sEOCR Meter Display

sEOCR Meter Display Option 다이얼로그를 통해서 sEOCR Detail Display 시 Voltage 또는 Power 를 선택할 수 있습

니다.

@ Current and Voltage 선택 시

@ Current and PF/Power 선택 시

1.4.5 Waveform Configure

Page 27: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Waveform 은 sEOCR 에서 지원되는 기능이며 Trip 직전 200mSec 동안의 Trip 파형을 저장합니다. 1st Waveform 은

가장 최근의 Trip 파형, 2nd Waveform 은 1st Waveform 바로 이전의 Trip 파형을 저장합니다.

Waveform Configure 버튼을 통해서 1st 또는 2nd Waveform 을 선택할 수 있습니다.

1.4.6 Waveform Current

Waveform Current 를 보기위한 Toolbar 버튼입니다.

버튼을 클릭하면 아래와 같이 Progress bar 를 통해서 Data 를 가져오는 과정을 볼 수 있게 됩니다.

이후 Detail Display Window 영역에 아래와 같은 Trip 직전 200mSec 동안의 파형을 관찰할 수 있습니다.

Page 28: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.4.7 Waveform Voltage

Waveform Voltage 를 보기위한 Toolbar 버튼입니다.

버튼을 클릭하면 Waveform Current 와 마찮가지로 Trip 직전 200mSec 동안의 Voltage 파형을 관찰할 수 있습니다.

1.4.8 Fault History Button

Icon display window 영역에서 Load 된 device 의 F-H 버튼을 클릭하면 Fault History Log Window 를 통해서 Fault

History 를 볼 수 있습니다.

Page 29: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

이 정보는 Log Dialog 를 통해서 저장할 수 있습니다.

1.4.9 Set Button

Icon display window 영역에서 Load 된 device 의 SET 버튼을 클릭하면 아래와 같이 EOCR Setting Program Dialog

가 생성됩니다. 이 Dialog 를 통해서 sEOCR 의 다양한 정보를 Read, Write 할 수 있습니다.

(SET 기능은 현재 sEOCR 만 지원되며 안전을 위해서 Write 기능은 Motor Stop 상태일 때만 지원됩니다.)

Page 30: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

________________________________________________________________________________________________

[주의]

@ EOCR Setting Program 기능을 사용 시 필히 [1st] System / Common, [2nd] Current,

[3rd] Voltage / Power 순서를 지켜서 진행해야 합니다.

자세한 사항은 아래

2. EOCR-MS Eays Use Procedure 의 Setting Procedure 편을 참고하십시요.

________________________________________________________________________________________________

Page 31: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

1.4.10 Chart Display Option

Chart Display Option Toolbar 버튼을 통해서 실시간 전력량, 유효전력, 역률, Max Current(RMS 단위) 를 파

악할 수 있습니다.

Page 32: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

2. EOCR-MS Easy Use

Procedure

이이이이 장에서는장에서는장에서는장에서는 EOCR-MS 를를를를 손쉽게손쉽게손쉽게손쉽게 사용하기사용하기사용하기사용하기 위한위한위한위한 방법방법방법방법, 사용사용사용사용 진행진행진행진행 순서를순서를순서를순서를 설명합니다설명합니다설명합니다설명합니다.

Page 33: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

2.1 Monitoring Procedure

2.1.1 Check Device Manager Communication Port : Modbus-RTU 연결 시

PC 장치관리자의 포트 COM 심볼릭링크 Number 를 확인하십시요.

PC 에서 통신포트는 아래와 같은 방법으로 확인할 수 있습니다.

바탕화면 -> 컴퓨터 아이콘 마우스 우측버튼 클릭 -> 속성 -> 하드웨어 -> 장치관리자 -> 포트

Page 34: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

2.1.2 Check Device Manager Communication Port : Modbus-TCP 연결 시

PC 네트워크 속성에서 로컬 영역 연결 속성의 IP 설정을 EOCR 본체 IP 의 끝자리가 충돌되지 않고 나머지 자리를 같

도록 설정하십시요.

2.1.3 EOCR-MS Loader Configuration and Start EOCR-MS Process

바탕화면에 있는 EOCR-MS Loader 아이콘을 클릭하여 EOCR-MS Loader 를 실행합니다.

장치관리자의 COM Port Number 와 동일한 COM Port 를 아래와 같이 세팅합니다.

(빨강 점선 테두리)

Page 35: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

위에서 Baud Rate, Parity, Stop Bit (파랑 점선 테두리) 는 EOCR 본체에 설정된 값과 동일한 값이어야 합니다.

________________________________________________________________________________________________

[참고]

@ Parity 와 Stop Bit 에 대한 상세 설명은 본 문서의 아래 제목편을 참고하십시요.

1.2 EOCR-MS Loader 설명 -> 1.2.3 Stop Bit

________________________________________________________________________________________________

위의 Response Time Category (회색 점선 테두리) 설정은 일단 기본값으로 그대로 놓아두십시요.

Modbus-TCP 연결시에는 아래와 같이 TCP/IP 1 ~ TCP/IP 10 중 하나를 선택하십시요.

Page 36: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

이후 Load EOCR-MS 버튼을 클릭하여 EOCR-MS 를 실행합니다.

2.1.4 Device Load Configuration and Start Monitoring

EOCR-MS 가 실행된 후 가장 먼저 해야하는 일은 아래 Device Load 버튼을 클릭하는 것 입니다.

Device Load 버튼을 클릭하면 아래와 같이 Device Load Dialog 가 실행됩니다.

Page 37: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Device Load Dialog 의 COMMUNICATION PORT INFORMATION READ 영역을 통해서

EOCR-MS Loader 를 통해서 설정한 통신 파라미터 정보를 확인할 수 있습니다.

#1 Device 부터 세팅을 시작합니다.

Motor Name Edit Box 를 통해서 User 가 Display 하고자 원하는 Device 정보를 입력합니다.

Product Name Combo Box 를 통해서 연결하려는 EOCR 제품, nEOCR 또는 sEOCR 을 선택합니다.

Modbus RTU 통신의 경우 Slave ID Combo Box 를 통해서 연결하려는 EOCR 본체의 Modbus RTU ID (1~248) 를 할

당합니다.

Modbus TCP 통신의 경우 EOCR 본체에 설정된 IP 를 세팅합니다.

Page 38: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Motor Name, Product Name, Slave ID, IP 가 설정되었으면 Load 버튼을 클릭하여 EOCR 본체와 통신을 연결합니다.

통신이 성공하면 아래와 같이 Load 버튼이 Connected 로 Display 됩니다.

통신이 실패하면 아래와 같이 Load 버튼이 Disconnected 로 Display 됩니다.

통신이 성공된 후 (Load 버튼이 Connected 로 바뀐 상태) Device Load Dialog 를 닫으면 아래와 같이 Icon display

window 영역에서 Load 된 device 의 Description 이 Display 되며 Monitoring 기능을 시작하게 됩니다.

Page 39: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Monitoring 기능 최초 시작전에 처음부터 다수의 Device 정보를 입력하여 Load 시켜도 되고

Monitoring 기능 수행 중 다시 Device 를 추가 Load 하거나 Description 을 수정하고 싶은 경우 다시 Load Dialog

를 실행시켜 기능을 수행하면 됩니다.

2.1.5 Rotate Display Mode & Stop Display Mode (순환 모드와 정지 모드)

아래는 앞의 과정을 통해서 31개의 Device 를 Load 한 후 Monitoring 기능을 수행하는 상태입니다. EOCR-MS 에서

의 기본 상태는 통신이 연결된 EOCR 을 우측의 창에서 5초 간격으로 순환하며 Diplay 하게 됩니다. 이 상태를

Rotate Display Mode (순환 모드) 라고 말합니다.

Page 40: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

아래와 같이 Load 된 Device 의 좌측 원형 Icon 을 클릭하면 순환하지 안고 선택된 Device 의 정보만 계속 보여주게

됩니다. 이 상태를 Stop Display Mode (정지 모드) 라고 말합니다.

2.1.6 Fault History View Example

Icon display window 영역에서 Load 된 device 의 F-H 버튼을 클릭하면 Fault History Log Window 를 통해서 Fault

History 를 볼 수 있습니다.

2.1.7 Waveform View Example

아래 Waveform Tab 에 있는 Toolbar 버튼을 통해서 Waveform 을 Display 할 수 있습니다.

단 Waveform 은 sEOCR 에서만 지원되며 Waveform 실행 전에 Waveform 을 보려는 Device 의 Icon 이 지정된 상

태 , Stop Display Mode 에서만 실행됩니다.

Page 41: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

2.2 Setting Procedure

SET 버튼을 통해서 EOCR 설정정보 및 기능을 Read, Write 할 수 있습니다.

Read 기능을 통해서 Detail Display Mode 가 보여주는 정보보다 더욱 다양한 정보를 확인할 수 있으며 Write 기능을

통해서 EOCR 의 모든 설정을 원격에서 수정할 수 있습니다.

2.2.1 Click Set Button and Start EOCR Setting Program

모든 Register 는 Read 후 Write 할 수 있습니다. (Write 버튼은 Read 후 Enable 됩니다.)

● 예 : EOCR Setting Program Read 전

● 예 : EOCR Setting Program Read 후

또한 EOCR 본체 Line up (Reference) 에 따라서 지원하지 않는 Register 는 세팅할 수 없도록 설정탭등이 Disable 됩

니다.

● 예 : EOCR 본체 Basic Line 제품에서는 지원되지 않는 ZCT, Loop Current or Metering Pulse

관련 기능

Page 42: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

________________________________________________________________________________________________

[주의]

@ Read 기능은 모터 상태와 상관없이 수행되나 Write 기능은 모터 Stop 상태일때만 수행됩니다.

________________________________________________________________________________________________

2.2.2 Start from 1st Setting : System / Common

1st Procedure 는 System / Common Register 를 세팅하는 것 입니다.

만약 이 카테고리의 Register 를 Write 할 필요가 없으면 다음 Procedure 카테고리

(2nd : Current, 3rd : Voltage / Power) 의 Register 를 세팅해도 되지만 만약 1st Procedure 카테고리에 있는 Register

를 Write 해야 한다면 다른 Procedure 카테고리의 Register 를 세팅하기

전에 우선 꼭1st Procedure 카테고리의 Register 를 Write 하십시요.

● Start from 1st Procedure Category : System / Common

Page 43: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

2.3 Multi-Process Procedure

EOCR-MS 는 물리적인 통신 포트가 지원(다수의 통신 장치 연결)하는 한 EOCR 본체를 무한 확장하여 동시에 모니터

링하여 사용할 수 있게 고안되었습니다.

수십~수백개의 EOCR 을 하나의 PC 에서 Monitoring 하려면 아래와 같이 사용하십시요.

2.3.1 Modbus-RTU 통신 시 물리적인 통신 포트의 확장

● Schneider Electric TSXCUSB485 : RS485 to USB 트랜시버

Page 44: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

위와 같은 USB Type 의 RS485 to USB 트랜시버 제품 2개를 연결하였을 때 장치관리자는 아래와 같이 2개의 COM

심볼릭 링크가 생성됩니다. (단 제품 연결전에 USB Driver 가 설치되어 있어야 하고 RS485 to USB 트랜시버 제품을

PC 에 연결 후 각 제품에 대한 USB Enumeration 과정이 마쳐진 상태이어야 합니다.)

● RS485 to RS232 변환장치 + PC PCI RS232

Page 45: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

아래와 같이 USB 형태가 아닌 데스크탑 형태에서 많이 사용되는 PCI RS232 Port 를 바로 이용할 수 있습니다. 단 이때

는 RS485 to RS232 변환장치가 필요합니다.

확장 필요시 PCI 카드를 더 연결하여 COM 통신 포트를 확장할 수 있습니다.

마찮가지로 PCI 포트 확장시 Legacy Driver 를 설치하여 장치를 연결하면 확장된 COM 심볼릭

링크가 생성됩니다.

2.3.2 Ethernet Gateway 연결

Modbus-RTU 를 지원하는 EOCR 을 Ethernet-to-Serial Gateway 를 통하여 아래와 같이 Ethernet 망을 통한 연결이

가능합니다.

아래는 Schneider EGX100 Gateway 제품을 통한 원격연결 예 입니다.

2.3.3 EOCR-MS Loader Configuration and Run another EOCR-MS

Modbus-RTU 통신 방식 사용 시,

다수개의 COM 심볼릭링크가 생성된 후 EOCR-MS Loader 를 통해서 확장된 새로운 COM 심볼링링크 Number 와 동

일한 설정 후 새로운 EOCR-MS 를 실행합니다.

RS485 to RS232

변환장치

Modbus-RTU 지원 EOCR

Page 46: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

아래와 같이 기존 COM3 로 연결된 EOCR-MS 가 실행되고 있는 상태입니다.

확장된 COM9 포트로 아래와 같이 다시 새로운 EOCR-MS 를 실행시킵니다.

Page 47: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

이후 Device Load Dialog 를 통해서 Device 를 Load 합니다.

이후 아래와 같이 2개의 EOCR-MS 를 통해서 Monitoring 되고 있는 상태를 확인할 수 있습니다.

EOCR-MS 의 Icon Display Window 영역은 다수개의 EOCR-MS 실행 시에 정열하여서 보여지는 GUI 의 최소부분으

로 고안되었습니다. 따라서 다수개의 EOCR-MS 실행 시 1개의 모니터에서라면 아래와 같이 정렬하여서 대화면의 모니

터에서 보기좋게 구성하여 Monitoring 하기 바랍니다.

Page 48: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

다수의 모니터에서는 아래와 같이(노트북 1개와 외부 모니터 1개) 각각의 모니터에 1개의 EOCR-MS 를 실행 후 보기

좋게 구성하여 사용하십시요.

Page 49: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

3. EOCR-MS 문제문제문제문제 해결해결해결해결

Guide

이이이이 장에서는장에서는장에서는장에서는 EOCR-MS 사용사용사용사용 중중중중 문제문제문제문제 발생발생발생발생 시시시시 해법에해법에해법에해법에 대해서대해서대해서대해서 설명합니다설명합니다설명합니다설명합니다.

Page 50: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

3.1 EOCR-MS License Error 발생 시

EOCR-MS 는 정식 라이선스 번호가 등록되어야 사용할 수 있는 SW 입니다.

EOCR-MS 라이선스가 없을 시에는 EOCR-MS Loader 에서 EOCR-MS 실행 시 아래와 같이 메시지와 함께 EOCR-MS

가 종료됩니다.

License Error 발생 시 아래 경고 Dialog 의 Contact 정보를 참고하여 표시된 License number 를 알려주셔야 합니다.

EOCR-MS 의 License 파일명은 EOCR_MS_License.dll 이며 Schneider Electric 으로부터 제공받은

EOCR_MS_License.dll 파일을 아래 디렉토리에 Copy 하여 사용하시면 됩니다

C:\Schneider Electric Korea\EOCR_MS

Page 51: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

3.2 EOCR-MS FAIL LOG WINDOW 통한 분석 시

EOCR-MS 의 아래쪽 하단 EVENT LOG WINDOW 의 구문 영역을 마우스 오른쪽으로 당겨오면 현재 통신 중에 일어

나는 상황을 디버깅 할 수 있는 디버깅 윈도우가 존재합니다.

(이러한 창을 만들어 놓은 이유는 개발 및 필드에서 일어나는 문제 상황에 대해서 분석하고 지원하기 위한 것 입니다.)

Page 52: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

문제 상황에 대해서는 Log Manage 아이콘을 클릭하여 Fail Log 창 내용을 저장 후 매일

( [email protected] )로 보내주시면 슈나이더 일렉트릭 코리아를 통해 기술지원 받으실 수 있습니

다.

3.2.1 EOCR-MS 통신 Error 발생 시

일단 정상적으로 통신이 연결되고 통신 중일 때 만약 통신관련 문제가 발생한다면 Timeout 과 CRC Error 2가지 종류

로 나타날 수 있습니다.

3.2.1.1 Timeout 발생 시

아래는 Timeout 이 발생하는 상황입니다.

이 상황은 아래와 같이 Fail Log Window 메시지를 통해서 확인할 수 있습니다.

Fail Log Window 에 위와 같이

‘<<FAIL>> xxxxx : CheckArrived Commnad Error’

로 출력시 Timeout Error 가 발생한 것 입니다.

이런 상황은 보통 통신 선로의 길이가 매우 길때, 또는 외부 요인에 의해서 정상적이던 통신 선로가 끊어졌을 때 등의

Page 53: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

원인으로 발생 할 수 있는 문제입니다.

만약 물리적인 통신 선로에 이상이 없을 시에도 여전히 이 Error 가 발생한다면 EOCR-MS 를 종료하고 EOCR-MS

Loader 에서 아래 Timeout 설정 시간을 늘인 후 다시 Load EOCR-MS 버튼을 눌러서 새로운 Timeout 값을 EOCR-

MS 에 적용하여 사용해보십시요.

3.2.1.2 CRC Error 발생 시

아래는 CRC Error 가 발생하는 상황입니다.

이 상황 역시 아래와 같이 Fail Log Window 메시지를 통해서 확인할 수 있습니다.

Page 54: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

Fail Log Window 에 위와 같이

‘<<FAIL>> ReceivePacket : Response packet received but CRC error occurred’

로 출력시 CRC Error 가 발생한 것 입니다.

이런 상황은 통신 선로의 길이가 길어서 신호의 세기가 약할 때, 통신 선로에 외부 Noise 가 영향을 미쳐서 신호가 깨

어질 때, 또는 통신 선로의 길이가 매우 길때 등의 다양한 원인으로 발생 할 수 있는 문제입니다. 이러한 경우 때로는

Modbus 신호 증폭기를 통신 선로에 보강하는 방법등이 필히 필요할 수 있습니다.

만약 물리적인 통신 선로에 이상이 없을 시에도 여전히 이 Error 가 발생한다면 EOCR-MS 를 종료하고 EOCR-MS

Loader 에서 아래 해당 Baud Rate 에 Match 되는 Interval 설정 시간을 늘인 후 다시 Load EOCR-MS 버튼을 눌러서

새로운 Interval 값을 EOCR-MS 에 적용하여 사용해보십시요.

3.3 EOCR-MS Message Box 발생 시

EOCR-MS 는 아래와 같이 Message Box 를 통해서 현재 문제 상황을 알려주고 있습니다.

이러한 문제는 잘못된 사용법에 의한 문제로 아래를 참고하여 해결하십시요.

@ 아래는 sEOCR 만 지원하는 기능을 다른 모델이 사용하려고 했을 때 발생하는 Message Box 입니다.

Page 55: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

@ 아래는 sEOCR 또는 nEOCR 로 선택되어야 하는 기능에서 다른 모델이 선택되었을 때 발생하는 Message Box 입

니다.

3.4 기타 주의 사항

3.4.1 통신 케이블의 길이 및 상태

EOCR-MS Loader 의 통신 설정 항목으로도 개선되지 않는 통신 관련 문제는 물리적인 통신 선로의 문제일 가능성이

높습니다. 이러한 상황은 Modbus 신호 증폭기 등의 연결, 선로 길이 조절, 통신 선로 주변 외부 Noise 개선등으로 해

결될 수 있습니다.

3.4.2 USB 통신 관련 주의 사항

현재 PC USB 포트로 연결되는 RS485 to USB 트랜시버 사용 시 매우 주의해서 사용해야 합니다.

아래를 필히 확인하여 사용하십시요.

@ PC 장치관리자를 통해 정상적인 USB Enumeration 과 심볼릭 링크 생성을 확인하십시요.

@ USB 연장 케이블 사용, 허브 연결 시등에는 매우 주의해야 합니다.

RS485 to USB 트랜시버 장치 이후 Line, 즉 RS485 to USB 트랜시버 에서부터 PC USB 입력라인의 길이는 짧아야 합

니다. (이 Line 은 480Mb/s 의 고속 Data 전송 Line 입니다.)

이 Line 이 길어서 문제가 발생 시에는 USB 케이블 길이를 조절하여 검증해보십시요.

USB 라인 길이를 줄이지 못하는 상황이라면 장치관리자에서 USB Enhanced Host Controller 를 ‘사용하지 않음’ 으로

설정하여 USB Full Speed 만을 지원하도록 변환하여 검증해보십시요.

@ PC 대기모드 발생 시에는 문제가 됩니다.

일반적인 RS485 to USB 트랜시버는 PC 대기모드 발생 시에 기능이 정지될 수 있습니다.

따라서 Screen Saver 에서 PC 대기모드가 발생하지 않도록 설정하시고 사용하십시요.

3.4.3 Ethernet Switch 사용 시

Modbus-TCP 사용 시 Ethernet 스위치 IP 와 EOCR IP 가 동일하게 세팅되는 상황이 없게 해야 합니다.

Page 56: Schneider Electric EOCR Multi-Monitoring and Setting Programorigin-faq.pro-face.com/resources/sites/PROFACE/content...SCHNEIDER ELECTRIC 은 EOCR-MS 기능을 추가, 텦상쉇큸고자

SCHNEIDER ELECTRIC EOCR-MS User Guide

Copyright of Schneider Electric Ltd. & All Rights Reserved http://www.schneider-electric.co.kr

또한 Ethernet Switch 는 서지와 노이즈에 강한 산업용 Ethernet Switch 를 사용하십시요.